MiCOM P543-545 Protection de ligne « différentielle & distance »

GRID

Technical Institute Formation Automation

DONNEES SYSTEME

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Données Système

• Généralités:

Menus de configuration général

4 groupes de réglages individuels • Gestion du mode « en service » et « en maintenance » de la ligne • Possibilité de changer le niveau de court-circuit en fonction de la configuration du réseau (principalement pour les fonctions Max I)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Données Système

• Réglages : » Choix entre Français, Anglais, Allemand et Espagnol

» Le langage choisi sera utilisé pour les textes sur l’afficheur LCD en face avant

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Données Système

• Réglages : » Nom du départ (visu. en face avant)

» Nom de l’usine (visu. en face avant)

» Fréquence : 50Hz ou 60Hz

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

COMMANDE DJ

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Commande DJ » Pas de commande manuelle du DJ » Les ordres d’ouverture/fermeture sont donnés par les fonctions de protection (réenclenchement auto, déclenchement, …)

» L’ordre fermeture / ouverture peut être donné via les HOT KEYS ou le menu DONNEES SYSTÈME en face avant » Il peut également être envoyé via le port de communication avant

» L’ordre fermeture / ouverture peut être

!

• Désactivé • Local • Distant • Local + Distant • Entrée TOR • Entrée + Local • Entrée + Distant • Ent. + Dist. + Local

donné via le port de communication arrière

» L’ordre fermeture / ouverture peut être donné via une entrée opto (une entrée pour la fermeture et une pour l’ouverture est requise)

» Les contacts des positions du DJ doivent être connectés au relais (via une entrée opto) quand la fonction Commande DJ est activée. © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Commande DJ

» Durée minimale de l’ordre

d’enclenchement envoyé au DJ

» Durée minimale de l’ordre de déclenchement envoyé au DJ

! » Une coordination entre ces réglages et les données constructeur du disjoncteur doit être faite pour assurer un fonctionnement sécurisé du DJ.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Commande DJ » Temps entre l’ordre local de fermeture manuelle donné par l’opérateur et l’ordre envoyé par le relais au DJ (pour laisser le temps de quitter la salle pour des raisons de sécurité)

» Fenêtre d’attente de la réception de

l’information DJ opérationnel, fournie par le disjoncteur. » Si le relais ne reçoit pas cette information, aucune commande de fermeture ne sera possible et le DJ sera verrouillé en position ouverte.

!

» Cette fonction requiert une entrée opto connectée à la logique interne DJ opérationnel (via l ’éditeur de PSL). 1, soit DJ toujours opérationnel.

Input L15 DDB #046

A défaut, DJ opérationnel sera considérée à

DJ opérationnel DDB #436

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Commande DJ

» Si DJ verrouillé, choix de la méthode de RAZ du verrouillage :

• Action opérateur (face avant) • Suite à une fermeture manuelle réussie

» A l’échéance de cette temporisation

» On indique quelles informations de position sont câblées sur le relais : » 52A pour position fermée du DJ » 52B pour position ouverte du DJ

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Commande DJ » Activation/Désactivation des cycles de réenclenchements monophasés.

» Activation/Désactivation des cycles de réenclenchement triphasés.

 Action opérateur (face avant)

ou / et  Action opérateur (logique programmable)

 Action sur état

ou  Action sur front

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

DATE ET HEURE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Date et Heure

» Visualisation / modification de la date

et de l’heure (face avant) » Lors de la création du fichier de paramètres, ces valeurs sont des valeurs par défaut

» Activation / Désactivation de la synchronisation par IRIG-B

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Rappel sur l’utilisation de MiCOM S1 Studio 2

1

1. 2. 3.

Sélectionner le relais Cliquer sur « superviser » Modifier

3

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Date et Heure

» État de la batterie » Lorsque ce paramètre est désactivé un niveau bas de la batterie n’entraîne pas d’alarme.

!

» En cas de coupure de l’alimentation auxiliaire, la batterie permet de sauvegarder la date, l’heure, les évènements, les enregistrements perturbographie et le descriptif des 5 derniers défauts enregistrés. » Les réglages/PSL sont enregistrés en mémoire EEPROM : la batterie n’intervient pas dans leur sauvegarde. » La durée de vie de la batterie est de 1 an si le relais n’est pas alimenté ou 10 ans si le relais est connecté en permanence à une source d’alimentation.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Date et Heure

» Permet de paramétrer la gestion

automatique des changements d’heure (UTC, heure d’été)

» Il est possible de paramétrer le

décalage entre UTC et l’heure locale.

