1046Z-00-DP-J-23K-GEI-000087

CONTRACTOR DOCUMENT N° : F10163 Project Code

Vendor Logo & Name :

PO Number:

GEI

INS

Vendor Discipline

Page:

1 de 8

DGM

000087

F

000

3

Document Type

Sequential N°

Lang.

Area:

Rev

Vendor Document N° :

NUOVO PIGNONE

SOM 5461126

SONATRACH

EXTRACTION DES LIQUIDES DES GAZ ASSOCIES HASSI MESSAOUD ET SEPARATION D’HUILE LDHP ZCINA ALGERIE ENC 08 1046Z

Unit Control System & Power Supply Schematic Contractor Return Code :

Vendor Action :

 Reviewed without comments (1)  Reviewed with comments (2)

New revision required : __

 Rejected (3)

At the latest on __/__/__

 Received for Information (4)

Date : __/__/__ (dd/mm/yy) Name : ____________________

 IFR

(dd/mm/yy)

 IFI

 IFC

 ASB

Signature : Comments :

7

REVISED see Revision Index Sh.2, AS BUILT WO 113984

6 5

El. Stored

Rev

Date

Page

Status

Description

Prepared by

Checked by

Approved by

3

21.05.13

8

FIN

ISSUED FOR CONSTRUCTION

CTQ

.

.

2

01.12.11

8

FIN

ISSUED FOR CONSTRUCTION

GARFAGNINI

GIOVANARDI

VISINTIN

1

21.09.10

6

FIN

ISSUED FOR CONSTRUCTION

GARFAGNINI

GIOVANARDI

VISINTIN

0

08.01.10

6

FIN

ISSUED FOR CONSTRUCTION

GARFAGNINI

GIOVANARDI

VISINTIN

D

22.11.09

6

COM

ISSUED FOR REVIEW

GARFAGNINI

GIOVANARDI

VISINTIN

C

30.09.09

6

COM

ISSUED FOR REVIEW

GARFAGNINI

GIOVANARDI

VISINTIN

B

24.07.09

6

COM

ISSUED FOR REVIEW

GARFAGNINI

GIOVANARDI

VISINTIN

A

20.03.09

6

COM

ISSUED FOR REVIEW

GARFAGNINI

GIOVANARDI

VISINTIN

21/05/13

CTQ

El. Stored

REVISED NETWORK ARCHITECTURE see Revision Index Sh.2

Baviera F.

Garfagnini G.

French Translation

Baviera F.

08/01/10 08/01/10

Visintin F.

01/12/11

4

REVISED see Revision Indedx Sh.2

GG

3

REVISED see Revision Indedx Sh.2

GG

22/11/09

2

REVISED see Revision Indedx Sh.2

GG

30/09/09

1

REVISED see Revision Indedx Sh.2

. GG

. 24/07/09

0

ISSUE

GG

REV

DESCRIPTION

PREP'D

. CHK'D

. APPR'D

ITEM

N. SOM 5461126 /3

TITLE

COVER SHEET

LANGUAGE

SHEET

A

20/03/09 DATE

1608994-97 .

JOB

© 2012 Nuovo Pignone S.r.l., all rights reserved

REPLACES

REPLACES

1/2 REPLACED BY

REPLACED

GE NuovoPignone - Electronically Approved Drawing - Checked: Garfagnini G.; Approved: Visintin F. - Internal DT-'N'

COMPANY DOCUMENT N° :

ACRONYMS LEGEND <1>

REVISION INDEX SHEET 1 2 3 4 5

TITLE

ADP

Auxiliary Distribution Panel

B/N

Bently Nevada

CMS

Control Monitoring System

DCP

Direct Current Panel

x x x x x xx x

F&G

Fire & Gas

x x x

HMI HS

x x x x

MCC PLC

Human Machine Interface Hydraulic Starter Motor Control Center Programmable Logic Controller

