Loading documents preview...
Distance Protection and
Earth-Fault Protection in
Medium-Voltage Distribution Networks ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F1 of 63
ABB
Content Introduction Distance Protection Limits of overcurrent protection Where is distance protection preferred ? Basic principle of distance protection Limits of the distance protection Special features for application in networks with isolated or resonant grounded neutrals Preferred starter mode Phase-preference-logic Pros and Cons compared with overcurrent protection
Earth-fault protection in networks with isolated neutrals Earth-fault protection in resonant grounded networks ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F2 of 63
ABB
Introduction Types of neutral grounding CE
CE
RN 3kV - 24kV - small rural networks - city networks - industry
8kV - 24kV - rural networks - big city networks
» 1500 A
5 ....300 A
3kV - 33kV - Generators - Industry - small networks
10 ... 64 kA
XN 33kV - 132kV Limited step- and touch-voltages.
33 kV - 800 kV
Different designations are used: - Petersen coil compensated - compensated - resonant grounded
Topics of this course ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F3 of 63
ABB
Introduction Types of neutral grounding CE
CE
RN
3 ... 24 kV (110 kV) IEmax = 3I0max
Z0source
of total network (except prot. line)
Umax Ph-E U0
very high
3 ... 24 kV
T2403 / T2403_2.ppt / C11e / F4 of 63
33 ... 132 kV
IE limited, with trip
» 3·RN
» Un ph-ph » Unphase -N
Topics of this course ABB Power Automation Ltd
10 ... 64 kA
XN
IE <30 A without trip IE >30 A rather with trip
XCE
» 1500 A
5 ....300 A
» 3·XN
33 ... 800 kV IE >10 kA with trip
(2 ... 4)·Z1source < 0.8·Un ph-ph < 0.73 Unphase -N
ABB
Distance Protection in medium voltage networks
Distance Protection Limits of overcurrent protection Where is distance protection preferred ? ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F5 of 63
ABB
Distance Protection in medium voltage networks Open Ring I>
non-directional
The direction of the short-circuit current is toward the fault. No return current is possible
0.6s
0.8s
IKS 0.6s
0.4s
0.4s
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F6 of 63
0.2s
0.2s
ABB
Distance Protection in medium voltage networks Open ring with two parallel lines I>
non-directional
The direction of the short-circuit current leaving the bus is toward the fault. No return current is possible
0.6s
0.8s
0.1s 0.6s
0.4s
0.8s
0.1s
I> directional Two directions are possible, due to parallel lines
0.4s
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F7 of 63
0.2s
0.2s
ABB
Distance Protection in medium voltage networks Closed ring departing from one common bus I>
non-directional
The direction of the short-circuit current leaving the bus is toward the fault. No return current is possible
I> directional Two directions are possible, due to the closed ring
1.0s
1.0s
0.2s
0.1s
0.8s
0.8s
1.0s
0.1s
0.4s 0.6s
0.4s ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F8 of 63
0.6s
ABB
Distance Protection in medium voltage networks Directional overcurrent is not applicable in meshed networks 0.4 s 0.2 s 0.2 s
TRIP
0.4 s
Infeed right
Infeed left 0.4 s 0.2 s 0.2 s
TRIP
0.4 s
TRIP
No selectivity possible ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F9 of 63
ABB
Distance Protection in medium voltage networks Distance protection solves the problem in the meshed network Zone 3, t3 » 0.6 .. 0.9 s Zone 2, t2 » 0.4 .. 0.5 s Zone 1, t1 = 0
Infeed right Infeed left
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F10 of 63
TRIP
TRIP
ABB
Distance Protection in medium voltage networks Distance-zone grading time [sec.]
