Loading documents preview...
Improving Motor Reliability with Intelligent Motor Control Centers and theTesys-T
Presenter’s Name: Wayne Thygesen, Consulting Engineering Specialist December 3, 2008
Improving Motor Reliability with Intelligent MCCs and the TeSys-T
Add photo in this area
Make the most of your energy
Make the most of SM your energy
Schneider Electric Intelligent MCC 2008
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
3
TeSys T is the Basic Tool Used for iMCC
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
4
TeSys T System Components Native protocol Native protocol connectivity connectivity X
X
X
MODBUS
Ethernet TCP/IP Additional Additional protection protection functions functions
Controller expansion module
or
Magelis terminal
or PC with PowerSuite External CT
Ground CT
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
Remote control Remote control and monitoring and monitoring
Control Unit Operator For up to 810A For up to 810A
Ground Fault Ground Fault Sensitivity Sensitivity
5
TeSys T Motor Management System
TeSys T Motor Management Controller and Control Unit Operator Modbus is native in the TeSys T relay plus additional communication options are available Currently designed into Model 6 iMCC
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
6
Motor Managment Controller : LTMR
Front view description Power Supply
6 Discrete inputs (internal powered inputs)
1 Fault relay output (NO/NC)
Plug-in terminals
Expansion module/ HMI/PC connection (modbus RS485)
Network connection (RJ45 port) Reset or Self test Button
Diagnostic Leds
3 relays outputs 5A
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
Ground Temp. Network fault connection Probe (screw terminal) input
7
Expansion module Assembling • Side by side or •Remote
Power Supply • Powered by Controller
Additional Motor Protection • Over / Under Voltage • Over / Under Power Factor • Over / Under Power • Load shedding • Voltage phase imbalance, lost and reversal
Additional Input • 4 discrete inputs
Input Power supply • 24 VDC or • 100-240 VAC 50/60Hz
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
8
TeSys T Measurements
Current
Voltage
Power
Depending on the controller configuration
Functions
Measured range
Thermal capacity Motor temperature sensor Line currents Ground current
0 to 200 %
Average current Current phase imbalance Frequency Line to line voltage Line voltage imbalance Active / Reactive Power Power factor (1) Active/Reactive Energy
Controller
Controller & Exp. module
0 to 6500 Ohms 0,4 to 810 A Internal : 0 to FLC External : depend on settings 0,4 to 810 A 0 to 200 % 0 to 100 Hz 0 to 830 VAC 0 to 200 % 0 to 6553.5 KW / KVar 0 to 100 0 to 400,000 KWhr / KVarhr
(1) : Value saved on power loss
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
9
TeSys T Motor Protection functions
Depending on the controller configuration
Functions
Current
Voltage
Power
Thermal overload (inverse & definite time) Current phase (imbalance, loss, reversal) Under/Over Current Long start, Jam Ground current Motor temperature sensor Rapid cycle lockout Voltage phase (imbalance, loss, reversal) Under/Over Voltage Voltage load shedding Under/Over Power Under/Over Power factor
Controller
Controller & expansion module
Note : All the protection functions include fault detection and most protection functions include warning detection
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
10
Monitoring : Statistics ● Counting log for every kind of faults Tesys T records the faults statistics for the analysis of the system maintenance
● Protection faults : overload, overcurrent, … ● Diagnostics faults : HMI port com loss, internal fault, …
● Recording the motor control history ● Motor starts count and operating time ● Motor starts per hour ● Rapid cycle lockout count ● Load shedding count ● Last start record
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
11
Monitoring : Statistics ● Recording the last 5 faults ● Fault code ● Date and time ● Value of parameters & measurements
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
12
Monitoring : Diagnostic faults ● Internal faults Tesys T records faults which affect the ability of the controller to work properly
● Watchdog : stack over/underflow ● Temperature
● Control command checks ● Start /stop command (current checking after the command) ● Run /stop check back (current checking during the stage)
● Connection fault ● Current Transformer connection ● Voltage connection ● Temperature sensor connection
● Communication loss ● Local terminal connection ● Communication loss : HMI, Network, expansion module
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
