Automation and Drives

DP/DP coupler for linking DP systems

SITRAIN IK-PBSYS / DP/DP Coupler

Page 1

Contents

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Page

Application and operating principle of the DP/DP coupler ................................................................. Data communication principle .......................................................................................................... Properties of the DP/DP coupler ...................................................................................................... Setting the PROFIBUS address with STEP7 ...................................................................................... Configuring the DP/DP coupler ...................................................................................................... DP/DP coupler configuration in network 1 ....................................................................................... DP/DP coupler configuration in network 2 ....................................................................................... S7 program in network 1 (DP master 1) ............................................................................................ S7 program in network 2 (DP master 2) ............................................................................................ Activating the "Data validity" diagnosis ............................................................................................... Diagnosis of DP/DP coupler malfunctions ........................................................................................ Diagnosis of DP/DP coupler malfunctions, LEDs SF and BF ......................................................... Diagnosis with system function SFC13 .............................................................................................. Exercise 1: Connect 2 DP networks using the DP/DP coupler ..........................................................

SITRAIN training for Automation and Industrial Solutions

Page 1

2 3 4 5 6 7 8 9 10 11 12 13 14 15

IK-PBSYS DP/DP Coupler

Automation and Drives

Application and operating principle of the DP/DP coupler

SITRAIN IK-PBSYS / DP/DP Coupler

Page 2

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Field of application The DP/DP coupler is used to link two PROFIBUS DP networks together and to transfer data from the master of one network to the master of the other network. The maximum length of data that can be transferred is 244 bytes input data and 244 bytes output data. Configuration

You can configure the DP/DP coupler using either STEP 7 or a configuring tool that links in the DP/DP coupler with the help of a GSD file. You can use STEP 7 to set the length of input and output data required. The output data of one side of the DP/DP coupler are transferred as the input data of the other side and vice versa. You enter these input/output data areas as slots with identifiers in STEP 7.

SITRAIN training for Automation and Industrial Solutions

Page 2

IK-PBSYS DP/DP Coupler

Automation and Drives

Data communication principle

SITRAIN IK-PBSYS / DP/DP Coupler

Page 3

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Data communicationThe example above shows that both networks are independent of one another. This means that you set one unique PROFIBUS address for each PROFIBUS DP network. In the diagram below, this is PROFIBUS address 3 in network 1 and PROFIBUS address 50 in network 2. In addition, it is possible to work with a different baud rate in each network. Network 1 fills the output buffer slower than it is read by Network 2. Network 2 therefore reads identical data several times consecutively. This applies conversely in the direction from network 2 to network 1. The output buffer is overwritten several times before it is read by network 1. The most recently written data are therefore always available. Note

You must ensure that the input and output areas of both networks are mutually coordinated.

SITRAIN training for Automation and Industrial Solutions

Page 3

IK-PBSYS DP/DP Coupler

Automation and Drives

Properties of the DP/DP coupler

SITRAIN IK-PBSYS / DP/DP Coupler

Properties

Page 4

03/2007 © Siemens AG 2007 - Subject to change without prior notice

The properties of the DP/DP coupler are: • Data transfer of up to maximum 244 bytes of input data and 244 bytes of output data, of which 128 bytes is consistent • Up to 16 I/O areas for exchanging data; when one side fails the outputs on the other side are held at the previous value • Support for DP V1 with complete and uniform diagnostics • PROFIBUS addresses can be set either via a switch on the DP/DP coupler or with STEP 7 (or with another configuring tool) • Different baud rates and PROFIBUS addresses can be set on each side of the DP/DP coupler • Electrical isolation between the two DP networks • Power supply on both sides

Slave address settings and diagnostics The slave addresses for the two slaves are set independently of one another by DIP switches on top of the unit. Addresses 1 to 124 can be set Please ensure that the addresses set on the hardware correspond to the parameters assigned during configuration. Subsequent changes to the slave addresses are not effective until the power has been switched off and on again. Diagnosis

The "Diagnosis" DIP switch provides an additional display of the data validity within the I/O data area. It has no effect on the normal diagnostic message frames of the DP/DP coupler. You can set the "Diagnosis" DIP switch to specify whether the validity of data is indicated by a defined bit within the configured I/O area.

