H801MPWD Connection Power Board Description
Compiled by Thunder-link.com A leading Professional Huawei GPON Networks Equipment Supplier
HUAWEI TECHNOLOGIES CO., LTD.
Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd. Address:
Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China
Website:
http://www.huawei.com
Email:
[email protected]
H801MPWD Board Contents 8.11.2 H801MPWD Board
8.11.2 H801MPWD Board The H801MPWD board is an AC power board, consisting of an AC power unit and a monitoring unit. The board supplies power to the device and supports the lead-acid battery for power backup. The AC power unit provides overcurrent protection, output overvoltage protection, short circuit protection, and over-temperature protection. The monitoring unit provides comprehensive management for the power system and storage battery, and also provides certain environment monitoring functions.
Feature and Specifications The H801MPWD board supports the following functions and specifications:
Input AC voltage: -100 V to -240 V
Input AC frequency: 50 Hz to 60 Hz
Single-phase three-wire AC power input
Battery port, a 3.3 V terminal socket, supporting DC input power
Lead-acid battery input, reverse polarity protection, and fuse protection
Output DC power voltage: -48 V (adjustable from -42 V to -57.6 V)
Rated output power: 400 W
Alarm monitoring
Enabling and disabling of the rectifier module; equalized and float charging for the rectifier module
Battery low voltage disconnection; charge and discharge management of storage batteries
Parameters Please refer to "Power Consumption and Maximum Frame Size of Boards".
Working Principle Figure 1 Working principle of the H801MPWD board
The basic working principle of the H801MPWD board is as follows:
AC input power is supplied to the board. After AC/DC conversion, the power is supplied to the system backplane at -48 V (adjustable).
The board supports battery input. The monitoring unit manages the charging and discharging of batteries.
The board communicates with the system through the backplane, reporting board hardware and electronic label information to the backplane.
The board supports communication with the monitoring unit through the 485 protocol to adjust voltage and current and report alarm information.
The board supplies 3.3 V power from the system to the monitoring unit.
The monitoring unit manages lead-acid batteries.
The optical coupler implements the battery low voltage disconnection function.
The board provides power distribution checking and alarm reporting functions.
Front Panel Ports
Indicator Indicator
AC IN
DC OUT
BAT
Name
AC input indicator
DC output indicator
Status
Meaning
Green: on
Indicates that the AC input power is normal
Off
Indicates that the AC input power is abnormal
Green: on
Indicates that the DC output power is normal
Off
Indicates that the DC output power is abnormal
Power input Green: on
Indicates that the relay is
Indicator
Name
Status
indicator
PMU
Running status indicator
Meaning
picked up Off
Indicates that the relay drops out
Green: blinks every 0.25s
Indicates that program loading is in progress
Green: blinks every 1s Indicates that the board runs normally Red: blinks
Indicating that the board is starting up
Red: on
Indicates that a critical alarm is reported
Orange: blinks
Indicates that a minor alarm (such as the high temperature alarm) is reported
Parent topic: Power Board (MPW)