Loading documents preview...
The Scottish Building Standards Agency
ACCREDITED CONSTRUCTION DETAILS (SCOTLAND)
ACCREDITED CONSTRUCTION DETAILS (SCOTLAND) (FOR THE LIMITATION OF THERMAL BRIDGING AND AIR LEAKAGE IN LOW AND MEDIUM RISE DOMESTIC TYPE) Status of this document This document provides guidance on one way to meet some of the requirements of the functional standards set out in Regulation 9 of the Building (Scotland) Regulations. There is however no need to follow the guidance in this document, as there are other ways of meeting the functional standards. Access to the Technical Handbook is available on the website of the Scottish Building Standards Agency at www.sbsa.gov.uk, and it may be downloaded free of charge.
------------------------------------------------------------------
1 INTRODUCTION
Background Improved energy performance measures for new construction work are now reflected in the Scottish building regulations. Achieving these standards generally means that buildings are more highly insulated and have better heating system efficiencies than ever before, whilst simultaneously retaining a good level of construction that limits: • air infiltration; and • heat-loss through junctions in the fabric. The Scottish Building Standards Agency recognise the need to provide guidance on how to address these two issues, whilst at the same time avoiding the risks which can arise. The details presented in this document do not endeavour to attain absolute levels of airtightness that will result in a change in the way that dwellings are currently ventilated, but when followed with care will limit air infiltration to an acceptable level. The details can be built using the construction skills currently available and minimise the risk of both surface condensation and interstitial condensation. The arrangements shown however go further than simply minimising condensation risk, to making a useful contribution to reduce heat-loss at junctions of building elements, where traditionally it can be difficult to maintain the insulation levels that can be achieved within the elements themselves. This document provides two levels of guidance. Specific guidance related to each selected construction type and on each construction detail. Supplementary guidance is also provided on associated issues including the selection of insulation, the selection of membranes, air infiltration and some examples of construction issues. Limitations on use The details illustrated here do not form part of the Technical Handbooks but are intended to provide sufficient information to enable users to achieve the level of performance presented in these documents. These details are generic in nature, show principles of construction and for this reason they are not dimensioned, nor drawn to scale. It should be noted that not all permutations of thermal insulation are shown; it is acceptable to provide multiple layers of insulation. Examples of this would be, in the timber frame wall an additional layer of insulation with a preserved
cavity may be provided to the outside of the sheathing board, or in the masonry cavity wall an insulated lining board may be installed in addition to the cavity insulation. All details are suitable for use in domestic type buildings up to six storeys high. Details are provided for the most common construction types: • masonry walls with external insulation • masonry cavity walls with full fill insulation • masonry cavity walls with partial fill insulation • masonry walls with internal insulation • timber frame walls • steel frame walls • miscellaneous junctions, e.g. door thresholds and roof windows. Aim The main aim in providing these details is to illustrate a ready means: • to manage thermal loss (to reduce energy requirement) • to avoid interstitial condensation (which can damage construction) • to avoid surface condensation (which can lead to mould growth and endanger health) • to limit air leakage (to reduce energy requirement) • to prevent rain penetration (which can damage construction and endanger health). The common factors which are illustrated in each detail are: • the position of insulation (to limit thermal bridging) • the position and extent of ventilation (to control condensation) • the position and the different performance characteristics of the building membranes (to manage air and vapour movement and to prevent water entering the building) • the position and type of cavity closers and cavity barriers (to minimise air movement and in the case of the latter, to provide fire resistance). Where these are proprietary types, it is assumed for the purposes of these details that they incorporate a DPC which is capable of directing moisture away from the inside of the building. Other requirements of the Scottish building regulations which are not illustrated by these details, but which should be considered by the designer include: • thermal performance of elements (U-values) • structural • fire resistance and flame spread • ventilation (of rooms) • airborne and impact noise (including flanking sound) • damp-proofing arrangements.
Supplementary Guidance Selection of Insulation The selection of insulation material and the choice of thickness of insulation to be provided will be influenced by a number of factors which are determined by the building procurer and the designer (e.g. architectural features). These fall outwith the scope of this publication. In terms of construction of elements the key issues are a combination of the following: • thermal transmittance (U-value) recommended in Scottish building regulations • thermal conductivity of the insulation material • thermal performance of the ‘non-insulating’ part of the construction (e.g. linings and structural components) • interaction of the insulation material and the remainder of construction (e.g. insulation position in relation to ventilation of the element or bridging of insulation by fixings). The U-value calculation is outwith the scope of this document. Guidance on how this can be done and the other options available are in Section 6 of the Technical Handbooks. Layers of differing insulation materials Where different types of insulation are used within a construction, it is recommended that the insulation nearest to the outer surface of the construction be the least resistant to the passage of water vapour. This is to reduce the possibility of condensation forming in between the insulation layers. For example, where mineral wool is used in conjunction with polystyrene board, the mineral wool should be the outer layer. Where it is essential that the outer layers of insulation has a higher vapour resistivity than the inner layer then condensation risk analysis should always be carried out. Selection of Membranes The details illustrate the location and characteristics of the membranes related to their function in resisting water, water vapour or air. These characteristics are fundamental to the success of the construction and selection of the correct membrane should be made with care. Vapour control layer A vapour control layer should be used: • principally to reduce the spread of water vapour throughout the construction element, where condensation can do harm to the building materials. • as a secondary function to improve the airtightness of the building fabric. Typically this layer is provided on the inside face of the insulation in, timber or steel frame walls, rooms in roof spaces, flat roofs and it may be incorporated as an integral part of a proprietary wall lining board A vapour control layer is a material with a vapour resistance greater than 200 MN·s/g.
Vapour permeable or breather membrane A vapour permeable or breather, water-resistant membrane should be used: • as a primary protection to vulnerable construction materials from the harmful effects of precipitation during the construction process; and • as a secondary protection to vulnerable construction materials from the harmful effects of precipitation, throughout the life of the building; and • to allow water vapour to escape from vulnerable construction materials that would otherwise be entrapped due to lack of ventilation. Typically this layer is provided on the outer face of the inner leaf of a timber frame wall or above sarking insulation where the space between the tiles or slates is ventilated. In the case of the former the membrane has a vapour resistance of no more than 0.6 MN·s/g and in the case of the latter, it has a vapour resistance of no more than 0.25 MN·s/g. Non-vapour permeable roofing membrane A non-vapour permeable, water-resistant roofing membrane should be used: • as a primary protection to vulnerable roof construction materials from the harmful effects of precipitation during the construction process; and • as a primary protection to vulnerable roof construction materials from the harmful effects of precipitation, for example the covering to a built-up felt flat roof directly above the insulation; and • as a secondary protection to vulnerable roof construction materials from the harmful effects of precipitation, for example as a roof tile underlay where the roof space is ventilated above the insulation. This type of layer has a vapour resistance of more than 0.25 MN·s/g. Sequence of construction Some of the details presented in this document can only be followed effectively if consideration is given to the sequence of construction. This is important with regard to the placing of insulation materials and particularly where insulation needs access from two sides to allow correct positioning. An example of this is at the eaves of a roof where it may be necessary to fit the insulation which links the wall and roof insulation before the soffit boards are fitted. Dense Block For the purposes of this document a dense block is one with a thermal conductivity greater than 0.7 W/mK. Thermal Conductivity (lambda - λ ) Thermal conductivity is a measure of a material’s ability to conduct heat. It is measured in W/mK and is the quantity of heat (in Watts) which will pass through 1 square metre of the material 1 metre thick for each degree difference in temperature between one side of the material and the other. Any quoted thermal conductivity of a given material is, therefore, independent of its thickness.
