Loading documents preview...
Institute of Integrated Electrical Engineers of the Philippines, Inc. 41 Monte de Piedad St., Cubao, Quezon City
A Technical Report on
Differences in ANSI/IEEE and IEC Short Circuit Calculations and Their Implications
___________________________________________________________________
Prepared by: Institute of Integrated Electrical Engineers, Inc. (IIEE) – Standards Committee 2011
Differences in ANSI/IEEE and IEC Short Circuit Calculations and Their Implications
Prepared by: IIEE Standards Committee March 19, 2011
i
Disclaimer It is not the intention of this paper to endorse over another the compared short-circuit calculations and standards. All discussions in this report are based on the featured system one line diagram only. The same parameters were considered for the American National Standards Institute/Institute of Electrical and Electronics Engineers (ANSI/IEEE) and the International Electro-technical Commission (IEC) calculations for result comparison. The values of these parameters, however, may vary from every project in terms of available utility short circuit levels, power system configuration, wiring method and all applicable factors to consider. IIEE and this Committee will not be responsible for any disputes that may arise out of referencing from this paper.
ii
Preface This technical report focuses on two of the most widely used short circuit calculation methods and standards/guidelines namely: American National Standards Institute/Institute of Electrical and Electronics Engineers (ANSI/C37/IEEE std 551) and the International Electrotechnical Commission (IEC 60909). To fully understand the analytical techniques of short circuit current analysis in industrial and commercial power system using both methods, a representative network model was exemplified and a comprehensive comparison between the two calculation methods was presented. For expediency, a short circuit calculating software was employed and the results were presented and evaluated at the end of the analysis. This technical report provides information and inculcates awareness to electrical practitioners in the country on the difference in the procedure of short circuit calculations and its implication between the standards cited. It is not intended to show the detailed short circuit current calculation for both methods. The reader is still recommended to consult technical books for reference on a complete and accurate calculation procedure. This paper starts off with a brief introduction on the current scenario in the Philippines and the importance of short circuit calculation in Chapter I and expounds on its basic principle in Chapter II. The equivalent short circuit schematic diagram is also available for analysis in simple calculation. Chapter III discusses the asymmetry current application focusing on the importance of determining the total available short circuit current in the design of electrical equipment such as circuit breakers, switches, transformers and fuses that are subjected to fault current. Chapter IV shows the different components in determining the short circuit calculation based on the two standard/guidelines, the ANSI/IEEE and the IEC. This is followed by Chapter V presenting the comparative matrix on both standards’ Calculation Method and Multiplying Factors with reference to the X/R ratio. Chapter VI clearly tabulates a comparison between the standards’ parameters particularly the device type, device capability and the calculated short circuit duty. In Chapter VII, an illustration of a sample network was configured consisting of two power transformers connected to a 13.2 kV bus wherein two different results from the ANSI/IEEE and IEC calculations were generated with the aid of short circuit calculating software. Chapter VIII presents the protective devices selection and evaluation focusing on the X/R ratio for breaker evaluation and on the short circuit test parameters while Chapter IX discusses the findings and results of the ETAP Total Bus Fault Short Circuit Study. The tables on the short circuit calculation clearly show the difference in values for the same parameters between ANSI/IEEE and IEC. This technical report was developed through the initiative of the IIEE Standards Committee. Any concern or contention as to its applicability, accuracy and completeness shall be addressed to the Institute of Integrated Electrical Engineers of the Philippines, Inc. for further validation and interpretation.
iii
Participants The following are the working group members of the Institute of Integrated Electrical Engineers of the Philippines, Inc. (IIEE) under the Standards Committee: Chairman: Gem J. Tan Fuji-Haya Audit Inspection and Maintenance Corporation Members: Arjun G. Ansay Technological University of the Philippines – Manila
Jesus C. Santos JC Santos and Associates
Arturo M. Zabala AC-DC-KV and Associates
Marites R. Pangilinan LJ Industrial Fabrication, Inc.
Edwin V. Pangilinan Total Power Box Solution, Inc.
Roderick T. Khu Airnergy and Renewables, Inc.
Frumencio T. Tan Safety Consultant
Samson D. Paden Department of Trade and IndustryBureau of Product Standards
Genesis A. Ramos Department of Energy
Vincent E. Jimenez Delta Power Engineering and Consulting
Gideon S. Tan Yu Eng Kao Electrical Supply and Hardware, Inc.
Wilson T. Yu Standards Committee Member
Jaime S. Jimenez Meralco Advisers: Arthur A. Lopez Private Consultant IIEE former president - year 2000 Willington K.K.C. Tan Columbia Wire and Cable Corporation IIEE former president - year 1990
Approved by the members of the IIEE Board of Governors on March 19, 2011: Armando R. Diaz, President
Virgilio S. Luzares, Region II
Jules S. Alcantara, VP- Internal Affairs
Roselyn C. Rocio, Region IV
Gregorio R. Cayetano, VP- External Affairs
Ronaldo D. Ebrada, Region V
Alex C. Cabugao, VP- Technical Affairs
Marlon T. Marcuelo, Region VI
Ma. Sheila C. Cabaraban, Secretary
Lelanie T. Mirambel, Region VII
Larry C. Cruz, Treasurer
Rey G. Paduganan, Region VIII
Florigo, C. Varona, Auditor
Victorianito E. Teofilo, Region IX
Francis R. Calanio, Region I
Gregorio Y. Guevarra, Immediate former President
iv
Table of Contents Chapter
Title
Page
I.
Introduction
1
II.
Basic Short-Circuit Discussion Figure 1 : Current Model for Asymmetry Figure 2 : Maximum Peak Asymmetrical Short Circuit Current
1 1 2
III.
Asymmetry Current Application
2
IV.
Short-Circuit Current Calculation Standard/Guideline
3
V.
Calculation Comparison Table 1 : Comparison Matrix of ANSI/IEEE and IEC
3 4
VI.
Comparison of Device Duty Rating and Short-Circuit Duty Table 2 : ANSI/IEEE Parameter Table 3 : IEC Parameter Table 4 : ANSI/IEEE vs. IEC Parameter
5 5 5 5
VII.
Sample Calculation using ANSI/IEEE and IEC Figure 3 : Single Line Diagram of the Sample Network Figure 4 : Single Line Diagram to consider IEC SC Result Figure 5 : Single Line Diagram to consider ANSI SC Result Figure 6 : Impedance Diagram for ANSI/IEEE SC Method
6 6 7 16 23
VIII.