» Le passage à l’heure d’été/hiver peut être adapté précisément

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

CONFIGURATION

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration

» Restaure les paramètres par défaut de tous les

réglages ou d’un groupe de réglages en particulier » Opération disponible uniquement en face avant

» 4 Groupes de réglages différents (PSL inclus) » Sélection du groupe actif via opto ou via menu » Activation / désactivation des fonctions de protection » L’activation d’une fonction la rend disponible dans le groupe de réglage :

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration

» Affichage ou masquage des menus généraux (hors fonctions de protection) » Choix de l’affichage des paramètres dans la programmation (valeurs primaires ou secondaires)

» Affichage ou masquage des raccourcis HOTKEYS et FUNCTION KEYS »Réglage du contraste en face avant © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration » Sélection par Menu : Le groupe de réglage est

» Sélection par Opto : Le groupe de réglage est

choisi par programmation (face avant ou via un PC en communication avant ou arrière). » Notes : la totalité des entrées peuvent être utilisées pour d ’autres applications

choisi dynamiquement par la combinaison des entrées logiques associées sur GR Sélect par x1 (poids faible) et GR Sélect par 1x (poids fort).

» Le groupe actif est choisi par le paramètre Réglages actifs

» Notes : » Les Entrées doivent être configurées dans le PSL » Le groupe de réglage ne peut être modifié que par les optos (par de modification via PC ou face avant).

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Opto x1 Opto 1x

0 0

Opto x1

1

Opto 1x

0

Opto x1

0

Opto 1x

1

Opto x1

1

Opto 1x

1

Groupe 1

Groupe 2

Groupe 3

Groupe 4

Configuration

» Il est possible d’avoir jusqu’à 4 groupes de réglages différents. Ceux-ci contiennent chacun des valeurs de paramétrages et un PSL.

!

» Il est conseillé de désactiver les groupes de réglages non-utilisés

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

RAPPORTS TC/TP

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Rapports TC / TP » Rapport du Transformateur de Tension principal (triphasé). » Emplacement de ces TP.

» Rapport du transformateur de tension utilisé pour la référence de tension de synchronisme. » Référence (AN, BN, CN, AB, BC, CA).

» Rapport du Transformateur de Courant de ligne (triphasé)

» Rapport du transformateur de courant neutre sensible (tore homopolaire) utilisé pour la fonction DTS ou DTS Wattmétrique

» Rapport des TC de la ligne parallèle. » Polarité des TC : Adelante ou inverse (adelanteP1 coté jeu de barres.

» TP connectés : Oui ou Non © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

CONTRÔLE ENREG.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Contrôle Enreg. » Permet de définir quels types

d’information seront enregistrés dans la mémoire des évènements Permet de vider la mémoire des enregistrements de perturbographie Disponible uniquement en face avant

» Permet de supprimer individuellement

un signal de type « Protection » pour ne pas qu’il apparaisse dans les évènements

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

PERTURBOGRAPHIE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Perturbographie » Configuration de la durée de

l’enregistrement de perturbographie » Choix du mode de fonctionnement (simple ou étendu)

» Sélection des signaux associés aux

voies analogiques (courant, tension…)

» Sélection des signaux associés aux voies logiques (état entrée, état sortie, démarrage, déclenchement…) » Sélection des critères d’enregistrement de fichier

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Perturbographie

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Perturbographie

» Mode démarrage Simple : on ignore le deuxième critère

» Mode démarrage Etendu : on prolonge l’enregistrement pour tenir compte du deuxième critère

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Perturbographie

» Pour chaque voie logique, on définit si c’est un critère d’enregistrement de la perturbographie : » oui, sur front montant » oui, sur front descendant » non, pas un critère

» Par défaut, la voie logique associée au contact R3

(Déclenchement) est un critère d’enregistrement de la perturbographie

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

CONFIG MESURES

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des mesures

» Affichage « Ecran de veille » du relais (15 minutes d’inactivité)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des mesures

IA

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

5.62A

Configuration des mesures

» La valeur sélectionnée sera la référence pour la calcul des déphasages entre les différentes mesures.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des mesures

Mode 0

i

Mode 1

P

i

u

u

P u

u

i

i Q

i

u

u

Q i

u

u

i

i

Mode 2

i

Mode 3

P

i

u

u

P u

u

i

i Q

i

u

u i

Q i

u

u i

Le sens de l'énergie est affiché sur le relais en fonction du mode choisi © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des mesures

» La protection calcule les valeurs moyennes sur cette période » Les valeurs sont rafraichies à l’échéance de chaque période

