1046Z-00-DP-J-23K-GEI-000087
CONTRACTOR DOCUMENT N° : F10163 Project Code
Vendor Logo & Name :
PO Number:
GEI
INS
Vendor Discipline
Page:
1 de 8
DGM
000087
F
000
3
Document Type
Sequential N°
Lang.
Area:
Rev
Vendor Document N° :
NUOVO PIGNONE
SOM 5461126
SONATRACH
EXTRACTION DES LIQUIDES DES GAZ ASSOCIES HASSI MESSAOUD ET SEPARATION D’HUILE LDHP ZCINA ALGERIE ENC 08 1046Z
Unit Control System & Power Supply Schematic Contractor Return Code :
Vendor Action :
Reviewed without comments (1) Reviewed with comments (2)
New revision required : __
Rejected (3)
At the latest on __/__/__
Received for Information (4)
Date : __/__/__ (dd/mm/yy) Name : ____________________
IFR
(dd/mm/yy)
IFI
IFC
ASB
Signature : Comments :
7
REVISED see Revision Index Sh.2, AS BUILT WO 113984
6 5
El. Stored
Rev
Date
Page
Status
Description
Prepared by
Checked by
Approved by
3
21.05.13
8
FIN
ISSUED FOR CONSTRUCTION
CTQ
.
.
2
01.12.11
8
FIN
ISSUED FOR CONSTRUCTION
GARFAGNINI
GIOVANARDI
VISINTIN
1
21.09.10
6
FIN
ISSUED FOR CONSTRUCTION
GARFAGNINI
GIOVANARDI
VISINTIN
0
08.01.10
6
FIN
ISSUED FOR CONSTRUCTION
GARFAGNINI
GIOVANARDI
VISINTIN
D
22.11.09
6
COM
ISSUED FOR REVIEW
GARFAGNINI
GIOVANARDI
VISINTIN
C
30.09.09
6
COM
ISSUED FOR REVIEW
GARFAGNINI
GIOVANARDI
VISINTIN
B
24.07.09
6
COM
ISSUED FOR REVIEW
GARFAGNINI
GIOVANARDI
VISINTIN
A
20.03.09
6
COM
ISSUED FOR REVIEW
GARFAGNINI
GIOVANARDI
VISINTIN
21/05/13
CTQ
El. Stored
REVISED NETWORK ARCHITECTURE see Revision Index Sh.2
Baviera F.
Garfagnini G.
French Translation
Baviera F.
08/01/10 08/01/10
Visintin F.
01/12/11
4
REVISED see Revision Indedx Sh.2
GG
3
REVISED see Revision Indedx Sh.2
GG
22/11/09
2
REVISED see Revision Indedx Sh.2
GG
30/09/09
1
REVISED see Revision Indedx Sh.2
. GG
. 24/07/09
0
ISSUE
GG
REV
DESCRIPTION
PREP'D
. CHK'D
. APPR'D
ITEM
N. SOM 5461126 /3
TITLE
COVER SHEET
LANGUAGE
SHEET
A
20/03/09 DATE
1608994-97 .
JOB
© 2012 Nuovo Pignone S.r.l., all rights reserved
REPLACES
REPLACES
1/2 REPLACED BY
REPLACED
GE NuovoPignone - Electronically Approved Drawing - Checked: Garfagnini G.; Approved: Visintin F. - Internal DT-'N'
COMPANY DOCUMENT N° :
ACRONYMS LEGEND <1>
REVISION INDEX SHEET 1 2 3 4 5
TITLE
ADP
Auxiliary Distribution Panel
B/N
Bently Nevada
CMS
Control Monitoring System
DCP
Direct Current Panel
x x x x x xx x
F&G
Fire & Gas
x x x
HMI HS
x x x x
MCC PLC
Human Machine Interface Hydraulic Starter Motor Control Center Programmable Logic Controller
UCS
Unit Control System
x x x
UPS
x x x x x
SGS SIL
Unanteruptable Power Supply Safeguarding System
0 1 2 3 4 5 6 7
x x xx x xx x
COVER SHEET REV. INDEX, LEGEND AND GENERAL REMARKS HARDWIRED CONFIGURATION NETWORKS STANDARD CONFIGURATION LOAD SHARING AND MASTER CONTROL
x
x
6
POWER SUPPLY DISTRIBUTION NETWORK
7
OVERALL NETWORK ARCHITECTURE
x
8
IP NETWORK ADDRESSING TABLES
x x
Limits of Supply
OTHERS
GE OIL & GAS
7
Revised index
6
Revised index
Safety Integrated Level
5
Revised index
4
Revised where shown <4>
JOB
3
Revised where shown <3>
ITEM
2
Revised where shown <2>
1
Revised where shown <1>
0 REV
ISSUE DESCRIPTION
TITLE
CONTROL SYSTEM SCHEMATIC REVISION INDEX, LEGEND AND GENERAL REMARKS © 2012 Nuovo Pignone S.r.l., all rights reserved
REPLACES
N.
