Test Report For Power Transformer Project: J3

Plant: PCG-SEZ

Report No: L&T/PT/ET-HCH200-007

Substation No: HCH200-10

Date of Testing: 18-08-2017

Transformer Details : Tag No :ET-HCH200-007

Serial No: 5417/1

Make: BHARAT BIJILEE

Type of Tap changer: OCTC

Type of Cooling:

ONAN

Primary Voltage: 33000 V

Rated MVA:

25

Secondary Voltage: 11500 V

Rated Amps: HV 437.3

Normal Tap :3

Rated Amps: LV

No. of Phase :3

1255.1

Temperature rise over 50▫C Ambient :

Top oil : 50

YOM:2014

Avg wdg : 55

Insulation Level:

HV

170KVp / 70 KV rms

Insulation Level:

LV

75 KVp / 28 KV rms

Insulation Level:

LVN

75 KVp / 28 KV rms

Core & Coil: 21500 Tank & Fittings: 13800 Mass Of Oil:6800 Total Mass:42400 Short Circuit Rating HV:

% Impedance HV/LV: 8.1279

Short Circuit Rating LV:

Vector Group: Dyn11

Load Loss Max(KW) : 90.594

Frequency: 50 Hz

No Load Loss Max (KW) : 11.064

TURN WHEEL TO REQUIRED TAP POSITION TAP POSITION

LEADS JOINED

HV VOLTAGE (KV)

1(MAX)

5-6

2

6-4 Contractor Engineer

HIGH VOLTAGE

LOW VOLTAGE

LINE CURRENT (A)

LINE CURRENT (A)

34650

416.5

-

33825

426.7

-

Reliance Engineer

Signature Name

Date Page 1 of 7

Reliance O&M/TPI

Test Report For Power Transformer Project: J3

Plant: PCG-SEZ

Report No: L&T/PT/ET-HCH200-007

3(NOR)

4-7

33000

437.3

1255.1

4

7-3

32175

448.6

-

5(MIN)

3-8

31350

460.4

-

Tests:

1.Winding Resistance: in mΩ Tap Position

Measured Value in HV Side (mΩ)

1

146.7 mΩ 157.4 mΩ 148.2 mΩ

2

142.2 mΩ 152.2 mΩ 144.2 mΩ

3

139.3 mΩ 145.5 mΩ 139.2 mΩ

4

135.6 mΩ 139.3 mΩ 135.4 mΩ

5

132.4 mΩ 135.7 mΩ

1U-1V

1V-1W

1W-1U

Measured Value in LV Side (mΩ) 2U-2V

2V-2W

2W-2U

2U-2N

12.59 mΩ

12.72 mΩ

12.69 mΩ

7.55 mΩ

2V-2N

2W-2N

7.47 mΩ

7.10 mΩ

131.9mΩ

2. Insulation Resistance Test: 5000 v (dc) in GΩ Applied Voltage between

Test Voltage

IR at 1 Min

IR at 10 Min

PI (10min /1min )

HV – Earth

5000 V

9.51 GΩ

18.9 GΩ

1.98

LV-Earth

5000 V

12.1 GΩ

31.7 GΩ

2.61

HV-LV

5000 V

13.1 GΩ

36.5 GΩ

2.78

3.Ratio Test:

Applied Voltage : 1U1V: 402 , 1V1W:403 , 1W1U:402 Calculated Ratio (415V)

Measured Ratio(V)

Tap No. 2U2V 2V2W 2W2U

2U2N

2V2N

2W2N 2U2V

2V2W

2W2U 2U2N

2V2N

2W2N

1

133.5 133.8

133.5

77.07

77.2

77.07

133.9

133.7

133.6

77.0

76.9

76.8

2

136.7 137.0

136.7

78.92

79.09 78.92

136.9

136.6

136.4

78.8

78.8

78.5

3

140.5 140.9

140.5

81.11

81.34 81.11

140.5

140.1

139.9

80.6

81.0

80.6

Contractor Engineer

Reliance Engineer

Signature Name

Date Page 2 of 7

Reliance O&M/TPI

Test Report For Power Transformer Project: J3

Plant: PCG-SEZ

Report No: L&T/PT/ET-HCH200-007

4

144.0 144.4

144.0

83.13

83.36 83.13

144.4

144.1

143.3

83.1

83.4

82.5

5

147.7 148.1

147.7

85.27

85.50 85.27

148.4

146.6

146.0

85.2

85.3

84.8

4.Magnetic Balance Test: Applied Voltage (V)

Tap No.