Air infiltration The details shown in this document contain measures designed to reduce air infiltration. This depends on the form of construction and the level of workmanship but the objective is to form a definable, continuous air barrier around the dwelling. Ways of preventing air infiltration should then be considered at every penetration of this barrier. Particular care on site should be paid to: • joints between structural components e.g. wall to floors • joints around components and opening within walls • service penetrations – plumbing, electrical and ventilation. General • close any vertical ducts at the top and bottom where they meet the air barrier (e.g. boxing round soil vent pipe’s) • seal any service penetrations through the air barrier • select the appropriate sealant or gap filler for the size of gap and degree of movement anticipated. Masonry Construction • ensure continuous ribbons of adhesive are used to fix to dry lining at perimeters of external walls, openings, and services on external walls. The importance of correct sealing of dry lining on dabs needs to be stressed, as this is a key area of infiltration and can seriously affect the overall ventilation rate • use joist hangers to support floor joists • seal under skirting boards where dry lining is used, or on suspended floors. Timber Frame • ensure DPC’s are turned up behind sole plates and lap with vapour control layers; alternatively seal with mastic or a gasket between the DPC and sole plate • place bead of mastic on timber floor deck before positioning wall panels (timber ground floors and intermediate floors) • ensure ‘sheet’ vapour control layers are properly lapped at junctions, and/or, • ensure any vapour control plasterboard is jointed in accordance with the manufacturer’s instructions • always return vapour control layers into door and window reveals, head and sills • cut vapour control layers tight to electrical outlets and seal at piped service penetrations, (with tape or sealant as appropriate) • ensure all breather control membranes overlap each other and are stapled in place.
Steel Frame • all joints between rigid insulation boards be lapped or sealed with tape approved by insulation manufacturer • ensure ‘sheet’ vapour control layers are properly lapped at junctions, and/or, • ensure any vapour control plasterboard is jointed in accordance with manufacturer’s instructions • always return vapour control layers into door and window reveals, heads and sills • cut vapour control layers tight to electrical outlets and seal at piped service penetrations. Examples of some common construction issues Poorly positioned cavity insulation The cavity wall insulation should be installed tight to the outer face of the inner leaf. This will prevent air circulation between the block and insulation reducing the performance of the insulation layer. Debris bridging the cavity Clear all debris including mortar droppings from the cavity as work progresses to prevent cold bridging occurring between the inner and outer leaf. Insulation cut short of the cavity closers Ensure that cavity insulation is cut to suit boards/batts that tightly butt against each other and against surrounding cavity closers and loose fill insulation. Service Penetrations Service penetrations should be core drilled to minimise damage to the insulation layer and facilitate remedial air sealing. Any damage caused to the insulation layer by penetrations through the air barrier should be made good following their installation. This can be achieved by filling any large gaps with loose fibrous insulation, expanding foam insulation and sealing with a thin mastic fillet. This includes behind bath panels, shower trays, kitchen units and into service shafts. Socket outlet/ switch plates Where the air barrier is formed by a plasterboard lining it is recommended that a continuous ribbon of adhesive is applied around the hole prior to installing the plasterboard. This will reduce air leakage through the sockets/ switches into the void beyond. Proprietary gasketed socket boxes and membranes are also available where required. Window and door frames Air leakage is often found to occur between window/door frames and the surrounding construction. Mastic seals are often required between plaster finishes, window boards and frames.
Recessed light fittings Recessed light fittings may permit air leakage where they breach the plasterboard ceiling line into the voids or lofts beyond. They should only be allowed to penetrate the primary air barrier if the units are of an air sealed type or a further secondary air barrier is formed beyond. Extract fans Termination of extract fan ducts should be installed and sealed to prevent air leakage occurring through plasterboard finishes. Where appropriate a continuous ribbon of adhesive should be installed around the penetration. Where possible the ducts should also be sealed to any masonry inner leaf. Extract fans may also be fitted with external flaps to minimise air infiltration through the unit. Stairs Plaster finishes are typically omitted from voids below staircases. Air infiltration may then occur through mortar joints in poor quality masonry into the externally ventilated wall cavities. Plaster finishes should be installed below stairs or a thin render/parge coat shoul be applied to the surface of the masonry. Dormers in room in roof The plasterboard linings surrounding the dormer will form the air barrier. Care should be taken to ensure that the linings form a continuous air barrier and are fully sealed to the window frames.
Section 1
Introduction and Supplementary Guidance
Section 2
2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20
Masonry: External Wall Insulation Pitched Roof, Ventilated Roofspace, Eaves Pitched Roof, Ventilated Roofspace, Gable Pitched Roof, Ventilated Rafter Void, Eaves Pitched Roof, Ventilated Rafter Void, Gable Pitched Roof, Ventilated Batten Void (warm roof), Eaves Pitched Roof, Ventilated Batten Void (warm roof), Gable Timber Flat Roof Timber Flat Roof with Parapet Lintel at Window Head Windows and doors, Jambs and sills Ground Bearing Floor, Insulation Above Slab Ground Bearing Floor. Insulation Below Slab Raft Foundation In-situ Suspended Ground Floor Slab Insulation Above Slab In-situ Suspended Ground Floor Slab, Insulation Below Slab Concrete Beam and Block Suspended Ground Floor Timber Suspended Ground Floor Separating Wall Concrete Intermediate Floor Timber Intermediate Floor
Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link
Section 3
3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 3.20 3.21 3.22
Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Roofspace, Eaves Pitched Roof, Ventilated Roofspace, Gable Pitched Roof, Ventilated Rafter Void, Eaves Pitched Roof, Ventilated Rafter Void, Gable Pitched Roof, Ventilated Batten Void (warm roof), Eaves Pitched Roof, Ventilated Batten Void (warm roof), Gable Timber Flat Roof Timber Flat Roof with Parapet Windows and doors, Lintel Windows and doors, Folded Lintel Windows and doors, Independent Lintel Windows and doors, Jambs and sills Ground Bearing Floor. Insulation Above Slab Ground Bearing Floor, Insulation Below Slab Raft Foundation In-situ Suspended Ground Floor Slab, Insulation above Slab In-situ Suspended Ground Floor Slab, Insulation Below Slab Concrete Beam and Block Suspended Ground Floor Timber Suspended Ground Floor Separating Wall Concrete Intermediate Floor Timber Intermediate Floor
Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link
Section 4
4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 4.19 4.20 4.21 4.22
Masonry: Cavity Wall Insulation: Partial Fill Pitched Roof. Ventilated Roofspace. Eaves. Pitched Roof. Ventilated Roofspace. Gable Pitched Roof, Ventilated Rafter Void, Eaves Pitched Roof, Ventilated Rafter Void, Gable Pitched Roof. Ventilated Batten Void (warm roof). Eaves. Pitched Roof, Ventilated Batten Void (warm roof), Gable Timber Flat Roof Timber Flat Roof with Parapet Lintel at Window Head Windows and doors. Folded Lintel Windows and doors. Independent Lintel Windows and doors. Jambs and sills Ground Bearing Floor. Insulation Above Slab Ground Bearing Floor. Insulation Below Slab Raft Foundation In-situ Suspended Ground Floor Slab, Insulation above Slab In-situ Suspended Ground Floor Slab, Insulation Below Slab Concrete Beam and Block Suspended Ground Floor Timber Suspended Ground Floor Separating Wall Concrete Intermediate Floor Timber Intermediate Floor
Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link
Section 5
5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 5.11 5.12 5.13 5.14 5.15 5.16 5.17 5.18 5.19 5.20
Masonry: Internal Wall Insulation Pitched Roof, Ventilated Roofspace, Eaves Pitched Roof. Ventilated Roofspace. Gable Pitched Roof, Ventilated Rafter Void, Eaves Pitched Roof. Ventilated Rafter Void. Gable Pitched Roof, Ventilated Batten Void (warm roof), Eaves Pitched Roof, Ventilated Batten Void (warm roof), Gable Timber Flat Roof Timber Flat Roof with Parapet Lintel at Window Head Windows and doors, Folded Lintel Windows and doors. Jambs and sills Ground Bearing Floor. Insulation Above Slab Ground Bearing Floor. Insulation Below Slab Raft Foundation In-situ Suspended Ground Floor Slab Insulation above Slab Concrete Beam & Block Suspended Ground Floor Timber Suspended Ground Floor Separating Wall Concrete Intermediate Floor Timber Intermediate Floor
Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link
Section 6
6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 6.10 6.11 6.12 6.13 6.14 6.15 6.16 6.17 6.18 6.19
Timber Frame Pitched Roof, Ventilated Roofspace, Eaves Pitched Roof. Ventilated Roofspace. Gable Pitched Roof, Ventilated Rafter Void, Eaves Pitched Roof, Ventilated Rafter Void, Gable Pitched Roof, Ventilated Batten Void (warm roof), Eaves Pitched Roof, Ventilated Batten Void (warm roof), Gable Timber Flat Roof Timber Flat Roof with Parapet Lintel at Window Head Windows and doors, Jambs and sills Ground Bearing Floor, Insulation Above Slab Ground Bearing Floor, Insulation Below Slab Raft Foundation In-situ Suspended Ground Floor Slab. Insulation Above Slab Concrete Beam and Block Ground Floor Timber Suspended Ground Floor Separating Wall Timber Intermediate Floor Wall junction
Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link
Section 7
7.00 7.01 7.02 7.03 7.04 7.05 7.06 7.07 7.08 7.09 7.10 7.11 7.12 7.13 7.14 7.15 7.16 7.17 7.18 7.19
Steel frame Pitched Roof, Ventilated Roofspace, Eaves Pitched Roof. Ventilated Roofspace. Gable Pitched Roof, Ventilated Rafter Void, Eaves Pitched Roof, Ventilated Rafter Void, Gable Pitched Roof, Ventilated Batten Void (warm roof), Eaves Pitched Roof, Ventilated Batten Void (warm roof), Gable Timber Flat Roof Timber Flat Roof with Parapet Lintel at Window Head Windows and doors, Jambs and sills Ground Bearing Floor, Insulation Above Slab Ground Bearing Floor, Insulation Below Slab Raft Foundation In-situ Suspended Ground Floor Slab. Insulation Above Slab Concrete Beam and Block Ground Floor Timber Suspended Ground Floor Separating Wall Timber Intermediate Floor Wall junction
Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link Link
8.00 8.01 8.02 8.03 8.04 8.05 8.06 8.07 8.08
General Arrangements For future development For future development Roof Window, Ventilated Rafter Void Roof Window. Ventilated batten Void (Warm Roof) Roof Window. Ventilated batten Void (Warm Roof) Level Threshold, Insulation above Slab, Ramped Access Level Threshold, Insulation below Slab, Ramped Access Level Threshold, Timber Floor, Ramped Access Ceilings, Services Penetrations
Link Link Link Link Link Link Link Link Link
Section 8
plaster or plasterboard on dabs solid masonry wall (any type) externally applied insulation system, various fixing methods (see BRE publication Thermal Insulation: avoiding risks - BR262 to establish where it can be used avoiding technical risk) cladding (render finish shown)
2.00 Masonry: External Wall Insulation Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m sarking board proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 10mm minimum continuous opening is required where the roof pitch is above 15° or ventilation gap equivilent to 25mm minimum continuous opening is required where the roof pitch is below 15°, insect mesh should be installed
Masonry: External Wall Insulation 2.01 Pitched Roof, Ventilated Roofspace, Eaves
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Roofspace, Gable
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation between last truss and gable wall
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: External Wall Insulation 2.02 Pitched Roof, Ventilated Roofspace, Gable
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Roofspace, Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
50mm air gap sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
sarking board
proprietary cross flow ventilator to maintain minimum 25mm air gap
where two insulation types are used together see supplementary guidance
roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation to roofspace ventilation gap equivilent to 25mm minimum continuous opening, insect mesh should be installed
Masonry: External Wall Insulation 2.03 Pitched Roof, Ventilated Rafter Void, Eaves
inhabited space vapour control layer
30 minute fire resisting cavity barrier continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Rafter Void, Gable
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be compressed between sarking and wall head
50mm ventilation path over insulation sarking board
roofing membrane where two insulation types are used together see supplementary guidance wall insulation should be taken up level with top of gable fill gaps at top of gable masonry with mortar to form an even surface
Masonry: External Wall Insulation 2.04 Pitched Roof, Ventilated Rafter Void, Gable
vapour control layer continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Rafter Void, Eaves
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
rigid insulation as sarking
support insulation between rafters on battens or clips
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge where two insulation types are used together see supplementary guidance
vapour permeable membrane with a vapour resistance of not more than 0.25 MN.s/g
inhabited space
lap roof and wall insulation minimum 50mm consider sequence of construction, see supplementary guidance
vapour control layer
ventilation to batten void proprietary over fascia ventilator
30 minute fire resisting cavity barrier continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters
Masonry: External Wall Insulation 2.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Batten Void (warm roof), Gable
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation to tile batten void lap roof and wall insulation, roof insulation to be compressed between sarking insulation and wall head vapour permeable membrane (with a vapour resistance of not more than 0.25 MN.s/g)
wall insulation should be taken up level with top of gable fill gaps at top of gable masonry with mortar to form an even surface
Masonry: External Wall Insulation 2.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
insulation between rafters supported on battens or clips
rigid insulation as sarking where two insulation types are used together see supplementary guidance ensure insulation is placed between gable wall and last rafter vapour control layer continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
roofing membrane vapour control layer
declevity piece
fix full height blocking piece and tightly pack mineral wool into void and under deck consider sequence of construction, see supplementary guidance
Masonry: External Wall Insulation 2.07 Timber Flat Roof
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
minimum distance 300mm between top of edge insulation and bottom of roof insulation
render or impervious cladding flashing minimum 150mm above finish roof level place 20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK around parapet roofing membrane declevity piece vapour control layer
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: External Wall Insulation 2.08 Timber Flat Roof with Parapet
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lintel of any type damp proof course 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK between packing pieces sealant to front of frame
Masonry: External Wall Insulation 2.09 Lintel at Window Head
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to back of frame
The same thermal principles apply at the head of doors Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
damp proof course 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK between packing pieces
sealant to front and back of frame/sill continuous ribbon of plaster adhesive, sealing joint between wall and board
plan view
15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK between packing pieces
damp proof course
sealant to front and back of frame/sill
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation carried up to underside of sill section view
Masonry: External Wall Insulation 2.10 Windows and doors, Jambs and sills
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course mastic seal
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed vapour control layer under timber floor finish
external ground level
wall insulation continued at least 150mm below top of floor insulation
Masonry: External Wall Insulation 2.11 Ground Bearing Floor, Insulation Above Slab
damp proof membrane above or below slab
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board damp proof course
mastic seal
external ground level
wall insulation continued at least 150mm below top of floor insulation
Masonry: External Wall Insulation 2.12 Ground Bearing Floor. Insulation Below Slab
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
damp proof membrane
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board damp proof course mastic seal
external ground level
wall insulation continued at least 150mm below top of floor insulation
Masonry: External Wall Insulation 2.13 Raft Foundation
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
damp proof membrane
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed vapour control layer under timber floor finish
mastic seal
external ground level damp proof membrane wall insulation continued at least 150mm below top of floor insulation
Masonry: External Wall Insulation 2.14 In-situ Suspended Ground Floor Slab Insulation Above Slab
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board damp proof course mastic seal
external ground level
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed damp proof membrane
wall insulation continued at least 150mm below top of perimeter insulation dense blocks should not be used below slab
Masonry: External Wall Insulation 2.15 In-situ Suspended Ground Floor Slab, Insulation Below Slab
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
N.B. 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
continuous ribbon of plaster adhesive, sealing joint between wall and board
vapour control layer under timber floor finish
damp proof course mastic seal wall insulation continued at least 150mm below top of floor insulation external ground level
damp proof membrane solum sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Masonry: External Wall Insulation 2.16 Concrete Beam and Block Suspended Ground Floor
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive sealing joint between wall and board expanding foam and continuous sealant 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed between wall and last joist damp proof course
insulation directly under flooring supported either on battens or on netting draped over joists and stapled at required depths
mastic seal external ground level wall insulation continued at least 150mm below top of floor insulation
floor joist ends supported on joist hangers or using scarcement wall solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area damp proof membrane
Masonry: External Wall Insulation 2.17 Timber Suspended Ground Floor
Revision F
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Masonry: External Wall Insulation 2.18 Separating Wall
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone gaps between wall and floor sealed
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Masonry: External Wall Insulation 2.19 Concrete Intermediate Floor
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Masonry: External Wall Insulation 2.20 Timber Intermediate Floor
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard on dabs
inner leaf (block shown) render finish if required/desired
full fill cavity wall insulation (see BRE publication Thermal Insulation: avoiding risks - BR262 to establish where it can be used avoiding technical risk) outer leaf (brick shown)
3.00 Masonry: Cavity Wall Insulation: Full Fill Revision C This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m
proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane
lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 10mm minimum continuous opening is required where the roof pitch is below 15° or ventilation gap equivilent to 25mm minimum continuous opening is required where the roof pitch is 15° or above
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board cavity closer (thin calcium silicate board or similar)
insect mesh should be installed
Masonry: Cavity Wall Insulation: Full Fill 3.01 Pitched Roof, Ventilated Roofspace, Eaves
Read in conjunction with Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Roofspace, Gable
