TEST REPORT FOR POWER TRANSFORMER Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD.

DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL. PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP

Sheet No 1 of 4

Location: POWER TRANSFORMER i.

GENERAL DETAILS NAME PLATE DETAILS Make

Serial No.

: - DT6272/ 01

Manufacturing Year Rated Power

: - 10/2018

Total Mass

: - 1600 KVA

Location

: Power Transformer :

Rated Voltage

: - 11000 V (HV)

Rated Current

: - 83.98 A (HV)

: - 433 V (LV) No. of Phase Winding Material Temperature rise Type of tap charger ii.

:-3 : - Copper

: - CG Power & Industrial Solution Ltd. : - 5800 Kg

: - 2133.4 A (LV) : - 50 Hz : - ONAN

: - 40°C (OIL) & 45°C (WDG)

Frequency Type of cooling Impedance

: - OFF load tap charger

Vector group

: - Dyn11

: - 6.48 % (HV-LV)

INSULATION RESISTANCE TEST

Reference Winding HV – EARTH

Applied Voltage 5000 V DC

IR value in G ohms 60 secs 600 secs 2.98 4.44

Polarization Index PI = 600s/60s 1.48

HV – LV

5000 V DC

3.14

6.27

2.0

LV – EARTH

500 V DC

>1GΩ

-

-

iii. WINDING RESISTANCE TEST LV side OTI: 42 oC Winding

WTI: 40 oC Resistance (mΩ) Site value @ 40 °C

2u – 2n

63 mΩ

2v – 2n

62 mΩ

2w – 2n

62 mΩ

Tested By L&T Name: SARAVANAN.A SIGN :

Witnessed by L&T Name: Mr. SATYENDRA KUMAR SIGN :

Client by IOCL Name: SIGN :

TEST REPORT FOR POWER TRANSFORMER Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD.

DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL. PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP

Sheet No 2 of 4

OTI: 42 oC Resistance (mΩ) Site value @ 40 °C

HV side Tap Position

WTI:

40 oC

U-V

V-W

W-U

1(MAX)

176 mΩ

178 mΩ

172 mΩ

2

189 mΩ

189 mΩ

192 mΩ

3(N)

204 mΩ

202 mΩ

206 mΩ

4

214 mΩ

216 mΩ

215 mΩ

5(MIN)

239 mΩ

227 mΩ

228 mΩ

iv.

MAGNETISING CURRENT TEST Applied voltage on HV side (V) IU – IV 1V – IW 1W – 1U

Tap Position

1U

Measured current in mA 1V 1W

1(MAX)

409

412

411

11.1

8.3

9.5

3(N)

409

412

411

11.9

8.9

9.9

5(MIN)

409

412

411

12.7

9.3

10.6

v. Voltage applied at

MAGNETIC BALANCE TEST Voltage measured at HV (V) 1U-1V 1V-1W 1W-1U

2u-2v

Voltage measured at LV (V) 2v-2w

2w-2u

Roff

226

410

184

14.23

13.50

0.908

Yoff

136

270

409

2.94

15.43

12.53

Boff

410

286

123

15.77

3.65

12.12

Tested By L&T Name: SARAVANAN.A SIGN :

Witnessed by L&T Name: Mr. SATYENDRA KUMAR SIGN :

Client by IOCL Name: SIGN :

TEST REPORT FOR POWER TRANSFORMER Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD.

DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL. PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP vi.

Sheet No 3 of 4

VECTOR GROUP TEST

Short the terminal 1U & 2U & apply 3 phase 415 volts across the HV terminals.

Vector Group: Dyn11 Measured between

Measured values (V)

Condition

Measured between

Measured values (V)

1U-1V

412

Input

1V-1W

412

1W-1U

411

Input

-

0

W1W2

392

<

V2W1

410

U12N+ 2NV1

9.22+398

=

U1V1

406.8

U1V1

405

=

U1W1

406

Vector group Dyn11 is confirmed: YES vii. Tap position

VOLTAGE RATIO TEST Applied Voltage in side HV (V) AC 1U-1V 1V-1W 1W-1U

Measured voltage in LV side (V) AC 2U-2V 2V-2W 2W-2U

Measured voltage in LV side (V) AC 2U-2N 2V-2N 2W-2N

1(MAX)

409

412

411

15.6

15.4

15.5

8.7

8.9

8.9

2

410

411

411

16.0

15.9

15.89

9.04

9.01

8.9

3(NOR)

409

412

409

16.35

16.26

16.20

9.31

9.27

9.31

4

409

412

411

16.72

16.72

16.71

9.53

9.57

9.60

5(MIN)

409

412

411

17.2

17.16

17.04

9.72

9.84

9.75

viii.

TRANSFORMER AUXILIARY PROTECTION CHECK

Tested By L&T Name: SARAVANAN.A SIGN :

Witnessed by L&T Name: Mr. SATYENDRA KUMAR SIGN :

Client by IOCL Name: SIGN :

TEST REPORT FOR POWER TRANSFORMER Location: POWER TRANSFORMER ROOM

LARSEN & TOUBRO LTD.

DATE : 12/10/2019

CLIENT: M/s. INDIAN OIL CORPORATION LIMITED - IOCL. PROJECT : LPG BOTTLING PLANT AT GORKHPUR, UP

Sheet No 4 of 4

Protection elements

Operation check up to HT PANEL

1.

Buchholz Alarm

Ok

2.

Winding Temperature High Alarm (WTI)

Ok

3.

Oil Temperature High Alarm

Ok

4.

MOG Alarm

Ok

5.

Buchholz Trip

Ok

6.

Oil Temperature High Trip

Ok

ix.

GENERAL CHECK Description

Operation check

1.

Check for any leakage of oil

No

2.

Check for any mechanical damage

No

3.

Check for tightness of terminal & connections

Okay

4.

Check for condition of silica gel

Blue / try

SETTINGS 1.

Setting of OTI alarm

85oC

2.

Setting of OTI trip

90oC

3.

Setting of WTI alarm

95oC

4.

Setting of WTI trip

100oC

x.

TRANSFORMER IS FIT FOR COMMISSIONING YES

Tested By L&T Name: SARAVANAN.A SIGN :

Witnessed by L&T Name: Mr. SATYENDRA KUMAR SIGN :