UCS

Unit Control System

x x x

UPS

x x x x x

SGS SIL

Unanteruptable Power Supply Safeguarding System

0 1 2 3 4 5 6 7

x x xx x xx x

COVER SHEET REV. INDEX, LEGEND AND GENERAL REMARKS HARDWIRED CONFIGURATION NETWORKS STANDARD CONFIGURATION LOAD SHARING AND MASTER CONTROL

x

x

6

POWER SUPPLY DISTRIBUTION NETWORK

7

OVERALL NETWORK ARCHITECTURE

x

8

IP NETWORK ADDRESSING TABLES

x x

Limits of Supply

OTHERS

GE OIL & GAS

7

Revised index

6

Revised index

Safety Integrated Level

5

Revised index

4

Revised where shown <4>

JOB

3

Revised where shown <3>

ITEM

2

Revised where shown <2>

1

Revised where shown <1>

0 REV

ISSUE DESCRIPTION

TITLE

CONTROL SYSTEM SCHEMATIC REVISION INDEX, LEGEND AND GENERAL REMARKS © 2012 Nuovo Pignone S.r.l., all rights reserved

REPLACES

N.

1608994-97

SOM5461126

LANGUAGE

/3

SHEET

A

2/3 REPLACED BY

<2>

CUSTOMER ELECTRICAL SUB-STATION MCC (Note 2)

CUSTOMER EQUIPMENT CONTROL ROOM

DCP CUSTOMER SGS

CUSTOMER CMS

PLANT F&G

<1>

EXTERNAL TRIP REQUEST

<2> DC MOTORS START/STOP AND RUNNING SIGNALS, DCP STATUS

<2>

VENTILATION CUT-OUT

Commands To/From Unit #2

TANK HEATER CUT-OUT

LUBE & SYNTHETIC OIL HEATER CUT-OUT

<1>

TRIP NOTIFICATION

NOTES 1. ONE HYDRAULIC STARTING SYSTEM IS COMMON FOR TWO GT UNITS. TWO HS ARE PROVIDED FOR ALL 4 GT UNITS. 2. AC MOTORS START/STOP, RUNNING SIGNALS, MCC STATUS (REDUNDANT MODBUS TCP/IP) SEE SH.4 FOR DETAILS 3. CUSTOMER CMS PROVIDES 4-20mA REPETITONS OF PD (DISCHARGE HEADER PRESSURE) & PS (SUCTION HEADER PRESSURE) TO MKVI. 4. ONLY INSIDE UCP1 & 3.

LOCAL ESD P.B.

CUMULATIVE FIRE & GAS TRIP NOTIFICATIONS

MKVI SIMPLEX TURBINE CONTROLLER

FIRE & GAS SYSTEM CUMULATIVE FIRE& GAS TRIP [FGS1]

Load Sharing and Master Controler signals To/From Unit #2 Load Sharing and Master Controler signals To/From Unit #3 Load Sharing and Master Controler signals To/From Unit #4

SEQUENCING, PROTECTION & CONTROL LOGIC

PERMISSIVES, FIRE ALARMS & TRIPS

Commands To/From Unit #1

UNIT CONTROL PANEL [UCP1]

COMMON ALARMS, OK STATUS, TRIP MULTIPLY CMD

MASTER LOAD SHARING

VIBRATION COMMON TRIP SIGNALS

[TCP1]

BN3590 VIBRATION MONITORING RACK [VIB1]

HYDRAULIC STARTER PLC [HSS1] HART MULTIPLEXER

GG SPEED PICK-UP to VIB.

<2>

REPEATER

GAS TURBINE

HYDRAULIC STARTING SKID

DIGITAL CONTROL & PROTECTION SIGNALS DIGITAL CONTROL & PROTECTION SIGNALS

ANALOG CONTROL & PROTECTION SIGNALS

CE-CO VIB. PROBES (RADIAL)