Protective Devices Selection and Evaluation Table 5 : Circuit Breakers Short Circuit Breaking Capacity Table 6 : Circuit Breakers Interrupting Capacity
26 26 27
IX.
Findings and Results Table 7 : IEC Short Circuit Calculation Table 8 : ANSI Short Circuit Calculation
27 27 27
X.
Conclusion and Recommendation
28
XI.
References
29
Appendix ABB MCB S200 Technical Features
30
v
I.
Introduction
In the emerging world market place, Electrical Engineers should be familiar with the basic differences between the American National Standards Institute (ANSI) and the International Electro-technical Commission (IEC) with regards to short circuit current calculation procedures. Both the ANSI and the IEC Standards developed these procedures to provide rating for electrical equipment. These two standards are currently being applied by the electrical practitioners in the Philippines and it is important to determine the differences between these standards so that a more logical evaluation and breaker rating selection can be appropriated. IEC procedure requires significantly more detailed modeling of the power system short circuit contribution than ANSI. A short circuit calculation is an important task undertaken by a professional in power systems planning and operation. Circuit breaker and switchgear selection, protection settings and coordination require a comprehensive, detailed and accurate short-circuit calculation. The report focuses on the guidelines found in the following shortcircuit standards: the North American ANSI/IEEE standard and its European counterpart, IEC.
II.
Basic Short Circuit Discussion
To come up with a precise short circuit calculation requires a very complex computation. What is important is that whatever the short circuit calculation method used, it should be compared with the assigned (tested) fault current rating of the protective devices. The final equivalent short circuit schematic diagram is shown below. R
L
i(t)
~
√2 Esin(ωt + Ø)
Figure 1: Current Model for Asymmetry The circuit constitutes a series of resistance, inductance, and a switch connected to an ideal sinusoidal voltage source. The fault is simulated by closing the switch and the magnitude of the rms symmetrical short circuit current, I, is determined by the equation below.
I where:
E Z
I = short circuit current (rms symmetrical) E = driving voltage (rms) Z = Thevenin’s equivalent system impedance from the fault point back to and including the source or sources of short-circuit currents for the distribution system.
The duration and magnitude of the asymmetrical current depends on the following parameters: a) The X/R ratio of the faulted circuit b) The phase angle of the voltage waveform at the time the short circuit occur 1
The asymmetrical fault current decay time is longer when X/R ratio is greater at the fault point. For specific X/R ratio, the angle of the applied voltage at the time of short-circuits initiation determines the degree of fault current asymmetry that will exist for that X/R ratio. The maximum asymmetrical short-circuit current occurs at the fault inception when the voltage sine wave is at zero point and not necessarily at the highest dc component.
Figure 2: Maximum Peak Asymmetrical Short Circuit Current
III. Asymmetry Current Application From the equipment design and application point of view, the phase with the largest fault peak current should be of major interest. This current subjects the equipment to the most severe magnetic force. The maximum magnetic force produced on a circuit element, such as a breaker, occurs at the instant the fault current through the circuit element is at a maximum. The largest fault peak typically occurs in the first cycle when the initiation of the shortcircuit current is near or coincident with the applied voltage passing through zero. This condition is called the condition of maximum asymmetry. Electrical equipment such as circuit breakers, switches, transformers and fuses that are subjected to carry fault current, the total available short circuit current must be determined. For correct equipment application, knowledge of the minimum test X/R ratio or maximum power factor of the applied fault current used in the acceptance test by ANSI, NEMA, UL and IEC is also required. Knowledge of peak fault current magnitudes are significant for some devices, such as low voltage breakers, while asymmetrical rms current magnitudes are equally significant for high voltage circuit breakers. This leads to the need to develop an X/R ratio dependent short circuit calculation for proper comparison to the equipment being applied. To determine the maximum peak or rms current magnitude that can occur in a circuit, every fault current calculation must consider the symmetrical ac component and the transient dc component of the calculated fault current. When the calculated fault X/R ratio is greater than the equipment X/R ratio, the higher X/R ratio must also be considered when evaluating or selecting the equipment.
2
IV. Short Circuit Calculation Standard / Guideline ANSI C37/IEEE Std. 551 The ANSI/IEEE method calls for determining the momentary network fault impedance which makes it possible to calculate the close and latch rating of the breaker. It also calls for identifying the interrupting network fault impedance which makes it possible to calculate the interrupting duty of the breaker. The interrupting network fault impedance value differs from the momentary network in that the impedance increases from the sub-transient to transient level. The IEEE standard permits the exclusion of 3 phase induction motors below 50 hp and all single phase motors. Hence no reactance adjustment is required for these sizes of motors. For detailed calculation requirements please refer to the applicable standards. IEC60909 The IEC method calls for the adjusted network impedance in calculating the symmetrical three phase fault (I” k) at a voltage higher than the nominal rating by a factor (c). The result is further manipulated to calculate peak current ip which is then compared to the breaker’s making capacity (I cm). Also, further manipulation of the calculated three-phase fault current I”k will result to the interrupting rating requirement that is compared to the selected breaker’s interrupting capacity (Ib). For detailed calculation requirements please refer to the applicable standards.
V.
Calculation Comparison
Table 1 presents a brief comparison of the ANSI/IEEE and IEC with regards to short circuit current calculation method and multiplying factors.
