Loading documents preview...
CIRCUIT BREAKERS
•
CIRCUIT BREAKER- FUNCTIONS CARRIES CURRENT WHEN CLOSED WITHSTANDS VOLTAGE WHEN OPEN WITHSTANDS FAULT CURRENTS FOR SHORT TIME CAN WITHSTANDS CLOSING THE FAULT CURRENT CAN INTTERUPT LOAD CURRENTS CAN INTERRUPT FUALT CURRENTS CAN INTERRUPT SMALL INDUCTIVE & CAPACITIVE CURRENTS WITHOUT CREATING EXCESSIVE OVERVOLTAGES
CIRCUIT BREAKERS CIRCUIT BREAKERS
Interrupting Unit
Mechanism
TYPES OF CIRCUIT BREAKERS
AIR BLAST CIRCUIT BREAKERS
BULK OIL CIRCUIT BREAKERS
MINIMUM OIL CIRCUIT BREAKERS
SF6 CIRCUIT BREAKERS
DIELECTRIC STRENGTH OF SF6 GAS
SINGLE POLE OPERATED OPERATED
GANG
11
LIVE TANK CBS DEAD TANK CBS
INTERRUPTER S
Interrupter
Open position
Interrupting Principle
Closed Position
SF6 CIRCUIT BREAKERS CONTACTS
DIAGRAMMATIC VIEW OF SF6 CB POLE
MECHANISM
Closed Position
Opened Position
Closed Position
Mechanism Housing – 145 / 72 kV SP/SP
Spring Mechanisms 72 / 145 kV - Closing Spring
Spring Mechanism 72/145 kV - Opening Spring (Rear View)
TRIP & CLOSE COIL POSITION
CLOSING MECHANISM- CLOSED VIEW
PHOTOGRAPHS OF DIFFERENT RATING’S CIRCUIT BREAKERS
33 KV CIRCUIT BREAKERS
132 KV CIRCUIT BREAKERS
220 KV CIRCUIT BREAKERS
400 KV CIRCUIT BREAKERS
800 KV CIRCUIT BREAKERS
COMMISSIONING OF CIRCUIT BREAKERS
Gas System
CIRCUIT BREAKER SPECIFICATION S
SOME IMPORTANT TERMS Transient Rate
Recovery Voltage
of Rise of Restriking Voltage
Recovery
Voltage
Reignition/
Restrike
Capacitive/Inductive/Resistive Current Various
Chopping Timings
Breaking
TYPICAL SYSTEM LUMPED PARAMETER MODEL
CURRENT, TRV AND RECOVERY VOLTAGE
CURRENT AND TRV WAVEFORMS DURING INTERRUPTION OF RESISTIVE CURRENT
CURRENT AND TRV WAVEFORMS DURING INTERRUPTION OF INDUCTIVE CURRENT
RECOVERY VOLTAGE IN CASE OF A CAPACITIVE LOAD
EVOLUTION OF VOLTAGES WITH RESTRIKE OCCURRING A HALF CYCLE AFTER CURRENT INTERRUPTION, IN THE CASE OF SINGLE-PHASE CAPACITIVE CURRENT SWITCHING
CIRCUIT BREAKER WITH MULTIPLE REIGNITIONS
TRV DURING CURRENT CHOPPING
VARIOUS TIMINGS
STANDARD SPECIFICATIONS FOR 145 KV CIRCUIT BREAKER
Rated Voltage
: 145 kV
Rated Lightning Impulse Voltage
: 650 kVp
Rated Power Frequency Voltage
: 275 kV
Creepage Distance (Total)
: 3625 mm
Applicable Standards
: IEC-62271-100/ IS 13118
Type of Mechanism
: Spring-Spring
Rated Normal Current
: 3150 Amps
Rated Operating Sequence
: O- 0.3 Sec.-CO-3 min.-CO
Rated Frequency
: 50 Hz
STANDARD SPECIFICATIONS FOR 145 KV CIRCUIT BREAKER
Rated Closing /Tripping Voltage
: 110 VDC
Current of Closing / Tripping Coil
: 6 Amps Max.
Rated Break Time
: 60 mSec.
Rated Closing Time
: 130 mSec.