1608994-97
SOM5461126
LANGUAGE
/3
SHEET
A
2/3 REPLACED BY
<2>
CUSTOMER ELECTRICAL SUB-STATION MCC (Note 2)
CUSTOMER EQUIPMENT CONTROL ROOM
DCP CUSTOMER SGS
CUSTOMER CMS
PLANT F&G
<1>
EXTERNAL TRIP REQUEST
<2> DC MOTORS START/STOP AND RUNNING SIGNALS, DCP STATUS
<2>
VENTILATION CUT-OUT
Commands To/From Unit #2
TANK HEATER CUT-OUT
LUBE & SYNTHETIC OIL HEATER CUT-OUT
<1>
TRIP NOTIFICATION
NOTES 1. ONE HYDRAULIC STARTING SYSTEM IS COMMON FOR TWO GT UNITS. TWO HS ARE PROVIDED FOR ALL 4 GT UNITS. 2. AC MOTORS START/STOP, RUNNING SIGNALS, MCC STATUS (REDUNDANT MODBUS TCP/IP) SEE SH.4 FOR DETAILS 3. CUSTOMER CMS PROVIDES 4-20mA REPETITONS OF PD (DISCHARGE HEADER PRESSURE) & PS (SUCTION HEADER PRESSURE) TO MKVI. 4. ONLY INSIDE UCP1 & 3.
LOCAL ESD P.B.
CUMULATIVE FIRE & GAS TRIP NOTIFICATIONS
MKVI SIMPLEX TURBINE CONTROLLER
FIRE & GAS SYSTEM CUMULATIVE FIRE& GAS TRIP [FGS1]
Load Sharing and Master Controler signals To/From Unit #2 Load Sharing and Master Controler signals To/From Unit #3 Load Sharing and Master Controler signals To/From Unit #4
SEQUENCING, PROTECTION & CONTROL LOGIC
PERMISSIVES, FIRE ALARMS & TRIPS
Commands To/From Unit #1
UNIT CONTROL PANEL [UCP1]
COMMON ALARMS, OK STATUS, TRIP MULTIPLY CMD
MASTER LOAD SHARING
VIBRATION COMMON TRIP SIGNALS
[TCP1]
BN3590 VIBRATION MONITORING RACK [VIB1]
HYDRAULIC STARTER PLC [HSS1] HART MULTIPLEXER
GG SPEED PICK-UP to VIB.
<2>
REPEATER
GAS TURBINE
HYDRAULIC STARTING SKID
DIGITAL CONTROL & PROTECTION SIGNALS DIGITAL CONTROL & PROTECTION SIGNALS
ANALOG CONTROL & PROTECTION SIGNALS
CE-CO VIB. PROBES (RADIAL)
CE-CO BEARING & TEMPERATURES
GEAR BOX BEARING TEMPERATURES
GEAR BOX VIB. PROBES (ACCEL., RADIAL, AXIAL) & KEY PHASOR
GT VIB. PROBES (RADIAL, AXIAL), KEY PHASORS & GAS GEN. ACCELEROMETER
4-20mA CONTROL & PROTECTION SIGNALS
ANALOG CONTROL SIGNALS
DIGITAL CONTROL & PROTECTION SIGNALS
GT TEMPERATURES & GT
TEMPERATURES GT BEARING TEMPERATURES & GT BEARING TEMPERATURES
GT ENCLOSURE DP & COMB. CHAMBER FLAME DETECTION
FUEL GAS SHUT-OFF VALVE & FUEL GAS VENT VALVE
ESD FIELD PB’S
ESD FIELD PB’S
GT MAGNETIC SPEED PICK-UP’S
<2>
FIRE & GAS DETECTION SENSORS, MANUAL DISCHARGE PB’s
DIGITAL INTERFACES
ANALOG INTERFACES
(Note 4)
CE-CO
GEAR BOX
SUCTION/DISCHARGE HEADER PRESSURE
PROCESS GAS
UNIT CONFIGURATION
(NOTE 1)
Limits of supply
1608994-97
JOB ITEM
OTHERS
GE O&G
2
Revised where shown <2>
1
Revised where shown <1>
0 REV
ISSUE DESCRIPTION
TITLE
N.