13
Monitoring : Motor states ● Operating states Tesys T records the motor states for the analysis of the device operation
● Ready ● Start ● Run ● Not ready
● Thermal overload status ● Time to trip (before the fault occurs) ● Time to reset (after a thermal overload occurs)
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
14
Control functions ● Motor control Overview ● Control Modes determines the device or devices that will command controller outputs : ● Local mode : Local terminal or Local HMI ● Remote mode : PLC or DCS connected to the network
● Operating Modes determines the behavior of the controller’s inputs and outputs (5 predefined modes and 1 custom mode) : ● Overload, Independant, Reverser, Two-Step, Two-Speed ● Custom : user customize the logical operation for the output command
● Operating States The controller provides control, monitoring and protection functions appropriate to each of the motor’s operating states : ● Ready, start, run and fault (not ready)
● Fault Management determines how the controller manages faults : ● Manual, Automatic and Remote reset
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
15
Operating modes Pre-configured operating mode Overload : The Start/Stop of the motor is realized by a mechanism other than the controller Independant : Direct on line full voltage non reversing motor starting Reverser : Direct on line full voltage reversing motor starting Two-Step : Reduced voltage starting motor Two-Speed : Two-Speed motor for motor types : Dahlander, Pole Changer
Custom operating mode PowerSuite logic editor : provides logic functions (Boolean, Register, Timers, Counter,…) that manage the controller behavoir to create a user mode
• • Note Note: :The Theselected selectedoperating operatingmode modedetermine determinethe thebehavior behaviorofofall all controller inputs and outputs. controller inputs and outputs.
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
16
Custom operating mode
PowerSuite logic editor : 2 languages
Possibility Possibilitytotouse usean an existing logic file to existing logic file tomodify modify the logic command that the logic command that manage managecontroller controller behavior behavior
List List Language Language
Function FunctionBlock Block Diagram Diagram
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
17
Motor Management Controller : LTMR ● Overview
Current Rating (internal CT)
Control Power supply
• 0.4 to 8 A • 1.35 to 27 A • 5 to 100 A
• 24 VDC or • 100-240 VAC 50/60Hz
Operating mode
Motor Protection
• Overload • Independant • Reverser • Two-Step • Two-Speed • Custom Mode
• Thermal Overload • Over/Under current • Long Start / Jam • Ground current • Motor temperature sensor
Network Communication
Inputs & Ouputs • 6 discrete inputs • 4 relay outputs • Ground fault input • Temperature sensor
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
LTMR...BD/FM
• Modbus • CANOpen • Profibus DP • DeviceNet • Ethernet (MB + TeSys Port)
18
Expansion Module : LTMEV
Front view description 3 Phase inputs Voltage (0 to 690 VAC)
HMI/PC connection
Controller RJ45 port
Status indication LED’s
Expansion module powered by the controller 4 discrete inputs (external powered inputs)
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
19
Operator Terminal: Magelis XBTN410
Configuration, Display & Control
Custom-built Touchscreen available for Water/Wastewater Applications!
One to One Application
Magelis MagelisXBTN410 XBTN410
• • Local LocalControl Control • • Configures Configuresparameters parameters • • Displays real-time Displays real-timevalues values • • Alarm monitoring Alarm monitoring
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
One to Many Application
• • 24V 24VDC DCsupply supplyneeded needed • • XBTZ938 cable XBTZ938 cable • • Modbus Modbusprotocol protocolfor fordata data tranfering tranfering
20
Maintenance
Controller LED description
LED
Appearance Description
HMI Comm Power
Flashing yellow Off
- Communication - No communication
Green Flashing green Off Red Flashing red (2/s) Flashing red Off (5/s) Red
- Motor off, no internal faults - Motor on, no internal faults - Power off or internal faults - Internal or protection fault - Warning -- Load shedoror rapid No power not com.cycle Loss
Alarm
Fallback PLC Comm
Yellow Off
- Com. loss with network or HMI communication - Network - No network communication
Problems Problemscan canbe bedetected detectedusing usingthe theLED’s LED’son onthe theexpansion expansionmodule, module, Magelis terminal, PowerSuite running in a PC or PLC connected Magelis terminal, PowerSuite running in a PC or PLC connectedtotothe the controller. controller.