» La protection calcule les valeurs moyennes sur les « x » sous périodes d’une durée de « y » minutes » Les valeurs sont rafraichies à l’échéance de chaque sous-période

» Pour la fonction Localisation de défaut, choix de l’unité de distance et du type d’affichage souhaité.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

CONTRÔLE DISJ

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Contrôle Disjoncteur

» Choix de l’exposant pour faire la somme des I ou des I^2 coupés

» Activation d’une alarme de maintenance DJ si la limite est atteinte : » Somme des ampères coupés » Nombre de manœuvres » Temps de manœuvre

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Contrôle Disjoncteur

» Activation du verrouillage DJ (en position ouverte) si la limite est atteinte : » Somme des ampères coupés » Nombre de manœuvres » Temps de manœuvre » Nombre d’opérations en un temps défini

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

CONTRÔLE DISJ

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des Opto » Il est obligatoire de choisir une tension de polarisation: - commune à toutes les Entrées Logiques, - ou spécifique à chacune d’entre elles.

» En cas d’absence de tension continue, il est possible d’utiliser la sortie 48VDC de la protection pour polariser les optos.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des Opto

Plage de tension de réglage

Plage de tension indéterminée

24 / 27VDC

16,2 – 19,2VDC

30 / 34VDC

20,4 – 24VDC

48 / 54VDC

32,4 – 38,4VDC

110 / 125VDC

75 – 88VDC

220 / 250VDC

150 – 176VDC

100% 80%

!

60%

1 Etat précédent*

» L’entrée peut être endommagée par des surtensions supérieures ou égales à 300VDC

0 0%

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Configuration des Opto

»1 = opto filtré  tps de réponse = 10ms »0 = opto non filtré  tps de réponse < 5ms

» Chaque Entrée Logique peut être filtrée. Ceci permet un

pré-filtrage d’½ cycle qui immunise l’Entrée Logique du bruit du câblage. » Cette entrée est sécurisante, mais peut s’avérer lente pour des applications comme l’Intertripping. Dans ce cas, on peut désactiver le filtrage. © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LONGUEUR DE LIGNE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Longueur de ligne » Longueur de l’ouvrage à protéger. » Impédance de 100% de la ligne. » Argument de l’ouvrage à protéger. » Coefficient et argument du K0. » A activer en cas de compensation de mutuelle homopolaire.

» Sélection de l’ordre des phases (utile

en cas d’inversion de raccordement des phases)

A

A

» Pour la fonction Localisation de défaut, choix de l’unité de distance et du type d’affichage souhaité.

C

B

» Triphasé » Mono et triphasé © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

C

B

Localisateur de défaut » La longueur de la ligne peut être exprimée en km ou en miles :

» Impédance Zd: impédance directe de la ligne » Argument ligne: angle de l’impédance directe » Comp. rés. kZN: impédance résiduelle de la ligne » Argument de kZn: angle de l’impédance résiduelle

Note : la distance au défaut est affichée dans le rapport de défaut. Elle peut s’exprimer en unité de distance ou en Ohms ou en % de la ligne:

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

REGLAGE DISTANCE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Distance » Choix entre Mho ou Parallélogramme pour les défauts polyphasés.

» Choix entre Mho ou Parallélogramme pour les défauts monophasés à la terre.

60°

60°

»Mho

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

»Quad

Réglage Distance (MHO) » Choix entre simple et étendue » Paramétrages des défauts Phase-phase » Pourcentage de l’impédance totale de la ligne programmée dans le menu « Longueur ligne ». Dans cette exemple : 10 » Z1 = 80% * 10  = 8  » Z2 = 150% * 10  = 15  » Z3 = 250% * 10  = 25  + Offset d’1  » Z4 = 150% * 10  = 15  (Amont)

» Paramétrages des défauts Phase-terre. » Pourcentage de l’impédance totale de la ligne programmée dans le menu « Longueur ligne ». Dans cette exemple : 10 » Z1 = 80% * 10  = 8  » Z2 = 150% * 10  = 15  » Z3 = 250% * 10  = 25  + Offset d’1  » Z4 = 150% * 10  = 15  (Amont)

» Angle de directionnalité © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

(directionnel Amont/Aval)

Réglage Distance (MHO) » Mode simple  calcul automatique des zones

» Mode simple  calcul automatique des zones

pour les défauts polyphasés.

pour les défauts monophasés.

Z1

Z1

Z2 Z2 Z3 Z3

Z4

»En mode simple ces données ne sont pas modifiables. »En mode avancé ces données doivent être renseignées.