CE-CO BEARING & TEMPERATURES

GEAR BOX BEARING TEMPERATURES

GEAR BOX VIB. PROBES (ACCEL., RADIAL, AXIAL) & KEY PHASOR

GT VIB. PROBES (RADIAL, AXIAL), KEY PHASORS & GAS GEN. ACCELEROMETER

4-20mA CONTROL & PROTECTION SIGNALS

ANALOG CONTROL SIGNALS

DIGITAL CONTROL & PROTECTION SIGNALS

GT TEMPERATURES & GT

TEMPERATURES GT BEARING TEMPERATURES & GT BEARING TEMPERATURES

GT ENCLOSURE DP & COMB. CHAMBER FLAME DETECTION

FUEL GAS SHUT-OFF VALVE & FUEL GAS VENT VALVE

ESD FIELD PB’S

ESD FIELD PB’S

GT MAGNETIC SPEED PICK-UP’S

<2>

FIRE & GAS DETECTION SENSORS, MANUAL DISCHARGE PB’s

DIGITAL INTERFACES

ANALOG INTERFACES

(Note 4)

CE-CO

GEAR BOX

SUCTION/DISCHARGE HEADER PRESSURE

PROCESS GAS

UNIT CONFIGURATION

(NOTE 1)

Limits of supply

1608994-97

JOB ITEM

OTHERS

GE O&G

2

Revised where shown <2>

1

Revised where shown <1>

0 REV

ISSUE DESCRIPTION

TITLE

N.

CONTROL SYSTEM SCHEMATIC HARDWIRED CONFIGURATION © 2012 Nuovo Pignone S.r.l., all rights reserved

SOM 5461126/3

LANGUAGE

SHEET

A REPLACES

3/4 REPLACED BY

<2> <2> <3> To other MKVI in

Notes: 1. “Redundant Modbus Master Direct Link” over Ethrnet from MKVI to MCC. 2.Displayed Data and Alarms on Alarm Banner from: - MarkVI - Bently Nevada Monitors 3. Local Display for F&G is provided. 4. Provided only inside UCP1 & 3. 5. Common for ALL GT Units 6. DCS Cables in customer scope of supply

To Ethernet Switch in UCP#2

UCP #2 #3 #4

<6>

CUSTOMER ELECTRICAL SUB-STATION

CUSTOMER EQUIPMENT CONTROL ROOM MCC CPU

UNIT CONTROL PANEL [UCP1]

<1>

(8)

HYDRAULIC STARTER PLC [HSS1]

FIELD

(5) (5) (8)

PANEL PC

<2>

(note 4)

RS485/F.O. Converters

<1>(5) MarkVI SIMPLEX TURBINE CONTROLLER With Redundant Direct Modbus link [TCP1]

(3)

(3)

<1>

(5) (5)

<2>

(1)

(note 5)

To Ethernet Switches in UCP#2, #3, #4

(5)

COPPER TRUNKS

ADH PDH UDH

To Ethernet Switches in UCP#2, #3, #4

(5)

HMI

FIBER TRUNKS

<6>

(4)

<3>

<3>

ADH PDH UDH

GAS CHROMATOGRAPH MONITORING SYSTEM [GC1]

(7)

[FGS1]

(4)

COPPER TRUNKS

(4)

35000/91

35000/22

ADH PDH UDH

COPPER TRUNKS

COPPER TRUNKS

<6> FIBER TRUNKS

Remote Network switch #1 [ESWR1A]

(4)

FIBER TRUNKS

<6>

Remote Network switch #2 [ESWR1B]

DOT MATRIX PRINTER [PRN1]

Network switch #2 [ESW1B]

(4)

(4)

(4)

ADH PDH UDH

(4)

B/N VIBRATION MONITOR [VIB1]

(4)

(5)

Network switch #1 [ESW1A]

<3> (note 3) FIRE & GAS SYSTEM

LOCAL CONTROL PANEL [LCP1]

(3)

(2)

FIBER TRUNKS

HMI

(note 6)

(1)

(6) (1)

(1)

CMS

(2)

<1>

(note 2)

LOCAL HMI [HMIL1]

(2)

Links Legend: (1) EGD (Ethernet Global Data) protocol over Ethernet (UDH) (2) TCP/IP, SNMP, NTP over Ethernet (Copper Cable) (3) Modbus TCP/IP over Fiber Optics (in Customer Scope of Supply) (4) Trunk Connection (PDH&UDH), over Ethernet (5) Modbus Master over RS485 (6) Parallel connection (7) Modbus over Ethernet TCP/IP (8) “S90 Triplex” over Ethernet (PHD)

(2)

