Doble Engineering - Testing Rectifier Transformers - Slides

  • Uploaded by: sulemankhalid
  • 0
  • 0
  • January 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Doble Engineering - Testing Rectifier Transformers - Slides as PDF for free.

More details

  • Words: 2,917
  • Pages: 22
Loading documents preview...
Testing Rectifier-Transformers y n

pa m o C

ring e e ngin Pierre Leblanc, Alcoa Mt Holly E le b o D Simard, Rio Tinto Alcan ©Hugo

Long Pong, Doble Engineering

Confidential Notice Doble Engineering (Doble) hereby grants the recipient (you) the right to retain this presentation and materials included within (the Presentation) for private reference. No other rights, title, or interest, including, but not limited to, the rights to copy, make use of, distribute, transmit, display or perform in public (or to third parties), edit, translate, or reformat any portion of the Presentation are hereby or otherwise granted and shall remain expressly reserved by Doble. You acknowledge and agree that ny aacceptance such limited license is expressly conditioned upon your of p m o the terms herein. You further agree that, in the event of your breach, g C for which there is no ninjury i Doble will suffer irreparable damage e and r e in addition to any other rights adequate remedy at law. As such, ginDoble, n E and remedies available,le be entitled to seek injunction by a tribunal b shall o of competent jurisdiction restricting you from committing or continuing D © any breach of these terms.

Testing Rectifier-Transformer, March 2012

1

Outline  Background and Motivations  Review Test Principles  Case Studies any p m Co Holy  Fuji Rectifier Transformer in g Alcoa-Mt n i r ee in RTA-Alma  ABB Rectifier Transformer n i g En  TTI Rectifier in RTA-Laterrière le Transformer b o D ©  CWC Rectifier Transformer in RTA-Arvida  Conclusion & Lessons Learned

Testing Rectifier-Transformer, March 2012

Rectifier Transformers - Vector Diagram 3-winding transformer

4 Case Studies: # 1

HV ∆

LV ∆∆

Case Study I. Alcoa-Mt Holy

Overall Excitation Ratio

2

Y

∆∆

3

Y

Y∆

4

YY

∆Y

5 6

∆Y ∆

E ∆ ∆ III. leRTA-Laterrière b o ©D IV. RTA-Arvida Y−Y Y−Y

7

Y

II. RTA-Alma



ng

eri e n i ng



any p m Co  

 



Y−Y Y−Y Testing Rectifier-Transformer, March 2012

2

Background & Motivation • Challenge: Short time for maintenance testing and disconnect the LV terminals from rectifier is major work. any with • Purposes: How to test a transformer p m Co valid test rectifier connected anderto ngobtain i e results for condition nginassessment of the E ble transformer ©Do insulation

Testing Rectifier-Transformer, March 2012

Field Challenge HV Side: Bushing

LV Side: Bus bars go through the building wall

ng

eri e n i ng

any p m Co

le E b o ©D

Testing Rectifier-Transformer, March 2012

3

Field Challenge • LV side: bus bars in the building come through wall from transformer • Surge capacitors (3-9uF) any p m to be disconnected Co g n i r during tests. inee

ng

le E b o ©D

LV Terminals

Testing Rectifier-Transformer, March 2012

Test Principle • Same as standard routine tests: – Overall – Bushing – Surge Arrestor – Exciting Current – Doble Ratio

any p m Co

ring e e in nghaving E • With Exception of rectifier connected ble o D © This affects only Overall test. at LV side.