Z4

Sensibilité (Z3, ZP, Z4 ) = max (5%In ,(0,25/Portée de la zone) Sensibilité (Z1, Z2) = max (5%In ,(0,25 / Portée de la zone),(1,5 x sensibilité de la Zone 4) ou Sensibilité (Z1, Z2) = max (5%In ,(0,25 / Portée de la zone),(1,5 x (0,25/Portée de la zone 4))) © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Distance (Parallélogramme)» Choix caractéristique parallélogramme pour les défauts polyphasés

» Paramétrage de la portée résistive proportionnel ou commune

» Pourcentage de l’impédance totale de la ligne programmée dans le menu « Longueur ligne ». Dans cette exemple : Z=10 et R=10 » Z1 / R1 = 80% * 10  = 8  » Z2 / R2 = 150% * 10  = 15  » Z3 / R3 = 250% * 10  = 25  + Offset d’1  » Z4 / R4 = 150% * 10  = 15  (Amont) 1

» Choix caractéristique parallélogramme pour les défauts monophasés

» Paramétrage de la portée résistive proportionnel ou commune

» Pourcentage de l’impédance totale de la ligne programmée dans le menu « Longueur ligne ». Dans cette exemple : Z=10 et R=10 » Z1 / R1 = 80% * 10  = 8  » Z2 / R2 = 150% * 10  = 15  » Z3 / R3 = 250% * 10  = 25  + Offset d’1  » Z4 / R4 = 150% * 10  = 15  (Amont) 1

» Angle de directionnalité © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

(directionnel Amont/Aval)

PROT. DISTANCE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Prot.distance (Parallélogramme) » Mode simple  calcul automatique des zones

» Mode simple  calcul automatique des zones

de la caractéristique polyphasé.

de la caractéristique monophasé.

Z1

Z1

Z2

Z2 Z3

Z3

Z4

»En mode simple ces données ne sont pas modifiables. »En mode avancé ces données doivent être renseignées. Z4 © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LOGIQUE PROGRAM.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LOGIQUE PROGRAM. » Choix pour toutes les zones

» Choix pour toutes les zones

» Programmation des temporisations indépendantes entre les défauts phases et les défauts terre

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LOGIQUE PROGRAM

»Deux schémas de téléaction indépendant avec le choix entre :

» Schéma PUR : distance uniquement » Schéma POR : distance + Comp dir DEF + Source faible » Schéma Blocage : distance + Comp dir DEF © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LOGIQUE PROGRAM. » Mode Enclenchement sur défaut

» Temps d’attente pour valider le mode enclenchement sur défaut lorsque les seuils courants et tensions sont inférieurs au paramétrage du menu ADD & Pôles ouverts. » Paramètre associé aux pôles ouverts.

» Declt pour l’enclt manuel ou pour le reenclenchement

» Fenêtre enclt manual Poles Ouverts » Fenêtre enclt manuel Entrée EXT; » Fenêtre réencl. Automatique. © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LOGIQUE PROGRAM. » Extension de la zone 1

Z1 Z1X © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

LOGIQUE PROGRAM. » Perte de transit

Défaut 8-N

A

Z1 »I=0 »I=0 »I > PDT
Ph0 Ph4 Ph8

!

Applicable uniquement pour les défauts monophasés avec les relais qui déclenchement triphasé

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

B

Z2

REGLAGE DIFF. PHASE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase

Is1 Is2

» Is1 doit être paramétré au-dessus du courant capacitif de la ligne ou du câble. Réglage typique : 2,5 x I capacitif.

» Is2 est normalement paramétré au dessus du courant de charge. Réglage typique : de 1,2 à 2 x I charge.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase

Is1 Is2

Doit être réglé supérieur au courant capacitif de la liaison (typiquement 2,5 x courant capacitif de la liaison)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase

Is1 Is2

Ces paramètres ne doivent pas être modifiés (paramètres utilisés pour les essais de validation)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase

Dans le transformateur : l’application doit être étudiée soigneusement au regard des défauts externes qui pourraient corrompre la stabilité

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase Temporisation de déclenchement

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase Temporisation de télé déclenchement conditionnel

Télédéclenchement conditionnel

Télédéclenchement conditionnel

Le télé déclenchement a lieu après si le courant vu par le relais en extrémité est supérieur à Is1

Télédéclenchement conditionnel

temps

Is1 Is2 © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase Temporisation de télé déclenchement conditionnel

Déclenchement après si courant > Is1

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Réglage Diff. Phase Correction rapport TC

