DF008 2

3

4

201

WDG - 1 220kV 110V 3 3 0.2, 75VA

220kV MAIN BUS - 1, & TRANSFER BUS, 2000A, 40KA FOR 1 SEC

WDG - 2 220kV 110V 3 3 3P, 10VA

WDG - 3 220kV 110V 3 3 3P, 10VA

97

97

8

9

10

204

TRANSFORMER-2

11

220kV DHANORA #1 MPCL

20389A 20389AE

20289A 20289AE

220kV DHANORA #2 MPCL

WDG - 2 WDG - 3 WDG - 1 220kV 110V 220kV 110V 220kV 110V 3 3 3 3 3 3 0.2, 75VA 3P, 10VA 3P, 10VA

2VT89BE 2VT89B

97

T

T

20189A 20189AE

20489A 20489AE

DISTANCE PROTECTION (MAIN-2)

27

UNDER VOLTAGE PROTECTION

46

NEGATIVE SEQUENCE PROTECTION

99

OVERFLUX PROTECTION FOR TRANSFORMER

50N

20452

20352

20252 20289T 20289TE

51

20389CE 20389C

20289CE 20289C FROM SELECTED BUS VT (WDG-1) P1

201CT CORE - 1 1600-800/1A CL: 0.2,10VA _ ISF<5

MVA

V MVAR

F

PF

MW

79

25

P141 50

CORE - 3 2000/1A _ CL-PS,Vk>1000 _ Rct <15Ω _ Im<60mA@Vk/2 CORE - 4 2000/1A _ CL-PS,Vk>1000 _ Rct <15Ω _ Im<60mA@Vk/2

202CT CORE - 1 300/1A CL: 0.5,10VA _ ISF<5 CORE - 2 300/1A CL: 0.2,10VA _ ISF<5

C264 (BCU) A

CORE - 2 1600-800/1A CL: 5P20,10VA

MFM

50N

51

51N

P1

ABT

MAIN

CHECK

FROM SELECTED BUS VT (WDG-1)

MFM

C264 (BCU) A

P1

V

F

PF

79

MVA

MVAR

MW

25

P2

CORE - 3 300/1A _ CL-PS,Vk>300 _ Rct <5Ω _ Im<30mA@Vk/2

P642 87T

CORE - 5 2000/1A _ CL-PS,Vk>1000 _ Ω Rct<15 _ Im<60mA@Vk/2 202LA

P2

20152 TO P141(1)

HV SEF

HV NCT(CORE-2) 300/1A _ CL-PS,Vk>300 _ Rct <3Ω _ Im<30mA@Vk/2

99

DR

FROM 33KV SIDE CT(CORE-1) P141(1) 50

50N

51

51N SEF 64R

DR

FROM HV NCT- CORE-1 FROM HV NCT- CORE-2 P746 50 87 BB LBB P2

T2 75/100 MVA ONAN/ONAF 220/33kV, YNynO Z = 17.5 % OLTC ± 8 X 1.25 % 30kV LA

HV BCT-1 300/1A _ CL-PS,Vk>300 _ Rct <3Ω _ Im<30mA@Vk/2

TO P141(1) HV 64R

46

203LA

FROM SELECTED BUS CVT(WDG-2)

CORE - 4 300/1A CL: 5P20,30VA

P746 50 87 BB LBB

5C

203CT

DR

SPARE

T1 75/100 MVA ONAN/ONAF 220/33kV, YNynO Z = 17.5 % OLTC ± 8 X 1.25 %

ABT

HV NCT(CORE-1) 300/1A _ CL-PS,Vk>300 _ Rct <3Ω _ Im<30mA@Vk/2

LV NCT(CORE-1) 300/1A _ CL-PS,Vk>300 _ Rct <3Ω _ Im<30mA@Vk/2

20489CE 20489C

20389T 20389TE

METERING & PROTECTION SAME AS TRANSFORMER-1

20189B 20189BE

204CT1 CORE - 1 800-400/1A CL: 0.2S,10VA _ ISF<5 CORE - 2 800-400/1A CL: 0.2,10VA _ ISF<5 CORE - 3 800-400/1A _ CL-PS,Vk>1300-650 _ Rct <10-5Ω _ Im<30-60mA@Vk/2 CORE - 4 800-400/1A _ CL-PS,Vk>1300-650 _ Rct <10-5Ω _ Im<30-60mA@Vk/2 CORE - 5 2000/1A _ CL-PS,Vk>1000 _ Rct <15Ω _ Im<60mA@Vk/2