The two conditions can be contradictory. Compromises are often necessary. Considering infeed-factors may help.
approx. 1.8·a
Z3 = 0.85 (a +b2) 1.2 a < Z2 < 0.85 (a + b1)
b2
Z1 = 0.85 • a b1 a
A ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F11 of 63
Z [W/phase]
B
C
ABB
Distance Protection in medium voltage networks Principle of the distance function (simplified) I
Relay
ZS UG »
UG I= ZS + ZL
ZL U
Uph - ph ZL = IR - IS for 2- and 3-phase faults
ZL =
Uph - ground Iph + 3I0 × k0
for single-phase to ground faults
Relay will trip for:
I > Iset AND ZL < Zset AND Fault forward ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F12 of 63
ABB
Distance Protection in medium voltage networks Distance protection consists of two main functions Starter Measurement • General fault criteria
• Accurate impedance measurement
• Phase-selection
• Directional
• Non-directional minimum impedance
• Several zones and timers for impedance/time grading
or overcurrent - used for switch-on-to-fault function - back-up trip
j·X
• Start of the zone-timers
Reactance Direction
j·X
Resistance
R R ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F13 of 63
ABB
Distance Protection in medium voltage networks Distance protection with overcurrent starter 30
[W/phase] Zone 4
20
j·X
Zone 3 10 Zone 2 0
Zone 1
R -10
-30
-20
-10
0
10
Distance-zones ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F14 of 63
20
30
[W/phase]
Ohm/Phase = positive sequence Ohms
ABB
Distance Protection in medium voltage networks Distance protection with minimum-impedance starter 30 Starter
[W/phase] 20
j·X
Zone 3 10 Zone 2 0
Zone 1
R -10 -30
-20
-10
0
10
20
Distance-zones ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F15 of 63
30
[W/phase]
Ohm/phase = positive sequence Ohms
ABB
Distance Protection in medium voltage networks Polygonal distance protection 5 directional zones 1 non-directional zone
j·X1 Starter Zone 3
REL316
Overreachingzone
Medium voltage distance protections require many zones. Remote back-up has to be provided for the adjacent lines, since redundant protection is not usual in such networks. Reverse directed zone
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F16 of 63
Zone 2 Zone 1
R1
ABB
Distance Protection in medium voltage networks Limits of the distance protection On very short overhead-lines and on most cable lines a reasonable zone grading is not possible • Several sections have to be protected together • A directional comparison scheme gets imperative Distance protection requires powerful CT’s If communication links are available between the two line ends, the following alternatives are possible: • Line-differential protection • Comparison schemes with directional overcurrent relays
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F17 of 63
ABB
Distance Protection in medium voltage networks Single-phase to ground fault in networks with directly grounded neutrals or neutrals grounded over current limiting reactors
Inductive zero sequence source, the short-circuit current is high
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F18 of 63
ABB
Distance Protection in medium voltage networks In Networks with direct grounding or grounding over current limiting reactors (some kA) the distance relays are able to detect phase-to-phase faults and phase-to-ground faults A separate ground fault protection is an option To detect phase-to-ground faults the protection shall be able to work even for fault currents below max. load current. The starter shall use a minimal impedance characteristic or other voltage dependent characteristics.
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F19 of 63
ABB
Distance Protection in medium voltage networks Distance protection in networks with isolated or resonant grounded neutrals cannot detect single-phase-to-ground faults In networks with isolated or resonant grounded neutrals the fault current for a single-phase-to-ground fault amounts from some 10 up to just over 100 Amps In such networks the distance protection operates for faults between phases only For ground faults the small fault current does in most cases not allow a distance measurement and the capacitive source impedance might fool the distance measurement
If single-phase to ground shall be detected, a separate protection becomes necessary ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F20 of 63
ABB
Distance Protection in medium voltage networks Requirements to distance protection in isolated and compensated networks As starter criteria overcurrent-functions are preferred. This will avoid non-desired starts for single ground faults The overcurrent starter is set above the maximal load current and well above the maximal capacitive earth-fault current Other advantages of the overcurrent-starter : • No fast fuse-failure blocking-function is required • In case of double-buses and VT’s on the buses only, no blocking of the distance function is required during the switching over procedure from one bus to another