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continue wall insulation to top of gable or alternatively 270mm above bottom of ceiling tie and insert cavity tray insulation between last truss and gable wall
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation: Full Fill 3.02 Pitched Roof, Ventilated Roofspace, Gable
Read in conjunction with Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Roofspace, Eaves
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
50mm air gap sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
sarking board
proprietary cross flow ventilator to maintain minimum 25mm air gap
where two insulation types are used together see supplementary guidance
roofing membrane inhabited space lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 25mm minimum continuous opening insect mesh should be installed
Masonry: Cavity Wall Insulation: Full Fill 3.03 Pitched Roof, Ventilated Rafter Void, Eaves
vapour control layer
30 minute fire resisting cavity barrier continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board cavity closer (thin calcium silicate board or similar)
Read in conjunction with Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Rafter Void, Gable
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be compressed between sarking and wall head
50mm ventilation path over insulation sarking board
roofing membrane where two insulation types are used together see supplementary guidance fill gaps at top of gable masonry with mortar to form an even surface wall insulation should be taken up level with top of gable
vapour control layer cavity closer (thin calcium silicate board or similar)
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation: Full Fill 3.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Rafter Void, Eaves
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
rigid insulation as sarking
support insulation between rafters on battens or clips
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g) lap roof and wall insulation minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance ventilation to batten void proprietary over fascia ventilator
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters
Masonry: Cavity Wall Insulation: Full Fill 3.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge
where two insulation types are used together see supplementary guidance
inhabited space
vapour control layer 30 minute fire resisting cavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board cavity closer (thin calcium silicate board or similar)
Read in conjunction with Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Batten Void (warm roof), Gable
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation to tile batten void lap roof and wall insulation, roof insulation to be compressed between sarking insulation and wall head vapour permeable membrane (with a vapour resistance of not more than 0.25 MN.s/g)
fill gaps at top of gable masonry with mortar to form an even surface wall insulation should be taken up level with top of gable
insulation between rafters supported on battens or clips
rigid insulation as sarking where two insulation types are used together see supplementary guidance ensure insulation is placed between gable wall and last rafter cavity closer (thin calcium silicate board or similar) vapour control layer continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation: Full Fill 3.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with Masonry: Cavity Wall Insulation: Full Fill Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed fix full height blocking piece and tightly pack mineral wool into void and under deck
roofing membrane vapour control layer
declevity piece
consider sequence of construction, see supplementary guidance
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board cavity closer (thin calcium silicate board or similar)
Masonry: Cavity Wall Insulation: Full Fill 3.07 Timber Flat Roof
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
minimum distance 300m between top of edge insulation and bottom of roof insulation
render or impervious cladding flashing minimum 150mm above finish roof level place 20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK around parapet roofing membrane declevity piece vapour control layer
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation: Full Fill 3.08 Timber Flat Roof with Parapet
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
steel lintel continuous baseplate 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK weep hole taken through render sealant to front of frame
steel lintel perforated baseplate weep hole taken through render continuous ribbon of plaster adhesive, sealing joint between wall and board sealant to front and back of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to back of frame
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
Masonry: Cavity Wall Insulation: Full Fill 3.09 Windows and doors, Lintel
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
folded steel lintel
folded steel lintel continuous baseplate
no baseplate weep hole taken through render sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board weep hole taken through render sealant to front and back of frame
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer
Masonry: Cavity Wall Insulation: Full Fill 3.10 Windows and doors, Folded Lintel
continuous ribbon of plaster adhesive, sealing joint between wall and board 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK
weep hole taken through render
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
cavity tray with a minimum upstand of 140mm and stop ends
any lintel type can be used insulation brought down to window opening and cavity closed weep hole taken through render
sealant to front of frame
Masonry: Cavity Wall Insulation: Full Fill 3.11 Windows and doors, Independent Lintel
continuous ribbon of plaster adhesive, sealing joint between wall and board sealant to back of frame
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front of frame damp proof course insulation between packing pieces sealant to back of frame continuous ribbon of plaster adhesive, sealing joint between wall and board insulation between packing pieces
plan view
sealant to front and back of sill
sealant to front and back of sill
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course
section view
Masonry: Cavity Wall Insulation: Full Fill 3.12 Windows and doors, Jambs and sills
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board vapour control layer under timber floor finish
damp proof course wall insulation continued at least 150mm below top of floor insulation
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
external ground level damp proof membrane above or below slab
Masonry: Cavity Wall Insulation: Full-Fill 3.13 Ground Bearing Floor. Insulation Above Slab
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
external ground level damp proof membrane wall insulation continued at least 150mm below top of floor insulation
Masonry: Cavity Wall Insulation: Full Fill 3.14 Ground Bearing Floor, Insulation Below Slab
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
external ground level wall insulation continued at least 150mm below top of perimeter insulation
Cavity Wall Insulation: Full Fill 3.15 Raft Foundation
damp proof membrane
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
vapour control layer under timber floor finish damp proof course
external ground level
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around any screed damp proof membrane
wall insulation continued at least 150mm below top of floor insulation
Masonry: Cavity Wall Insulation: Full Fill 3.16 In-situ Suspended Ground Floor Slab, Insulation above Slab
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course wall insulation continued at least 150mm below top of perimeter insulation
external ground level
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed damp proof membrane
dense blocks should not be used below slab
Masonry: Cavity Wall Insulation: Full Fill 3.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board vapour control layer under timber floor finish 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
damp proof course
wall insulation continued at least 150mm below top of floor insulation external ground level cavity barrier type sleeve through cavity
Masonry: Cavity Wall Insulation: Full Fill 3.18 Concrete Beam and Block Suspended Ground Floor
damp proof membrane solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
expanding foam and continuous sealant 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed between wall and last joist
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
wall insulation continued at least 150mm below top of floor insulation damp proof course external ground level cavity barrier type sleeve through cavity
solum
floor joist ends supported on joist hangers or using scarcement wall sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area damp proof membrane
Masonry: Cavity Wall Insulation: Full Fill 3.19 Timber Suspended Ground Floor
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Masonry: Cavity Wall Insulation: Full Fill 3.20 Separating Wall
plan view
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone gaps between wall and floor sealed
continuous ribbon of plaster adhesive, sealing joint between wall and board
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Masonry: Cavity Wall Insulation: Full Fill 3.21 Concrete Intermediate Floor
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone continuous ribbon of plaster adhesive, sealing joint between wall and board
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Masonry: Cavity Wall Insulation: Full Fill 3.22 Timber Intermediate Floor
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard on dabs
inner leaf (block shown)
partial fill cavity wall insulation
outer leaf (brick shown)
render finish if required/desired
4.00 Masonry: Cavity Wall Insulation: Partial Fill Revision C This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m sarking board proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 10mm minimum continuous opening is required where the roof pitch is below 15° or ventilation gap equivilent to 25mm minimum continuous opening is required where the roof pitch is 15° or above insect mesh should be installed
Masonry: Cavity Wall Insulation: Partial Fill 4.01 Pitched Roof. Ventilated Roofspace. Eaves.
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar) Read in conjunction with Masonry: Cavity Wall Insulation : Partial Fill, Ventilated Loft, Gable. Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continue wall insulation to top of gable or stop wall insulation 270mm above bottom of ceiling tie place loft insulation between last truss and gable wall
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation: Partial-Fill 4.02 Pitched Roof. Ventilated Roofspace. Gable.
Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Roofspace, Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
50mm air gap sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
where two insulation types are used together see supplementary guidance
proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane
inhabited space lap roof and wall insulation minimum 50mm thickness at narrowest point - consider sequence of construction see supplementary guidance
vapour control layer
30 minute fire resisting cavity barrier continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters
30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
ventilation gap equivalent to 25mm minimum continuous opening
Masonry: Cavity Wall Insulation - Partial Fill 4.03 Pitched Roof, Ventilated Rafter Void, Eaves
Read in conjunction with Masonry: Cavity Wall Insulation: Partial Fill Pitched Roof, Ventilated Rafter Void, Gable
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be compressed between sarking and wall head
50mm ventilation path over insulation sarking board
roofing membrane where two insulation types are used together see supplementary guidance fill gaps at top of gable masonry with mortar to form an even surface
vapour control layer
wall insulation should be taken up level with top of gable
30 minute fire resisting cavity barrier (thin calcium silicate board or similar) continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation: Partial Fill 4.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with Masonry: Cavity Wall Insulation: Partial Fill Pitched Roof, Ventilated Rafter Void, Eaves Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
rigid insulation as sarking
support insulation between rafters on battens or clips
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g) lap roof and wall insulation minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance ventilation to batten void proprietary over fascia ventilator
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters
Masonry: Cavity Wall Insulation: Partial Fill 4.05 Pitched Roof. Ventilated Batten Void (warm roof). Eaves.
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge where two insulation types are used together see supplementary guidance
inhabited space
vapour control layer 30 minute fire resisting cavity barrier
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Read in conjunction with Masonry: Cavity Wall Insulation: Partial Fill Pitched Roof, Ventilated Batten Void (warm roof), Gable Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be compressed between sarking and wall head vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g)
fill gaps at top of gable masonry with mortar to form an even surface wall insulation should be taken up level with top of gable
insulation between rafters supported on battens or clips
rigid insulation as sarking where two insulation types are used together see supplementary guidance vapour control layer ensure insulation is placed between gable wall and last rafter 30 minute fire resisting cavity barrier (thin calcium silicate board or similar) continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation - Partial Fill 4.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with Masonry: Cavity Wall Insulation - Partial Fill Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
fix full height blocking piece and tightly pack mineral wool into void and under deck consider sequence of construction, see supplementary guidance vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer and sealed
roofing membrane vapour control layer
declevity piece
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Masonry: Cavity Wall Insulation - Partial Fill 4.07 Timber Flat Roof
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
minimum distance 300mm between top of edge insulation and bottom of roof insulation
render or impervious cladding flashing minimum 150mm above finish roof level place 20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK around parapet roofing membrane declevity piece vapour control layer
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Cavity Wall Insulation - Partial Fill 4.08 Timber Flat Roof with Parapet
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
steel lintel continuous baseplate 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK weep hole taken through render sealant to front of frame
steel lintel perforated baseplate
continuous ribbon of plaster adhesive, sealing joint between wall and board
continuous ribbon of plaster adhesive, sealing joint between wall and board weep hole taken through render sealant to front and back of frame
sealant to back of frame
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer N.B. in areas of extreme exposure, a cavity tray type damp proof course will be applied on top of the lintel - check with lintel manufacturer
Masonry: Cavity Wall Insulation: Partial Fill 4.09 Lintel at Window Head
note that the same principal applies at the head of doors
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
steel lintel
steel lintel with continuous base plate
weep hole taken through render weep hole taken through render sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board sealant to front and back of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK sealant to back of frame
N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
Masonry: Cavity Wall Insulation: Partial-Fill 4.10 Windows and doors. Folded Lintel
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
any lintel types can be used insulation brought down to window opening and cavity closed weep hole taken through render
sealant to front of frame
Masonry: Cavity Wall Insulation: Partial-Fill 4.11 Windows and doors. Independent Lintel
cavity tray with minimum upstand of 140mm and stop ends
continuous ribbon of plaster adhesive sealing joint between wall and board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar) sealant to back of frame
Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front of frame damp proof course insulation brought to window frame and 30 minute fire resisting proprietary fire / insulating cavity barrier incorporating damp proof course sealant to back of frame continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to front and back of sill
sealant to front and back of sill damp proof course insulation brought to underside of sill and 30 minute fire resisting proprietary fire / insulating cavity barrier incorporating damp proof course
Masonry: Cavity Wall Insulation: Partial Fill 4.12 Windows and doors. Jambs and sills
plan view
continuous ribbon of plaster adhesive, sealing joint between wall and board
section view Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board vapour control layer under timber floor finish
damp proof course
wall insulation continued at least 150mm below top of floor insulation
N.B. 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
external ground level damp proof membrane above or below slab
Masonry: Cavity Wall Insulation: Partial Fill 4.13 Ground Bearing Floor. Insulation Above Slab
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive sealing joint between wall and wallboard damp proof course
wall insulation continued at least 150mm below top of floor insulation
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
external ground level damp proof membrane
Masonry: Cavity Wall Insulation: Partial Fill 4.14 Ground Bearing Floor. Insulation Below Slab
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
damp proof course
external ground level
wall insulation continued at least 150mm below top of perimeter insulation
Masonry: Cavity Wall Insulation: Partial-Fill 4.15 Raft Foundation
continuous ribbon of plaster adhesive sealing joint between wall and wallboard 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
damp proof membrane
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive sealing joint between wall and wallboard
damp proof course
vapour control layer under timber floor finish
wall insulation continued at least 150mm below top of floor insulation external ground level damp proof membrane
Masonry: Cavity Wall Insulation: Partial Fill 4.16 In-situ Suspended Ground Floor Slab, Insulation above Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive sealing joint between wall and wallboard damp proof course wall insulation continued at least 150mm below top of perimeter insulation external ground level
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed damp proof membrane
dense blocks should not be used below slab
Masonry: Cavity Wall Insulation: Partial Fill 4.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive sealing joint between wall and board damp proof course vapour control layer under timber floor finish
wall insulation continued at least 150mm below top of floor insulation external ground level cavity barrier type sleeve through cavity
Masonry: Cavity Wall Insulation: Partial Fill 4.18 Concrete Beam and Block Suspended Ground Floor
damp proof membrane solum sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive sealing joint between wall and board
flexible insulation/expanding foam and continuous sealant insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed between wall and last joist wall insulation continued at least 150mm below top of floor insulation damp proof course external ground level cavity barrier type sleeve through cavity
solum
floor joist ends supported on joist hangers or using scarcement wall sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area damp proof membrane
Masonry: Cavity Wall Insulation: Partial-Fill 4.19 Timber Suspended Ground Floor
Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
damp proof course
plan view
Masonry: Cavity Wall Insulation: Partial Fill 4.20 Separating Wall
plan view
Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone gaps between wall and floor sealed
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Masonry: Cavity Wall Insulation: Partial Fill 4.21 Concrete Intermediate Floor
Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive, sealing joint between wall and board
wall insulation continued across floor zone continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Masonry: Cavity Wall Insulation: Partial Fill 4.22 Timber Intermediate Floor
Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard internally applied insulation system (various fixing methods) inner leaf (block shown) outer leaf (brick shown)
render finish if required/desired
5.00 Masonry: Internal Wall Insulation Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m sarking board proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 10mm minimum continuous opening is required where the roof pitch is below 15° or ventilation gap equivilent to 25mm minimum continuous opening is required where the roof pitch is 15° or above
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
insect mesh should be installed
Masonry: Internal Wall Insulation 5.01 Pitched Roof, Ventilated Roofspace, Eaves
Read in conjunction with Masonry: Internal Wall Insulation Pitched Roof, Ventilated Roofspace, Gable
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation between last truss and gable wall
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Internal Wall Insulation 5.02 Pitched Roof. Ventilated Roofspace. Gable.
Read in conjunction with Masonry: Internal Wall Insulation Pitched Roof, Ventilated Roofspace, Eaves
Revision A
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
50mm air gap sarking board
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
sarking board
proprietary cross flow ventilator to maintain minimum 25mm air gap
where two insulation types are used together see supplementary guidance
roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation to roofspace ventilation gap equivilent to 25mm minimum continuous opening insect mesh should be installed
Masonry: Internal Wall Insulation 5.03 Pitched Roof, Ventilated Rafter Void, Eaves
inhabited space vapour control layer
30 minute fire resisting cavity barrier continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar) Read in conjunction with Masonry: External Wall Insulation Pitched Roof, Ventilated Rafter Void, Gable
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be compressed between sarking and wall head
50mm ventilation path over insulation sarking board
roofing membrane where two insulation types are used together see supplementary guidance fill gaps at top of gable masonry with mortar to form an even surface wall insulation should be taken up level with top of gable
Masonry: Internal Wall Insulation 5.04 Pitched Roof. Ventilated Rafter Void. Gable.