20589CE 20589C

20489T 20489TE

20589T 20589TE

51N

59

ABT

ABT

MAIN

CHECK

FROM LINE VT (WDG-1)

MFM FROM LINE VT (WDG-2)

C264 (BCU) A

P1

V

F

PF

79

MVA

MVAR

MW

P2

25

205CT2 (TARRIF) 205CVT1 (TARRIF)

P444 (MAIN-1) 21 M1

DR

46

59

27

67

5C

205CT1

67N PSB DFL SOTF

97

FROM LINE VT (WDG-3)

1C

P443 (MAIN-2) 21 M2

DR

46

59

27

67

67N PSB DFL SOTF

97

FROM LINE VT (WDG-4) P746 50 87 BB LBB

67/ 67N

LV BCT- 1 2000/1A _ CL-PS,Vk>2000 _ Rct <15Ω _ Im<60mA@Vk/2

OVER CURRENT PROTECTION WITH TIME DELAY

EARTH FAULT PROTECTION WITH TIME DELAY

OVER VOLTAGE PROTECTION

205LA

P2

DIRECTIONAL OVER CURRENT & EARTH FAULT PROTECTION AUTO RECLOSURE RELAY

87BB

BUS DIFFERENTIAL PROTN

87T

TRANSFORMER DIFFERENTIAL PROTECTION

64R

97

F

STAND-BY EARTH FAULT

RESTRICTED EARTH FAULT PROTECTION

FUSE FAIL RELAY

DR

DISTURBANCE RECORDER

DFL

DISTANCE TO FAULT LOCATION

E

205LVT SOTF

SWITCH ON TO FAULT

PSB

POWER SWING BLOCK

25

CHECK SYNCHRONISATION

FUNCTIONS IN BCU:-

204LA D

G

INSTANTANEOUS EARTH FAULT RELAY

79

SEF

WDG - 1 220kV 110V 3 3 0.2, 30VA

P141(2) LV LV SEF 64R

INSTANTENEOUS OVERCURRENT RELAY

P1

204CT2 (TARRIF) CORE - 1 800-400/1A CL: 0.2S,20VA _ ISF<5 204CVT1 (TARRIF)

LV NCT(CORE-2) 300/1A _ CL-PS,Vk>300 _ Rct <3Ω _ Im<30mA@Vk/2

LOCAL BREAKER BACKUP PROTECTION

20552

METERING & PROTECTION SAME AS DHANORA LINE-1

220kV MAIN BUS - 2, 2000A, 40KA FOR 1 SEC

E

21 M2

50

20589B

G

F

DISTANCE PROTECTION (MAIN-1)

LBB T

20489B

20389B

20289B

21 M1

H

20589A 20589AE T

12

PROTECTION FUNCTIONS:-

205

2VT89AE 2VT89A

2MBVT2

97

7

203

TRANSFORMER-1

2MBVT1

97

97

6

202

BUS COUPLER & BUS VT

H

5

WDG - 3 WDG - 1 WDG - 2 220kV 110V 220kV 110V 220kV 110V 3 3 3 3 3 3 0.2, 30VA 0.2, 10VA 3P, 10VA

204LVT

97

WDG - 4 220kV 110V 3 3 3P, 10VA

MW

REAL POWER MEASUREMENT

F

FREQUENCY

MVA

ACTIVE POWER MEASUREMENT

A

CURRENT(R,Y,B)

MVAR

REACTIVE POWER MEASUREMENT

PF

V

POWER FACTOR

D

VOLTAGE(R,Y,B)