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F21 of 63
ABB
Distance Protection in medium voltage networks
Cross-country faults in networks with neutrals isolated or resonant grounded
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F22 of 63
ABB
Distance Protection in medium voltage networks
“Cross-country” faults in networks with isolated or resonant grounded neutrals are short circuits and have to be tripped by the distance protection
Two subsequent single-phase to ground faults with footing points in different locations ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F23 of 63
ABB
Distance Protection in medium voltage networks Cross - country fault on radial lines R S T Ground
Infeed
Line1
Ground
Line 2
Ground
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F24 of 63
ABB
Distance Protection in medium voltage networks Phase preference logic for distance protection In networks with isolated neutrals or with Petersen coil grounding some clients specify a so called “phase preference logic”. In case of cross-country faults in a meshed network, it is the aim of this logic to trip only one line. To reach this goal, “phase-switched” measurement is used (in case of “full-scheme” relays the 5 non-relevant loop-measurements are blocked)
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F25 of 63
ABB
Distance Protection in medium voltage networks Cross - country fault in a meshed network Currents used for distance measurement if phase preference is R - T - S
R S T Ground
Ground R S T
Line1
Ground
Line 2
Ground
To trip only one line, all distance protections have to measure in one and the same type of fault loop (R-E in above example). The protection needs a Phase-Preference Logic. All distance protections in the network shall use identical logic's. ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F26 of 63
ABB
Distance Protection in medium voltage networks Phase preferences Phase preferences R - T - S acyclic means :
R
R has preference over T For a fault R - Ground - T the line with the fault R to ground will trip
acyclic
T has preference over S For a fault S - Ground - T the line with the fault T to ground will trip
R has preference over S
T
S
For a fault R - Ground - S the line with the fault R to ground will trip
R
Phase preferences R - T - S - (R) cyclic means : R has preference over T For a fault R - Ground - T the line with the fault R to ground will trip
cyclic
T has preference over S For a fault S - Ground - T the line with the fault T to ground will trip
S has preference over R For a fault R - Ground - S the line with the fault S to ground will trip ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F27 of 63
T
S
ABB
Distance Protection in medium voltage networks Phase preferences Modes with acyclic phase-preference R-T-S R-S-T T-S-R T-R-S S-R-T S-T-R
[mechanical relay LI4]
Modes with cyclic phase-preference R - T - S - (R) T - R - S - (T)
[mechanical relays LH1, L3, LZ3]
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F28 of 63
ABB
Earth-fault protection in medium voltage networks
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F29 of 63
ABB
Earth-fault protection in medium voltage networks Measurement of 3I0 is not influenced by phase-currents
3I0>
IT>
IS>
IR>
3 phase-currents + earth-current 3I0
3I0>
IT>
IR>
2 phase-currents + earth-current 3I0
Measurement of 3I0 allows a low setting for ground-faults The setting is independent on load current ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F30 of 63
ABB
Earth-fault protection in medium voltage networks Earth-fault protection with definite time overcurrent relays
Radial network, neutral grounding in infeed station only 110 kV
16 kV
On consumer ends, neutrals on MV-level are NOT grounded Note: Every grounded neutral behaves like an earth-fault current source !! ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F31 of 63
ABB
Earth-fault protection in medium voltage networks Earth-fault protection with non-directional IDMTL overcurrent relays
Example: Normal inverse BS 142
t[s] =
0.14s × k 0.02
æ IE ö ç ÷ I set è ø
Tripping time in seconds
Radial network, neutral grounding in infeed station only 100
10
t-min
k is settable (typically 0.05 .... 1.1) The t-min setting allows time-grading with the main short-circuit protection, i.e. overcurrent, distance, line-differential.
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F32 of 63
1
1
10 IE / Iset
100
ABB
Earth-fault protection in medium voltage networks CT in Holmgreen connection, measurement of 3I0 Ratio depends on load current
Ratio depends on load current
2000/1A
Ratio Independent of load current
65/1 (=195/1 related to 3I0)
2 secondary windings
3 I0 (IR + IS + IT) + (DIR + DIS + DIT) ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F33 of 63
Error due to load current cancelled out, in case all CT's produce identical errors.