30 minute fire resisting cavity barrier (thin calcium silicate board or similar) continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Read in conjunction with Masonry: Internal Wall Insulation Pitched Roof, Ventilated Rafter Void, Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
rigid insulation as sarking
support insulation between rafters on battens or clips
vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g) lap roof and wall insulation minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance ventilation to batten void proprietary over fascia ventilator restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters
Masonry: Internal Wall Insulation 5.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge where two insulation types are used together see supplementary guidance inhabited space
vapour control layer
30 minute fire resisting cavity barrier continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Read in conjunction with Masonry: Internal Wall Insulation Pitched Roof, Ventilated Batten Void (warm roof), Gable
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation, roof insulation to be compressed between sarking and wall head vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g)
30 minute fire resisting cavity barrier (thin calcium silicate board or similar) fill gaps at top of gable masonry with mortar to form an even surface
insulation between rafters supported on battens or clips
rigid insulation as sarking
where two insulation types are used together see supplementary guidance ensure insulation is placed between gable wall and last rafter vapour control layer continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Internal Wall Insulation 5.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with Masonry: Internal Wall Insulation Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed fix full height blocking piece and tightly pack mineral wool into void and under deck consider sequence of construction, see supplementary guidance
roofing membrane
vapour control layer
declevity piece
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board 30 minute fire resisting cavity barrier (thin calcium silicate board or similar)
Masonry: Internal Wall Insulation 5.07 Timber Flat Roof
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
minimum distance 300mm between top of edge insulation and bottom of roof insulation
render or impervious cladding flashing minimum 150mm above finish roof level place 20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK around parapet roofing membrane declevity piece vapour control layer
continuous ribbon of plaster adhesive, sealing joint between wall and ceiling board
Masonry: Internal Wall Insulation 5.08 Timber Flat Roof with Parapet
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
steel lintel continuous baseplate
weep hole taken through render sealant to front of frame
continuous ribbon of plaster adhesive, sealing joint between wall and board 15mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK sealant to back of frame N.B. in certain circumstances the lintel will require fire resistance - check with lintel manufacturer N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
Masonry: Internal Wall Insulation 5.09 Lintel at Window Head.
The same thermal principles apply at the head of doors Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
folded steel lintel continuous baseplate weep hole taken through render
continuous ribbon of plaster adhesive, sealing joint between wall and board
sealant to front of frame 15mm strip of insulation with thermal conductivity value) not exceeding 0.025W/mK
sealant to back of frame N.B. in certain circumstances the lintel will require fire resistance check with lintel manufacturer N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
Masonry: Internal Wall Insulation 5.10 Windows and doors, Folded Lintel
The same thermal principles apply at the head of doors Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front of frame damp proof course 30 minute fire resisting proprietary fire / insulating cavity barrier, incorporating damp proof course sealant to back of frame continuous ribbon of plaster adhesive, sealing joint between wall and board 15mm strip of insulation with thermal conductivity value) not exceeding 0.025W/mK
plan View
15mm strip of insulation with thermal conductivity value) not exceeding 0.025W/mK sealant to front and back of sill
30 minute fire resisting proprietary fire / insulating cavity barrier, incorporating damp proof course
continuous ribbon of plaster adhesive, sealing joint between wall and board
damp proof course
wall insulation carried up to underside of sill section view
Masonry: Cavity Wall Insulation: Partial-Fill 5.11 Windows and doors. Jambs and sills
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive applied to perimeter of wall flexible insulation /expanding foam
damp proof course
vapour control layer under timber floor finish
external ground level damp proof membrane above or below slab 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
Masonry: Internal Wall Insulation 5.12 Ground Bearing Floor. Insulation Above Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive applied to perimeter of wall flexible insulation /expanding foam
damp proof course
external ground level
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
damp proof membrane
Masonry: Internal Wall Insulation 5.13 Ground Bearing Floor. Insulation Below Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive applied to perimeter of wall flexible insulation /expanding foam
damp proof course
external ground level
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around slab and any screed
damp proof membrane
Masonry: Internal Wall Insulation 5.14 Raft Foundation
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive applied to perimeter of wall flexible insulation /expanding foam
damp proof course
vapour control layer under timber floor finish 20mm strip of perimeter insulation with thermal conductivity ( value) not
external ground level
exceeding 0.025W/mK should be installed around any screed damp proof membrane
Masonry: Internal Wall Insulation 5.15 In-situ Suspended Ground Floor Slab Insulation above Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
flexible insulation /expanding foam continuous ribbon of plaster adhesive applied to perimeter of wall
vapour control layer under timber floor finish 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
damp proof course
damp proof membrane
external ground level cavity barrier type sleeve through cavity
Masonry: Internal Wall Insulation 5.16 Concrete Beam & Block Suspended Ground Floor
solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive applied to perimeter of wall flexible insulation /expanding foam insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed between wall and last joist
floor joist ends supported on joist hangers or using scarcement wall external ground level cavity barrier type sleeve through cavity and cavity tray type damp proof course locally over sleeve
Masonry: Internal Wall Insulation 5.17 Timber Suspended Ground Floor
solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area damp proof membrane
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
damp proof course
continuous ribbon of plaster adhesive applied to perimeter of wall
Plan View Masonry: Internal Wall Insulation 5.18 Separating Wall
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster adhesive applied to perimeter of wall flexible insulation /expanding foam
100mm insulation should be installed in cavity projecting minimum 100mm above and below floor zone (insulation may need to be damp proof course faced in areas of severe exposure) gaps between wall and floor sealed
100mm continuous ribbon of plaster adhesive, sealing joint between wall and board separating floors require additional layers & components to comply with Section 2: Fire and Section 5: Noise
Masonry: Internal Wall Insulation 5.19 Concrete Intermediate Floor
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK continued accross floor zone
continuous ribbon of plaster adhesive applied to perimeter of wall
flexible insulation /expanding foam
continuous ribbon of plaster adhesive, sealing joint between wall and board separating floors require additional layers & components to comply with Section 2: Fire and Section 5: Noise
Masonry: Internal Wall Insulation 5.20 Timber Intermediate Floor
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plasterboard structural timber frame vapour control layer insulation sheathing board vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) stainless steel wall tie cavity outer leaf (brick shown) render finish if required/desired
6.00 Timber Frame Revision B This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m sarking board proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 10mm minimum continuous opening is required where the roof pitch is above 15° or ventilation gap equivilent to 25mm minimum continuous opening is required where the roof pitch is below 15° insect mesh should be installed
Timber Frame 6.01 Pitched Roof, Ventilated Roofspace, Eaves
vapour control layer vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate insulation material in timber frame Read in conjunction with Timber Frame Pitched Roof, Ventilated Roofspace, Gable Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
loft insulation continued up to sheathing of spandrel panel
cavity barrier giving 30 minute fire resistance
vapour control layer vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
Timber Frame 6.02 Pitched Roof. Ventilated Roof Space. Gable
Read in conjunction with Timber Frame Pitched Roof, Ventilated Roofspace, Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
50mm air gap
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
sarking board
proprietary cross flow ventilator to maintain minimum 25mm air gap
where two insulation types are used together see supplementary guidance
roofing membrane inhabited space lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 25mm minimum continuous opening insect mesh should be installed
Timber Frame 6.03 Pitched Roof, Ventilated Rafter Void, Eaves
vapour control layer
30 minute fire resisting cavity barrier
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) vapour control layer cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate insulation material within timber frame
Read in conjunction with Timber Frame Pitched Roof, Ventilated Rafter Void, Gable
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane lap roof and wall insulation, roof insulation to be compressed between sarking and timber frame
differential movement gap sealed with compressible foam or sealant
sarking board 50mm ventilation path over insulation
where two insulation types are used together see supplementary guidance vapour control layer cavity barrier giving 30 minute fire resistance vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
Timber Frame 6.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with Timber Frame Pitched Roof, Ventilated Rafter Void, Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
rigid insulation as sarking
support insulation between rafters on netting, battens or clips vapour permeable membrane (with a vapour resistance of not more than 0.6 MN.s/g) lap roof and wall insulation minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance
ventilation to batten void proprietary over fascia ventilator
restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters
Timber Frame 6.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge to batten space where two insulation types are used together see supplementary guidance
inhabited space vapour control layer
30 minute fire resisting cavity barrier
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) vapour control layer cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate insulation material within timber frame
Read in conjunction with Timber Frame Pitched Roof, Ventilated Batten Void (warm roof), Gable
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation to tile batten void vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g) lap roof and wall insulation, roof insulation to be compressed between sarking and timber frame
insulation between rafters supported on battens, clips or netting rigid insulation as sarking where two insulation types are used together see supplementary guidance vapour control layer
differential movement gap sealed with compressible foam or sealant vapour control layer cavity barrier giving 30 minute fire resistance vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