CONTROL SYSTEM SCHEMATIC HARDWIRED CONFIGURATION © 2012 Nuovo Pignone S.r.l., all rights reserved
SOM 5461126/3
LANGUAGE
SHEET
A REPLACES
3/4 REPLACED BY
<2> <2> <3> To other MKVI in
Notes: 1. “Redundant Modbus Master Direct Link” over Ethrnet from MKVI to MCC. 2.Displayed Data and Alarms on Alarm Banner from: - MarkVI - Bently Nevada Monitors 3. Local Display for F&G is provided. 4. Provided only inside UCP1 & 3. 5. Common for ALL GT Units 6. DCS Cables in customer scope of supply
To Ethernet Switch in UCP#2
UCP #2 #3 #4
<6>
CUSTOMER ELECTRICAL SUB-STATION
CUSTOMER EQUIPMENT CONTROL ROOM MCC CPU
UNIT CONTROL PANEL [UCP1]
<1>
(8)
HYDRAULIC STARTER PLC [HSS1]
FIELD
(5) (5) (8)
PANEL PC
<2>
(note 4)
RS485/F.O. Converters
<1>(5) MarkVI SIMPLEX TURBINE CONTROLLER With Redundant Direct Modbus link [TCP1]
(3)
(3)
<1>
(5) (5)
<2>
(1)
(note 5)
To Ethernet Switches in UCP#2, #3, #4
(5)
COPPER TRUNKS
ADH PDH UDH
To Ethernet Switches in UCP#2, #3, #4
(5)
HMI
FIBER TRUNKS
<6>
(4)
<3>
<3>
ADH PDH UDH
GAS CHROMATOGRAPH MONITORING SYSTEM [GC1]
(7)
[FGS1]
(4)
COPPER TRUNKS
(4)
35000/91
35000/22
ADH PDH UDH
COPPER TRUNKS
COPPER TRUNKS
<6> FIBER TRUNKS
Remote Network switch #1 [ESWR1A]
(4)
FIBER TRUNKS
<6>
Remote Network switch #2 [ESWR1B]
DOT MATRIX PRINTER [PRN1]
Network switch #2 [ESW1B]
(4)
(4)
(4)
ADH PDH UDH
(4)
B/N VIBRATION MONITOR [VIB1]
(4)
(5)
Network switch #1 [ESW1A]
<3> (note 3) FIRE & GAS SYSTEM
LOCAL CONTROL PANEL [LCP1]
(3)
(2)
FIBER TRUNKS
HMI
(note 6)
(1)
(6) (1)
(1)
CMS
(2)
<1>
(note 2)
LOCAL HMI [HMIL1]
(2)
Links Legend: (1) EGD (Ethernet Global Data) protocol over Ethernet (UDH) (2) TCP/IP, SNMP, NTP over Ethernet (Copper Cable) (3) Modbus TCP/IP over Fiber Optics (in Customer Scope of Supply) (4) Trunk Connection (PDH&UDH), over Ethernet (5) Modbus Master over RS485 (6) Parallel connection (7) Modbus over Ethernet TCP/IP (8) “S90 Triplex” over Ethernet (PHD)
(2)
CUSTOMER DCS
CUSTOMER CONTROL ROOM Limits of supply OTHERS
GE O&G
6
Revised where shown <6>
3
Revised where shown <3>
2
Revised where shown <2>
1
Revised where shown <1>
0 REV
ISSUE DESCRIPTION
040.2222
JOB ITEM
N. SOM 5461126 /3
TITLE
CONTROL SYSTEM SCHEMATIC NETWORK TOPOLOGY FOR SINGLE UNIT © 2012 Nuovo Pignone S.r.l., all rights reserved
LANGUAGE
SHEET
A REPLACES
4/5 REPLACED BY
UCP1
UCP2 MKVI
SPEED CONTROL, ANTISURGE
SPEED CONTROL, ANTISURGE
UCP3 MKVI
Flow Set Point
Flow Set Point
MASTER PROCESS CONTROLLER
MASTER PROCESS CONTROLLER
& LOAD SHARING
& LOAD SHARING
Interface Control Signals via EGD
Flow Set Point
Interface Control Signals via EGD
Interface Control Signals via EGD From/To Unit1
MASTER PROCESS CONTROLLER & LOAD SHARING
Interface Control Signals via EGD From/To Unit1
Interface Control Signals via EGD From/To Unit4
PS & PD
PS & PD
PS & PD
PS & PD
MASTER PROCESS CONTROLLER