I0 Same errors as std. Holmgreen
ABB
Earth-fault protection in medium voltage networks Toroidal CT's are used to achieve a correct measurement of low ground currents. Accuracy and CT ratio are independent of load current
Grounding cable routed back through the CT, since the shield current may not influence the measurement.
isolated
3 I0
3 I0 = IR + IS + IT Load current has no influence on measurement ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F34 of 63
ABB
Earth-fault protection in medium voltage networks
Phase - CT‘s
CT for measurement of 3·I0 = earth-fault current by use of a toroidal cable-CT
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F35 of 63
ABB
Earth-fault protection in medium voltage networks Required blocking of sensitive earth-fault protection, in case phaseCT’s are used for ground-current measurement (Holmgreen) Since the the current-setting is low, the earth-fault protection should be blocked by the ph-ph start of the short-circuit protection (overcurrent, distance or line-differential) or alternatively be delayed for a couple of seconds. Reason: During high current phase-to-phase faults, secondary spill-currents in the neutral of the CT’s can be produced, due to unequal CT errors in the individual phases. Such currents might fool the sensitive ground fault protection.
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F36 of 63
ABB
Earth-fault protection in medium voltage networks
Earth-fault detection in networks with isolated or compensated neutrals
C0
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F37 of 63
3 C0
High impedance zero sequence source, the short-circuit current is small
ABB
Earth-fault protection in medium voltage networks Phase-to-ground voltages in isolated or compensated networks RF = 0 W During a single-phase to ground fault N
R
USN
T
E
UTN
USN
U0
UTE
USE
URE
U0 = UNE = - URN
S
UTN
UNE = U0
URN
U0
UTE
U0 UTE
USE
E
The positive sequence voltage remains unchanged The negative sequence voltage = 0 The zero sequence voltage U0 = - pos. seq. voltage of the grounded phase
URN = URE
USE + UTE = 3 U0
URN
USE
U0 U0
USE No-fault condition
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F38 of 63
UTN = UTE USN = USE
ABB
Earth-fault protection in medium voltage networks VT‘s in not effectively grounded systems, i.e.isolated neutral, Petersen coil compensated or grounding over resistance
Un 3
100V 3 100V 3
2 secondary windings ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F39 of 63
n e
Rated voltage factor = 1.9 for (8) hours. Specify VT for not effectively grounded network. Un-e = U0 = voltage neutral to earth = neutral displacement voltage For a metallic single-phase to ground fault in a not effectively grounded system U0max = UnPhase -Neutral U0 Un - e = 3 = U0 = 100V 3 Other standard secondary voltages are: 110 V, 115 V, 125 V
ABB
I [A] at 1.6 Ohm station ground resistance
U [V]
Earth-fault protection in medium voltage networks Admissible step- and touch-voltages as specified by the Swiss-authorities (SEV)
Fault-duration 0 .... 0.9 s
Fault-duration over 0.9 s
1000
80
U I
100
U
70 60 50 40
I
30 20
10
10 0
1 0,0
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F40 of 63
0,1
1
0,5
Time [s]
0.9
0.9
2
3
4
5
6
7
Time [s]
RE = 1.6 Ohm = measured value
ABB
Earth-fault protection in medium voltage networks
Earth-fault detection in networks with isolated neutrals
C0
3 C0 Capacitive source impedance, the short-circuit current is small
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F41 of 63
ABB
Earth-fault protection in medium voltage networks Radial lines are preferred, I> directional required for lines
110 kV
16 kV
I> nondirectional
I>
I>
I>
I>
I>
directional
directional
directional
directional
directional
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F42 of 63
ABB
Earth-fault protection in medium voltage networks Earth-fault
R S T Ground
Line with ground-fault
3·I0 = IE » 0
Ground
IT URE=0 3·I0 = IE
Line(s) without fault
IS USE
UTE
3·U0 ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F43 of 63
Ground
ABB
Earth-fault protection in medium voltage networks Single-line diagram
Network with isolated neutrals Distribution of capacitive ground currents
DEF
Line # 1
IC1 DEF
IF = S IC
Line # 2
IC2 DEF
Use functions Isinj or I0*U0*sinj
Line # 3
I0> U0
IC3
DEF Line # 4
C = 3 C Phase to ground
IC4 ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F44 of 63
C
ABB
Earth-fault protection in medium voltage networks Equivalent diagram in symmetrical Neutrals isolated components
G
Single line diagram
Positive sequence
U1 = URN
Line #1 Negative sequence C01
Line #2
U2 » 0
Line #3 I01
C02
C03
UF RF
isolated
Ground-fault R-E
I02
C01
I03
C03 U0 IF/3
C02 Zero sequence
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F45 of 63
ABB
3 RF
UR
U0 UT
US
Phase to ground voltages [p.u.]