Timber Frame 6.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with Timber Frame Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed eaves - fix full height blocking piece and tightly pack mineral wool into void and under deck
roofing membrane vapour control layer
declevity piece
verge - tightly pack mineral wool into void over wall and under deck (not shown)
differential movement gap sealed with compressible foam or sealant consider sequence of construction, see supplementary guidance
cavity barrier vapour control layer vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
Timber Frame 6.07 Timber Flat Roof
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane to be taken minimum 150mm above finished roof level vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed differential movement gap sealed with compressible foam or sealant
cavity barrier giving 30 minute fire resistance declevity piece
vapour control layer
Timber Frame 6.08 Timber Flat Roof with Parapet
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) Revision A
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
cavity barrier giving 30 minute fire resistance
vapour control layer 10mm strip of insulation with thermal conductivity value) not exceeding 0.25W/mK
weep hole taken through render
weep hole taken through render
vapour control layer sealant to front and back of frame
sealant to front of frame
N.B. in certain circumstances the lintel will require fire resistance check with lintel manufacturer
steel lintel
Timber Frame 6.09 Lintel at Window Head
N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
sealant to back of frame
alternative for heavy duty lintel
The same thermal principles apply at the head of doors. Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front of frame damp proof course cavity barrier giving 30 minute fire resistance vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) vapour control layer
Plan View
sealant to back of frame
cavity barrier giving 30 minute fire resistance
sealant to front and back of frame/sill damp proof course
vapour control layer
section view
Timber Frame 6.10 Windows and doors, Jambs and sills
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
damp proof course
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed vapour control layer
vapour control layer under timber floor finish
perpend vent external ground level damp proof membrane above or below slab
Timber Frame 6.11 Ground Bearing Floor, Insulation Above Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
damp proof course
perpend vent
vapour control layer
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
external ground level damp proof membrane
Timber Frame 6.12 Ground Bearing Floor, Insulation Below Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
damp proof course perpend vent
external ground level
Timber Frame 6.13 Raft Foundation
vapour control layer
vapour control layer under timber floor finish damp proof membrane 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
damp proof course
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed vapour control layer vapour control layer under timber floor finish
perpend vent
external ground level damp proof membrane
Timber Frame 6.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
vapour control layer vapour control layer under timber floor finish
damp proof course perpend vent
damp proof membrane external ground level
cavity barrier type sleeve through cavity
Timber Frame 6.15 Concrete Beam and Block Ground Floor
solum sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer expanding foam or continuous sealant
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
insulation directly under flooring - supported either on battens or on netting draped over joists and stapled at required depths
damp proof course
perpend vent external ground level
cavity barrier type sleeve through cavity
Timber Frame 6.16 Timber Suspended Ground Floor
solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area damp proof membrane
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
flexible cavity barrier
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g)
cavity barriers giving 30 minute fire resistance, ensure cavity barriers are not breeched by inappropriate insulation material in the timber frame
vapour control layer alternative corner details, see Timber Frame, Wall Junction
acoustic insulation not shown
Plan View
Timber Frame 6.17 Separating Wall
Revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of no more than 0.6 MN.s/g) continuous bead of sealant applied to floor deck prior to positioning of upper wall panel
perpend vent cavity barriers giving 30 minute fire resistance
vapour control layer
sealant between skirting and floor 20mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK installed around floor perimeter
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Timber Frame 6.18 Timber Intermediate Floor
Revision E
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
standard corner detail - insulation tucked into corner
alternative detail where required for structural reasons - insulation placed in void before wall panels are erected vapour permeable membrane(with a vapour resistance of no more than 0.6 MN.s/g) vapour control layer
plan view
Timber Frame 6.19 Wall Junction
cavity barriers with 30 minute fire resistance are not shown, ensure that those provided are not breeched by inappropriate insulation in the timber frame Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plasterboard structural light gauge steel frame vapour control layer compressible mineral wool insulation rigid insulated sheathing board
stainless steel wall tie in channels fixed to stud structure through insulation cavity outer leaf (brick shown) render finish if required/desired
7.00 Steel Frame
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35° or the roof span is more than 10m sarking board proprietary cross flow ventilator to maintain minimum 25mm air gap roofing membrane lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 10mm minimum continuous opening is required where the roof pitch is above 15° or ventilation gap equivilent to 25mm minimum continuous opening is required where the roof pitch is below 15° insect mesh should be installed
Steel Frame 7.01 Pitched Roof, Ventilated Roofspace, Eaves
vapour control layer cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material mineral wool insulation between the studs in addition to the rigid board over. This insulation must be tightly packed and be in direct contact with the rigid board stainless steel wall tie in channels fixed to stud structure through insulation Read in conjunction with Warm Steel Frame Pitched Roof, Ventilated Roofspace, Gable
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
loft insulation continued up to inner face of the rigid sheathing insulant
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
stainless steel wall tie in channels fixed to stud structure through insulation
vapour control layer
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
Steel Frame 7.02 Pitched Roof. Ventilated Roof Space. Gable
Read in conjunction with Steel Frame Pitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
50mm air gap
ventilation gap equivalent to 5mm minimum continuous opening at ridge is required
sarking board
proprietary cross flow ventilator to maintain minimum 25mm air gap
where two insulation types are used together see supplementary guidance
roofing membrane inhabited space lap roof and wall insulation, minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters ventilation gap equivilent to 25mm minimum continuous opening insect mesh should be installed stainless steel wall tie in channels fixed to stud structure through insulation
Steel Frame 7.03 Pitched Roof, Ventilated Rafter Void, Eaves
vapour control layer 30 minute fire resisting cavity barrier vapour control layer cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board Read in conjunction with Steel Frame Pitched Roof, Ventilated Rafter Void, Gable
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane lap roof and wall insulation, roof insulation to be compressed between sarking and timber frame
sarking board 50mm ventilation path over insulation
where two insulation types are used together see supplementary guidance differential movement gap sealed with compressible foam or sealant
stainless steel wall tie in channels fixed to stud structure through insulation
Steel Frame 7.04 Pitched Roof, Ventilated Rafter Void, Gable
vapour control layer
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
Read in conjunction with Steel Frame Pitched Roof, Ventilated Rafter Void, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
rigid insulation as sarking support insulation between rafters on netting, battens or clips vapour permeable membrane (with a vapour resistance of not more than 0.6 MN.s/g) lap roof and wall insulation minimum 50mm thickness at narrowest point consider sequence of construction, see supplementary guidance
ventilation to batten void proprietary over fascia ventilator restraint required for insulation, for example metal banding, wire mesh or similar material, fixed between rafters stainless steel wall tie in channels fixed to stud structure through insulation
Steel Frame 7.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation gap equivalent to 5mm minimum continuous opening is required at ridge to batten space where two insulation types are used together see supplementary guidance inhabited space
vapour control layer
30 minute fire resisting cavity barrier
vapour control layer cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
Read in conjunction with Steel Frame Pitched Roof, Ventilated Batten Void (warm roof), Gable
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation to tile batten void vapour permeable membrane (with a vapour resistance of no more than 0.25 MN.s/g) lap roof and wall insulation, roof insulation to be compressed between sarking and frame
insulation between rafters supported on battens, clips or netting rigid insulation as sarking where two insulation types are used together see supplementary guidance vapour control layer
differential movement gap sealed with compressible foam or sealant stainless steel wall tie in channels fixed to stud structure through insulation
vapour control layer
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material mineral wool insulation between the studs in addition to the rigid board over. This insulation must be tightly packed and be in direct contact with the rigid board
Steel Frame 7.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with Steel Frame Pitched Roof, Ventilated Batten Void (warm roof), Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed eaves - fix full height blocking piece and tightly pack mineral wool into void and under deck
roofing membrane vapour control layer
declevity piece
verge - tightly pack mineral wool into void over wall and under deck (not shown)
differential movement gap sealed with compressible foam or sealant
vapour control layer
consider sequence of construction, see supplementary guidance stainless steel wall tie in channels fixed to stud structure through insulation
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
Steel Frame 7.07 Timber Flat Roof This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane to be taken minimum 150mm above finished roof level
differential movement gap sealed with compressible foam or sealant
insulated upstand having a minimum R value of 0.75 m2K/W supported on a sheathing board around the parapet tightly packed compressible insulant between the wall studs above the level of the roof deck vapour control layer turned up edge of roof insulation, lapped with roof waterproofing layer, and sealed
cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material
stainless steel wall tie in channels fixed to stud structure through insulation
declevity piece vapour control layer
mineral wool insulation between the studs in addition to the rigid board over.This insulation must be tightly packed and be in direct contact with the rigid board
Steel Frame 7.08 Timber Flat Roof with Parapet This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cavity barrier giving 30 minute fire resistance
vapour control layer
weep hole taken through render weep hole taken through render
vapour control layer sealant to front and back of frame
sealant to front of frame
N.B. in certain circumstances the lintel will require fire resistance check with lintel manufacturer
steel lintel
Steel Frame 7.09 Lintel at Window Head
N.B. in areas of extreme exposure, a cavity tray type DPC will be applied on top of the lintel - check with lintel manufacturer
sealant to back of frame
alternative for heavy duty lintel
The same thermal principles apply at the head of doors.
