ETAP Knowledge Base
Transformer Losses Description: Calculation of Transformer Losses in Load Flow studies Category:
Load Flow
Type:
Calculation
Keywords:
Power Losses Power Losses on 2W transformer Transformer data (Rating): kV := 13.8
Percent Impedance at 100 MVA Base (Values taken from the LF Branch Connection report)
MVA := 100
R% := 0.2
2
Z :=
kV
X% := 10.0
MVA
Z = 1.904
in ohms where Z = R + jX
Z% := 10.0
Transformer impedance in ohms R := Z⋅ X := Z⋅
R% 100 X% 100
−3
R = 3.809 × 10 X = 0.19
Case 1:
Case 2:
I1 := 419.8
I2 := 630.7
Losses due to transformer resistance
Losses due to transformer resistance
P1 := R ⋅ I1
2
P3φ := P1⋅ 3
P1 = 671.233
P2 := R ⋅ I2 3
P3φ = 2.014 × 10
in kW
Losses due to transformer reactance Q1 := X⋅ I1
2
Q3φ := Q1⋅ 3
4
Q1 = 3.356 × 10
2
P3φ := P2⋅ 3
5
in kvars
3
P3φ = 4.545 × 10
in kW
Losses due to transformer reactance Q2 := X⋅ I2
Q3φ = 1.007 × 10
3
P2 = 1.515 × 10
2
Q3φ := Q2⋅ 3
4
Q2 = 7.575 × 10
5
Q3φ = 2.273 × 10
in kvars
This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by Operation Technology, Inc. All Rights Reserved.