1

3

5

Measured Voltage (V)

Ø out

1U1V

1V1W

1W1U

2U2V

2V2W

2W2U

2U2N

2V2N

2W2N

R

130.3

270.1

399

26.94

128.9

101.9

25.06

51.7

76.7

Y

204.0

404

199.6

116.4

115.2

1.046

39.26

77.0

38.38

B

402

271.6

131.8

129.1

26.84

101.5

77.0

51.7

25.34

R

203.3

404

199.2

121.9

120.9

0.99

40.5

78.6

39.32

Y

132.1

269.9

399

27.68

134.9

107.2

26.50

53.8

80.5

B

402

269.8

134.2

135.4

27.34

107.9

80.9

53.9

26.89

R

132.0

270.2

399

29.28

142.0

112.7

28.05

56.9

84.2

Y

205.1

405

199.8

128.7

128.0

1.20

42.9

85.1

42.0

B

402

271.1

132.4

142.7

29.34

113.2

84.9

56.8

27.81

5.Magnetizing Current Test: 5A. Magnetizing Current from HV Side: 415 V

Tap No.

Applied Voltage (V)

Measured Current (mA)

1U1V

1V1W

1W1U

1U

1V

1W

1

402

402

402

13.16

12.09

12.39

2

402

402

402

13.30

12.12

13.84

3

402

402

402

14.34

13.75

13.19

4

403

403

402

15.27

13.94

13.27

5

403

404

402

14.16

13.51

16.06

5B. Magnetizing Current from LV Side: 230 V Contractor Engineer

Reliance Engineer

Signature Name

Date Page 3 of 7

Reliance O&M/TPI

Test Report For Power Transformer Project: J3

Plant: PCG-SEZ

Report No: L&T/PT/ET-HCH200-007

Applied Voltage (V)

Measured Current (mA)

2U2N

2V2N

2W2N

2U

2V

2W

226.6

234.8

234.8

122.9

100.7

123.7

6. Core and Frame Insulation Resistance Test(0-1 GΩ) Applied Voltage

Frame – Earth

Core-Earth

Frame-Core

between Test Voltage

500 V

IR at 1 Min

>1GΩ

>1GΩ

>1GΩ

7.Vector Group Test (at Normal Tap):

Terminal Shorted: 1U – 2U

Applied Voltage : 415 V

Condition – 1:

1U1V = 1U2N+1V2N

402=80.8+322.9

Condition – 2:

1U2w=1U2v

140.2=140.9

Condition – 3:

1W2W<1W2V Contractor Engineer

289.3<425 Reliance Engineer

Signature Name

Date Page 4 of 7

Reliance O&M/TPI

Test Report For Power Transformer Project: J3

Plant: PCG-SEZ

Condition 1U1V 1U2N 1V2N 1W2W

Report No: L&T/PT/ET-HCH200-007

Measured Voltage, V 402 80.8 322.9 289.3

Result: OK

Condition 1U2W 1U2V 1W2V -

Transformer Vector Group is :

Measured Voltage, V 140.2 140.9 425 OK

Attach Test Certificate For Earth Resistance(Wherever Applicable): Attach Test Certificate For Dissolved Gas Analysis (Wherever Applicable): Attach Test Certificate for Stability Test – Differential / Ref. (Wherever Applicable): Attach Test Certificate for Transformer Oil : Attach Test Certificate for Feeder / Cables

:

Silica Gel: Protection Device Checks Buchholz Relay up to Panel/Relay end Magnetic Oil Indicator up to Panel/Relay end Oil Temperature Indicator up to Panel/Relay end Winding Temperature Indicator up to Panel/Relay end Pressure Relief Valve up to Panel/Relay end

Alarm Contact

Trip Contact

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

Marshalling Box Checks : Description

Remarks

Tightness of Neutral CTs wiring Lighting Circuit checks Contractor Engineer

Reliance Engineer

Signature Name

Date Page 5 of 7

Reliance O&M/TPI

Test Report For Power Transformer Project: J3

Plant: PCG-SEZ

Heater circuit Checks

Report No: L&T/PT/ET-HCH200-007

IR=

Coil resistance=

Earth checks wherever applicable

8. Cooling Fan Test (Wherever Applicable) : Fan Details: Make : Marathon Electric Frequency : 50Hz Watts :

Phase : Voltage : Rpm :

Amps : Insulation Class :

Fan No

Sr.No

Insulation Resistance

Fan 1 Fan 2 Fan 3 Fan 4

-

-

UV -

Winding Resistance VW UW -

Comments: NIL Test Result: OK

Test Instrument Used Sr. No. of Instrument 116805

Instrument Name Digital multimeter

Contractor Engineer

Make Rishi

Model No 15S

Reliance Engineer

Signature Name

Date Page 6 of 7

Rating 1000 V

Tested on Northlab India Pvt.ltd

Calibration Validity 10-07-2017

Reliance O&M/TPI

Test Report For Power Transformer Project: J3 2304.08W093

Plant: PCG-SEZ Transformer Resistance Meter

Report No: L&T/PT/ET-HCH200-007 Scope

TRM 104

10Ma-20Ω

Scope T&M India Pvt.ltd

03.02.2018

B2009342

Digital Insulation tester

Kyoritsu

3125

5000 V

Northlab India Pvt.ltd

25.01.2018

HTC1506CG0009

Leakage Tester

HTC

CL-2054

40ma100mA

Northlab India Pvt.ltd

08.04.2018

Contractor Engineer

Reliance Engineer

Signature Name

Date Page 7 of 7

Reliance O&M/TPI