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front of frame damp proof course
proprietary cavity barrier giving 30 minute fire resistance
vapour control layer
Plan View
sealant to back of frame
proprietary cavity barrier giving 30 minute fire resistance
sealant to front and back of frame/sill damp proof course stainless steel wall tie in channels fixed to stud structure through insulation
vapour control layer
section view
Steel Frame 7.10 Windows and doors, Jambs and sills This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
stainless steel wall tie in channels fixed to stud structure through insulation the wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption damp proof course
vapour control layer seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant vapour control layer under timber floor finish
perpend vent external ground level damp proof membrane above or below slab
Steel Frame 7.11 Ground Bearing Floor, Insulation Above Slab This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
stainless steel wall tie in channels fixed to stud structure through insulation the wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption damp proof course perpend vent
vapour control layer seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
external ground level damp proof membrane
Steel Frame 7.12 Ground Bearing Floor, Insulation Below Slab This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
stainless steel wall tie in channels fixed to stud structure through insulation the wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption damp proof course perpend vent
external ground level
vapour control layer
seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant vapour control layer under timber floor finish damp proof membrane 20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK around slab and any screed
Steel Frame 7.13 Raft Foundation This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed
stainless steel wall tie in channels fixed to stud structure through insulation the wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption damp proof course
vapour control layer Seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant vapour control layer under timber floor finish
perpend vent external ground level damp proof membrane
Steel Frame 7.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
20mm strip of perimeter insulation with thermal conductivity ( value) not exceeding 0.025W/mK should be installed around any screed vapour control layer
stainless steel wall tie in channels fixed to stud structure through insulation
seal between the wall and floor membrane with a flexible sealant or seal the gap between the skirting board and floor using a flexible sealant
the wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption
vapour control layer under timber floor finish
damp proof course perpend vent
damp proof membrane external ground level
cavity barrier type sleeve through cavity
solum sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
Steel Frame 7.15 Concrete Beam and Block Ground Floor This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
stainless steel wall tie in channels fixed to stud structure through insulation
seal the gap between the skirting board and floor using a flexible sealant
the wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption
vapour control layer under timber floor finish
insulating block
optional mineral wool insulation directly under flooring
perpend vent
light steel joist with bitumen coated ends built onto masonry wall
damp proof course
external ground level cavity barrier type sleeve through cavity
solum
rigid insulation fixed to the underside of the joists
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area damp proof membrane
Steel Frame 7.16 Steel Suspended Ground Floor This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
stainless steel wall tie in channels fixed to stud structure through insulation
cavity barriers giving 30 minute fire resistance, ensure cavity barriers are not breeched by inappropriate insulation material in the steel frame
vapour control layer
acoustic insulation not shown
Plan View
Steel frame 7.17 Separating Wall This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
continue the wall insulation across the floor abutment zone
sealant between skirting and floor
perpend vent cavity barriers giving 30 minute fire resistance
stainless steel wall tie in channels fixed to stud structure through insulation
separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise
Steel Frame 7.18 Steel Intermediate Floor This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
corner detail using standard sized studs insulation placed in void before second stud is erected
alternative detail using increased stud size - insulation fitted within the stud
vapour control layer
vapour control layer
plan view
Steel Frame 7.19 Wall Junction
cavity barriers with 30 minute fire resistance are not shown, ensure that those provided are not breached by inappropriate rigid sheathing insulation material
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane sarking board ventilation to rafter void consideration to be given to maintenance of circulation proprietary drainage gutter
where two insulation types are used together see supplementary guidance
proprietary flashing window frame to be level or lower than top of counterbatten to minimise thermal bridging
vapour control layer
pack with insulation push flexible insulation into gap between frame and tile batten
side gutter of proprietary flashing
For proprietary details consult roof window manufacturer
proprietary flashing
10mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK to be installed around reveals
General Arrangements 8.02 Roof Window, Ventilated Rafter Void
Revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a vapour resistance of not more than 0.25MN.s/g) rigid insulation as sarking ventilation to batten void
where two insulation types are used together see supplementary guidance
proprietary drainage gutter proprietary flashing window frame to be level or lower than top of counterbatten to minimise thermal bridging
vapour control layer
pack with insulation push flexible insulation into gap between frame and tile batten
side gutter of proprietary flashing
For proprietary details consult roof window manufacturer
proprietary flashing
10mm strip of insulation with thermal conductivity ( value) not exceeding 0.025W/mK to be installed around reveals
General Arrangements 8.03 Roof Window. Ventilated batten Void (Warm Roof)
Revision A
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
U-value through loft hatch should not exceed 0.35W/m ² K
ensure loft hatch / proprietary hatch is fully draught sealed counterbearers and boarding should be provided if access to loft is required
General Arrangements 8.04 Loft Hatch
revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary weather bar seal for air leakage / rain penetration damp proof course stepped down locally at entrance ramped access
surrounding ground level
General Arrangements 8.05 Level Threshold, Insulation above Slab, Ramped Access
continue floor insulation up to back of sill
vapour control layer under timber floor finish damp proof membrane above or below slab
revision D
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary weather bar seal for air leakage / rain penetration damp proof course stepped down locally at entrance ramped access
for sill types other than timber / plastic / composite also include a perimeter of insulation to the rear of sill, minimum 20mm thick, with thermal conductivity ( value) not exceeding 0.025W/mK damp proof membrane
surrounding ground level
continue floor insulation up to back of sill
General Arrangements 8.06 Level Threshold, Insulation below Slab, Ramped Access
revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary weather bar seal for air leakage and rain penetration damp proof course
ramped access
insert 20mm insulation with thermal conductivity ( value) not exceeding 0.025W/mK against inner leaf and back of sill surrounding ground level
solum
sub floor ventilation should be provided, minimum 1500mm ² per metre run of external wall or 500mm ² per m ² floor area
General Arrangements 8.07 Level Threshold, Timber Floor, Ramped Access
revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
seal all service penetrations with expanding foam or other suitable sealant for large voids mineral wool or other material may be used to provide a backing for the sealant similar arrangements should be adopted for service penetrations through ground floors N.B. insulation material has been omitted for clarity
General Arrangements 8.08 Ceilings, Service Penetrations
revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
WWW.SBSA.GOV.UK