Rated Short Circuit Making Current
: 80 kA
Rated Short Circuit Breaking Current
: 40 kA
Rated Line Charging Breaking Current
: 50 Amps
STANDARD SPECIFICATIONS FOR 145 KV CIRCUIT BREAKER
Rated Line Charging Breaking Voltage
: 2.5 Times
Rated Cable Charging Breaking Current
: 160 Amps
Rated Cable Charging Breaking Voltage
: 2.5 Times
Rated Single Capacitor Bank Breaking Current
: 400 Amps
Rated Single Capacitor Bank Breaking Voltage
: 2.5 Times
Rated Out of Phase Breaking Current
: 7.9 kA
STANDARD SPECIFICATIONS FOR 145 KV CIRCUIT BREAKER
First Pole to Clear Factor
: 1.5
Auxiliary Contacts
: 8 NO + 8 NC
SF6 Gas Pressure at 200C: Normal
: 6 Kg/cm2
SF6 Gas Pressure at 200C: Alarm
: 5.5 Kg/cm2
SF6 Gas Pressure at 200C: Lock Out
: 5 Kg/cm2
Weight
: 1450 Kg.
Seismic Acceleration
: 0.3 g
CONTROL CIRCUITS
VARIOUS CONTROL CIRCUITS
CB Auxiliary Contacts
Common Ferrules & CB Changing Activity
Semaphore Circuit
ON/OFF Indication Circuit
Spring Charge Control & Indication Circuit
SF6 Alarm & Lockout Circuit
Remote Closing
Antipumping Circuit
Remote Tripping
Post Close & Pre Close Supervision Circuit
PDR Circuit
TEMPERATURE COMPENSATED PRESSURE SWITCH
SERIES RESISTORS FOR REDUCING THE COIL OPERATING VOLTAGE
CB LOCAL/REMOTE & ON/OFF SWITCH
CB OPERATIONAL INDICATORS
TB IN CB MB
AUXILIARY DRUM TB
CB AUXILIARY DRUM
CB Auxiliary Drum
CB MB FRONT VIEW
NUMBERS & SPECIFICATIONS OF VARIOUS ITEMS
Item No.
Nomenclature
52C
Closing Coil
52 T1
Trip Coil
52 T2
Trip Coil
ACTUAL CONTROL CIRCUIT
CLOSING CIRCUIT WITH ANTIPUMPING
SPRING CHARGING CIRCUIT
SF6 CIRCUITS
TROUBLESHOOTI NG
OF CIRCUIT BREAKE RS
CIRCUIT BREAKER TESTING
INSULATION RESISTANCE MEASUREMENT
INSULATION RESISTANCE MEASUREMENT 1. 2. 3. 4. 5.
TOP – EARTH BOTTOM - EARTH TOP – BOTTOM (CB OPEN) TOP – BOTTOM (CB CLOSE) TOP, BOTTOM – EARTH (CB CLOSE)
ACCEPTABLE LIMITS • PHASE TO EARTH : 1000 MΩ • ACROSS OPEN CONTACTS : 1000 MΩ (5/10 kV MEGGER)
DEW POINT MEASUREMEN T
DEW POINT MEASUREMENT SET UP
Sr. No. Make of CB
Dew point Dew point at at rated Atmospheric pressure (Min. º C)
1
2
4
BHEL
CGL
ABB
Pressure
Remarks
(limit) (Min º C)
-15
-36
At the time of commissioning
-7
-29
During O&M
-5
-27
Critical
-15
-35
At the time of commissioning
-10
-31
During O&M
-15
-35
At the time of commissioning
-5
-26
During O&M
OPERATIONAL CIRCUIT AND OTHER CHECKS
POLE DISCREPENCY CHECK
ANTI HUNTING/ PUMPING FEATURE
BREAKER POSITION INDICATOR
REMOTE TRIPPING WITH TC1 & TC2
REMOTE CLOSING
ILLUMINATION IN CB MB
SPACE HEATER IN CONTROL/SWITCH CUBICLE
OTHER CHECKS COIL
RESISTANCE MEASUREMENT.
LEAKAGE CHECK OF SF6 GAS. IR VALUE OF CONTROL CIRCUIT CB OPERATION COUNTER HEALTHINESS. OIL/AIR PRESSURE DROP TEST. OIL/AIR PRESSURE LEAKAGE IN 24 HRS. SPRING CHARGING TIME.