3
Table 1: Comparison of ANSI/IEEE and IEC Standard Calculation Method
ANSI/IEEE North America
IEC Europe Predominant
1. Voltage Source is equivalent to the pre-fault voltage at the location
4. Bolted Fault is assumed hence arc resistance is neglected
1. Pre-fault voltage is automatically adjusted by a factor ( c ) 2. Machines are represented by their internal impedances 3. Line capacitance of transmission lines and static loads are considered for unbalanced ground faults following a Shunt Admittance Model 4. System impedances are assumed balanced 3-phase 5. Uses symmetrical components for unbalanced fault calculations
5. System impedances are assumed balanced 3-phase
6. (I”k) Initial RMS Symmetrical SCC calculates through adjusted impedance network of synchronous
2. Machines are represented by their internal impedances 3. Line capacitance and static loads are neglected
machine Zk
6. Uses symmetrical components for unbalanced fault calculations
7. (ip) Peak Short circuit current =
7. Momentary calculates through sub-transient impedance network at half cycle
8. (Ib) Symmetrical Short-Circuit
8. Interrupting calculates through transient impedance network at 1.5 – 4 cycles 9. Steady-State calculates through steady-state impedance network at and beyond 30 cycles
k1*sqrt 2* I”k where k is determined by Method A, B or C Breaking Current = I”k for near generator faults and = u*I”k for synch machines = u*q*I”k for asynch. machines 9. Asymmetrical SC Breaking Current = I”k + Idc component current 10.Steady State SC current (Ik) accounts for power grid, generator and synch machine contributions (ip) Peak Short circuit current = k1*sqrt. 2 * I”k
Multiplying Factors
1. MF(m) Momentary multiplying factor – I mom. rms asym = I mom. rms sym * MF(m) 2. MF(p) Peak multiplying factor – I mom. peak = I mom. rms. Sym * MF(p) 4
1. C – pre-fault voltage factor (taken from IEC) 2. k – factors determined by IEC method A, B or C
VI. Comparison of Device Duty Rating and Short-Circuit Duty The tables below show the different parameters used in evaluating a protective device in terms of calculated short circuit duty of the ANSI/IEEE and IEC Standards. Table 2:
ANSI/IEEE Parameter
DEVICE TYPE HV BUS BRACING LV BUS BRACING HVCB LVCB Table 3:
Asymm. KA rms Symm. KA rms Symm. KA rms Asymm. KA rms C and L Capability KA rms C and L Capability KA Crest Interrupting KA
CALCULATED SHORTCIRCUIT DUTY (Momentary Duty) Asymm. KA rms Symm. KA rms Symm. KA rms Asymm. KA rms Asymm. KA rms Asymm. KA Crest Adjusted KA
Rated Interrupting KA
Adjusted KA
DEVICE CAPABILITY
IEC Parameter
DEVICE TYPE
CALCULATED SHORT-CIRCUIT DUTY (Momentary Duty) ip
DEVICE CAPABILITY Making
MVCB
AC Breaking
Ib ,symm
Making
LVCB Fuse
ip
Breaking
Ib ,symm
Breaking
Ib ,symm
Table 4: The ANSI/IEEE vs. IEC DEVICE TYPE DEVICE CAPABILITY ANSI
IEC
HVCB
MVCB
ANSI
IEC
C and L cap. KA rms
Making (ip)
C and L cap. KA rest
n/a
Interrupting KA
AC breaking (Isc) Ib asymm
CALCULATED SHORT CIRCUIT DUTY ANSI IEC Asymm. KA ip rms Asymm. KA rest Adjusted KA Ib symm Ib asymm
Idc LVCB
LVCB
Rated interrupting KA
Iohm
Ish
Breaking (Ib symm) ICU
Ib symm
Making peak (ICM)
ip
Ib asymm
Ib asymm
Ish
Ish
5
or Ik
VII. Sample Calculation using ANSI/IEEE and IEC Description of Sample network The sample network consists of two power transformers connected to a 13.2 KV bus. One of the transformers feeds a bus at a nominal voltage of 240 V, while the other transformer feeds a bus at a nominal voltage of 2.3 KV. The data of the transformer and other equipment and their principal characteristics are presented in Fig. 3. For the purpose of presenting a discussion on fault calculation, points B l and B2 are selected to have experienced a 3 phase bolted fault.
Figure 3: Single Line Diagram of the Sample Network
6
A. IEC SHORT CIRCUIT RESULT
Figure 4: Single Line Diagram to consider IEC SC Result 7
ETAP 6.0.0C
Project:
Page:
1
Date:
10-19-2010
Contract:
SN:
FUJIHAYAPH
Engineer:
Revision: Base
Location:
Study Case: SC
Filename: sample
Config.: Normal
Electrical Transient Analyzer Program Short-Circuit Analysis IEC 60909 Standard 3-Phase Fault Currents Maximum Short-Circuit Current
Number of Buses:
Number of Branches:
Swing 1
V-Control 0
Load 7
Total 8
XFMR2 2
XFMR3 0
Reactor 0
Line/Cable 0
Synchronous Generator Number of Machines:
0
Power Synchronous Induction Motor Machines Grid 1 0 5
Impedance 0
Tie PD 5
Lumped Load
Total
1
7
System Frequency: 60 Hz Unit System:
English
Project Filename:
sample
Output Filename:
D:\Etap6.0 Projects\SC sample attachments_2010_10_18\Untitled.SI1
8
Total 7
Adjustments Apply Adjustment
Individual /Global
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
Overload Heater Resistance:
No
Transmission Line Length:
No
Cable Length:
No
Tolerance
Percent
Apply Adjustment
Individual /Global
Degree C
Transformer Resistance:
Yes
Global
20
Cable Resistance:
Yes
Global
20
Temperature Correction
Bus Input Data Bus
Initial Voltage
ID
Type
Nom. kV
Base kV
Sub-sys
%Mag.
Ang.
B1
Load
0.240
0.240
1
100.00
0.00
B2
Load
2.300
2.300
1
100.00
0.00
Bus4
Load
0.240
0.240
1
100.00
0.00
Bus5
Load
2.300
2.300
1
100.00
0.00
Bus6
Load
2.300
2.300
1
100.00
0.00
Bus7
Load
2.300
2.300
1
100.00
0.00
Bus8
Load
2.300
2.300
1
100.00
0.00
UB
SWNG
13.200
13.200
1
100.00
0.00
8 Buses Total All voltages reported by ETAP are in % of bus Nominal kV. Base kV values of buses are calculated and used internally by ETAP
2-Winding Transformer Input Data Transformer
Rating
Z Variation
% Tap Setting
Adjusted
Phase Shift
ID
MVA
Prim. kV
T1
1.500
13.200
0.240
5.75
7.10
0
0
0
0
0
5.7500
Std Pos. Seq.
0.0
T2
5.000
13.200
2.300
7.15
12.14
0
0
0
0
0
7.1500
Std Pos. Seq.
0.0
Sec. kV
%Z
X/R
+5%
-5%
%Tol.
Prim.
Sec.
%Z
Type
Angle
Branch Connections CKT/Branch
Connected Bus ID
% Impedance, Pos. Seq., 100 MVAb
ID
Type
From Bus
To Bus
R
X
Z
T1
2W XFMR
UB
B1
51.58
366.13
369.74
T2
2W XFMR
UB
B2
11.76
142.82
143.31
CB6
Tie Breaker
B1
Bus4
CB7
Tie Breaker
B2
Bus5
CB8
Tie Breaker
B2
Bus6
CB9
Tie Breaker
B2
Bus7
CB10
Tie Breaker
B2
Bus8
9
Y
Power Grid Input Data Power Grid
Connected Bus
ID
ID
MVAsc
kV
U1
UB
720.000
13.200
R
% Impedance 100 MVA Base X"
R/X
0.00014
13.88889
0.00
Rating
Total Connected Power Grids ( = 1 ): 720.000 MVA
Induction Machine Input Data Induction Machine ID
Connected Bus
% Impedance (Motor Base)
Rating
ID
mFact.
