AN HOI DIESEL POWER PLANT

DATA SHEET

TITLE: DATA SHEET FOR MV SWITCHGEAR & PANEL

PROJECT NAME: AN HOI DIESEL POWER PLANT CLIENT: CON DAO COMMITTEE PROJECT NO.:

REV. NO.

DATE

REV. NO. PREPARATION DEPT.

DESCRIPTION

PREP'N

NGOC N.T A 28-Jul-11

PREP'N

REVIEW

REVIEW

CHECK

CHECK

APPROVAL

APPROVAL

AN HOI DIESEL POWER PLANT

PAGE: 1 of 9

DATA SHEET 1

Service Description:

MV SWICHGEAR ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

13.8 °C

Max: Altitude:

8

MV SWITCHGEAR GENERAL DATA

40 °C < 1000m

System Voltage:

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

N/A

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

POWER SYSTEM

Outdoor

PURCHASER'S REQUIREMENTS

UNITS

9

Standard of Manufacture

10

Type

11

Location

12

Rated voltage

kV

24

13

Rated frequency

Hz

50

14

Number of phases

15

Rated lightning impulse withstand voltage (IEC 60694)

kV (peak)

95

16

Rated short duration power frequency w'stand voltage

kV (rms)

50 (1 minute)

17

Rated short time withstand current and time

kA (rms)

12.5 kA for 1 secs

18

Internal arc fault withstand, to IEC 60298 Annex AA

19

Duration of internal arc fault test

20

Air insulated, metal enclosed Indoor, non-hazardous

3

Criteria 1 through 6 secs

1

Rated peak withstand current

kA (peak)

125

21

Earth busbar withstand current and time

kA (rms)

12.5 kA for 1 secs

22

Busbar system:

23

Rated normal current (main busbar)

24

Phase segregated busbars

25

Busbar arrangement (Single / Duplicate)

26

Busbar identification

27

Busbar material

28

Busbar insulation

Yes/No

Yes

29

Future busbar extension at either end

Yes/No

No

A

400

Yes / No

VTA Single Colour coded (R-Y-B) HDHC copper

30 31 0

32

Document/drawings:

33

Single line diagrams

34

Project specification

35 36 37 38 39 40 41 42 43 44 45 46 47 48 0

49 50

VENDOR'S RESPONSE

AN HOI DIESEL POWER PLANT

PAGE: 2 of 9

DATA SHEET 1

Service Description:

MV SWICHGEAR

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

13.8 °C

Max:

40 °C

Altitude:

9 Panel exterior paint colour

11

Panel interior paint colour

12

Paint specification

13

Overall dimensions of the switchboard:

14

Total weight

15

Largest shipping section dimensions

16

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

UNITS

PURCHASER'S REQUIREMENTS

Voltage

V

230 VAC

Power consumption

W

Anti-condensation heaters:(external source)

10

< 1000m

System Voltage:

Non-Hazardous

PARTICULARS OF EQUIPMENT

7 8

POWER SYSTEM

Outdoor

VTA

Light grey 10 A 03 White 0

VTA LxWxH

mm

VTA (Note 7)

kg

VTA

(L X W x H)

mm

VTA

Shipping sections (number and weights)

kg

VTA

17

Expected assembly heat dissipation

kW

VTA

18

Ingress protection rating

19

Earthing:

20

Method of busbar earthing

21

Rated short circuit current and time

22

Asymmetrical peak making current capability

23

Key interlock

IP42

Earth switch (ES) 25 kA for 3 secs

kA kA pk

125

Yes/No

Yes, with VCBs

24 25

TEST REQUIREMENTS

26

Type Test

Yes/No

Certificate only required

27

Routine Tests

Yes/No

Yes, see Note 4

28

Special Tests

Yes/No

No

0

29 30 31 32 33 34 35 36 37 38 39 40 0

41 42 43 44 45 46 47 48 49 0

50 51 52 53

VENDOR'S RESPONSE

AN HOI DIESEL POWER PLANT

PAGE: 3 of 9

DATA SHEET 1

Service Description:

MV SWICHGEAR

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

POWER SYSTEM

Outdoor 13.8 °C

Max:

40 °C

Altitude:

< 1000m

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

System Voltage:

PURCHASER'S REQUIREMENTS

UNITS

8

CIRCUIT BREAKER PANEL DATA (* Current Rating Amps) one (1)

9

Number of circuit breakers

10

Panel type

No.