SITRAIN training for Automation and Industrial Solutions

Page 4

IK-PBSYS DP/DP Coupler

Automation and Drives

Setting the PROFIBUS address with STEP7

DP/DP coupler for network 1

SITRAIN IK-PBSYS / DP/DP Coupler

Page 5

03/2007 © Siemens AG 2007 - Subject to change without prior notice

PROFIBUS address In the delivery condition, the PROFIBUS address "126" is stored in the nonvolatile memory of the DP/DP coupler. Procedure

1.Set the "ADDR" DIL switch to "ON". This means that the PROFIBUS address will be read out of the non-volatile memory in the DP/DP coupler. 2.Switch on the 24 V power supply (or power supplies) for the DP-DP coupler. LED(s) ON1 and/or ON2 light up. 3.Connect the PG/PC via a PG cable to the DP network or to the DP/DP coupler. 4.Open the STEP 7 hardware configuration and configure the DP/DP coupler 5.Select the configured DP/DP coupler 6.Change to PLC Æ PROFIBUS Æ Assign PROFIBUS address. The window "PROFIBUS address" appears. 7.Enter the configured PROFIBUS address and confirm with "OK". The PROFIBUS address is transferred to the DP/DP coupler and stored in the non-volatile memory of the DP/DP coupler.

SITRAIN training for Automation and Industrial Solutions

Page 5

IK-PBSYS DP/DP Coupler

Automation and Drives

Configuring the DP/DP coupler

DP/DP coupler for network 1

IO modules SITRAIN IK-PBSYS / DP/DP Coupler

Page 6

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 6

IK-PBSYS DP/DP Coupler

Automation and Drives

DP/DP coupler configuration in network 1

Address area for data exchange with network 2

Properties in network 1

SITRAIN IK-PBSYS / DP/DP Coupler

Page 7

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 7

IK-PBSYS DP/DP Coupler

Automation and Drives

DP/DP coupler configuration in network 2

2. Address area for data exchange with network 2

Address area for data exchange with network 1

Properties in network 2

SITRAIN IK-PBSYS / DP/DP Coupler

Page 8

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 8

IK-PBSYS DP/DP Coupler

Automation and Drives

S7 program in network 1 (DP master 1)

SITRAIN IK-PBSYS / DP/DP Coupler

Page 9

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 9

IK-PBSYS DP/DP Coupler

Automation and Drives

S7 program in network 2 (DP master 2)

SITRAIN IK-PBSYS / DP/DP Coupler

Page 10

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 10

IK-PBSYS DP/DP Coupler

Automation and Drives

Activating the "Data validity" diagnosis

When the "Diagnosis" DIL switch is set, a "1" is stored in the first configured INPUTbyte in EW62 = I 62.0 when the other side of the DP/DP coupler is operating correctly. In the event of an error, there is a "0" here.

SITRAIN IK-PBSYS / DP/DP Coupler

Diagnosis

Page 11

03/2007 © Siemens AG 2007 - Subject to change without prior notice

The "Diagnosis" DIP switch provides an additional display of the data validity within the I/O data area. It has no effect on the normal diagnostic message frames of the DP/DP coupler. You can set the "Diagnosis" DIP switch to ensure that the validity of data is indicated by a defined bit within the configured I/O area. If one of the masters is not active or if, for example, due to a fault on an interface of the DP/DP coupler, no data transfer takes place, this must be signaled to the other master so that it can reject the data read over the coupler. The validity of the data can either be determined using the slave diagnostics or, when the data validity display is active, it can be directly evaluated within the data.DIP switch at "1": The first bit in the LSB byte (low byte in the data unit), i.e. the first configured input byte, is used to indicate data validity. This can be evaluated in the user program. If the bit has the value "1", all the DP/DP coupler data are valid.