Testing Rectifier-Transformer, March 2012

4

Test Principle • Preparation: Isolate, short-circuit and ground both sides

ble ©Do

LV2

ring e e ngin

LV1

HV

ny

pa m o C

E

DC Bus Testing Rectifier-Transformer, March 2012

Test Principle

ng

eri e n i ng

any p m Co LV2

LV1

HV

• Preparation: Isolate, short-circuit and ground both sides

le E b o ©D

DC Bus Testing Rectifier-Transformer, March 2012

5

Test Principle • Preparation: Isolate, short-circuit and ground both sides

ble ©Do

LV2

ring e e ngin

LV1

HV

ny

pa m o C

E

DC Bus Testing Rectifier-Transformer, March 2012

Test Principle

any p m Co LV2

LV1

HV

• Preparation: Disconnect all surge capacitors

ng

eri e n i ng

le E b o ©D

DC Bus

Testing Rectifier-Transformer, March 2012

6

Test Principle

ble ©Do

ring e e ngin

ny

pa m o C LV2

LV1

HV

• Preparation: Disconnect all surge capacitors

E

DC Bus

Testing Rectifier-Transformer, March 2012

Test Principle

any p m Co LV2

LV1

HV

• Preparation: Disconnect all surge capacitors

ng

eri e n i ng

le E b o ©D

DC Bus

Testing Rectifier-Transformer, March 2012

7

Test Principle

ble ©Do

LV2

ring e e ngin

ny

pa m o C LV1

HV

LV2

LV1

HV

• Two Configurations of Rectifier Circuit

E

Without DC bus interconnection

+

-

With DC bus interconnection in Red line

Testing Rectifier-Transformer, March 2012

Test Principle - Overall Test • Without DC side interconnection: – Tested as three-winding transformer all the time

• With DC side interconnection: – Tested as two-winding transformer; both LV any p windings are shorted together m o gC n – Tested as three-winding transformer in factory, i r e e n i commissioning orEdiagnostic ng

ble

©Do

Testing Rectifier-Transformer, March 2012

8

LV2 LV2

LV1

E

HV

ble ©Do

HV

any p m Co LV1 winding: gTesting n i r ee (0.5kV, Lines 5, 6 & 7) n i g n

LV2

LV1

HV

Test connection as 3-winding: without DC bus interconnection

LV1

Test Principle - Overall Test

Testing HV winding: (Lines 1, 2 & 3) Testing LV2 winding: (0.5kV, Lines 9, 10 & 11)

Testing Rectifier-Transformer, March 2012

Test Principle - Overall Test

+

le- E b o ©D

Testing HV winding: (Lines 1, 2 & 3)

LV2

ng

eri e n i ng

any p m Co LV1

HV

LV2

LV1

HV

Test connection as 2-winding: with DC bus interconnection

+

-

Testing LV windings: (0.5kV, Lines 5, 6 & 7)

Testing Rectifier-Transformer, March 2012

9

Case Study There are 4 case studies in the papers: 1. Fuji rectifier transformer (1979) at Alcoa plant in Mt-Holy, SC y aatnRTA p 2. ABB rectifier transformer (2010) m Co plant in Alma, QC ering e ngin 3. TTI rectifier transformer (1988) at RTA E le b o plant in Laterrière, QC ©D 4. CWC rectifier transformer (1941) at RTA plant in Arvida, QC

Testing Rectifier-Transformer, March 2012

1. Case Study-Fuji rectifier transformer at Alcoa Transformer Description:

ble

©Do

With DC interconnection in red line

Testing Rectifier-Transformer, March 2012

LV2

g

D/ D D eerin in EnFAg

any p m Co LV1

Fuji 1979 34.28 MVA 35.2/0.638; 0.638

HV

Manufacturer Year Capacity (MVA) Voltage (kV) HV/LV1; LV2 Configuration Class

+

-

10

1. Case Study-Fuji rectifier transformer at Alcoa

LV1

LV2

ble ©Do

ee n i g En

ny

pa m o C

HV

• Tested as 2-winding: – Without rectifier (factory), – With rectifier & surge capacitor – With rectifier & no surge capacitor • Tested as 3-winding as experimentation. ring

+

-

Testing Rectifier-Transformer, March 2012

1. Case Study-Fuji rectifier transformer at Alcoa Overall Test results as 2-winding Insulation

Without rectifier (Factory) %PF

CH+CHL

%PF

17,200

0.35

CH

8,450

0.53

CHL

8,750

0.28

CL+CHL

0.25

Cap (pF)

With Rectifier & With Surge Cap

0.23

CL CH+CL

0.18

0.36

17,155

ring e e 8,779 ngin

15,000 0.35 le E b o D © 6,250 0.35

CHL

Cap (pF) 8,376

With Rectifier & Rectifier Without Surge Cap Insulation %PF

Cap (pF)

ny a17,159 p m o 8,371 C0.53

Cap (pF)