Type
Qty
HP/kW
kVA
kV
Amp
PF
R
X"
R/X"
MW/PP
M2
Motor
1
Bus5
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M3
Motor
1
Bus6
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M4
Motor
1
Bus7
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M5
Motor
1
Bus8
500.00
440.28
2.300
110.52
90.82
2.96
15.41
0.19
0.19
M1
Motor
1
Bus4
125.00
110.12
0.240
264.91
91.51
4.62
16.01
0.29
0.05
Total Connected Induction Machines ( = 5 ): 1871.3 kVA
Lumped Load Input Data Lumped Load Lumped Load
Connected Bus
Motor Loads Rating
ID
ID
kVA
kV
L1
B1
1000.0
0.240
% Load Amp
% PF
MTR
2405.63
85.00
60
Total Connected Lumped Loads ( = 1 ): 1000.0 kVA
10
% Impedance Machine Base
Loading
STAT 40
m Fact.
kW
kvar
R
X"
R/X"
MW/PP
510.0
316.1
6.46
15.37
0.42
0.51
SHORT - CIRCUIT REPORT B1
3-Phase fault at bus: Nomimal kV Voltage c Factor Peak Value Steady State
= = = =
0.240 1.10 181.348 68.754
(Maximum If) kA Method A kA rms
Contribution From Bus
To Bus
ID
ID
B1
Total
%V From Bus 0.00
UB
B1
Voltage and Initial Symmetrical Current (rms) kA kA X/R kA Real
Imaginary
Ratio
Magnitude
13.406
-78.631
5.9
79.766
96.12
9.232
-68.170
7.4
68.792
L1
B1
100.00
3.690
-8.782
2.4
9.526
M1
Bus4
100.00
0.485
-1.680
3.5
1.748
Bus4
B1
0.00
0.485
-1.680
3.5
1.748
Breaking and DC Fault Current (kA) Based on Total Bus Fault Current TD (S)
Ib sym
Ib asym
Idc
0.01
78.916
101.347
63.588
0.02
78.315
86.941
37.756
0.03
77.529
80.547
21.843
0.04
76.761
77.794
12.637
0.05
76.017
76.406
7.704
0.06
75.656
75.79
4.504
0.07
75.301
75.347
2.633
0.08
74.952
74.968
1.539
0.09
74.610
74.616
0.939
0.10
74.275
74.277
0.551
0.15
73.582
73.582
0.039
0.20
72.918
72.918
0.003
0.25
72.285
72.285
0.000
0.30
72.260
72.260
0.000
11
3-Phase fault at bus:
B2
Nomimal kV
= 2.300
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 51.136
kA Method A
Steady State
= 17.417
kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus ID
To Bus ID
%V From Bus
kA Real
kA Imaginary
X/R Ratio
kA Magnitude
B2
Total
0.00
1.882
-20.420
10.9
20.506
UB
B2
90.44
1.297
-17.377
13.4
17.425
M5
Bus8
100.00
0.146
-0.761
5.2
0.775
M4
Bus7
100.00
0.146
-0.761
5.2
0.775
M3
Bus6
100.00
0.146
-0.761
5.2
0.775
M2
Bus5
100.00
0.146
-0.761
5.2
0.775
Bus5
B2
0.00
0.146
-0.761
5.2
0.775
Bus6
B2
0.00
0.146
-0.761
5.2
0.775
Bus7
B2
0.00
0.146
-0.761
5.2
0.775
Bus8
B2
0.00
0.146
-0.761
5.2
0.775
Breaking and DC Fault Current (kA) Based on Total Bus Fault Current TD (S)
Ib sym
Ib asym
Idc
0.01
20.014
28.877
20.816
0.02
19.722
25.04
15.429
0.03
19.441
22.464
11.254
0.04
19.174
20.857
8.208
0.05
18.921
19.955
6.342
0.06
18.799
19.373
4.679
0.07
18.681
18.997
3.453
0.08
18.566
18.74
2.548
0.09
18.456
18.564
2.001
0.10
18.349
18.409
1.486
0.15
18.145
18.148
0.336
0.20
17.954
17.954
0.076
0.25
17.775
17.775
0.017
0.30
17.769
17.769
0.004
12
3-Phase fault at bus:
Bus4
Nomimal kV
= 0.240
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 181.348
kA Method A
Steady State
= 68.754
kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus ID
To Bus ID
%V From Bus
kA Real
kA Imaginary
X/R Ratio
kA Magnitude
Bus4
Total
0.00
13.406
-78.631
5.9
79.766
M1
Bus4
100.00
0.485
-1.680
3.5
1.748
UB
B1
96.12
9.232
-68.170
7.4
68.792
L1
B1
100.00
3.690
-8.782
2.4
9.526
B1
Bus4
0.00
12.921
-76.952
6.0
78.029
Breaking and DC Fault Current (kA) Based on Total Bus Fault Current TD (S)
Ib sym
Ib asym
0.01
78.916
101.347
63.588
0.02
78.315
86.941
37.756
0.03
77.529
80.547
21.843
0.04
76.761
77.794
12.637
0.05
76.017
76.406
7.704
0.06
75.656
75.790
4.504
0.07
75.301
75.347
2.633
0.08
74.952
74.968
1.539
0.09
74.61
74.616
0.939
0.10
74.275
74.277
0.551
0.15
73.582
73.582
0.039
0.20
72.918
72.918
0.003
0.25
72.285
72.285
0.000
0.30
72.26
72.260
0.000
13
Idc
3-Phase fault at bus:
UB
Nomimal kV
= 13.200
Voltage c Factor
= 1.10
(Maximum If)
Peak Value
= 90.256
kA Method A
Steady State
= 31.492
kA rms
Contribution
Voltage and Initial Symmetrical Current (rms)
From Bus ID
To Bus ID
%V From Bus
kA Real
kA Imaginary
X/R Ratio
kA Magnitude
UB
Total
0.00
0.142
-32.117
226.5
32.117
B1
UB
13.64
0.060
-0.167