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
21
MCC Starter
With Configuration, Display & Control – LUCM Display
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
22
MCC Starter
With Configuration, Display & Control – LUCM Display
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
23
TeSys T Connected on Modbus OR
PLC DCS
OR
OR
Modbus
Modbus DeviceNet Modbus is good data collection system Ethernet TCP/IP
Up to 32 devices for data (Practical limitation is lower for control) Network not compromised by lost node Redundancy is not standard or easy to implement with Modbus
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
24
TeSys T Connected on CANopen PLC DCS
Modbus
DeviceNet
CANopen is good data collection and control system
Ethernet TCP/IP
Up to 63 devices for data (Practical limitation is ??? for control) Network not compromised by lost node No redundancy on CANopen Similar network to DeviceNet
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
25
TeSys T Connected on Profibus PLC DCS
Modbus
DeviceNet
Profibus is good data collection and control system
Ethernet TCP/IP
Up to xx devices for data (Practical limitation is 4 to 8 for control) Network not compromised by lost node Multi-masters is available on Profibus
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
26
TeSys T Connected on DeviceNet PLC DCS
Modbus
DeviceNet DeviceNet
DeviceNet is good control system
Ethernet TCP/IP
Up to 63(?) devices for data (Practical limitation is 4 to 8 for control) Network not compromised by lost node No redundancy on DeviceNet
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
27
TeSys T Connected on Ethernet AND /OR
PLC DCS
AND
AND
/OR
/OR
Modbus
Daisy chain Ethernet (Potential ring) Ethernet TCP/IP
Traditional Star wired Ethernet
DeviceNet
Ethernet is good control and data acquisition system
Ethernet TCP/IP
Up to 32 devices on self-healing ring More devices on ethernet switch Network not compromised by lost node No redundancy on DeviceNet
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
28
PowerSuite Software V2.5
Programming, Configuration & Display One to One Application or One to Many Application
PowerSuite PowerSuiteSoftware Software
• • Configures Configuresparameters parameters • • Displays real-time Displays real-timevalues values • • Alarm monitoring Alarm monitoring • • Logic Logicblock blockprogramming programming
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
• • RS232/485 RS232/485Converter: Converter: VW3A8106 VW3A8106 • • Direct Directethernet ethernet88pin pincable: cable: VW3A8306R10 VW3A8306R10
29
TeSys T with the PowerSuite
Setting menu
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
30
TeSys T with the PowerSuite
Monitoring interface
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
31
To Summarize ● Controller integrated design: 1 single product ● Main protection and control features integrated into the controller ● Current sensing integrated from factory up to 100 A ● Most common Operating Mode ready to use ● Full functionality and protection even when bus system fail MODBUS
Ethernet TCP/IP
● Communication ● 5 main protocols ● Double network connectivity
● Customization ● Custom operating mode: truth table and logic block ● User map: rearrange register table for faster communicating ● Flexible cabling layout: removable and changeable terminal strips
● Optional enhancement ● Voltage and Power protection ● Voltage, Power and Energy consumption monitoring
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
32
Preferred System Architecture Ethernet Network
Ethernet Switch
Ethernet Switch
Ethernet Switch located in each shipping split All motor control will have direct ethernet connection
w/ IP address utilizing advanced services like “Faulty Device Replacement” and “Transparent Ready Webpages” Existing Schneider Products: ATV61/71 VFD’s; TeSys-T Overload; ATS48 w/ETG
Factory
tested for correct device operation
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
33
Architecture Questions TeSys
T Overload:
Should it be powered by bucket CPT? O/L and display will be OFF when disconnect is OFF Disallows daisy-chain ethernet with possible redundancy No communications issue with Modbus, DeviceNet, Profibus Should it be remotely powered by 24 VDC? O/L and display always ON Disconnect can still be effectively “Locked Possible redundant ethernet communications These factors should be considered: TeSys T has realtime clock – “Clock”
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
or CANopen
Out/Tagged Out”
is stopped when power not applied
34
Transparent Ready Advantages Keep
in mind that ethernet web pages can be accessed without using I/O Points in the Scada System. (See costs on List Price sheet below)
Note
that pages are already built – no engineering costs
If
device is replaced or updated years from now with newer product Scada web link would still be good!