0.33

0.13

8,786

5,971,794

1.94

23,385 8,385

5,962,622

2.93

14,609 8,359

8,774

0.13

8,784

15300

Testing Rectifier-Transformer, March 2012

11

1. Case Study-Fuji rectifier transformer at Alcoa Overall Test results as 2-winding Insulation

Without rectifier (Factory) %PF

CH+CHL

0.25

CH CHL CL+CHL

0.23

Cap (pF)

0.36

8,450

0.53

17,155

With Rectifier & Rectifier Without Surge Cap Insulation

y Cap an(pF) p m o 17,159 C0.33 %PF

Cap (pF)

0.53

8,371

8,779

0.13

8,786

5,971,794

1.94

23,385 8,385

0.35

5,962,622

2.93

14,609 8,359

0.18

8,774

E 8,750 le 0.28 b o ©D15,000 0.35 15300

Cap (pF)

ring e e 8,376 ngin

0.35

CHL CH+CL

%PF

17,200

6,250

CL

With Rectifier & With Surge Cap

0.13

8,784

See only capacitor

Testing Rectifier-Transformer, March 2012

1. Case Study-Fuji rectifier transformer at Alcoa Overall Test results as 2-winding Insulation

Without rectifier (Factory) %PF

CH+CHL

%PF

17,200

0.35

CH

8,450

0.53

CHL

8,750

0.28

CL+CHL

0.25

Cap (pF)

With Rectifier & With Surge Cap

0.23

CL CH+CL

0.18

0.36

17,155

ring e e 8,779 ngin

15,000 0.35 le E b o D © 6,250 0.35

CHL

Cap (pF) 8,376

With Rectifier & Rectifier Without Surge Cap Insulation %PF

Cap (pF)

ny a17,159 p m o 8,371 C0.53

Cap (pF)

0.33

0.13

8,786

5,971,794

1.94

23,385 8,385

5,962,622

2.93

14,609 8,359

8,774

0.13

8,784

15300

See only LV winding (oil) < capacitor Rectifier (dry type) Testing Rectifier-Transformer, March 2012 Expect a higher CL %PF, because more dry type Insulation

12

1. Case Study-Fuji rectifier transformer at Alcoa

pa m o C

ring + e e n i ng LV side = ? (Diode may conduct)

LV2

Testing Rectifier-Transformer, March 2012

LV2

-

LV1

E

HV

LV1

HV

+

LV2

ny

HV should be ok.

ble ©Do

LV1

HV

Can it be overall tested as 3-winding?

+

-

1. Case Study-Fuji rectifier transformer at Alcoa Can it be overall tested as 3-winding? Test results: kV %PF Cap (pF) Correlate to 2-winding test Insulation CH + CHL1 10 0.90 12,797 ≈ CH+CHL-CHL2 CH 10 0.72 8,380 ≈ CH in 2-winding CHL1 10 0.53 4,417 ≈ CHL/2 = (8,786 / 2) ny a p CL1 + CL12 0.049 2.78 12,274,610 Rectifier om conducting C g CL1 0.049 4.86 7,405 erin ≈ CL/2 = (14,609 / 2) e n i g CL12 0.049 2.06 Rectifier conducting En12,268,740 e l b o CL2 + CHL2 0.049 11,597 ≈ CL+CHL-CL1-CHL1 ©D 3.51 CL2 0.049 4.81 7,207 ≈ CL/2 = (14,609 / 2) CHL2 0.049 1.02 4,378 ≈ CHL/2 = (8,786 / 2) Test results correlate well to 2-winding test. Rectifier is Testing Rectifier-Transformer, March 2012 conducting at 50V, so test should be done as 2-winding.