97

4R/PH.-1/C-630 SQ. mm XLPE Cu. CABLE(TYP)

4R/PH.-1/C-630 SQ. mm XLPE Cu. CABLE(TYP)

30kV LA TO 33KV SWITCHGEAR I/C-2

TO 33KV SWITCHGEAR I/C-1

LEGEND :-

MAIN OUTDOOR EQUIPMENTS MOTOR OPTD ISOLATOR WITH INTEGRAL MAIN EARTH SWITCH

M

C

POWER TRANSFORMER WITH BUSHING CT

SL.No

MOTOR OPTD HIGH SPEED EARTH SWITCH

M

DESCRIPTION

QTY.

1

75/100 MVA (ONAN/ONAF) 220/33kV 3 PHASE POWER TRANSFORMER WITH BUSHING CTS

2 NOS

2

245kV, 2000A, 40KA, FOR 1 SEC. 3P,SF6 CIRCUIT BREAKER,

5 NOS

3

245kV, 800A, 40KA, FOR 1 SEC. 5 -CORE, 1 -Ph C.T. (800-400/1/1/1/1. 2000/1A) FOR LINE BAY

6 NOS

C

SL.No. SF6 / 33kV CABLE PLUG IN CABLE TERMINATION (3 POLE) CH400 STANDS FOR 400 SQ.mm CU CABLE

1.0

220KV SYSTEM

SYSTEM PARAMETER MINIMUM CLEARANCES ADOPTED (mm) :

4

245 kV, 300A, 40KA, FOR 1 SEC. 5 -CORE, 1 -Ph C.T. (300/1/1/1/1. 2000/1A) FOR TRAFO. BAY

6 NOS

5

245kV, 1600A, 40KA, FOR 1 SEC. 4 -CORE, 1 -Ph CT. (1600-800/1/1, 2000/1/1A) FOR B/C BAY

3 NOS

6

245 kV, 800A, 40KA, FOR 1 SEC. 1 -CORE, 1 -Ph MPCL TARRIF METERING CT. (800-400/1A)

6 NOS

7

245 kV, 1 -P1h BUS CVT , WITH 3 SECONDARIES (220/ 3)/0.11/ 3/0.11/ 3/0.11/ 3 kV

6 NOS

8

245 kV, 1 -Ph LINE CVT , WITH 4 SECONDARIES (220/ 3)/0.11/ 3/0.11/ 3/0.11/ 3/0.11/ 3 kV

6 NOS

9

245 kV, 1 -Ph MPCL TARRIF METERING CVT , WITH 1 SECONDARIY (220/ 3)/0.11/ 3kV)

10 11

CONDUCTOR DETAILS CONDUCTOR

SL.No.

SYSTEM PARAMETER FOR 33kV GIS

SL.No

DESCRIPTION 220 kV

CIRCUIT BREAKER i.

T

2100

EMVT 2 NOS. SEC. WDG. TANDEM ISOLATOR

ii. CAPACITIVE VOL. DETECTING SYSTEM

ISOLATOR WITH ONE E/S

4C

4 CORE CURRENT TRANSFORMER

5C BUS CVT WITH 3 SECONDARIES

B

PHASE TO PHASE

3C

1C

LINE CVT WITH 4 SECONDARIES

5 CORE CURRENT TRANSFORMER 3 CORE CURRENT TRANSFORMER

PHASE TO EARTH

1.

MAIN SYSTEM

2.

RATED OPERATION VOLTAGE

3.

RATED CURRENT

6 NOS

4.

245 kV, 2000A, 40KA, FOR 1 SEC. 3-POLE ISOLATORS WITH 1E/S (MECHANICALLY GANG).

16 NOS

245 kV, 2000A, 40KA, FOR 1 SEC. 3-POLE TANDEM ISOLATORS(MECHANICALLY GANG).

4 NOS

2100

iii.