Earth-fault protection in medium voltage networks Phase-to-ground voltages in isolated or compensated networks at different neutral displacement voltages U0 = f(RF) 2 1.8 1.6 1.4 1.2 1 0.8 0.6 0.4 0.2 0
UT US
UR
Earth-fault indication only Phase indication possible
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Neutral displacement voltage U0 [p.u.]
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F46 of 63
ABB
Earth-fault protection in medium voltage networks VT’s with damping resistor against ferro-resonance Specify also the long-time permitted current in the open delta winding.
Un 3
n
100V 3
e
R
In small a network exists the danger of ferro-resonance due to resonance between the network capacity phase to ground and the VT reactance. Generator buses or other buses not yet loaded with lines, are likely to produce ferro-resonance. R will damp ferro-resonance.
100V 3
Note:
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F47 of 63
In Petersen compensated networks the angular error of the VT, loaded with R, meight harm the wattmetric protection. Use non-linear device or feed relays from another VT.
ABB
Earth-fault protection in medium voltage networks
Earth-fault in networks with resonant grounded neutrals
L
C0
L
3 C0
1 wL » 3wC0
High impedance zero sequence source, the ground current is small ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F48 of 63
ABB
Earth-fault protection in medium voltage networks Single-line diagram
Network with resonant grounded neutrals Distribution of capacitive ground currents
Line # 1
IC1 Line # 2
IF << S IC
IC2 Line # 3
IF
Petersen coil
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F49 of 63
IC3
S IC Line # 4
IC4
ABB
Earth-fault protection in medium voltage networks Petersen-coil compensated network (resonant grounding) Equivalent diagram in symmetrical components
Single line diagram Line 1 C01
G Positive sequence system
Line 2
Line 3
C02
C03 Negative sequence system
RF
R
U1 = URN
L
U2 » 0
I01 UF
Ground fault R-E I02
C01
C02
3 RF
I03
3R
3L
C03
U0
IF/3
Zero sequence system
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F50 of 63
ABB
Earth-fault protection in medium voltage networks Amplitude-error Fi and angular-error di of CT‘s Ohmic burden
Ip
Reactive burden
S1
P1
Is
Rw
Im P2
Ip Rb
Zb
S2
S1
P1 Rw
Im P2
Is Xb
S2
Im
Us = Ip (Rw+Rb) Us = Ip (Rw+j Xb)
Im Fi » 0
di
Is
Fi di
Is
Ip
Ip
Is leads Ip
The angular error di might fool the earth-fault protection in a resonant grounded network ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F51 of 63
ABB
Earth-fault protection in medium voltage networks Compensated network with ohmic neutral resistor Distribution of the ground currents Line # 1
IF »I resistive
IC1
Use functions Icosj or I0*U0*cosj
Line # 2
IC2 Line # 3
IF
R
S IC Line # 4
Iresist. ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F52 of 63
IC3
IC4
ABB
Earth-fault protection in medium voltage networks
3 single-phase transformers
Injection of ohmic current by means of three single phase transformers
I0Watt
I0Watt
IWatt = 3 I0Watt primary
U0>
T2403 / T2403_2.ppt / C11e / F53 of 63
t1
t2
R I0Watt secondary
ABB Power Automation Ltd
I0Watt
t1 avoids pick-up in case of self-extinguishing faults t2 limits the time the resistor is loaded
ABB
Earth-fault protection in medium voltage networks Other principles for directional earth-fault functions Functions using 5th harmonics The ground currents of the 5th harmonics are not compensated by the Petersencoil. Directional functions measuring U0250Hz·I0250Hz·sin j can be used. Condition which allow application: The amount of 5th harmonics must be relevant and the capacity phase-to ground of the total network shall be relatively high.