13

1. Case Study-Fuji rectifier transformer at Alcoa Observations: • At the factory, the transformer should be tested as 3winding transformer • Surge capacitor need to be disconnected to n avoid y a p masking problem m Co g as n i • This transformer should be tested two-winding r e e n i when connected to this Engrectifier e l b • Other TestsD(bushing, surge and Exciting current) are © inothe same as standard test. performed

Testing Rectifier-Transformer, March 2012

Case Study- Rio Tinto Alcan (RTA) Three rectifier transformers were planned to be tested: 2. ABB Transformer, in Alma plant 3. TTI Transformer in Laterrière plant any p m o 4. CWC Transformer in n Arvida g C plant

ri

ee ngin

le E b o ©D

Testing Rectifier-Transformer, March 2012

14

2. Case Study- RTA in Alma Test was not done, but we observe the following •

HV Bushings are in enclosure duct separated from H0 H1 H2 H3

ring e e in

y

an p m o

C

H0

ng

le E b o ©D

H0 bushing will not be shorted to the phase bushings for overall test.

Testing Rectifier-Transformer, March 2012

2. Case Study- RTA in Alma Test were not done, but we observe the following Rectifier has DC interconnection, so this transformer should be tested as 2winding when connected to rectifier LV1

any p m Co LV2

ng

eri e n i ng

HV



le E b o ©D

+

-

Testing Rectifier-Transformer, March 2012

15

3. Case Study- RTA in Laterrière Pot line substation single line

ny

ble ©Do

ring e e ngin

pa m o C

E

Testing Rectifier-Transformer, March 2012

3. Case Study- RTA in Laterrière Transformer Description: Manufacturer

TTI

Year

1988

Capacity (MVA)

91.73

ny Voltage (kV) HV1, HV2 / 69/0.924;pa 0.924 m o LV1, LV2 gC n i r Configuration DY/DD inee Class

ng

le E b o D

©

ONAN/ODAF

Testing Rectifier-Transformer, March 2012

16

3. Case Study- RTA in Laterrière S3

Transformer Description:

S2

S1

∆ (LV1)

a

∆ (LV2) omp

H3 H2 H1

ble ©Do

h12

gC nR1 i r e R2 e n i g n

E

R2

h13 R1

H1 H2 H3

R3

S2

h22 S1

R3 h11

Y ny∆

h23

h21

S3

Testing Rectifier-Transformer, March 2012

3. Case Study- RTA in Laterrière Transformer connected to Rectifier: No DC Interconnection between rectifiers -> 3-winding system Surge Capacitors Disconnected

S3

S2

∆ (LV1)

H1

Y ∆

R2

ng

eri e n i ng

leR3 E b o ©D

∆ (LV2) R1

S1

H2

any p m Co

H3

Surge Capacitors Disconnected

Testing Rectifier-Transformer, March 2012

17

3. Case Study- RTA in Laterrière Overall Test results as 3-winding Without rectifier With rectifier Rectifier (10/20/2011) (10/31/2011) Insulation kV Insulation %PF Cap (pF) %PF Cap (pF) any CH + CHL1 10 0.28 34,384 0.33 34,607 p m o CH 10 0.27 33,895 in0.28 g C 34,200 r e CHL1 10 0.26 ngine 477 0.33 401 E le CL1 + CL12 0.5 ob0.24 22,736 0.36 28,591 5,855 D © CL1 0.5 0.23 22,587 0.32 28,438 5,851 CL12 0.5 0.12 150 0.08 152 CL2 + CHL2 0.5 0.23 23,020 0.36 28,756 5,736 CL2 0.5 0.23 22,622 0.38 28,271 5,649 March 397 2012 CHL2 Testing Rectifier-Transformer, 0.5 0.3 0.27 484 86

3. Case Study- RTA in Laterrière Excitation Test results H1 – H3 Test kV

mA Watts

H2 – H1 X

mA

H3 – H2

Watts X

mA Watts

X

224 1254 L 182 1065 L 175 1032 H L anLy p m Exciting current pattern is HLL, due to combined Co the zigzag segments, Delta and Y windings: ering

