I Title: SI.No. Sr. No.
IPOWER
I CONSUMPTION
Description Rotating equipment With Hot SA fan
Unit
Auxilial"'i power consumption at motor a. 100% b. 80% Total installed Bagasse Imported power KW coal
1
10 fans (VFD)
kW
260
105
2 x 180
2
FD fans (VFD)
kW
135
90
2x90
3
SA fans'
kW
291
270
2 x 180
5
Boiler feed water pumps
kW'
571
470
3 x 390
Boiler feed water transfer pumps
kW
60
55
2 x 75
7
HP/LP Dosing pumps
kW
2
2
4 x 0.75
8
Extractor
kW.
8
-
5 x3.7
9
Screw Conveyors
kW
5
-
5x 3.7
10
Drag chain feeder
kW
-
10
4 x3.7
11
Mechanicalspreader
kW
-
5
4 x 3.7
12
Cyclomotor
kW
0.4
-
2 x 0.37
13
Hydraulic Drive
kW
4
4
2 x3.7
14
ESP
kW
80
65
-
15
Margin
kW
40
40
-
I
16
RAVs, Soot Blowers, MOVs
kW
I
17
Total Auxiliary power consumption at MCR at Motor terminals
kW
'6 I~
I I ,I I, Ii I: I
I I
~
Excluded 1456.4
1116.0
Notes: 1. The total guranteed power consumption is for continuous operating equipments only. 2. The above break up is for indication only. The total auxiliary power consumption at MCR is guaranteed. 3. Performance and power consumption measurement tolerance shall be subject to IS 4894 code for fans, HIS code for feed pumps, and IS 325 code for motor efficiency. If these tolerances are not to be applied, a margin of 40KW in the guaranteed figures will be added. 4. All the 10 I FD fans, Bagasse extractor and screw feeder power consumption is based on AC-VFD's
81