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Coefficient correcteur (toujours supérieur à 1) permettant de compenser les rapports de TC à chaque extrémité de la ligne

0.8A

800A

1000/1 A In TC

1A

800/1A In TC

1/0.8 = 1.250 1.250 © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

1/1 = 1.000 1.000 1.000

Secondaire TC 1A Cablage sur 1A

1A

Secondaire TC 5A Cablage sur 5A

2,5A

1000A

1000/1 A

In TC

2000/5A

In TC 1/1 = 1.000 1.000

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

5/2,5 = 2.000 1.000 2.000

Secondaire TC 1A Cablage sur 1A

1A

Secondaire TC 5A Cablage sur 5A

1A

1000A

1000/1 A In TC

5000/5A In TC

1/1 = 1.000 1.000

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

5/1 = 5.000 5.000 1.000

Réglage Diff. Phase Correction courant capacitif de la ligne ou transformateur en ligne Sélection entre Aucun, Chargement cap ou transformateur.

Ynd1

Susceptance de la ligne (Unité Siemens) © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Transformateur avec blocage H2 et compensation de l’indice horaire

MAX I (50/51/67)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Max I (50/51/67)

• Seuils I>1 et I>2 Le temps d’opération des seuils I>1 et I>2 peut être à : » Temps Constant (DT) OU » Temps inverse (suivant courbes standard internationales : CEI, IEEE…)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Max I (50/51/67)

• Seuils I>1 et I>2 » Les seuils I>1 et I>2 peuvent être : Non directionnel OU Directionnel aval OU Directionnel amont

» L’angle de directionnel est réglable entre -95° et +95° » Il est commun à tous les seuils de la fonction » La tension de polarisation minimale est fixée à 0.5V (en dessous la polarisation synchrone prend le relais)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Max I (50/51/67)

• Seuils I>1 et I>2 » Réglage du seuil de courant et de la temporisation associée (ou du TMS pour un seuil à temps inverse)

» PSL : Discrimination de phase Toute phase Discrimination de phase Toute phase

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Démarrage Déclenchement

Max I (50/51/67)

• Seuils I>1 et I>2 » Temporisation de maintien avant réinitialisation du seuil

tRESET = 0 I>1

TEMPO

TRIP

tRESET ≠ 0 I>1

TEMPO © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

TRIP

Max I (50/51/67)

• Seuils I>3 et I>4 » Les seuils I>3 et I>4 sont définis à temps constant uniquement :

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Max I (50/51/67)

Les différents seuils peuvent être bloqués : » par un défaut TP détecté par la fonction Supervision (utile pour la directionnelle) » par détection d’harmonique 2 (courant d’appel)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Max I (50/51/67) Action de la fonction Supervision TP sur la décision directionnelle : » cas du seuil configuré en Directionnel Aval avec perte des tensions :

Supervision TP Désactivée

Défaut Aval

Défaut Amont

Supervision TP Signalisation

Supervision TP Blocage

NO TRIP

NO TRIP

TRIP

NO TRIP

NO TRIP

NO TRIP

NO TRIP

NO TRIP

TRIP

NO TRIP

NO TRIP

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

NO TRIP

S/I COMP INVERSE (46)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surintensité Composante Inverse (46)

• Seuils Ii>1 et Ii>2 Le temps d’opération des seuils Ii>1 et Ii>2 peut être à : » Temps Constant OU » Temps inverse (suivant courbes standard internationales : CEI, IEEE…)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surintensité Composante Inverse (46)

• Seuils Ii>1 et Ii>2

» Les seuils Ii>1 et Ii>2 peuvent être : Non directionnel OU Directionnel aval OU Directionnel amont

» L’angle de directionnel est réglable entre -95° et +95° » Il est commun à tous les seuils de la fonction » Le seuil minimal de la tension de polarisation (Vi) est

configurable : à régler au-dessus de la tension inverse à l’état stable

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surintensité Composante Inverse (46)

• Seuils Ii>1 et Ii>2

» Réglage du seuil de courant et de la temporisation associée (ou du TMS pour un seuil à temps inverse)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surintensité Composante Inverse (46)

• Seuils Ii>1 et Ii>2 » Temporisation de maintien avant réinitialisation du seuil

tRESET = 0 Ii>1

TEMPO

TRIP

tRESET ≠ 0 Ii>1

TEMPO © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

TRIP

Surintensité Composante Inverse (46)

• Seuils Ii>3 et Ii>4 » Les seuils Ii>3 et Ii>4 sont définis à temps constant uniquement :