CUSTOMER DCS

CUSTOMER CONTROL ROOM Limits of supply OTHERS

GE O&G

6

Revised where shown <6>

3

Revised where shown <3>

2

Revised where shown <2>

1

Revised where shown <1>

0 REV

ISSUE DESCRIPTION

040.2222

JOB ITEM

N. SOM 5461126 /3

TITLE

CONTROL SYSTEM SCHEMATIC NETWORK TOPOLOGY FOR SINGLE UNIT © 2012 Nuovo Pignone S.r.l., all rights reserved

LANGUAGE

SHEET

A REPLACES

4/5 REPLACED BY

UCP1

UCP2 MKVI

SPEED CONTROL, ANTISURGE

SPEED CONTROL, ANTISURGE

UCP3 MKVI

Flow Set Point

Flow Set Point

MASTER PROCESS CONTROLLER

MASTER PROCESS CONTROLLER

& LOAD SHARING

& LOAD SHARING

Interface Control Signals via EGD

Flow Set Point

Interface Control Signals via EGD

Interface Control Signals via EGD From/To Unit1

MASTER PROCESS CONTROLLER & LOAD SHARING

Interface Control Signals via EGD From/To Unit1

Interface Control Signals via EGD From/To Unit4

PS & PD

PS & PD

PS & PD

PS & PD

MASTER PROCESS CONTROLLER

MKVI

SPEED CONTROL, ANTISURGE

& LOAD SHARING

Interface Control Signals via EGD From/To Unit3

Interface Control Signals via EGD From/To Unit4

MKVI

Flow Set Point

Interface Control Signals via EGD

<2>

SPEED CONTROL, ANTISURGE

UCP4

Interface Control Signals via EGD From/To Unit2

FT

PGT25 DLE

3BCL

CUSTOMER CMS (Note 1)

UNIT 1

<1> FT

PGT25 DLE

3BCL UNIT 2

PS

PS

PS PD

PD

PD

FT

PGT25 DLE

3BCL UNIT 3

Notes: 1. CUSTOMER CMS provides a 4-20mA signal repetition of PD (Discharge Pressure of the common line) and PS (Suction Pressure of the common line) by a MEDIAN voting logic to each MKVI.

Limits of supply FT

GE O&G

OTHERS

PGT25 DLE

3BCL

POSSIBLE STATUS FOR “MASTER PROCESS CONTROLLER” UCP1 AUTO TRACKING

UCP2

UCP3

UNIT 4

UCP4

TRACKING TRACKING TRACKING AUTO

TRACKING TRACKING

AUTO

TRACKING TRACKING TRACKING

ITEM

TRACKING AUTO

1608994-97

JOB

TRACKING TRACKING

2

Revised where shown <2>

1

Revised where shown <1>

0 REV

ISSUE DESCRIPTION

TITLE

N.

CONTROL SYSTEM SCHEMATIC LOAD SHARING & MASTER CONTROL © 2012 Nuovo Pignone S.r.l., all rights reserved

SOM 5461126 /3

LANGUAGE

SHEET

A REPLACES

5/6 REPLACED BY

Notes: 1. All these items are only inside UCP1 & 3. 2. Common for all GT Units.

110Vdc From DCP

<6> <4>

1.1Kw – 4 Hours

<1>

<1>

230Vac – 50Hz From UPS Line A 5.4Kw – ½ Hours

230Vac – 50Hz From UPS Line B 4.5Kw – 4 Hours

<3>

<3>

<2>

230Vac – 50Hz From ADP 2kw

<2> <2> CUSTOMER EQUIPMENT CONTROL ROOM

<2> <2>

<2>

UNIT CONTROL PANEL [UCP1] <1>

<1>

<2>

(note 1) 230Vac

(Spare 350W)

230Vac

230Vac

230Vac

230Vac

230Vac (Spare 350W)

24Vdc

24Vdc

230Vac

DACA

24Vdc

24Vdc

24Vdc

24Vdc

110Vdc

<2> MKVI POWER DISTRIBUTION MODULE (110 Vdc)