SECTIONAL CLEARANCE

4500

2.0

SYSTEM NEUTRAL EARTHING

3.0

HIGHEST SYSTEM VOLTAGE

245KV (r.m.s)

4.0

POWER FREQ. WITHSTAND VOLTAGE

460KV (r.m.s)

SOLIDLY EARTHED

12 1 CORE CURRENT TRANSFORMER

5.0

LIGHTNING IMPULSE WITHSTAND VOLTAGE

SURGE ARRESTOR

6.0

SYSTEM FAULT LEVEL

±1050 kvp

40KA FOR 1 SEC

198kV, 7 KJ/kV, GAPLESS 1-Ph, LIGHTNING ARRESTER

3PH, 3WIRE, AC 50+/-, 5% Hz

1

MAIN BUS I CUM TRANSFER BUS

TWIN MOOSE ACSR

33kV

2

MAIN BUS II

TWIN MOOSE ACSR

2500A

3

JACK BUS / EQUIPMENT CONNECTION FOR LINE BAY

SINGLE MOOSE ACSR / 3.5" IPS AL. TUBE - (EH TYPE)

RATED INSULATION VOLTAGE

36kV

4

JACK BUS / EQUIPMENT CONNECTION FOR TRANSFORMER BAY

SINGLE MOOSE ACSR / 3.5" IPS AL. TUBE - (EH TYPE)

5.

DRY FREQ. WITHSTAND VOLTAGE (r.m.s)

70KV

5

JACK BUS / EQUIPMENT CONNECTION FOR BUS COUPLER BAY

TWIN MOOSE ACSR / 3.5" IPS AL. TUBE - (EH TYPE)

6.

RATED IMPULSE VOLTAGE (PEAK)

7

SYSTEM FAULT LEVEL

B

170KV

CLIENT:

12 NOS

13

30kV, 5 KJ/kV, GAPLESS 1-Ph, LIGHTNING ARRESTER

6 NOS

14

315kVA, 33/0.433kV, AUX. TRANSFORMER

1 NOS

BHARAT OMAN REFINERIES LIMITED.

40kA FOR 1SEC.

BINA, MADHYA PRADESH 8.

DESIGN AMBIENT TEMP.

40°C

DEVELOPMENT CONSULTANTS PVT. LTD. CONSULTING ENGINEERS KOLKATA MUMBAI CHENNAI NEW DELHI Name

5427PK095-BIN- E - SYD - SYS-0401-SL

220/33kV KEY SINGLE LINE DIAGRAM

7703-71-60-A1-0101 (REV-E)

MAIN SINGLE LINE DIAGRAM -220/33KV SYSTEM

1. 33KV PSLD AND 33KV CT/CVT SIZING CALCULATION SHALL BE SUBMITTED SEPARATELY.

0 DESCRIPTION 1

2

3

NOTES 4

5

REV.No. 6

DESCRIPTION 7

DATE

BINA REFINERY PROJECT 220/33kV SUB-STATION AT BINA

SUBSTATION

Name Date Sign. Name Date Sign. Name Date Sign. Name Date Sign.

A

REFERENCE NO.

PROJECT:

Date Sign.

CONTRACT No. TITLE:

1. CEP/WBSETCL/Sub-Stn/Package-19 /SUPPLY / 2013-14 / 27 dated 30.11.13 2. CEP/WBSETCL/Sub-Stn/Package-19/Erection (E)/2013-14/28 dated 30.11.13 A

PROTECTION & METERING SINGLE LINE DIAGRAM (220KV SIDE) ALSTOM T&D INDIA LTD.

DRAWING No.

FORMERLY AREVA T&D INDIA LTD.

A1 DRAWN

REVIEW

8

ELE.

CIVIL CHECKED

MECH.

APPROVED

9

STATUS

GRID

DLF IT PARK, PREMISES NO.-8 MAJOR ARTERIAL ROAD TOWER-C, 8TH FLOOR, KOLKATA- 700 156.

10

5427PK095-BIN- E - SYD - SYS-0451-SL 11

TOTAL SH. SH.No. REV. 1 SCALE 1 OF 1 0 NTS 12