Acueducto

  • Uploaded by: Nieves Rodriguez Tineo
  • 0
  • 0
  • January 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Acueducto as PDF for free.

More details

  • Words: 2,518
  • Pages: 8
Loading documents preview...
ELABORADO POR: Ing. Cirilo Torbisco L. CIP. Nº 56123

DISEÑO DE ACUEDUCTO AEREO A.- DATOS DEL PUENTE

(Puente Simplemente Apoyado de un Solo Tramo)

LUZ LIBRE DEL PUENTE

L=

15.00 mts.

PERALTE PARCIAL DE LA VIGA ANCHO DE VIGA

h= d=

0.35 mts. 0.15 mts.

PROYECTO : PEQ. SIST. RIEGO PONGOCOCHA-PONTURCO

Distrito: Accomarca,

OTROS DATOS

Prov.: Vilcashuaman

0.15

0.15 0.20

Ancho de fondo de canal Espesor de losa Ancho de viga

(b) = [d'] = (d) =

0.20 m. 0.15 m. 0.15 m.

Altura parcial de Viga Paralte total de Viga

(h) = (H) =

0.35 m. 0.50 m. G1

H

h = 0.35

Viga G1

G3

h

Viga

0.35 Losa

(c)= (f'c)= (a)=

Peso específico Concreto Resistencia de Concreto Peso específico agua

2,400.00 Kg/m3 210.00 Kg/cm2

B.

d'

A.

C.

0.15

G2

1,000.00 Kg/m3

b d

d

1.- PREDIMENSIONAMIENTO CARGAS QUE ACTUAN EN ACTUEDUCTO : Presión lateral del agua sobre las vigas. : Peso del agua sobre losa. : Preso propio de la estructura.

M A= ((h+0.5d)3/6)a

i) La presión lateral del agua genera un momento en el punto "A".

M C= (q(b+d)2/8) - MA ii) El momento en el centro de losa el punto "C", se determina con : q = (h  ) + (d  )  = Donde: Peso específico de agua (Kg/m3) a c a c= Peso específico de concreto (Kg/m3) q=

710.00

Kg/m3

2.- METRADO DE CARGA MUERTA (considerando la mitad de la estructura) CARGA REPARTIDA =(h +d)dc G1 G2

180.00 Kg/m 71.00 Kg/m 251.00 Kg/m

= 0.5qb

Carga Muerta Carga Viva La suma total de carga Wd= 251.00 Kg/m

3.- CALCULO DE ESFUERZO CORTANTE Y MOMENTO MAXIMO i).- El momento en el punto "A".

El momento en el punto "C".

M A= ((h+0.5d)3/6)a

MA=

Momento último será:

Mu= (1.8MA)*100 Mu= 2,302.97 Kgcm/cm Mu= 0.02 Tn-m/m

M C= (q(b+d)2/8) - MA M C= -1.92

12.79 Kgm/m

Kg/m

4.- CALCULO DE ACERO PARA LA CAJA (*)

CHEQUEO DE PERALTE POR SERVICIO: Datos: f'c= 210.00 Kg/cm2 fc= 0.40f'c Kg/cm2 fs= 0.4Fy Kg/cm2 Fy= 4,200.00 Kg/cm2 Asumir acero diámetro Cálculos: n= Es/Ec = 9.66 r= fs/fc= 20.00 k= n/(n+r)= 0.33 j= 1.0 - k/3= 0.89 Peralte: d=[2M/(fcxjxkxb)]^0.5= d=

3.55

===>> ===>>

fc= fs=

3/8 " ====>

0.95 cm Donde: Es=2.1x10^6 kg/cm2 Ec=15,000(f'c)^0.5

donde:

b=

0.15

dmín=

3.55

m

cm COMO:

(**)

84.00 Kg/cm2 1,680.00 Kg/cm2

<

10.52

OK

CALCULO DE ACERO POR ROTURA: De la figura:

Pág.(1)

ELABORADO POR: Ing. Cirilo Torbisco L. CIP. Nº 56123

d=

10.52

cm

B=b=

15.00

cm

Según la relación matemática: Mu/(f'cxB) = (d-0.5a)(0.765a) >>>>>> a1 ={ -(-0.765xd)+((0.765xd)-4x0.3825x(Mu/(f'cxB)))^0.5}/(2x0.3825)= a2 ={ -(-0.765xd)-((0.765xd)-4x0.3825x(Mu/(f'cxB)))^0.5}/(2x0.3825)= Se asume el menor valor = AREA DE ACERO:

a=

0.091

As = Mu/(0.85xfy(d-a/2)) =>>>>>>

Area de acero para la Viga:

As =

De donde resulta dos valores 0.09 cm SI 20.96 cm NO

cm As=

0.062

cm2

0.06 cm2

Según las Normas el Acero Mínimo es ASMIN=0.0015x100xd ASMIN=0.0015x100xd ASUMIR ACERO MAYOR

=====>>

ASMIN=

1.579

cm2

=====>>

ASMIN=

1.789

cm2

r

<

rmáx

0.00039

<

0.016

1.579 cm2

ACERO PARA LA LOSA

Según las Normas el Acero Mínimo es ASMIN=0.0017x100xd ASMIN=0.0017x100xd POR ENDE:

El refuerzo por contracción y temperatura será:

i) Para la cara de la viga

=0.0025x100xd

=====>

3.75 cm2/m

ii) Para la losa

=0.0020x100xd

=====>

3.00 cm2/m

C=a/0.85 = C<< hlosa

0.11

5.- VERIFICACION DE VALORES: Comprobación zona comprimida: a=0.85C; De donde Luego:

0.11

<<<

Verificación de cuantías: Donde: rb = [(0.85xf'cxB1)/Fy)x0.003xEs/(0.003xEs+Fy) =>>>

cm

OK

15.0 B1= 0.85 rb =

rmáx =0.75xrb =

0.021675 Es=2.1x10^6 kg/cm2

rmáx = 0.016

Ec=15,000(f'c)^0.5

Cuantía de la viga: r = As/bxd=

0.0004

Luego: ====>>>>

(...) Para no verificar deflexión: fmáx=0.18f'c/Fy = 0.009

fmáx

>

0.00039

0.009

>

0.00039

Debe ser:

OK

OK

6.- CALCULO DE ACERO PARA VIGA LATERAL O PRINCIPAL W=

71.000

Kg/m MD=WL2/8

MD= 1,996.88 Kg-m

MA=W 1L2/8

MA= 5,062.50 Kg-m

Carga Muerta L= W 1=

180.00

15.00

m

Kg/m

Carga viva

Momento último: MU=1.8MD + 1.5MA

====>> L= (*)

15.00

m

MU=

11,188.13 Kg-m

MU=

11.19 Tn-m

CHEQUEO DE PERALTE POR SERVICIO: Datos: f'c=

210.00

Kg/cm2

fc=

0.40f'c

Kg/cm2

===>>

fc=

84.00 Kg/cm2

fs=

0.4Fy

Kg/cm2

===>>

fs=

1,680.00 Kg/cm2

Fy=

4,200.00

Kg/cm2

Asumir acero diámetro

5/8 " ====>

1.59 cm

Cálculos: n=

Es/Ec =

9.66

Donde:

r=

fs/fc=

20.00

Es=2.1x10^6 kg/cm2

k=

n/(n+r)=

0.33

Ec=15,000(f'c)^0.5

j=

1.0 - k/3=

0.89

Peralte: d=[2M/(fcxjxkxb)]^0.5=

donde:

b=

0.50

m

Pág.(2)

ELABORADO POR: Ing. Cirilo Torbisco L. CIP. Nº 56123

d=

42.84

cm COMO:

(**)

dmín=

42.84

<

46.71

OK

CALCULO DE ACERO POR ROTURA: De la figura: d=

46.71

cm

B=b=

Según la relación matemática:

50.00

cm

Mu/(f'cxB) = (d-0.5a)(0.765a) >>>>>>

De donde resulta dos valores

a1 ={ -(-0.765xd)+((0.765xd)-4x0.3825x(Mu/(f'cxB)))^0.5}/(2x0.3825)=

3.08 cm

SI

a2 ={ -(-0.765xd)-((0.765xd)-4x0.3825x(Mu/(f'cxB)))^0.5}/(2x0.3825)=

93.41 cm

NO

Se asume el menor valor = AREA DE ACERO:

a=

3.084

cm

As = Mu/(0.85xfy(d-a/2)) =>>>>>>

Area de acero para la Viga:

As =

As=

6.939

cm2

6.94 cm2

Según las Normas el Acero Mínimo es ASMIN=0.0020xbxd ASMIN=0.0020xbxd

ASMIN=

=====>>

1.401

cm2

Entonces deberá colocarse refuerzo mínimo: ASUMIR ACERO MAYOR

6.939 cm2 Area de acero

UTILIZAR ACERO

5/8

4.0

2.00

cm2

Barras

7.- VERIFICACION DE VALORES: Comprobación zona comprimida: a=0.85C;

De donde

C=a/0.85 = C<< hviga

Luego:

3.63

3.63

<<<

Verificación de cuantías: Donde: rb = [(0.85xf'cxB1)/Fy)x0.003xEs/(0.003xEs+Fy) =>>>

cm

OK

35.0 B1= 0.85 rb =

rmáx =0.75xrb =

0.021675 Es=2.1x10^6 kg/cm2

rmáx = 0.016

Ec=15,000(f'c)^0.5

Cuantía de la viga: r = As/bxd=

0.0030

====>>>> (...) Para no verificar deflexión: fmáx=0.18f'c/Fy = 0.009

Debe ser:

r

<

rmáx

0.00297

<

0.016

Luego:

fmáx

>

0.00297

0.009

>

0.00297

OK

OK

RESUMEN DE ACERO EN VIGA 6 Fierros de  5/8

4 Fierros de  1/2

Pág.(3)

ELABORADO POR: Ing. Cirilo Torbisco L. CIP. Nº 56123

8.- CALCULO ESTRUCTURAL DE LA VIGA SUPERIOR EN LA COLUMNA, COLUMNA Y ZAPATA

DATOS DE COLUMNA, ZAPATA Y VIGA

0.10

Base de la viga

(a) =

0.40 m.

Largo de viga

(L) =

0.70 m.

Altura de Viga

(D) =

0.30 m.

Ancho de columna

[B] =

0.30 m.

Espesor de columna

(e) =

0.40 m.

Altura de columna

(H) =

1.50 m.

Largo de zapata

(m) =

1.60 m.

Ancho de zapata

(n) =

1.60 m.

Altura de zapaya

(y) = (c)=

0.40 m.

Peso específico Concreto Resistencia de Concreto

G3 Canal

h = 0.20 D = 0.30

Viga G3

Viga

L=

0.70 Columna

2,400.00 Kg/m3

(f'c)=  t=

Capacidad portante del suel

0.18

210.00 Kg/cm2

G4

1.50

1.50 Kg/cm3

0.40

G5

0.65

Zapata

0.30

0.65 1.60 m

9.- CALCULO ESTRUCTURAL DE LA VIGA SUPERIOR DE COLUMNA La fuerza cortante última es: Ru= 1.8(W A)+1.5(W c)L*0.5

Ru=

====>>>

2,983.50 Kg

Cálculo del acero de la viga Mu=0.5(b-B+d)(2*Ru)

`====>>

Mu=

149.18 Kg-m

Mu= (*)

0.15

Tn-m

CHEQUEO DE PERALTE POR SERVICIO: Datos: f'c=

210.00

Kg/cm2

fc=

0.40f'c

Kg/cm2

===>>

fc=

84.00 Kg/cm2

fs=

0.4Fy

Kg/cm2

===>>

fs=

1,680.00 Kg/cm2

Fy=

4,200.00

Kg/cm2

Asumir acero diámetro

5/8 " ====>

1.59 cm

Cálculos: n=

Es/Ec =

9.66

Donde:

r=

fs/fc=

20.00

Es=2.1x10^6 kg/cm2

k=

n/(n+r)=

0.33

Ec=15,000(f'c)^0.5

j=

1.0 - k/3=

0.89

Peralte: d=[2M/(fcxjxkxb)]^0.5= d=

6.39

donde:

0.30

dmín=

6.39

m

cm COMO:

(**)

b=

<

OK

25.21

CALCULO DE ACERO POR ROTURA: De la figura: d=

25.21

cm

Según la relación matemática:

B=b=

30.00

cm

Mu/(f'cxB) = (d-0.5a)(0.765a) >>>>>>

De donde resulta dos valores

a1 ={ -(-0.765xd)+((0.765xd)-4x0.3825x(Mu/(f'cxB)))^0.5}/(2x0.3825)=

0.12 cm

SI

a2 ={ -(-0.765xd)-((0.765xd)-4x0.3825x(Mu/(f'cxB)))^0.5}/(2x0.3825)=

50.29 cm

NO

Se asume el menor valor = AREA DE ACERO:

a=

0.123

As = Mu/(0.85xfy(d-a/2)) =>>>>>>

Area de acero para la Viga:

As =

cm As=

0.166

cm2

0.17 cm2

Según las Normas el Acero Mínimo es ASMIN=0.0020xbxd ASMIN=0.0020xbxd

=====>>

ASMIN=

1.800

cm2

Entonces deberá colocarse refuerzo mínimo: ASUMIR ACERO MAYOR

1.800 cm2 Area de acero

UTILIZAR ACERO

5/8

1

2.00

cm2

Barras

Pág.(4)

ELABORADO POR: Ing. Cirilo Torbisco L. CIP. Nº 56123

10.- VERIFICACION DE VALORES: Comprobación zona comprimida: a=0.85C;

De donde

C=a/0.85 = C<< hviga

Luego:

0.14

0.14

<<<

cm

OK

30.0 B1= 0.85

Verificación de cuantías: Donde: rb = [(0.85xf'cxB1)/Fy)x0.003xEs/(0.003xEs+Fy) =>>>

rb =

rmáx =0.75xrb =

0.021675 Es=2.1x10^6 kg/cm2

rmáx = 0.016

Ec=15,000(f'c)^0.5

Cuantía de la viga: r = As/bxd=

0.0002

====>>>> Para no verificar deflexión: fmáx=0.18f'c/Fy = 0.009

r

<

rmáx

0.00022

<

0.016

Luego:

fmáx

>

0.00022

0.009

>

0.00022

Debe ser:

11.- CALCULO ESTRUCTURAL DE LA COLUMNA La reacción total será igual RTOTAL=4Ru

RTOTAL=

El peso propio de la viga superiorb es: G3=(LxaxD)xc ===>>

G3=

201.60 Kg

El peso propio de la columna es: G4=(HxBxe)xc ===>>

G4=

432.00 Kg

11,934.00

OK

OK

Kg

La carga última: Pu=(RTOTAL)+1.5(G3+G4)===>>

Pu= 12,884.40 Kg Además la columna debe resistir también un momento Mu=P ue', donde e'=0.10e que viene a ser excentricidad. Mu=Pu(0.10e) El factor

===>> K=

Mu= 51,537.60 Kg-cm

2.0

para el presente caso de columna

r= (I/A)1/2

Donde

I=(e4/12)

A=Bxe= Reemplazando valores

r=

13.33

cm

El factor KL/r debe ser mayor que 22.

I= 213,333.33 cm4

1,200.0

cm2

de datos

KL/r=

PCR=2EI/(KL)2 La carga crítica de la columna 1.5 0.5 E = 4,270(f'c) También: ====> c c

L=

>

22.50

150

cm4

22

CONSIDERAR ESBELTEZ

EI= (EcIg/2.5)/(1+d)

Donde Ec=

230,067.03

Ig=I=

### cm4

Kg/cm2 =

0

EI= 1.96E+010 Kgcm2 PCR= = Cm/(1-(Pu)/(PCR)

2,150,749.76

Kg Cm=

Donde

=

1.0

0.7

Reemplazando valores =

1.01

El momento simplificado resulta de: Mc= Mu =====>>

Mc=

51,982.47 Kg-cm El factor /h=( e-2(4+(/2)))/B

La relación de excentricidad: e/h=Mc/(Puxe) =====>>

e/h=

Asumir acero diámetro 5/8 " ====> El factor Pu/(f'cbh)= Reemplazando valores Pu/(f'cbh)=

/h=

0.10

1.01

1.59 cm

0.073

CON ESTOS VALORES SE ENTRA AL GRAFICO DEL LIBRO "Design Of Concrete Structues" Resulta del gráfico el area siguiente POR ENDE: El acero Mìnimo es:

As=

1.25

Aminimo=0.01xbxh Aminimo=

12.00

cm2 =====>

Aminimo=

cm2

cm2 Area de acero

UTILIZAR ACERO

12.00

5/8

6

2.00

cm2

Barras

Pág.(5)

ELABORADO POR: Ing. Cirilo Torbisco L. CIP. Nº 56123

12.- CALCULO ESTRUCTURAL DE LA ZAPATA Peso propio de la zapata: G5=(m)x(n)x(y)(c) =====>>

G5= 2,457.60 Kg

G6=(G5)(14/24)

G6= 1,433.60 Kg

=====>>

CASO SIN AGUA Quiere decir quebrada seca, donde van a estar los apoyos.