2.8
0.178
B2
UB
13.86
0.081
-0.458
5.7
0.465
U1
UB
100.00
0.000
-31.492
99999.0
31.492
Breaking and DC Fault Current (kA) Based on Total Bus Fault Current TD (S)
Ib sym
Ib asym
Idc
0.01
32.048
55.226
44.977
0.02
32.004
55.166
44.934
0.03
31.959
54.943
44.692
0.04
31.915
54.723
44.452
0.05
31.874
54.998
44.82
0.06
31.853
54.889
44.701
0.07
31.833
54.781
44.583
0.08
31.814
54.674
44.464
0.09
31.795
55.076
44.971
0.10
31.777
55.024
44.921
0.15
31.74
54.801
44.674
0.20
31.706
54.581
44.427
0.25
31.673
54.362
44.182
0.30
31.672
54.164
43.939
14
Short Circuit Summary Report 3-Phase FaultCurrent
Bus ID B1
Device kV
ID
Type
Device Capacity (kA) Making Peak
Ib sym
Short-Circuit Current (kA)
Ib asym
Idc
I"k
ip
79.766
181.348
Ib sym
Ib asym
Idc
Ik
0.240
B1
Bus
0.240
CB2
CB
220.000
100.000
102.111
79.766
181.348
77.920
83.044
28.718
0.240
CB6
CB
176.000
80.000
80.426
79.766
181.348*
77.219
77.219
17.549
B2
2.300
B2
Bus
20.506
51.136
17.417
Bus4
0.240
Bus4
Bus
79.766
181.348
68.754
0.240
CB6
CB
79.766
181.348*
UB
13.200
UB
Bus
32.117
90.256
176.000
80.000
80.426
68.754
77.219
79.188
31.492
ip is calculated using method A Ib does not include decay of non-terminal faulted induction motors Ik is the maximum steady state fault current Idc is based on X/R from Method C and Ib as specified above LV CB duty determined based on ultimate rating. Total through current is used for device duty. *Indicates a device with calculated duty exceeding the device capability. # Indicates a device with calculated duty exceeding the device marginal limit ( 95 % times device capability)
Short Circuit Summary Report
Device Capacity
3-Phase Short-Circuit Current
Bus ID
Device ID
1thr (kA)
Tkr (sec.)
Ith (kA)
B1
CB2
100.000
1.00
75.613
B1
CB6
65.000
1.00
75.613*
Bus4
CB6
65.000
1.00
75.613*
1thr = Rated short-circuit withstand current Tkr = Rated short-time Ith = thermal equivalent short-time current *Indicates a device with calculated duty exceeding the device capability. # Indicates a device with calculated duty exceeding the device marginal limit ( 95 % times device capability )
15
17.549
B. ANSI SHORT CIRCUIT RESULT
FIGURE 5:
Single Line Diagram to consider ANSI SC Result 16
ETAP
Project: ANSI Calc Total Bus Fault Peak Current
Page:
1
Date:
10-19-2010
Contract:
SN:
FUJIHAYAPH
Engineer:
Revision: Ansi Breaker
6.0.0C
Location:
Study Case: SC
Filename: sample
Config.: Normal
Electrical Transient Analyzer Program Short-Circuit Analysis ANSI Standard 3-Phase Fault Currents
Swing Number of Buses:
Number of Branches:
1
XFMR2 2
V-Control 0
Load 7
XFMR3
Reactor 0
0
Total 8
Line/Cable Impedance 0 0
Synchronous Power Synchronous Induction Generator Grid Motor Machines Number of Machines:
0
1
0
5
Tie PD
Total
5
7
Lumped Load
Total
1
7
System Frequency:
60 Hz
Unit System:
English
Project Filename:
sample
Output Filename:
D:\Etap6.0 Projects\SC sample attachments_2010_10_18\Untitled.SA1
17
Adjustments Apply Adjustment
Individual /Global
Transformer Impedance:
Yes
Individual
Reactor Impedance:
Yes
Individual
Overload Heater Resistance:
No
Transmission Line Length:
No
Cable Length:
No
Tolerance
Percent
Apply Adjustment
Individual /Global
Degree C
Transformer Resistance:
Yes
Global
20
Cable Resistance:
Yes
Global
20
Temperature Correction
Bus Input Data Bus
Initial Voltage
ID
Type
Nom. kV
Base kV
Sub-sys
%Mag.
Ang.
B1
Load
0.240
0.240
1
100.00
0.00
B2
Load
2.300
2.300
1
100.00
0.00
Bus4
Load
0.240
0.240
1
100.00
0.00
Bus5
Load
2.300
2.300
1
100.00
0.00
Bus6
Load
2.300
2.300
1
100.00
0.00
Bus7
Load
2.300
2.300
1
100.00
0.00
Bus8
Load
2.300
2.300
1
100.00
0.00
UB
SWNG
13.200
13.200
1
100.00
0.00
8 Buses Total All voltages reported by ETAP are in % of bus Nominal kV. Base kV values of buses are calculated and used internally by ETAP
2-Winding Transformer Input Data Transformer
Rating
Z Variation
% Tap Setting
Adjusted
Phase Shift
ID
MVA
Prim. kV
T1
1.500
13.200
0.240
5.75
7.10
0
0
0
0
0
5.7500
Std Pos. Seq.
0.0
T2
5.000
13.200
2.300
7.15
12.14
0
0
0
0
0
7.1500
Std Pos. Seq.
0.0
Sec. kV
%Z
X/R
+5%
-5%
%Tol.
Prim.
Sec.