11

Rated normal current

A

12

Rated voltage

kV

24

13

Rated short time withstand current and time

kA (rms)

25 kA for 3 secs

14

Rated peak withstand current

kA (peak)

125

15

Rated short circuit breaking current

kA (rms)

50

16

Rated dc component of short circuit breaking current

%

≥ 35

17

Insulation levels:

18

Rated lightning impulse withstand voltage (IEC 60694)

kV (peak)

110 kV across contacts

19

Rated short duration power frequency withstand voltage

kV (rms)

60 kV across contacts for 1 min

20

Trip coil:

Voltage

V

230 VAC (from UPS source)

Power

VA

VTA

Voltage

V

N/A

Power

VA

N/A

Vacuum or SF6, withdrawable 400 0

21 22

Close coil:

23 24

Circuit breaker closing time

msecs

VTA

25

Circuit breaker opening time

msecs

VTA

26

Mechanical endurance

#

27

Electrical endurance

#

VTA

28

Anti pumping device

Yes/No

Yes

29

Mechanical operations counter

Yes/No

Yes

30

Manual mechanical trip facility

Yes/No

Yes

31

Closed/open position indication

Yes/No

32

Charged/discharged spring indication

Yes/No

Yes

33

Emergency shutdown (ESD) trip

Yes/No

No

34

Load shedding trip

Yes/No

35

Power cable entry

Bottom

36

Control cable entry

Bottom

37

Gland plate

38

Overall dimensions of the panel:

39

Panel Control and Indication

40

"Closed" indication (Red)

Yes/No

41

"Open" indication (Green)

Yes/No

Yes

42

Tripped circuit or blown fuse indication (Amber)

Yes/No

Yes

43

Anti-condensation heater 'ON' indication

Yes/No

Yes

44

Indication Earth switchgear

Yes/No

45

Free contacts for remote Indications

46

HV switchgear Closed

Yes/No

Yes

47

HV switchgear opened

Yes/No

Yes

48

Earth switch connected / disconnected

Yes/No

Yes

VTA 0

Yes 0

No

Brass 0

(D x W x H)

VTA

mm 0

Yes 0

Yes 0

49 50 51 52 53 54 55 0

56

VENDOR'S RESPONSE

AN HOI DIESEL POWER PLANT

PAGE: 4 of 9

DATA SHEET 1

Service Description:

MV SWICHGEAR

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

POWER SYSTEM

Outdoor 13.8 °C

Max:

40 °C

Altitude:

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

< 1000m

System Voltage:

PURCHASER'S REQUIREMENTS

UNITS

VENDOR'S RESPONSE

8 LOCAL

9

Control mode

10

Ammeter & selector switch

Yes/No

11

Voltmeter & selector switch

Yes/No

12

Trip & control circuit supervision

Yes/No

Yes

13

Digital multimeter functions

Yes/No

Yes (as per Single line Diagrams)

14

Relay Types

15

Differential

Yes/No

No

16

Feeder Protection

As per drawings

17

Lockout

As per drawings

18

Trip Circuit Supervision

As per drawings

19

Under voltage/Overvoltage

As per drawings

20

Other

0

Yes Yes 0

Make

As required

21 22 23

Communications

24

Communications with DCS:

Modbus RS485/RS232

Protocol

25

DCS control inputs

Yes/No

26

DCS status outputs

Yes/No

Yes Yes 0

27

Hardware

28

Redundant

Yes Yes/No

29 30

MV CABLES

31

Outgoing Feeders:

32

Type of cable

33

Voltage grade

34

No. of cables and conductor size

35

Cable entry

36

Incomers:

37

Type of cable

38

Voltage grade

39

No. of cables and conductor size

40

Cable entry

0

kV 0

mm² Top/bottom

kV mm² 0

Top/bottom 0

41 42 43 44 45 46 47 48 49 50 51 0

52 53 0

54

Model

AN HOI DIESEL POWER PLANT

PAGE: 5 of 9

DATA SHEET 1

Service Description:

MV PANEL ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

POWER SYSTEM

Outdoor 13.8 °C

Max:

40 °C

Altitude:

8

MV PANEL GENERAL DATA

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

< 1000m

System Voltage:

PURCHASER'S REQUIREMENTS

UNITS

9

Standard of Manufacture

10

Type

11

Location

12

Rated voltage

kV

24

13

Rated frequency

Hz

50

14

Number of phases

15

Rated lightning impulse withstand voltage (IEC 60694)

kV (peak)

95

16

Rated short duration power frequency w'stand voltage

kV (rms)

50 (1 minute)

17

Rated short time withstand current and time

kA (rms)

12.5 kA for 1 secs

18

Internal arc fault withstand, to (IEC 60298 Annex AA.6)

19

Duration of internal arc fault test

20

Air insulated, metal enclosed Indoor, non-hazardous

3

Criteria 1 through 6 sec

1

Rated peak withstand current

kA (peak)

125

21

Earth busbar withstand current and time

kA (rms)

12.5 kA for 1 secs

22

Busbar system:

23

Rated normal current (main busbar)

24

Phase segregated busbars

25

Busbar arrangement (Single / Duplicate)

26

Busbar identification

27

Busbar material

28

Busbar insulation

Yes/No

29

Future busbar extension at either end

Yes/No

30

Panel exterior paint colour

31

Panel interior paint colour

32

Paint specification

33

Overall dimensions of the switchboard:

34

Total weight

35

Largest shipping section dimensions

36

A

400

Yes / No

VTA Single Colour coded (R-Y-B) HDHC copper Yes No Light grey 10 A 03 White 0

VTA LxWxH

mm

VTA (Note 7)

kg

VTA

(L X W x H)

mm

VTA

Shipping sections (number and weights)

kg

VTA

37

Expected assembly heat dissipation

kW

VTA

38

Ingress protection rating

39

Document/drawings:

40

Single line diagrams

41

Project specification

IP42

0

42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57

VENDOR'S RESPONSE

AN HOI DIESEL POWER PLANT

PAGE: 6 of 9

DATA SHEET 1

Service Description:

MV PANEL

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

13.8 °C

Max:

40 °C

Altitude:

< 1000m

System Voltage:

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7 8

POWER SYSTEM

Outdoor

PURCHASER'S REQUIREMENTS

UNITS

Anti condensation heater

No

Yes/No 0

N/A

9

Anti condensation heater rating & voltage

10

Power cable entry

W/V

Bottom

11

Control cable entry

Bottom

12

Gland plate

13

Overall dimensions of the panel:

0

Brass (D x W x H)

VTA

mm 0

14 15 16 17 0

18 19 20 21 22 0

23 0

24

TEST REQUIREMENTS

25

Type Test

Yes/No

Certificate only required

26

Routine Tests

Yes/No

Yes, see Note 4

27

Special Tests

Yes/No

No

0

28 0

29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 0

52 53 54 55

VENDOR'S RESPONSE

AN HOI DIESEL POWER PLANT

091135-PVG-EK-003 PAGE: 7 of 9

DATA SHEET 1

Service Description:

MV PANEL

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

POWER SYSTEM

Outdoor 13.8 °C

Max:

40 °C

Altitude:

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

< 1000m

System Voltage:

PURCHASER'S REQUIREMENTS

UNITS

8

CIRCUIT BREAKER DATA (* Current Rating Amps)

VENDOR'S RESPONSE

one (1)

9

Number of circuit breakers

10

Panel type

No.