El momento que actúa sobre la zapata es: M=(2xR)(y)(0.25xY)

M=

R=(G1+G2)L/2

La presión sobre el terreno es: t= ((4R)+G3+G4+G6)/(mxn) Factor de seguridad

R=

1,882.50

Kg

37,650.00 Kg-cm

3

 t=

 c/  t=

0.37

Kg-cm

>

4.00

3

OK

Cálculo de excentricidad de las cargas verticales: e=M/((2xR)+G3+G4+G6)

e= Como

Fuerza cortante:

Vu=4xRu+1.5(G3+G4)

La carga unitaria sobre la parte inferior es:

6.46

cm e

<<<<

Como X=m/

X=

26.67

OK

Vu= 12,884.40 Kg  u= Vu/(mxn)  u= 0.50 Kg/cm2

La sección perimétrico está ubicada a una distancia de largo de la columna entre dos: Comprende un área La fuerza última

(B+2xe/2)^2=A' Vu1:

Vu1=u(K^2-A')

26.67

e/2=

20

cm

4,900.00 cm2 Vu1=

10,418.25

Kg

El esfuerzo cortante es: u1= Vu1/(b'f)

Pág.(6)

DISEÑO DE PUENTE VIGA-LOSA A.- PREDIMENSIONAMIENTO LUZ DEL PUENTE

L

Puente simplemente apoyado de un sólo tramo =

19.00 mts.

PERALTE DE LA VIGA H = L/15 = ESPESOR DE LA LOSA E =

1.27 mts. 0.20 mts.

PROYECTO Puede redondear

:

OFICINA ZONAL:

Puente Carrozable Huaylacucho AYACUCHO

B.- DISEÑO DE VIGAS Area de influencia de la viga Metrado de cargas Ancho de via Longitud de vereda Ancho de viga

Peso losa = Peso viga = Asfalto = Acera = Volado =

(A) = (c)= (b)= ( f )= Espesor de losa (E)= (g)= (m)= Separación de vigas (S)= (a)= E x (a + b + S/2 ) x 2.4 T/m³. = f x b x 2.4 T/m³. = 0.05 x A/2 x 2 Ton/m³. = 0.55 x 0.4 Ton/m³. = 0.10 x 2.4 Ton/m³. = Wd =

3.60 0.60 0.50 1.07 0.20 0.15 0.85 1.70 0.65 0.960 1.280 0.180 0.220 0.261 2.901

m. m. m. m. m. m. m. m. m.

Ton.

1-MOMENTO POR PESO PROPIO Número de diafragmas = 4 Peso propio Diafragma Wdiaf = 0.8 x 0.2 x S/2 x 2.4 = Momento total por carga muerta Md = Wdiafx(L/4+2xL/8)+WdxL²/8 = 2-MOMENTO POR SOBRECARGA Sobrecarga vehicular H20S16 por viga Ms/c=P/2*(9*L2/4-10,5*L+4,41)/L P= 4000 Kg. M s/c =M*(1+0,7/(s+b)) M s/c =

0.136 132.20

Ton-m

64.96

Ton-m

76.78

Ton-m

3-MOMENTO POR SOBRECARGA EQUIVALENTE por viga M eq=9*L/4+0,96*L*L/8

M eq =

43.94

Ton-m

4-CARGAS POR EJE TAMDEN M et =(L-1,2)*6/2

M et =

53.40

Ton-m

Ml

=

76.78

Ton-m

Mi

=

20.53

Ton-m

229.50

Ton-m

Tomando el mayor Momento ( Ml ) 5-MOMENTO POR IMPACTO I = 15,24 / ( L + 38 ) = 0.27 I < = 0.30, I = 0.27 Momento por impacto M i = i x M l

B1.- DISEÑO POR SERVICIO Verificacion del peralte M=Md+Ml+Mi Fy = F'c = Fc=0,4*F'c fy =0,4* fy r = fy / Fc

4,200 Kg/cm². 210 Kg/cm². 84 Kg/cm². 1,680 Kg/cm². 20 9.6609 0.3257 0.8914 126.67 cms.

n=2100000/(15000*(raiz(f'c))

k = n / (n+r) J = 1 - k/3 H=

d=raiz(2*M*100000/(F"c*k*j*b)) d= d
92.49

cms. 1

b = L/4 = b = 16 x E + 0,5 = b = 0,5 + S = b = mínimo valor

OK

4.75 3.70 2.20 2.20

B2.- DISEÑO POR ROTURA Mu =1,3 x ( Md + 1,67 x (Ml+Mi) )

Mu=

383.11

Ton-m

Area de acero b (cms) = d = H - 0,1 (cms) =

50.00 120.67

0.496252 W=(0,845-RAIZ(0,7182-1,695*Mu*100000/(0,9*F"c*b*d2)) W= 0.351248 As = w x f'c / fy x b x d As= 105.96 Ø 1"

cm².