%Z
18
Type
Angle
Branch Connections CKT/Branch
Connected Bus ID
% Impedance, Pos. Seq., 100 MVAb
ID
Type
From Bus
To Bus
R
X
Z
Y
T1
2W XFMR
UB
B1
53.48
379.58
383.33
T2
2W XFMR
UB
B2
11.74
142.52
143.00
CB6
Tie Breaker
B1
Bus4
CB7
Tie Breaker
B2
Bus5
CB8
Tie Breaker
B2
Bus6
CB9
Tie Breaker
B2
Bus7
CB10
Tie Breaker
B2
Bus8
Power Grid Input Data % Impedance 100 MVA Base
Power Grid
Connected Bus
Rating
ID
ID
MVASC
kV
X/R
R
X
U1
UB
720.000
13.200
99999
0.00014
13.88889
Total Connected Power Grids ( = 1 ): 720.000 MVA
Induction Machine Input Data Induction Machine ID
Connected Bus
Rating
% Impedance (Motor Base)
X/R Ratio
Qty
ID
HP/kW
kVA
kV
RPM
M2
1
Bus5
500.00
440.28
2.300
1800
M3
1
Bus6
500.00
440.28
2.300
M4
1
Bus7
500.00
440.28
M5
1
Bus8
500.00
M1
1
Bus4
125.00
X"/R
X'/R
R
X"
X'
10.89
10.89
2.21
24.05
36.08
1800
10.89
10.89
2.21
24.05
36.08
2.300
1800
10.89
10.89
2.21
24.05
36.08
440.28
2.300
1800
10.89
10.89
2.21
24.05
36.08
110.12
0.240
1800
8.71
8.71
2.30
20.00
50.00
Motors
Total Connected Induction Machines ( = 5 ): 1871.3 kVA
Lumped Load Input Data Lumped Load Lumped Load Connected Bus
Motor Loads
Rating
% Load
Loading
X/R Ratio
Static Loads
% Imp. (Machine Base)
Loading
ID
ID
kVA
kV
MTR
STAT
kW
kvar
X"/R
X'/R
R
X"
X'
kW
kvar
L1
B1
1000.0
0.240
60
40
510.00
316.1
2.38
2.38
8.403
20.00
50.00
340.00
210.71
Total Connected Lumped Loads ( = 1 ): 1000.0 kVA
19
SHORT - CIRCUIT REPORT
B1
3-Phase fault at bus:
=
100.00% of nominal bus kV ( 0.240 kV ) 100.00% of base ( 0.240 kV )
Prefault voltage = 0.240 =
Contribution
1/2 Cycle
From Bus
To Bus
%V
kA
kA
Imag.
ID
ID
From Bus
kA Symm.
Real
Imaginary
/Real
Magnitude
B1
Total
0.00
10.893
-67.489
6.2
68.362
UB
B1
96.57
8.165
-60.047
7.4
60.600
L1
B1
100.00
2.577
-6.134
2.4
6.653
M1
Bus4
100.00
0.150
-1.307
8.7
1.316
*Bus4
B1
0.00
0.150
-1.307
8.7
1316
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
3-Phase fault at bus:
B2
Prefault voltage = 2.300
= =
100.00% of nominal bus kV ( 2.300 kV ) 100.00% of base ( 2.300 kV )
Contribution From Bus
To Bus
ID
ID
B2
Total
1/2 Cycle %V
1.5 to 4 Cycle
kA
kA
Imag.
kA Symm.
From Bus 0.00
Real
Imaginary
/Real
Magnitude
1.368
-17.787
13.0
17.840
kA
kA
Imag.
kA Symm.
Real
Imaginary
/Real
Magnitude
0.00
1.311
-17.177
13.1
17.227
%V From Bus
UB
B2
91.20
1.201
-15.965
13.3
16.010
91.19
1.199
-15.962
13.3
16.007
M5
Bus8
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
M4
Bus7
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
M3
Bus6
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
M2
Bus5
100.00
0.042
-0.456
10.9
0.458
100.00
0.028
-0.304
10.9
0.305
* Bus5
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
* Bus6
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
* Bus7
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
* Bus8
B2
0.00
0.042
-0.456
10.9
0.458
0.00
0.028
-0.304
10.9
0.305
20
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
3-Phase fault at bus:
B4
Prefault voltage = 0.240
= =
100.00% of nominal bus kV ( 0.240 kV ) 100.00% of base ( 0.240 kV )
From Bus ID Bus4
Contribution To Bus ID Total
%V From Bus 0.00
kA Real 10.893
1/2 Cycle kA Imaginary -67.489
Imag. /Real 6.2
kA Symm. Magnitude 68.362
M1 UB L1
Bus4 B1 B1
100.00 96.57 100.00
0.150 8.165 2.577
-1.307 -60.047 -6.134
8.7 7.4 2.4
1.316 60.6 6.653
*B1
Bus4
0.00
10.743
-66.181
6.2
67.048
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
3-Phase fault at bus:
UB
Prefault voltage = 13.200
= =
Contribution From Bus
To Bus
ID
100.00% of nominal bus kV ( 13.200 kV ) 100.00% of base ( 13.200 kV ) 1/2 Cycle
1.5 to 4 Cycle kA
kA
Imag.
kA Symm.
Real
Imaginary
/Real
Magnitude
0.00
0.037
-31.742
863.6
31.742
0.128
4.81
0.018
-0.052
2.8
0.055
0.289
6.50
0.018
-0.198
11.0
0.199
31.492
100.00
0.000
-31.492
99999.0
31.492
%V
kA
kA
Imag.
kA Symm.
ID
From Bus
Real
Imaginary
/Real
Magnitude
UB
Total
0.00
0.068
-31.901
470.9
31.901
B1
UB
11.24
0.041
-0.121
2.9
B2
UB
9.44
0.026
-0.288
11.0
U1
UB
100.00
0.000
-31.492
99999.0
%V From Bus
NACD Ratio = 1.00 # Indicates a fault current contribution from a three-winding transformer * Indicates a fault current through a tie circuit breaker If faulted bus is involved in loops formed by protection devices, the short-circuit contribution through these PDs will not be reported
21
Momentary Duty Summary Report 3-Phase Fault Currents: (Prefault Voltage = 100% of the Bus Nominal Voltage
Bus
Device
Momentary Duty
Device Capability
ID
kV
ID
Type
Symm. kA rms
X/R Ratio
M.F.
Asymm kA rms
Asymm. kA Crest
B1
0.240
B1
Bus
68.362
6.9
1.342
91.741
157.859
B2
2.300
B2
Bus
17.840
13.1
1.496
26.68
45.067
Bus4
0.240
Bus4
Bus
68.362
6.9
1.342
91.741
157.859
UB
13.200
UB
Bus
31.901
999.9
1.728
55.139
90.088
Symm kA rms
Asymm. kA rms
Method : IEEE - X/R is calculated from separate R and X networks. Protective device duty is calculated based on total fault current * Indicates a device with momentary duty exceeding the device capability
Interrupting Duty Summary Report 3-Phase Fault Currents:
Bus
(Prefault Voltage = 100% of the Bus Nominal Voltage
Device
Interrupting Duty CPT
ID
kV
B1
0.240
B2
2.300
Bus4
0.240
UB
13.200
ID CB6
CB6
Type Molded Case Molded Case
Test
Rated
Adjusted
Ratio
M.F.
kA rms
kV
PF
Int.