Note

It is important to note that when this function is used, the I/O bit from the user program is overwritten with the validity display. Example: - Network 1: 16-byte inputEW 60, i.e. I 60.0 =1 for valid data exchange - Network 2: 16-byte input EW 50, i.e. I 50.0 =1 for valid data exchange The first bit in the 16-byte input block of network 1 and the first bit in the 16-byte input block of network 2 display the data validity. Value equal to 1: Data valid Value equal to 0: Data invalid

DIP switch at "0":

Within the I/O data, there is no indication of the data validity. The LSB byte can be used for normal I/O data.

SITRAIN training for Automation and Industrial Solutions

Page 11

IK-PBSYS DP/DP Coupler

Automation and Drives

Diagnosis of DP/DP coupler malfunctions SF 1:

Group fault in PROFIBUS DP network 1 (red)

SF 2:

Group fault in PROFIBUS DP network 2 (red)

BF 1:

Bus fault in PROFIBUS DP network 1 (red)

BF 2:

Bus fault in PROFIBUS DP network 2 (red)

ON 1:

24 V power supply for DP/DP coupler network 1 (green)

ON 2:

24 V power supply for DP/DP coupler network 1 (green)

SF 1:

Group fault in PROFIBUS DP network 1 (red)

SF 2:

Group fault in PROFIBUS DP network 2 (red)

BF 1:

Bus fault in PROFIBUS DP network 1 (red)

BF 2:

Bus fault in PROFIBUS DP network 2 (red)

SITRAIN IK-PBSYS / DP/DP Coupler

Page 12

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 12

IK-PBSYS DP/DP Coupler

Automation and Drives

Diagnosis of DP/DP coupler malfunctions, LEDs SF and BF

SF 1: Group fault PROFIBUS DP network 1 (red) SF 2: Group fault in PROFIBUS DP network 2 (red) BF 1: Bus fault PROFIBUS DP network 1 (red) BF 2: Bus fault PROFIBUS DP network 2 (red)

SITRAIN IK-PBSYS / DP/DP Coupler

Page 13

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Notes

SITRAIN training for Automation and Industrial Solutions

Page 13

IK-PBSYS DP/DP Coupler

Automation and Drives

Diagnosis with system function SFC13

SITRAIN IK-PBSYS / DP/DP Coupler

Page 14

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Diagnosis with SFC13 The figure above contains an example of a DP/DP coupler malfunction. The figure below shows an example display indicating correct operation of the DP/DP coupler.

SITRAIN training for Automation and Industrial Solutions

Page 14

IK-PBSYS DP/DP Coupler

Automation and Drives

Exercise 1 : Connect 2 DP networks using a DP/DP coupler

SITRAIN IK-PBSYS / DP/DP Coupler

Page 15

03/2007 © Siemens AG 2007 - Subject to change without prior notice

Task description:

Your task is to connect 2 physically separate DP systems via the DP/DP coupler. Define the data of network 1 as output data and process them in network 2 as input data.

Procedure:

1.Change the name of your hardware station to "Network_1", copy your system to the clipboard and paste it in again under the name “Network_2". As a result you should have one station called network_2 and one called network_1 in your project. 3.Change the system network_2 in such a way that it is linked to an independent PROFIBUS network. After step 2, your project should also contain two PROFIBUS networks. 4.Now insert the DP/DP coupler type in the "Hardware configuration“ tool using the hardware catalog. 5.Configure an output area in network_1 and an input area in network_2. Download the modified hardware stations to the relevant CPU. 6.Change your S7 program, if necessary, to ensure that output data are generated and input data are processed.

SITRAIN training for Automation and Industrial Solutions

Page 15

IK-PBSYS DP/DP Coupler

Related Documents

05 Dp Dp Coupler
January 2021 3
Plan Maestro Dp Dts
March 2021 0
Full Report Dp 1
February 2021 1
Dp Breaking Bad
February 2021 1
[dp] Nisaafatm - Alaska.pdf
February 2021 0

More Documents from "Aunii Oktaa"

04 Intelligent Slaves
January 2021 0
01 Profibus Technology
January 2021 0
0_ik-pbsys_cover15_v201
January 2021 2
05 Dp Dp Coupler
January 2021 3
Lake Shore Drive Forma
February 2021 0