MKVI
SPEED CONTROL, ANTISURGE
& LOAD SHARING
Interface Control Signals via EGD From/To Unit3
Interface Control Signals via EGD From/To Unit4
MKVI
Flow Set Point
Interface Control Signals via EGD
<2>
SPEED CONTROL, ANTISURGE
UCP4
Interface Control Signals via EGD From/To Unit2
FT
PGT25 DLE
3BCL
CUSTOMER CMS (Note 1)
UNIT 1
<1> FT
PGT25 DLE
3BCL UNIT 2
PS
PS
PS PD
PD
PD
FT
PGT25 DLE
3BCL UNIT 3
Notes: 1. CUSTOMER CMS provides a 4-20mA signal repetition of PD (Discharge Pressure of the common line) and PS (Suction Pressure of the common line) by a MEDIAN voting logic to each MKVI.
Limits of supply FT
GE O&G
OTHERS
PGT25 DLE
3BCL
POSSIBLE STATUS FOR “MASTER PROCESS CONTROLLER” UCP1 AUTO TRACKING
UCP2
UCP3
UNIT 4
UCP4
TRACKING TRACKING TRACKING AUTO
TRACKING TRACKING
AUTO
TRACKING TRACKING TRACKING
ITEM
TRACKING AUTO
1608994-97
JOB
TRACKING TRACKING
2
Revised where shown <2>
1
Revised where shown <1>
0 REV
ISSUE DESCRIPTION
TITLE
N.
CONTROL SYSTEM SCHEMATIC LOAD SHARING & MASTER CONTROL © 2012 Nuovo Pignone S.r.l., all rights reserved
SOM 5461126 /3
LANGUAGE
SHEET
A REPLACES
5/6 REPLACED BY
Notes: 1. All these items are only inside UCP1 & 3. 2. Common for all GT Units.
110Vdc From DCP
<6> <4>
1.1Kw – 4 Hours
<1>
<1>
230Vac – 50Hz From UPS Line A 5.4Kw – ½ Hours
230Vac – 50Hz From UPS Line B 4.5Kw – 4 Hours
<3>
<3>
<2>
230Vac – 50Hz From ADP 2kw
<2> <2> CUSTOMER EQUIPMENT CONTROL ROOM
<2> <2>
<2>
UNIT CONTROL PANEL [UCP1] <1>
<1>
<2>
(note 1) 230Vac
(Spare 350W)
230Vac
230Vac
230Vac
230Vac
230Vac (Spare 350W)
24Vdc
24Vdc
230Vac
DACA
24Vdc
24Vdc
24Vdc
24Vdc
110Vdc
<2> MKVI POWER DISTRIBUTION MODULE (110 Vdc)
GAS CHROMAT. POWER UNIT 0.1KW FIELD SOLENOIDS
<3> LOCAL CONTROL PANEL (PULSE JET) 1KW
LOCAL CONTROL PANEL (HMI PANEL PC) On Field 150 W
24 Vdc SUPPLY LINE
<4>
HMI INTERFACE (PC, LCD, Printer, Eth Switches) On CCR
24 Vdc BUS
(note 2)
GAS CHROMATOGRAPH HMI INTERFACE (PC, LCD)
<2>
400 W
(Spare 350W)
100 W
VERSAMAX HS PLC Modules (RX3i #1)
900 W <6>
100 W
100 W
HS PLC (RX3i #2) 100 W
TURBINE CONTROL PANEL (MKVI)
BN3500 Vibration Monitor
Ethernet Switch #1
Ethernet Switch #2
1200 W
300 W
100 W
100 W
FIRE & GAS Detection Rack, Alarm Annunciator Panel/Horn 800 W
Barriers 300 W
SOLENOID & SHUT-OFF
HART Multiplexer
N.6 Internal Lighting
N.6 Ventilation FAN
N.1 Receptacle
500 W
150 W
40 W each
40 W each
1000 W
<3>
EARTH LEAKAGE CIRCUIT BREAKER AUTOMATIC CIRCUIT BREAKER
Limits of supply LOCKABLE ISOLATING SWITCH OTHERS
DOOR LIMIT SWITCH PLUG & SOCKET
GE O&G
6
Revised where shown <6>
4
Revised where shown <4>
3
Revised where shown <3>
2
Revised where shown <2>
1
Revised where shown <1>
0 REV
ISSUE DESCRIPTION
1608994-97
JOB ITEM
TITLE
CONTROL SYSTEM SCHEMATIC POWER SUPPLY DISTRIBUTION NETWORK © 2012 Nuovo Pignone S.r.l., all rights reserved
REPLACES
N.