GAS CHROMAT. POWER UNIT 0.1KW FIELD SOLENOIDS

<3> LOCAL CONTROL PANEL (PULSE JET) 1KW

LOCAL CONTROL PANEL (HMI PANEL PC) On Field 150 W

24 Vdc SUPPLY LINE

<4>

HMI INTERFACE (PC, LCD, Printer, Eth Switches) On CCR

24 Vdc BUS

(note 2)

GAS CHROMATOGRAPH HMI INTERFACE (PC, LCD)

<2>

400 W

(Spare 350W)

100 W

VERSAMAX HS PLC Modules (RX3i #1)

900 W <6>

100 W

100 W

HS PLC (RX3i #2) 100 W

TURBINE CONTROL PANEL (MKVI)

BN3500 Vibration Monitor

Ethernet Switch #1

Ethernet Switch #2

1200 W

300 W

100 W

100 W

FIRE & GAS Detection Rack, Alarm Annunciator Panel/Horn 800 W

Barriers 300 W

SOLENOID & SHUT-OFF

HART Multiplexer

N.6 Internal Lighting

N.6 Ventilation FAN

N.1 Receptacle

500 W

150 W

40 W each

40 W each

1000 W

<3>

EARTH LEAKAGE CIRCUIT BREAKER AUTOMATIC CIRCUIT BREAKER

Limits of supply LOCKABLE ISOLATING SWITCH OTHERS

DOOR LIMIT SWITCH PLUG & SOCKET

GE O&G

6

Revised where shown <6>

4

Revised where shown <4>

3

Revised where shown <3>

2

Revised where shown <2>

1

Revised where shown <1>

0 REV

ISSUE DESCRIPTION

1608994-97

JOB ITEM

TITLE

CONTROL SYSTEM SCHEMATIC POWER SUPPLY DISTRIBUTION NETWORK © 2012 Nuovo Pignone S.r.l., all rights reserved

REPLACES

N.

SOM 5461126 /3

LANGUAGE

SHEET

A

6/7 REPLACED BY

UNIT CONTROL PANEL [UCP1] Local Network switch #1 [ESW1A]

ADH PDH UDH

COPPER TRUNKS

UNIT CONTROL PANEL [UCP3]

Local Network switch #2 [ESW1B] FIBER TRUNKS

ADH PDH UDH

COPPER TRUNKS

Local Network switch #1 [ESW3A] FIBER TRUNKS

FIBER TRUNKS

(3)

COPPER TRUNKS

UDH PDH ADH

(3)

(2)

(1)

Local Network switch #1 [ESW2A]

(2) (1)

ADH PDH UDH

COPPER TRUNKS

ADH PDH UDH

COPPER TRUNKS

UDH PDH ADH

(3)

Local Network switch #1 [ESW4A]

Local Network switch #2 [ESW2B] FIBER TRUNKS

COPPER TRUNKS

UNIT CONTROL PANEL [UCP4]

UNIT CONTROL PANEL [UCP2] (3)

Local Network switch #2 [ESW3B] FIBER TRUNKS

Local Network switch #2 [ESW4B] (1)

FIBER TRUNKS

FIBER TRUNKS

COPPER TRUNKS

UDH PDH ADH

FIBER TRUNKS

COPPER TRUNKS

(2)

UDH PDH ADH

(1)

(2)

(3)

(3)

(3)

(3)

(2) (1) (1) (2)

HMI

HMI

(2)

Redundant Remote Ethernet Switches [EWSR1A,EWSR1B]

(1)

HMI (1)

HMI

(2)

LOCAL HMI [HMIL2] LOCAL HMI [HMIL4]

(2)

CMS LOCAL HMI [HMIL1]

LOCAL HMI [HMIL3] (2)

(2)

(2)

(2) (2)

(2)

(2)

CUSTOMER DCS (note 1)

CUSTOMER CONTROL ROOM Notes: 1. CUSTOMER CMS and relevant connecting cables are in customer scope of supply

Links Legend: (1) EGD (Ethernet Global Data) protocol over Ethernet (UDH) (2) TCP/IP, SNMP, NTP over Ethernet (PDH) (3) Trunk Connection (PDH&UDH), over Ethernet

Limits of supply

1608994-97

JOB ITEM

OTHERS

TITLE

GE O&G 6 REV

ADDED Sh. DESCRIPTION

N.