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surintensité Composante Inverse (46)

Les différents seuils peuvent être bloqués : » par un défaut TP détecté par la fonction Supervision (utile pour la directionnelle) » par détection d’harmonique 2 (courant d’appel)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surintensité Composante Inverse (46) Action de la fonction Supervision TP sur la décision directionnelle : » cas du seuil configuré en Directionnel Aval avec perte des tensions :

Supervision TP Désactivée

Défaut Aval

Défaut Amont

Supervision TP Signalisation

Supervision TP Blocage

NO TRIP

NO TRIP

TRIP

NO TRIP

NO TRIP

NO TRIP

NO TRIP

NO TRIP

TRIP

NO TRIP

NO TRIP

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

NO TRIP

RUPT. CONDUCTEUR (46BC)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Rupture de conducteur (46BC)

» On définit la proportion de courant inverse/courant direct et la temporisation associée

» Note : cette fonction, contrairement à la fonction 46, permet une détection de déséquilibre qui ne dépend pas de la charge de courant

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

PROTECTION DEFAUTS TERRE (50N/51N/67N)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N) » 2 types de protection de défaut terre » basée sur le calcul de IN

» basée sur la mesure de IN Sensible

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N)

• Seuils IN>1 et IN>2

Le temps d’opération des seuils IN>1 et IN>2 peut être à: » Temps Constant (DT) OU » Temps inverse (suivant courbes standard internationales : CEI, IEEE…)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N) » Seuils IN>1 et IN>2 » Les seuils IN>1 et IN>2 peuvent être : Non directionnel OU Directionnel aval OU Directionnel amont

» L’angle de directionnel est réglable entre -95° et +95° » Il est commun à tous les seuils de la fonction La polarisation peut se faire » soit par la tension résiduelle (-3Vo) – seul choix possible pour la fonction DTS : on définit alors le seuil minimal de présence tension » soit par les éléments inverses : dans ce cas, le courant résiduel génère le démarrage et la direction est déterminée par le biais de la tension et du courant résiduel : on définit alors les seuils minimaux de présence de ces éléments

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N)

• Seuils IN>1 et IN>2

» Réglage du seuil de courant et de la temporisation associée (ou du TMS pour un seuil à temps inverse)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N)

• Seuils IN>1 et IN>2 » Temporisation de maintien avant réinitialisation du seuil

tRESET = 0 IN>1

TEMPO

TRIP

tRESET ≠ 0 IN>1

TEMPO © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

TRIP

Protection Défauts Terre (50N/51N/67N)

• Seuils IN>3 et IN>4

» Les seuils IN>3 et IN>4 sont définis à temps constant uniquement :

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N)

Les différents seuils peuvent être bloqués : » par un défaut TP détecté par la fonction Supervision (utile pour la directionnelle)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Défauts Terre (50N/51N/67N) Action de la fonction Supervision TP sur la décision directionnelle : » cas du seuil configuré en Directionnel Aval avec perte des tensions :

Supervision TP Désactivée

Défaut Aval

Défaut Amont

Supervision TP Signalisation

Supervision TP Blocage

NO TRIP

NO TRIP

TRIP

NO TRIP

NO TRIP

NO TRIP

NO TRIP

NO TRIP

TRIP

NO TRIP

NO TRIP

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

NO TRIP

Protection Défauts Terre (50N/51N/67N)

• Compléments de la fonction DTS/DTR

DTS Dans certaines applications, il peut être difficile de discriminer le départ sain du départ en défaut car les valeurs de courant résiduel peuvent être proches. On utilise alors IcosΦ car le départ en défaut a une composante active de courant résiduel plus grande que celle du départ sain. Pour les réseaux isolés, on utilise plutôt IsinΦ Wattmétrique Il est possible de rajouter un critère puissance aux seuils précédemment définis en choisissant la caractéristique Wattmétrique

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

COMP.DIRECTIONNELLE (67N Aided)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Comp. Directionnelle de terre (67N Aided)

Les différentes polarisations sont :

» Validation du fonctionnement de la fonction

comparaison directionnelle associé avec l’émission et la réception du signal 1. Récept. TA1 DDB #493

» Validation du fonctionnement de la fonction

comparaison directionnelle associé avec l’émission et la réception du signal 2. Récept. TA2 DDB #507

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Comp. Directionnelle de terre (67N Aided) » Angle programmable entre -95° et +95° »Seuil minimal de tension résiduelle qui doit être franchi. »Seuil minimal de courant résiduel qui doit être franchi.