Int.
68.362
6.9
1.070
73.118
0.240
20.00
85.000
85.000
17.227
13.1
68.362
6.9
1.070
73.118
0.240
20.00
85.000
85.000
(Cy)
31.742
X/R
Device Capability Adj. Sym.
99184.7
Method: IEEE - X/R is calculated from separate R and X networks. HV CB interrupting capability is adjusted based on bus nominal voltage Short-Circuit multiplying factor for LV Molded Case and Insulated Case Circuit Breakers is calculated based on peak current. Generator protective device duty is calculated based on maximum through fault current. Other protective device duty is calculated based on total fault current. * Indicates a device with interrupting duty exceeding the device capability.
22
Asymm kA Crest
C. ANSI/IEEE Short Circuit Method (for Manual Calculation) Impedance Diagram Development @ 100 MVA base
XU RT2
RT1 XT1 RM1 XM1
where:
B2
B1
XT2 RM3
RM2
RL XL
XM2
XM3
HP(0.746) (Eff)(pf)(100) 500(0.746) (1000)(0.9325)(0.9082)
MOTOR (MVA) = RM4
RM5
XM4
XM5
M2 =
M2 = 0.440 MVA
Figure 6: Impedance Diagram
1. X U
2. R T1
3. X T1
4. R T2
5. X T2
6. R M1
7. X M1
8. R L
9. X L
10. X M2M5 11. R M2M5
100 j 0.13889 720 100 0.575costan 7.1 0.53463 1.5 100 0.575sin tan 7.1 j 3.79587 1.5 100 0.0715costan 12.14 0.11739 5 100 0.0715sin tan 12.14 j1.42157 5 100 0.2costan 8.707 20.74547 0.11 100 0.2sin tan 8.707 j180.63078 0.11 100 0.2costan 2.38 12.91214 1.00.6 100 0.2sin tan 2.38 j30.73089 1.00.6 100 0.24051sin tan 10.888 j54.43227 0.44 100 0.24051sin tan 10.888 12.91214 0.44 j
23
Solving for ½ cycle 3 phase fault at Z T B1
Z
T2
Z M2 Z M3 Z M4 Z M5 Z U Z T1 Z M1 Z L
0.56271 I T3 B
1
j3.44496
3.49062 80.72
B2
Z M2 Z M3 Z M4 Z M5 0.10787
I T3 B 2
100 x 10 6 68.9 kA 3 240 3.49062
Solving for ½ cycle, 3phase fault at Z T B2
B1
Z
M1
Z L Z T1 Z U Z T2
j1.40240 1.40655 85.6
100 x 10 6 17.85 kA 3 2300 1.40655
IEC Short Circuit Calculation
1. XUK
j0.13889
2. RT1K K K
0.534630.965
0.51592
0.965 as per60909IECformula Cmax 0.965 ; ZK ZT K 1 0.6XT
Cmax 1.1 Table1 of 60909 0
3. XT1K j3.795870.965 j3.66301
4. RT2K 0.117391.0
0.11739
5. XT2
j1.42517
j1.425171.0
6. RM1K 20.745470.8
7. XM1K j180.630780.8 8. RLK 9. XLK
12.912140.77
j30.730890.77
16.596 j144.505 9.942 j23.66
10. XM2KM5K j54.432270.64 34.837 11. RM2KM5K 4.999290.64 24
3.199
Solving for 3 phase fault at Z TK B1
Z
T2K
B1
Z M2K Z M3 K Z M4K Z M5K Z UK Z T1K Z M1K Z L
0.54641 I"K B
1
I"K B
2
j3.22821
100 x 10 6 1.1 3 240 3.27412
Solving for 3 phase fault at Z TK B 2
, I "K
B2
3.27412 80.39
80 kA
, I "K
Z M2K Z M3K Z M4K Z M5K
Z
0.10307
1.32948 85.6
j1.32547
M1K
Z LK Z T1K Z UK Z T2K
100 x 10 6 1.1 17.85 kA 3 2300 1.32948
* It is therefore the basic inclusion of factors C m and k that increases the calculated short-circuit of IEC method when being compared to the result of the ANSI method.
25
VIII.
Protective Devices Selection and evaluation
X/R Ratio for Breaker Evaluation The fault point X/R ratio is a critical factor in the calculation of short circuit current when evaluating breakers. The X/R ratio determines the amount of dc component in the short circuit current and in the application to the circuit breaker withstands and interrupting time duties. ANSI/IEEE C37.010-1999 recommends a separate R and jX network reduction to determine the fault point X/R ratio while IEC 61909 allows several methods to provide a conservative X/R ratio. The peak current calculation that yields a very close approximation to the exact peak current and is conservative for most values of circuit X/R ratios greater than 0.81. The non-conservative errors for circuit X/R ratio around 10 are negligible. Please refer to equation below: Half cycle I ac peak 1 e X / R or
ANSI / IEEE
2 I ac rms 1 e X / R
3 Half cycle I ac peak 1.02 0.98 e X / R or
IEC 60909
3 2 I ac rms 1.02 0.98 e X / R
Circuit Breaker Short Circuit Test Parameters Based on IEC 60947-2, the circuit breakers short circuit breaking capacity, power factor and ratio, η, between short circuit making capacity and short circuit breaking capacity should be in accordance with Table 5. Table 5: Circuit Breakers Short Circuit Breaking Capacity Short circuit breaking capacity, Ib, kA rms 4.5 ≤ I ≤ 6 6 < I ≤ 10 10 < I ≤ 20 20 < I ≤ 50 50 < I
Lagging Power factor 0.7 0.5 0.3 0.25 0.2
X/R 1.02 1.73 3.18 3.87 4.9
Minimum value required for Short-circuit making capacity η = Short-circuit breaking capacity 1.5 1.7 2.0 2.1 2.2
Ratio η between Short-circuit making capacity and Short-circuit breaking capacity and related power factor or X/R ratio (for ac circuit breaker). 26
Based on NEMA AB1/UL489, the circuit breakers interrupting capacity, lagging power factor should be in accordance with Table 6. Table 6: Circuit Breakers Interrupting Capacity kA I ≤ 10 10 < I ≤ 20 20 < I All All
MCCB and ICB Power Circuit Breaker (Unfuse) Power Circuit Breaker (Fuse)
lagging pf 0.45 – 0.5 0.25 – 0.30 0.15 – 0.20 0.15 0.20
X/R 1.98 – 1.73 3.87 – 3.17 6.59 – 4.90 6.59 4.90
IX. Findings and Results From the result of ETAP Total Bus Fault Short Circuit Study, the following results were found: Table 7: IEC Short Circuit Calculation Bus ID
Device
B1
CB2
Device Capacity (kA) Making Ib sym Ib asym Peak 176
80
80.426
Short Circuit Calculation Result (kA) I"b
ip
Ib sym
Ib asym
79.8
181.348*
77.219
79.188
Note: Method A, Total Bus Fault
From the data in Table 7, the calculated short circuit current level of 79.8kA (I”k) is within the circuit breaker
capacity of 80 kA (Ib sym), however, other parameters such as peak short circuit current ( ip) is 181.348 kA exceeded the circuit breaker rating equivalent to 176 kA (making peak) only. Therefore, the selected IEC rated circuit breaker is not suitable for this particular application. The reason for this difference is that the calculated X/R ratio at 3-phase fault at point B1 is 5.9, which is greater than the device capacity X/R ratio of only 4.9 (see ETAP IEC method result above) applied during the testing of circuit breaker interrupting capacity or the Icu rating of the circuit breaker. Table 8: ANSI Short Circuit Calculation Bus ID
Device
B1
CB2
Device Capacity (kA) Rated Int.