CIRCUIT BREAKER TIMING TEST
TIMING TEST KIT
TEST LIMITS Close
(C-operation)
<=150ms
Open
(O-operation)
<=60ms
Close-Open
(C-O operation)
<=160ms
CONTACT RESISTANCE MEASUREMENT
STATIC CONTACT RESISTANCE – ACCEPTABLE VALUES: 150
µΩ
DYNAMIC CONTACT RESISTANCE MEASUREMENT
MOVING CONTACT PROBLEMS
ARCING CONTACT PROBLEMS
DCRM CAN DETECT Erosion of Arcing Contact Contact
misalignments
Wipe
of main and arcing contact
Main
& arcing contact resistance
Healthiness Contact
of damping system
travel & speed
DCRM CONNECTION ARRANGEMENT
DCRM KIT
TYPICAL DCRM SIGNATURE
CASE STUDY-1
400 kV GCB AT at Hosur WITH SPRING-PNEUMATIC MECHANISM COMMISIONED IN 2003.
420 kV SF6 GCB With SP/Pneumatic Mechanism
DCRM SIGNATURES OF B PHASE
DCRM SIGNATURES OF R PHASE
DCRM SIGNATURE OF Y PHASE
Static contact CONTACT RESISTANCE VALUES resistance reported to be about
53 micro-ohm at the time of commissioning Static
Contact resistance has found to be
87 micro-ohm
Y PHASE DCRM AFTER ADJUSTMENT OF TRAVEL/WIPE
CASE STUDY 2
CB 952 inspected in March,2006 at Hyderabad s/s.
DCRM of B pole was not alright. The problem is rectified & DCRM taken but found abnormal again.
The Test kit was changed but same problem was indicated in DCRM.
New spare pole was erected but same problem was again indicated.
M/s Scope was called with new kit but problem continued
ABB then brought Contact Assembly from factory and then rectified the problem.
952-B PHASE
952-B PHASE- NEW KIT
AFTER POLE REPLACEMENT BY SCOPE KIT
CONTACT ASSEMBLY CHANGED
AFTER RECTIFICATION ON 30.03.2006
CONCLUSIONS Test for CBs proved useful in indicating
DCRM
condition of main/ arcing contacts for erosion, misalignment and looseness etc. misalignment and looseness etc. Prevention Major
of Major failures by timely diagnosis
overhauling
of
Interrupters/
chamber can be decided based on DCRM
Arcing
MAINTENANCE OF CIRCUIT BREAKERS
QUARTERLY MAINTENANCE OF CIRCUIT BREAKERS
PORCELAIN
1
Clean all porcelain thoroughly
2
Check for cracks.
3
Check for flash over marks. OPERATING MECHANISM BOX
1
Check connection for tightness.
2
Check and clean for auxiliary contacts.
3
Check cubic heater.
QUARTERLY MAINTENANCE OF CIRCUIT BREAKERS
MARSHALLING BOX
1
Clean the connection by CTC/Equivalent.
2
Check connection for tightness.
3
Check L.T. Plug point.
4
Clean switch contacts.
5
Check the fuses.
6
Clean the M.B.
7
Check MK box for vermin proofing.
QUARTERLY MAINTENANCE OF CIRCUIT BREAKERS
RESISTANCE MEASUREMENT
1 Closing Coil 2 Tripping Coil - I 3 Tripping Coil - II LOCAL/REMOTE BREAKER OPERATIONS
1
Closing Operations
2
Tripping Operations through TC-I & TC-II
3
Trip Trial through Protection
ANNUAL MAINTENANCE OF CIRCUIT BREAKERS
1
Breaker Timing
a Closing Time b Tripping Time c
CO Time
2
Checking of operation counter
3
Check pole discrepancy
4
Check of interlocks
ANNUAL MAINTENANCE OF CIRCUIT BREAKERS
5
Static Contacts resistance
6
Checking of tightness of all the termination in the MB.
7
Checking of door sealing gaskets and replacement there of if necessary
8
General cleaning of MB and repainting of metallic surface if required.
9
Check functioning of space heater / illumination.
ANNUAL MAINTENANCE OF CIRCUIT BREAKERS
10
Record the Winding Resistance of the Spring Charging Motor
11
Record the Current drawn by the Spring Charging Motor
12
Record the Time Taken to charge the spring by the Spring Charging Motor
13
Check the operation of Limit Switch
14
Check for Gas Leakage if any
MAJOR REPLACEMENTS/OVERHAULINGS Operating Inspection Item
Inspection & Renewal of Main Contacts
Renewal of Parts of Operating Mechanism
Condition
/Renewal Period
Small Current Interruptions
After @ 4000 Operations
Rated Continuous Current Interruptions
After @ 2000 Operations
Rated Short Circuit Current Interruptions
After @ 20 Operations
Total Number of Operations
After @ 5000 Operations