Transient measurement (Wischer-Relay) At fault inception the polarities of the rate of change of zero-sequence current and voltage is compared, this comparison is used to determine the direction. Disadvantages:
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F54 of 63
Only suitable for alarm, not for tripping Only one measurement at fault inception is possible
ABB
Earth-fault protection in medium voltage networks Industrial plant with high-voltage motors In industrial networks with high-voltage motors a minimal value of ground-fault current is welcomed to realise a stator-earthfault protection by simple I0> functions. However, the earth-fault current is limited to avoid high damages in the faulted motor. A protection range of 70 - 80% of full winding is aimed for i.e. 20 - 30% of the winding, located towards the neutral, are not protected. The ground fault current for the not protected part is 70 - 80% reduced.
To achieve the necessary current, the neutrals of the infeedtransformers are grounded over resistors.
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F55 of 63
ABB
Earth-fault protection in medium voltage networks Damages on high-voltage motors due to stator ground-faults (Source : Leroy Sommer) 80
Fault-current [A]
70 60 50 40
high damages
considerable damages
30 20
small damages
10 0 0
1
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F56 of 63
2
3
4
5
6
Fault time [seconds]
7
8
9
10
ABB
Earth-fault protection in medium voltage networks Earth-faults protection in network with isolated neutrals: Earth-fault directional relays for lines and sensitive zerosequence overcurrent relays for machines and transformers. Earth-faults protection in network with resonant grounding : The protection system has to be carefully planned and set. For measurements based on fundamental frequency, toroidal cable CT‘s are required with low angular errors.
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F57 of 63
ABB
Earth-fault protection in medium voltage networks
Special cases and explanation of some not obvious phenomena
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F58 of 63
ABB
Earth-fault protection in medium voltage networks Not-permitted scheme !!! Never ground two neutrals of a transformer in a compensated network
Netz L
CE
Single line diagram
Equivalent diagram for the zero-sequence system
X0Source
XTransfo H-L
+j 3wL
>5 XTransfo H-L
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F59 of 63
X»0
3 I0 >> IEnormal U0 >> U0normal -j X0C = -j / (wCE )
Series - resonance !!! Þ very high U0
ABB
Earth-fault protection in medium voltage networks Isolated neutrals, only one outgoing line I00°
R
IW
I090°
Single line diagram
IC
Use directional I0> functions with 45° characteristic measuring angle
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F60 of 63
ABB
Earth-fault protection in medium voltage networks High capacitive ground-current in a network with isolated neutrals might produce extensive U0-voltage for a fault at end of a long line Single line diagram
Netz G
Equivalent diagram in the zero-sequence system
3·I0 > IEnormal U0 > U0normal
j X0L
-j X0C
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F61 of 63
U0normal
ABB
Earth-fault protection in medium voltage networks Compensated network, wrong watt-metric zero-sequence currents due to different zero-sequence impedance’s of parallel lines IE 1 IE
Overhead line Cable
IE
IE 2 URN IE 2 IE
Overhead line
IE
Iw’
Iw’
-Iw’ IE 1
IE
Cable
U0
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F62 of 63
ABB
Earth-fault protection in medium voltage networks Never use auto-transformers in a network with isolated or compensated neutrals 6 kV
3 kV R
UNE = U0 U0 = - URN(6)
URE(3) USE(3) UTE(3)
URN(3) USN(3) UTN(3)
URN(6)
USN(6) UTN(6)
USE(6) UTE(6)
URE(6)
S T
N
Ground U0 URN(6) U0
URN(3)
The zero-sequence voltage is not transformed, because the transformer-neutral is not grounded. The zero-sequence voltage of the 6kV side will be fully effective in the 3kV side. Motors might be damaged.
URE(6) =0
U0
USN(6)
UTE(6)
U0
UTN(3)
U0
USN(3)
URE(3)
UTN(6)
U0
USE(6) UTE(3)
ABB Power Automation Ltd T2403 / T2403_2.ppt / C11e / F63 of 63
USE(3)
ABB