»Lorsque la polarisation est «homopolaire» cela force le mode polarisation virtuelle des courants. Si le relais détecte une variation typique de 4%.In, cela provoque une polarisation artificielle équivalente à Vn (Ph-Gnd)

»Le relais provoquera le déclenchement en cas de réception du signal de téléaction avec franchissement du seuil I0, même lorsque les trois tensions sont équilibrées, les tensions doivent être supérieures au seuil pôle ouvert V< selon la formule suivante : 2 x réglage V< / 3

En cas de signal partagé, le PSL doit être modifié ainsi pour donner la priorité à la fonction distance

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

DTN S/T RESID (59N)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Détection surtension résiduelle (59N) Note : cette fonction est basée sur la calcul de VN = VA+VB+VC

» Le temps d’opération du seuil VN>1 peut être à : Temps Constant (DT) OU Temps inverse (IDMT) » On configure alors le seuil et la temporisation / TMS le cas échéant

» Le deuxième seuil VN>2 est défini à temps constant uniquement » On configure simplement le seuil et la temporisation associée

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Détection surtension résiduelle (59N) » Seuil VN>1 » Temporisation de maintien avant réinitialisation du seuil

tRESET = 0 VN>1

TEMPO

TRIP

tRESET ≠ 0 VN>1

TEMPO © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

TRIP

SURCHARGE THERM (49)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Surcharge thermique (49) Note : » La caractéristique simple (à une constante de temps) est utilisée pour protéger les câbles, les transformateurs à sec. » La caractéristique double (à deux constantes de temps) est utilisée pour les transformateurs isolés à l’huile avec un refroidissement naturel à air » une constante de temps protège contre l’élévation progressive de la température de l’huile » une constante de temps protège contre l’élévation rapide de la température des enroulements

» On définit le courant de charge maximale admissible » On peut définir une alarme thermique pour prévenir d’une augmentation de l ’image thermique

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

ANTI-POMPAGE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Antipompage

Les différentes polarisations sont :

» Validation du fonctionnement de la fonction

comparaison directionnelle associé avec l’émission et la réception du signal 1. Récept. TA1 DDB #493

» Validation du fonctionnement de la fonction

comparaison directionnelle associé avec l’émission et la réception du signal 2. Récept. TA2 DDB #507

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

VOLT PROTECTION

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Voltmétrique » Mode de mesure : Phase-Neutre

VAN

50 V

VAN

VBN

VCN

Pas de démarrage du seuil V<1 © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

VCN

50 V

VBN

Démarrage du seuil V<1

Protection Voltmétrique » Mode de mesure : Phase-Phase

VAN VAN

50 V

50 V

VBN

VCN

Pas de démarrage du seuil V<1 © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

VCN

VBN

Démarrage du seuil V<1

Protection Voltmétrique » Mode de fonctionnement: » Toute phase : la protection démarre si le défaut apparaît sur au moins une phase » Triphasé : la protection démarre si le défaut apparaît sur les trois phases en même temps

Note : le mode de mesure et le mode de fonctionnement sont définis indépendamment pour les fonctions MIN. TENSION et MAX. TENSION. En revanche, ils s’appliquent pour tous les seuils définis dans chacune de ces fonctions.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Voltmétrique » Configuration de courbe

Réglages de la courbe temps constant : » Seuil » Tempo

Réglages de la courbe temps inverse (disponible uniquement pour V<1 et V>1) : Tinv = K / (1 – M) avec : K = coeff multiplicateur de temps TMS M = rapport tension mesurée / seuil tension

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Voltmétrique » Inhibition Min tension quand disjoncteur ouvert

Il est possible d’inhiber les seuils à minimum de tension quand le disjoncteur est ouvert en activant le paramètre « Pôle HT Inh »

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

PROT FREQUENCE

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Fréquence » Configuration des seuils

Réglages du seuil : » Valeur du seuil » Temporisation

Note : 4 seuils disponibles pour la fonction MINI FREQUENCE et 2 seuils disponibles pour la fonction MAXI FREQUENCE.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection Fréquence » Inhibition seuils MINI FREQUENCE quand disjoncteur ouvert Il est possible d’inhiber les seuils à minimum de fréquence quand le disjoncteur est ouvert en cochant la case adéquate:

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

DF/DT PROTECTION

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection df/dt » Configuration des seuils

Réglages du seuil : » Valeur du seuil (variation df/dt en Hz/s) » Temporisation (pour déclenchement) » Direction: » Negatif pour fonctionner sur une baisse de fréquence » Positif pour fonctionner sur une hausse de fréquence » Les deux

Note : 4 seuils disponibles pour la fonction DF/DT

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Protection df/dt » Calcul du taux de variation de fréquence Le calcul de variation sur 6 cycles sera plus rapide mais moins précis que le calcul sur 12 cycles. Le temps maximum de détection du défaut sera: t = 2 x M + 1 (en cycles) où M = Cycles.Moy df/dt

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

ADD & Pôles ouverts

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Automate Défaillance Disjoncteur » Automatisme Défaillance Disjoncteur : seuil n°1 (re-trip) avec temporisation réglable

» Automatisme Défaillance Disjoncteur : seuil n°2 (back trip) avec temporisation réglable

!