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
35
Embedded Webpages in TeSys T!
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
36
Embedded Webpages in TeSys T!
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
37
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
38
Measure of the current Internal CT for current range up to 100A
External CT to expand the current range up to 810A
External load CT LT6CT... or LUTC… or Customer Choice
33windows windowswith withembedded embeddedCT CTfor for measuring the phase current measuring the phase current
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
Controller Controlleraccept accept5A 5Aand and1A 1A secondary signal from external secondary signal from externalCT CT
39
External Current transformers
Characteristics of the external CT
Protection CT provides a good accuracy at high current and has a higher precision limit (linearity zone) . Requirement for the CTs (standard IEC 60044-1) Accuracy class 5
Motor protection P
Accuracy limit factor 10 or 15
Accuracy class : define the current error at the nominal current and at the accuracy limit current ( example : accuracy class = 5, the current error is +/- 1% if current ≤ 2x I nominal and +/-5% at the Accuracy limit current) Accuracy limit factor : define the maximum error at the accuracy limit current (example accuracy class=5 and accuracy limit factor=10, the maximum error is +/5% at 10xIn.
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
40
Measure of ground fault External ground CT for precise ground sensitivity
Ground GroundCT CTmeasures measuresground groundfault faultas aslevel level significantly lower then internal ground significantly lower then internal groundfault fault (controller sensibility : 20 mA to 10 A) (controller sensibility : 20 mA to 10 A)
Ground fault CT (current =0 => no ground fault)
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
41
Architecture : TeSys T connected on the Modbus
network
PLC DCS
DeviceNet Ethernet TCP/IP
TeSys TeSysTTon onthe thenetwork network: : • • Remote RemoteControl Control • • Configures Configures&&sets setsup upthe the functions functions • • Monitoring Monitoring
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
•• Network NetworkConnection ConnectionPort Porton on the thefront front(picture (pictureshows showsRJ45 RJ45 for Modbus) for Modbus) •• Terminal TerminalStrip Strip (For DeviceNet, (For DeviceNet,only onlyterminal terminal strip is presented) strip is presented)
42
Main power circuit 11 Circuit Circuitbreaker breaker 22 Contactor Contactor
1
33 Control Controlpower powersupply supply (24VDC / 100-240VAC) (24VDC / 100-240VAC) 2
66 HMI HMIororPowerSuite PowerSuiteport port connection connection 77 Cable Cableconnection connection (controller (controller&&expansion) expansion) 88 Network Networkport port
6
3
7
8
Controller
Expansion module
44 Ground Groundfault faultcurrent current transformer transformer 55 PTC PTCthermistor thermistor(binary (binaryoror analog) analog)
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
4 5
43
Control wiring 66logic logicinput input- -Internal Internal supplied power supplied power
44logic logicinput inputrequire requireexternal external power power
22control controlrelay relay output output
Fault Faultrelay relayoutput output 97-98: 97-98:NO NO; ;95-96: 95-96:NC NC
Warning Warningrelay relay output output
isolated isolatedwith withinput inputon onthe thecontroller controller
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
44
Control modes
Local mode : Terminal or HMI Control ControlThrough ThroughTerminal TerminalStrips Strips
Monitor MonitorThrough Through Network Network Control ControlThrough ThroughMagelis MagelisHMI HMI
Network
• • Control Controllocal localmode modeselection selectionisisdefined definedby byinput inputI.6: I.6:00==Local Localmode mode • • Control Controllocal localchannel channelsetting: setting:00==Local LocalTerminal, Terminal,11==Local LocalHMI HMI • • Local LocalStop StopCommand Commandwill willalways alwaysbe beresponded respondedregardless regardlessofofthe thecontrol controlmode mode