SOM 5461126 /3
LANGUAGE
SHEET
A
6/7 REPLACED BY
UNIT CONTROL PANEL [UCP1] Local Network switch #1 [ESW1A]
ADH PDH UDH
COPPER TRUNKS
UNIT CONTROL PANEL [UCP3]
Local Network switch #2 [ESW1B] FIBER TRUNKS
ADH PDH UDH
COPPER TRUNKS
Local Network switch #1 [ESW3A] FIBER TRUNKS
FIBER TRUNKS
(3)
COPPER TRUNKS
UDH PDH ADH
(3)
(2)
(1)
Local Network switch #1 [ESW2A]
(2) (1)
ADH PDH UDH
COPPER TRUNKS
ADH PDH UDH
COPPER TRUNKS
UDH PDH ADH
(3)
Local Network switch #1 [ESW4A]
Local Network switch #2 [ESW2B] FIBER TRUNKS
COPPER TRUNKS
UNIT CONTROL PANEL [UCP4]
UNIT CONTROL PANEL [UCP2] (3)
Local Network switch #2 [ESW3B] FIBER TRUNKS
Local Network switch #2 [ESW4B] (1)
FIBER TRUNKS
FIBER TRUNKS
COPPER TRUNKS
UDH PDH ADH
FIBER TRUNKS
COPPER TRUNKS
(2)
UDH PDH ADH
(1)
(2)
(3)
(3)
(3)
(3)
(2) (1) (1) (2)
HMI
HMI
(2)
Redundant Remote Ethernet Switches [EWSR1A,EWSR1B]
(1)
HMI (1)
HMI
(2)
LOCAL HMI [HMIL2] LOCAL HMI [HMIL4]
(2)
CMS LOCAL HMI [HMIL1]
LOCAL HMI [HMIL3] (2)
(2)
(2)
(2) (2)
(2)
(2)
CUSTOMER DCS (note 1)
CUSTOMER CONTROL ROOM Notes: 1. CUSTOMER CMS and relevant connecting cables are in customer scope of supply
Links Legend: (1) EGD (Ethernet Global Data) protocol over Ethernet (UDH) (2) TCP/IP, SNMP, NTP over Ethernet (PDH) (3) Trunk Connection (PDH&UDH), over Ethernet
Limits of supply
1608994-97
JOB ITEM
OTHERS
TITLE
GE O&G 6 REV
ADDED Sh. DESCRIPTION
N.