» Les deux seuils ADD sont strictement indépendants

Note : suite au déclenchement de la protection, si le disjoncteur n’est pas ouvert avant l’échéance de la temporisation réglée, le seuil de Défaillance Disjoncteur correspondant s’active © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Automate Défaillance Disjoncteur

» Activation de la fonction Défaillance DJ

Décl. DJ ouvert Pas de défaillance DJ

Tempo DJ1 Activation défail. DJ1

Décl.

DJ ouvert

Tempo DJ1 Activation défail. DJ1 © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Défaillance DJ

Automate Défaillance Disjoncteur Acquittement de l’ADD lorsque la défaillance disjoncteur est initialisée par une fonction non basée sur le courant : » I< seulement : Lorsque les courants mesurés tombent en dessous des seuil I< et seuil IN<. » DJ ouvert & I< : Lorsque les courants mesurés tombent en dessous des seuil I< et seuil IN< ET que la protection reçoit la position ouverte du DJ (sur une entrée opto). » RAZ prot & I< : Lorsque les courants mesurés tombent en dessous des seuil I< et seuil IN< ET que la fonction qui a fait déclencher s’est réinitialisée (le défaut a disparu)

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Automate Défaillance Disjoncteur Acquittement de l’ADD lorsque la défaillance disjoncteur est initialisée par une protection externe* : » I< seulement : Lorsque les courants mesurés tombent en dessous des seuil I< et seuil IN<. » DJ ouvert & I< : Lorsque les courants mesurés tombent en dessous des seuil I< et seuil IN< ET que la protection reçoit la position ouverte du DJ (sur une entrée opto). » RAZ prot & I< : Lorsque les courants mesurés tombent en dessous des seuil I< et seuil IN< ET que la fonction qui a fait déclencher s’est réinitialisée (le défaut a disparu)

* Nécessite de câbler dans le fichier PSL le signal déclenchement externe à une entrée optique :

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Automate Défaillance Disjoncteur Lorsque le critère d’acquittement de l’ADD I< est pris en compte, on définit les seuils en dessous desquels on considère que le courant a disparu : » Seuil I< et Seuil IN< pour toutes les protections basées sur le courant (hors DTS) + les protections non basées sur le courant + les protections externes » Seuil ITS< pour la protection défaut terre sensible (DTS)

Il peut être intéressant de bloquer les signaux de démarrage des premiers seuils I> et IN> lors d’une situation de défaillance disjoncteur: dans le cas où ces signaux sont utilisés pour bloquer une protection amont, l’ADD permet de débloquer la protection amont afin qu’elle ouvre son DJ associé.

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

SUPERVISION

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Supervision des TP et TC » Action de la STP sur détection anomalie: » Signalisation = Génération d’une alarme uniquement » Blocage = Verrouillage optionnel des éléments de protection dépendants de la tension + conversion optionnelle des éléments à maximum de courant directionnels en non-directionnels

» Suite à la détection d’une anomalie par STP, le signal de blocage sera maintenu après expiration de la Tempo STP » Mode réinit. STP: L’aquittement du maintien se fait soit manuellement (par la face avant ou la communication) soit automatiquement par rétablissement des 3 tensions phases (3 V > seuil fixe – 30V pour Vn=100/120V)

Note : la STP fonctionne lorsqu’une tension résiduelle est détectée en l’absence de courant inverse. En cas de perte de tension sur les 3 phases, d’autres mécanismes sont mis en place pour détecter une anomalie sur les mesures tension. © ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Supervision des TP et TC » Il est possible d’inhiber le blocage généré par STP si le courant phase (resp. inverse) dépasse le seuil Déverr. STP I> (resp. Déverr. STP Ii>). » Par exemple, en cas de défaut triphasé proche lors de la mise sous tension de la ligne, la fonction STP ne doit pas bloquer le déclenchement!

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

www.alstom.com

© ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.