Adj. Int
85.0
85.0
Short Circuit Calculation Result (kA) Sym Adj. Sym X/R ratio M.F rms rms 68.362 6.9 1.07 73.118
From the data in Table 8, the calculated symmetrical rms current of 68.362 kA needs to be adjusted by the multiplying factor (MF) of 1.070 (see computation below) resulting to 73.118 kA. This is because the calculated X/R ratio 6.9 is greater than the X/R ratio used in testing the circuit breaker interrupting capacity which is only 4.9 (Table 6). Comparing the adjusted symmetrical rms value of 73.118 kA against the selected NEMA rated device interrupting capacity of 85kA, the selected circuit breaker is suitable for the particular application. 27
MF
1 e 1 e
R X C R X T
1 e 1 e
1 6 .9 C 1 4 .9 T
1.07
Where:
R X
T
R X C
- Break test R/X ratio - Calculated R/X ratio at the point fault
MF - Multiplying factor
X.
Conclusion and Recommendation
From the above short circuit calculation examples, IEC method shows a higher value of short circuit current as compared to ANSI/IEEE calculation method. This is due to the differences in the consideration as mentioned above. Both methods are being used and internationally acceptable. In any electrical system, it is important to know the short circuit level of each of the protective equipment. However, we should not forget to verify the X/R ratio of the faulted bus against the circuit breaker test power factor or X/R ratio based on their product standard (e.g. UL/NEMA/ANSI or IEC). The example above illustrates clearly the importance of X/R ratio in evaluating or selecting the circuit breaker. Understanding the relationship between the product standards and electrical codes is of utmost importance. It is up to the engineers/designers to decide which method of short circuit calculation they are more comfortable with provided they have to take note of the different considerations in the selection of the protective equipment.
28
XI. References 1 IEEE Std 551-2006, IEEE Recommended Practice for Calculating Short-Circuit currents in Industrial and Commercial Power System. 2 IEEE Papers, Simplifying IEEE/ANSI and IEC Fault Point X/R Ratio for Breaker Evaluation by Ketut Dartawan and Conrad St. Pierre 3 IEC 60497-1:2009, Low-voltage switchgear and control gear - Part 1: General rules 4 IEC 60497-2:2009, Low-voltage switchgear and control gear - Part 2: Circuit-breakers 5 ANSI C37.5-1989, Calculation of Fault Currents for Application of Power Circuit Breakers Rated on a Total Current Basis 6 UL 489-1986, Molded Case Circuit Breaker and Circuit Breakers Enclosure 7 IEC 60909-0, Corrigendum 1 - Short-circuit currents in three-phase A.C. systems - Part 0: Calculation of currents 8 Electrical Transient Analyzer Program (ETAP) Software version 6.0
29
Appendix
Courtesy of ABB Phil., Inc.
proM Compact
Technical features
S 200
of MCBs S 200 series
Series Characteristics Rated current
[A]
Breaking capacity
[kA]
Reference standard IEC 23-3/EN 60898 IEC/EN 60947 - 2 Alternating current
Nr. Poles lcs lcu
1, 1P + N 2,3,4 2,3,4
lcs
1, 1P + N
B,C,D K,Z
S 200 P B,C,D K,Z
B,C,D K,Z
0.5 ≤ ln ≤ 63
0.2 ≤ ln ≤ 25
32 ≤ ln ≤ 40
50 ≤ ln ≤ 63
80≤ LN ≤ 100
6
10
25
15
15
6
133 230 230 400 500 690
20 10 20 10
25➇ 15➇ 25➇ 15➇
40 25 40 25
25 15 25 15
25 15 25 15
15 6 10 6
133
15
18.7➇
20
18.7
18.7
15
Ue [V] 230 / 400
S 200 B,C,D K,Z
S 200 M B,C,D K,Z
0.5 ≤ ln ≤ 63
30
S 280 B,C
(continued …)
2,3,4 2,3,4
IEC/EN 60497 - 2 Direct current T= lR≤ 5ms for all series except S280 UC and S800S-UC where T = lR <15ms
lcu
1, 1P + N
2
3,4
lcs
1, 1P + N
2
3,4
230 230 400 500 690
7.5 15 ➀ 7.5
11.2➇ 18.7➇ 11.2➇
12.5 20 12.5
11.2 18.7 11.2
7.5 18.7 7.5
6 10 6
24 60 125 250 48 125 250 500 600 800 375 500 750 1000 1200
20 10
10
15
10
10
10
20 10
10
15
10
10
10
24 60 125 250 48 125 250 500 600 800 375
20 10
10
15
10
10
10
20 10
10
15
10
10
10
31
(continued …) 500 750 1000 1200 UL 1077 / C22.2 No 235 Alternating current
lnt. cap.
1, 1P + N 2,3,4
UL 1077 / C22.2 No 235 Direct current UL 489/ C22.2 No 5 Alternating current
lnt. cap.
IEC / EN 60947 - 3
lcw
lnt. cap.
1, 1P + N 2,3,4 1 2,3,4
2 3,4
120 277 240 480Y / 277
10 6 10
10 10 10
10 10 10
10 10 10
6
10
10
10
60 125
10 10
240 277 240 480y / 277 800 1200
➇ <50 A
32