ETAP Knowledge Base
Asymmetrical Short Circuit and Symmetrical Short Circuit Description: ANSI Max Short-circuit calculation only provides symmetrical fault values Category:
Short Circuit - ANSI
Type:
Simulation
Keywords:
Short Circuit, Asymmetrical, Symmetrical, ANSI 3 phase device duty
Q: Why does the Max short circuit calculation does not report the asymmetrical fault current values?
A: The Max Short Circuit Analysis has not been designed to report the asymmetrical values. This is the job of the ANSI SC Device Duty calculation. Typically the Max short-circuit calculation is designed mostly for unbalanced faults. The asymmetrical fault currents are considered to be worse case under the three-phase bolted fault conditions (device duty condition) In the future ETAP may consider adding the asymmetrical fault current values to the Max shortcircuit calculation as well for informational purposes.
This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by Operation Technology, Inc. All Rights Reserved.