21

varillas

B3.- VERIFICACION POR AGRIETAMIENTO Por paquetes Z = 2,300 Kg/cm² A = 2 x b x 10 / N Fs máx = 23,000 / ( 8.25 x A ^(1/3)) Fs = Mu / ( As x j x d ) 2042,90<3189,57

= = =

47.19 3,149.92 2,013.60 1 O,K

166.67 2,068.36 2,013.60 1

B4.- VERIFICACION POR CORTE POR PESO PROPIO Vd=Wd*L/2+W1*(1+0,75+0,5+0,75)

27.90

Ton.

POR SOBRECARGA HS 20 Vl=2,52(4*p*1+4*p*0,79+p*0,58)

19.81

Ton.

5.30

Ton.

DISEÑO POR ROTURA Vu =1,3(Vd+1,67*(Vl+Vi))

90.79

Ton.

Esfuerzo cortante nominal V"u=Vu/0,85*(b*d)

4.02

cms.

Esfuerzo cortante resis de concreto Vc=0,85*(0,5(f"c)^1/2+175*r*Vu*d/Mu)

7.08

kg/cm²

POR IMPACTO

r=

0.021675 Vc>V"u

1

Av=2*0,71 S=Av*Fy/(Vu-Vc)*b

1.42 39

ACERO LATERAL A=0,1*As

As =

10.60

Ø 3 / 4"

4

cm². varillas

B5.- VERIFICACION POR FATIGA Mu= Fs max=M/(As*j*d) Fmin=Mmin/(As*j*d) Fs-Fmin= Valor admisible (Fa) 1635,36-0,36*Fmin= Fa>(Fs-Fmin)

229.50 2013.60 1159.88 853.71 1328.022951139 1

C.- DISEÑO DE LA LOSA METRADO DE CARGAS Peso propio (1m) x (e) x (2,4 T/m³) Asfalto (1m) x (0.05) x (2T/m³)

0.48 0.1 0.58

Md=Wd*s/10

0.17

Ml=(s+0,61)/9,74*P P=7,258 Momento positivo=0,8*Ml Momento Negativo=0,9*Ml

1.72 7.258 1.38 1.55

Momento por Impacto I=15,24/(S+38) I=<0,3

0.38 0.30 Menor valor

0.3

Momento positivo=I*M+ Momento negativo=I*M-

0.41 0.46

VERIFICACION DEL PERALTE d=raiz(2*M*/(Fc*j*k*100) d
5.82 1 14

cms

4.64 9.20

T-m cm².

4.74 1

cm².

DISEÑO POR ROTURA M+=1,3*(Md+1,67*(M+I)) As=(0,845-raiz(0,7182-1,695*Mu* 100000/(0,9*F':c*b*d))*F"c*b*d/Fy: verificando la cuantia minima As min=14*b*d/Fy As min
M-=1,3*(Md+1,67*(M+I)) As=(0,845-raiz(0,7182-1,695*Mu* 100000/(0,9*F':c*b*d))*F"c*b*d/Fy: verificando la cuantia minima As min=14*b*d/Fy As min
=

@

22

=

cms

5.13 10.28

T-m cm².

4.74 1

cm².

@

19

distancia 0.825 0.550 0.517 0.325 1.000 Md= 0.10 0.59 0.18

Momento 0.10 0.07 0.01 0.10 0.15 0.43

cms

D.- DISEÑO TRAMO EN VOLADIZO Momento por peso propio 0,35*0,15*2,4 0,25*0,2*2,4 0,25*0,05/2*2,4 Asf,(a*e) Branda 0,15

carga 0.126 0.120 0.015 0.312 0.150

x=distancia al sardinel rueda Ml=p*x/(0,8*x+1,143) Momento impacto = DISEÑO POR ROTURA As=

2.23 T-m 4.14

cm². cms

Ø 5/8" AGE

Usar fierro @

48

cms

Related Documents

Acueducto
January 2021 0
Acueducto Aereo
January 2021 2

More Documents from "Josue Rivera Aguirre"