CONTROL SYSTEM SCHEMATIC OVERALL NETWORK ARCHITECTURE © 2012 Nuovo Pignone S.r.l., all rights reserved

SOM 5461126 /3

LANGUAGE

SHEET

A REPLACES

7/8 REPLACED BY

TAG

Description

UDH

PDH

ADH NA NA

TCP1

Turbine Control Panel

192.168.101.1Y1

VIB1

Vibration Monitor (3500/91)

192.168.101.1Y4

NA NA

FGS1 HMIL1

Fire & Gas system Human Machine Interface

NA 192.168.101.00W

192.168.201.10Z 192.168.201.00W

NA NA

ESW1A ESW1B

Local Ethernet Switch A Local Ethernet Switch B

NA NA

192.168.201.22n 192.168.201.23n

NA NA

HSS1 LCP1

Hydraulic Starter PLC Local Control Panel

NA NA

192.168.201.0Y9 192.168.201.0Y7

NA NA

<7>

Table 1: UCP “y” Devices IP Addresses: (Y=1 W=4 Z=0), (Y=2 W=5 Z=1), (Y=3 W=6 Z=2), (Y=4 W=7 Z=3) <7> ESWR1A ESWR1B

Remote Ethernet switch A

NA NA

Remote Ethernet switch B

192.168.201.240 192.168.201.241

NA NA

Table 2: REMOTE Ethernet Switches IP Addresses

IP Ethernet Address: 192.168.ABC.XYZ Network Type

A Type

UDH

1

BC Network Number 01-99

X Controller/Device Number 1 = Gas Turbine 2= Steam Turbine

0 = All other devices on UDH

PDH

2

01-54

Y Unit Number 1= Unit 1 2= Unit 2 . . 8= Unit 8

1= Unit 1 2= Unit 2 . . 8= Unit 8 9=Remote (common to all units)

Z Type Of Device 1= R0 2 =S0 3= T0 4= VIB MON. 5= TEMP. MON. 6= SIS R0 7= SIS S0 8= SIS T0 9= PLC 0 = Static Starter 1= Local Main HMI 2 =Local Backup HMI 3= Historian 4= OSM 5= Comm. Gateway A 6= Comm. Gateway B 7= Remote HMI 8= F&G A (provision) 9= F&G B (provision) 0= NTP

Note 1: Devices such as HMI Servers, Communication Geteways, 20n with n from 1 to 49 are reserved Historian, Remote HMIs that are both on the UDH and PDH should use the same number for the last for switches octal in the IP address 25n with n from 1 to 4 are reserved Note 2: Fire & Gas or Fire fighting protection devices when for NTP servers on PDH should have address 192.168.201.0Y8 (and 0Y9 for the redundant device) 2 to 100 reserved for GE supplied items such as Viewers and Printers

Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26

ESWnA UCP 192.168.201.22n DeviceTag HMIL1 ( PDH main) CMS A HSS1

HMIL1 (UDH main)

Switch ESW1B Switch ESWR1A LCP1

Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic

Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk

Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26

Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk

Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26

ESWnB UCP 192.168.201.23n Device Tag HMIL1 (PDH backup) CMS B F&G1

HMIL1 (UDH backup) TCP1 VIB1 (3500/91)

Switch ESW1A Switch ESWR1B

Table 3: Local Switch A Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26

ESWR1A CCR 192.168.201.240 DeviceTag

Switch ESW1A Switch ESW2A Switch ESW3A Switch ESW4A

Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic

Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic

Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk

Table 4: Local Switch B ESWR1B CCR 192.168.201.241 Device Tag

Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic

Switch ESW1B Switch ESW2B Switch ESW3B Switch ESW4B

Table 5: Remote Switch A

Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk

Table 6: Remote Switch B

Table 7:Ethernet addressing rules

1608994-97

JOB ITEM

TITLE 7

Revised where shown <7>

6

ADDED Sh.

REV

DESCRIPTION

CONTROL SYSTEM SCHEMATIC IP NETWORK ADDRESSING TABLES © 2012 Nuovo Pignone S.r.l., all rights reserved