CONTROL SYSTEM SCHEMATIC OVERALL NETWORK ARCHITECTURE © 2012 Nuovo Pignone S.r.l., all rights reserved
SOM 5461126 /3
LANGUAGE
SHEET
A REPLACES
7/8 REPLACED BY
TAG
Description
UDH
PDH
ADH NA NA
TCP1
Turbine Control Panel
192.168.101.1Y1
VIB1
Vibration Monitor (3500/91)
192.168.101.1Y4
NA NA
FGS1 HMIL1
Fire & Gas system Human Machine Interface
NA 192.168.101.00W
192.168.201.10Z 192.168.201.00W
NA NA
ESW1A ESW1B
Local Ethernet Switch A Local Ethernet Switch B
NA NA
192.168.201.22n 192.168.201.23n
NA NA
HSS1 LCP1
Hydraulic Starter PLC Local Control Panel
NA NA
192.168.201.0Y9 192.168.201.0Y7
NA NA
<7>
Table 1: UCP “y” Devices IP Addresses: (Y=1 W=4 Z=0), (Y=2 W=5 Z=1), (Y=3 W=6 Z=2), (Y=4 W=7 Z=3) <7> ESWR1A ESWR1B
Remote Ethernet switch A
NA NA
Remote Ethernet switch B
192.168.201.240 192.168.201.241
NA NA
Table 2: REMOTE Ethernet Switches IP Addresses
IP Ethernet Address: 192.168.ABC.XYZ Network Type
A Type
UDH
1
BC Network Number 01-99
X Controller/Device Number 1 = Gas Turbine 2= Steam Turbine
0 = All other devices on UDH
PDH
2
01-54
Y Unit Number 1= Unit 1 2= Unit 2 . . 8= Unit 8
1= Unit 1 2= Unit 2 . . 8= Unit 8 9=Remote (common to all units)
Z Type Of Device 1= R0 2 =S0 3= T0 4= VIB MON. 5= TEMP. MON. 6= SIS R0 7= SIS S0 8= SIS T0 9= PLC 0 = Static Starter 1= Local Main HMI 2 =Local Backup HMI 3= Historian 4= OSM 5= Comm. Gateway A 6= Comm. Gateway B 7= Remote HMI 8= F&G A (provision) 9= F&G B (provision) 0= NTP
Note 1: Devices such as HMI Servers, Communication Geteways, 20n with n from 1 to 49 are reserved Historian, Remote HMIs that are both on the UDH and PDH should use the same number for the last for switches octal in the IP address 25n with n from 1 to 4 are reserved Note 2: Fire & Gas or Fire fighting protection devices when for NTP servers on PDH should have address 192.168.201.0Y8 (and 0Y9 for the redundant device) 2 to 100 reserved for GE supplied items such as Viewers and Printers
Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26
ESWnA UCP 192.168.201.22n DeviceTag HMIL1 ( PDH main) CMS A HSS1
HMIL1 (UDH main)
Switch ESW1B Switch ESWR1A LCP1
Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic
Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk
Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26
Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk
Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26
ESWnB UCP 192.168.201.23n Device Tag HMIL1 (PDH backup) CMS B F&G1
HMIL1 (UDH backup) TCP1 VIB1 (3500/91)
Switch ESW1A Switch ESWR1B
Table 3: Local Switch A Switch Location IP Address Ports Port_1 Port_2 Port_3 Port_4 Port_5 Port_6 Port_7 Port_8 Port_9 Port_10 Port_11 Port_12 Port_13 Port_14 Port_15 Port_16 Port_17 Port_18 Port_19 Port_20 Port_21 Port_22 Port_23 Port_24 Port_25 Port_26
ESWR1A CCR 192.168.201.240 DeviceTag
Switch ESW1A Switch ESW2A Switch ESW3A Switch ESW4A
Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic
Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic
Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk
Table 4: Local Switch B ESWR1B CCR 192.168.201.241 Device Tag
Cable Type CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CAT5 CrossOver CrossOver CrossOver CrossOver CrossOver Fiber Optic Fiber Optic
Switch ESW1B Switch ESW2B Switch ESW3B Switch ESW4B
Table 5: Remote Switch A
Subnet PDH PDH PDH PDH PDH PDH PDH PDH UDH UDH UDH UDH UDH UDH UDH UDH ADH ADH ADH Copper Trunk Copper Trunk Copper Trunk Copper Trunk Copper Trunk Fiber Trunk Fiber Trunk
Table 6: Remote Switch B
Table 7:Ethernet addressing rules
1608994-97
JOB ITEM
TITLE 7
Revised where shown <7>
6
ADDED Sh.
REV
DESCRIPTION
CONTROL SYSTEM SCHEMATIC IP NETWORK ADDRESSING TABLES © 2012 Nuovo Pignone S.r.l., all rights reserved
REPLACES
N.
SOM 5461126 /3
LANGUAGE
SHEET
A
8/8 REPLACED BY