L

8

e ngin E le Results DobTotal

H3 H2 H1

©

Phase

Delta

Wey

H1-H3

H+h

H+h+H+l

3H+2h+l

Highest

H2-H1

L+h

L+h+ H+h

H+2L+3h

Lower

H3-H2

H+l

H+l+L+h

2H+L+h+2l

Lowest

Testing Rectifier-Transformer, March 2012

h12

h11

h22

h13

h21

h23

18

3. Case Study- RTA in Laterrière Two Methods of Doble Ratio Tests: 1. Standard Test: HV to LV phase as normal ratio 2. Modified Test: Short-circuit one leg of LV winding to eliminate the HV zigzag effect. For example ofyPhase A

n

H3 H2 H1

ng4

le E b o ©D R2

h12

R3

h11

h13

Test Ratio ring e e Line in

h21

R1

h22

pa m o C

HV TTR-Cap + Cable LV Lead

H1-H3/ S2 H1 R1-R3

5

H2-H1/ S1 R2-R1 h23

H2

6

H3-H2/ R3-R2

H3

Ground

R1

H3, R2, R3

R2

H1, R1, R3

R3

H2, R1, R2

S3

Expectation: Both methods won’t obtain NP ratio, but Testing Rectifier-Transformer, March 2012 Method 2 provide consistent ratios among phases.

3. Case Study- RTA in Laterrière Doble Ratio Test results

Winding

NP Ratio Method

H-L1 (S) Y-D

42.96

H-L2 (R) D-D

74.40

1

H1-H3/ X1-X3 85.72

H2-H1/ H3-H2/ X2-X1 X3-X2 104.74

56.61g rin e 1 73.25ine 77.10 ng 81.36 2 le E81.36 Dob 2

56.55

Notes Max %Cv

y

Inconsistent

0.11%

Consistent

80.48 pan

om C56.67

Inconsistent

72.20 81.43

0.05%

Consistent

©

Method 2 provide consistent ratio among phases as expected.  Can be used for condition assessment Testing Rectifier-Transformer, March 2012

19

4. Case Study- RTA in Arvida Transformer Description: H1

H2

N1

H2 N1

A2

A3

H3

A4

A1

N2

ny mpa A5

A6 A5 A4 A3 A2 A1 B1 B2 B3 B4 B5 B6

H1

ring e e ngin

Co

H3

le E b o Manufacturer ©D

A6

B3

B2 N2

B1

B4

B5

B6

CWC

Year

1941

Capacity (MVA)

7.5

Voltage (kV) HV / LV1, LV2 Configuration

13.2/0.624; 0.624 D / Y-Y Y-Y

Testing Rectifier-Transformer, ClassMarch 2012

ONAN/ONAF

4. Case Study- RTA in Arvida Test Results • Only Overall test on HV winding, unable to disconnect the surge capacitor ny Historical Data mpa Routine Test Co (2007) (2011) g n i r Insulation Test kV e e gin Cap (pF) %PF Cap (pF) n%PF E oble D © CH + CHL 10 0.81 9,940 0.99 9,986 CH

10

1.14

2,030

1.64

2,038

CHL(UST)

10

0.55

7,910

0.77

7,941

Testing Rectifier-Transformer, March 2012

20

4. Case Study- RTA in Arvida Test Results • Excitation tests provide normal pattern (2H, 1L), because no zigzag any p m o H1 - H2 H2 - H3 H3 - H1 gC n i r e e Test gin kV mA Watts e X EnmA Watts X mA Watts bl o D © 6384. 3

816.23

L

5048.1

L

999.79

H

5

L

1068.8

6354

X

L

H

Testing Rectifier-Transformer, March 2012

The 4 Case Studies - RTA Conclusion and Observations: • At the factory, the transformer should be tested as 3winding transformer • Surge capacitor need to be disconnected • H0 will be left out for case 2 (Alma) as experimentation • Transformer should be tested as two-winding anywhen p m o connected to this rectifier with DC interconnection gC n i r • Transformer should be tested ee as three-winding when inwith g connected to this rectifier no DC interconnection n E e l • Zigzag winding Dobaffect the pattern of exciting current © • Zigzag winding affect the turns ratio in single-phase source test. • Use the ratio Method 2 for condition assessment. Testing Rectifier-Transformer, March 2012

21

Testing Rectifier-Transformers

Any questions?

ny

pa m o C

ring e e Pierre Leblanc, n Alcoa gin Mt Holly E Hugo Simard, ble Rio Tinto Alcan ©Do

Long Pong, Doble Engineering

Testing Rectifier-Transformer, March 2012

ng

eri e n i ng

any p m Co

le E b o ©D

22

Related Documents


More Documents from "verma210"