11

Rated normal current

A

12

Rated voltage

kV

24

13

Rated short time withstand current and time

kA (rms)

12.5 kA for 1 secs

14

Rated peak withstand current

kA (peak)

125

15

Rated short circuit breaking current

kA (rms)

50

16

Rated dc component of short circuit breaking current

%

≥ 35

17

Insulation levels:

18

Rated lightning impulse withstand voltage (IEC 60694)

kV (peak)

110 kV across contacts

19

Rated short duration power frequency withstand voltage

kV (rms)

60 kV across contacts for 1 min

20

INDICATION & METERING

21

Anti condensation heater

22

Anti condensation heater rating & voltage

23

Power cable entry

Bottom

24

Control cable entry

Bottom

25

Gland plate

26

Overall dimensions of the panel:

27

Indications

28

"Closed" indication (Red)

Yes/No

Yes

29

"Open" indication (Green)

Yes/No

Yes

30

Blown fuse indication (Amber)

Yes/No

31

Anti-condensation heater 'ON' indication

Yes/No

32

Control mode selector switch

33

Metering

34

Kilowatt Hours meter

35

Number of phases

36

Current transformer

Yes/No

Yes

37

Potential Transformer

Yes/No

Yes

38

LIGHTNING SURGE ARRESTORS

39

Rated voltage

kV

24

40

Rated frequency

Hz

48 - 62

41

Continuous operating voltage

kV

42

Nominal discharge current

kA

43

Power frequency reference voltage

kV

24

44

Lightning impulse residual voltage

kV

VTA

45

Steep current impulse residual voltage

kV

46

Switching impulse residual voltage

kV

Load Break Switch with HRC Fuses 400 0

Yes/No

No

W/V

N/A

Brass 0

(D x W x H)

VTA

mm 0 0

Yes 0

No LOCAL 0

Yes

Yes/No 0

3 phase

0

19.2 0

10

VTA 0

47 48 49 50 51 52 53 54

VTA

Make

Model

AN HOI DIESEL POWER PLANT

PAGE: 8 of 9

DATA SHEET 1

Service Description:

MV PANEL

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

13.8 °C

Max: Altitude:

40 °C < 1000m

System Voltage:

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

POWER SYSTEM

Outdoor

8

LIGHTNING SURGE ARRESTORS (Continuing)

PURCHASER'S REQUIREMENTS

UNITS

9

Rectangular current withstand 2000 μs

kA

10

High current withstand 4/10 μs

kA

11

Line discharge Class

12

Partial discharge

13

Creepage distance

mm

VTA

14

Lightning impulse withstand

kV

VTA

15

Power frequency withstand (wet 1 min)

kV

VTA

16

HV CABLES

17

Cable in

18

Type of cable

19

Voltage grade

20

No. of cables and conductor size

21

Cable entry

22

Cable out

23

Type of cable

24

Voltage grade

25

No. of cables and conductor size

26

Cable entry

VTA 0

VTA 1 0

VTA

0

kV 0

mm² Top/bottom

kV mm² 0

Top/bottom 0

27 28 29 30 0

31 32 33 34 35 36 37 38 39 40 41 42 0

43 44 45 46 47 48 0

49 0

50 0

51 52 0

VENDOR'S RESPONSE

AN HOI DIESEL POWER PLANT

PAGE: 9 of 9

DATA SHEET 1

Service Description:

MV SWICHGEAR / PANEL

ENVIRONMENTAL CONDITIONS

2 3

Location:

Indoor

4

Ambient air temp:

Min:

5

Humidity:

87%

6

Hazardous area classification:

POWER SYSTEM

Outdoor 13.8 °C

Max: Altitude:

40 °C < 1000m

8

NOTES:

22000

V



5%

System Frequency:

50

Hz



2%

Neutral Earthing:

Isolated neutral

Non-Hazardous

PARTICULARS OF EQUIPMENT

7

System Voltage:

PURCHASER'S REQUIREMENTS

UNITS

VENDOR'S RESPONSE

9

1. Withdrawable circuit breakers shall be interchangeable with others of the same voltage and current rating.

10

2. Circuit breaker operating mechanisms shall be of the motor/manual spring charge, stored energy, manual/electrical release type.

11

3. Rated short time withstand & breaking currents for circuit breakers shall be not less than ratings for main busbar.

12

4. Refer to High Voltage Switchgear Specification for additional information.

13

5. Refer to Metering & Protection SLD

14

6. Refer to Electrical Equipment Layout for additional information.

15

7. VTA = Vendor to advise.

16

8. N/A = Not Application