Loading documents preview...
WIN-S
Troubleshooting of Automatic Voltage Regulation System
WIN-S Check symptoms of Failure & Sequence of Alarms
Voltage Built up Failure Overvoltage Voltage Hunting
WIN-S Voltage Builtup Failure
X X
√
Check Input to AVR
Check Ex On Interlock
√
Check AVR Power Supply
Check Power Supply PT
Start Prev Step
X
Voltage Built Up
X
√
Next 1 Page
√
Check for Actual Value Measuring Fault
Reason Identified
WIN-S Prev 1 Page
√
Carry out Field Flashing
Check Residual Voltage *
Check Output From AVR
X
Start Prev Step
X
X
√
Check Other External Connections & Alternator
Carry out Lamp Test Replace / Readjust AVR
Voltage Built Up
√
Reason Identified
WIN-S Check symptoms of Failure & Sequence of Alarms
Voltage Built Up Failure Overvoltage Voltage Hunting
WIN-S Overvoltage
X
Check Feedback PT
Check C/O from field Flashing To AVR *
X X
√
Connections To Field
√
Carry out Lamp Test √ Replace / Readjust AVR
X Start Prev Step
No O/V
√
Reason Identified
WIN-S Check symptoms of Failure & Sequence of Alarms
Voltage Built Up Failure Overvoltage Voltage Hunting
WIN-S Voltage Hunting
√
Hunting (Specific Mode)
X Check respective wiring
√
In Droop Mode In VDC Mode
Hunting Intermittently
In pf / VAR Mode
X Start Prev Step
X
Adjust Programming Engine Running
√
Reason Identified