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
45
Control modes
Remote mode Terminal TerminalStrips Stripsonly onlyfor forSignal SignalInput Input
Control ControlCommand Command Through ThroughNetwork Network Magelis MagelisHMI HMIonly onlyfor forMonitoring Monitoring
Network
• • Control ControlRemote Remotemode modeselection selectionisisdefined definedby byinput inputI.6: I.6:1= 1=Remote Remotemode mode • • The Thebumpless bumplessparameter parameterdetermines determinesthe thebehavior behaviorofofoutputs outputsO1 O1&&O2 O2when when changing control mode. If this parameter is enable the outputs remain the changing control mode. If this parameter is enable the outputs remain thesame same position when there is a changing control mode. position when there is a changing control mode. • • Local LocalStop StopCommand Commandwill willalways alwaysbe beresponded respondedregardless regardlessofofthe thecontrol controlmode mode
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
46
Current Transformer wiring Internal CT Measuring phase currents direct from 0.4 to 100 A Wiring Wiringthrough throughthe thewindows(Ø windows(Ø18mm) 18mm)
Wiring Wiringusing usingMulti-turns Multi-turns
Wiring Wiringusing usingLug-Lug Lug-Lugkit kit
1
2 4
3
11: :Lug Lugshroud shroud(ref. (ref.31172-005-01) 31172-005-01) 22: :Lug Lug (ref. (ref.: :31154-023-50) 31154-023-50)
33: :L1 L1&&L3 L3bus busterminals terminals(ref. (ref.: :31172-017-01) 31172-017-01) 44: :L2 L2bus busterminal terminal(ref. (ref.: :31172-018-01) 31172-018-01)
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
47
Current Transformer wiring External CT Measuring phase currents up 810 A
Controller Controlleraccept accept5A 5Aand and1A 1Asecondary secondaryfrom from external current. The recommended controller external current. The recommended controller model modelfor forthese thesecurrent currentisis0.4 0.4toto8A 8A(Ref. (Ref. LTMR08xxx) LTMR08xxx)
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
48
Current Transformer wiring External ground fault CT Precise ground protection
Z1 Z2
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
The Thecontroller controllerhas has22terminals terminals(Z1 (Z1&&Z2) Z2)toto connect connectan anexternal externalground groundCT. CT.The Theground ground CT measure ground sensitivity as level CT measure ground sensitivity as level significantly significantlylower lowerthen theninternal internalground groundfault fault (sensibility : 20 ma to 10 A) (sensibility : 20 ma to 10 A)
49
Temperature sensor wiring Types of sensor can be used PTC binary, PTC or NTC Analog (Set up the sensor parameter)
T1 T1and andT2 T2returns returnsthe thetemperature temperature value measured by resistance value measured by resistance sensor. sensor.
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
50
Setting
Configuration & Setting via HMI/PC or Remote PLC/DCS
HMI/PC connection HMI
Network connection PLC/DCS
XBTN410
Or PC Network
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
51
Setting with the PowerSuite
Monitoring menu
Add photo in this area
Make the most of your energy
Make the most of SM your energy
Setting with the PowerSuite
Parameters menu
Add photo in this area
Make the most of your energy
Make the most of SM your energy
To summarize ● Controller integrated design: 1 single product ● Main protection and control features integrated into the controller ● Current sensing integrated from factory up to 100 A ● Most common Operating Mode ready to use ● Full functionality and protection even when bus system fail MODBUS
Ethernet TCP/IP
● Communication ● 5 main protocols ● Double network connectivity
● Customization ● Custom operating mode: truth table and logic block ● User map: rearrange register table for faster communicating ● Flexible cabling layout: removable and changeable terminal strips
● Optional enhancement ● Voltage and Power protection ● Voltage, Power and Energy consumption monitoring Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
54
Schneider Electric - Water Wastewater Competency Center – Wayne Thygesen – 3 December 2008
55