Loading documents preview...
TYPES OF THREE-PHASE TRANSFORMER CONNECTIONS & APPLICATION
Learning Objectives Introduction Types of Three-phase Transformer Connections General Considerations for Three-Phase
Transformer Applications Advantages and Disadvantages Recommendations
To familiarize with the common variations of three-
phase transformer connections To
familiarize
with
the
applicability
of
each
transformer connection for specific systems To determine the advantages and disadvantages of
each transformer connection To be able to properly select the appropriate
transformer connection for specific types of systems
Three-Phase Transformer Connections
Three-phase Transformer Connections The
three-phase
transformer
can
be
constructed by either: 1. Banking of three individual single-phase
transformers 2. Combined with one core - single tank
three-phase unit
The individual single-phase transformers can be banked by several configurations. Some of the common configurations are the following: Delta-Wye Wye-Delta Delta-Delta Wye-Wye Open-Delta
The
single
unit
three-phase
transformer
windings are connected also by the same
configuration but its connections are made in one single core. Some other connections are the following: Zig-Zag Scott and T connection
Comparison between Three Single-phase and Single Tank Three-Phase Transformers
Types of Common Transformer Connections and their Characteristics
A. Delta-Wye Transformer Connection
A. Delta-Wye Transformer Connection
A. Delta-Wye Transformer Connection
Three-phase excitation current wave forms (solid) and the third harmonic components combined (dotted).
A. Delta-Wye Transformer Connection
•
Type of three-phase electric power transformer design with Delta-connected windings on its primary and Wye/Star connected windings on its secondary.
•
A neutral wire can be provided on wye output side.
•
Either a single three-phase transformer, or built from three independent single-phase units.
•
Equivalent term is Delta-Star transformer.
A. Delta-Wye Transformer Connection
•
•
Phase voltage = Line voltage / 1.732 Phase current = Line current
•
Used universally for connecting generators to transmission systems because of two very important reasons: 1. Generators are usually equipped with
sensitive ground fault relay protection.
2. Rotating machines can literally be
shaken apart by mechanical forces resulting from zero-sequence currents. The ∆-connected winding blocks zerosequence currents on the transmission system from the generator.
A. Open Delta - Open Delta Transformer Connection
A. Wye – Wye Transformer Connection
A. Wye – Wye Transformer Connection
•The most obvious way of transforming voltages and currents in a three-phase electrical system is to operate each phase as a separate singlephase system. This requires a four-wire system comprised of three phase wires plus a common neutral wire that is shared among the three phases. Each phase is transformed through a set of primary and secondary windings connected phase-to neutral.
The term ‘‘Y-Y connection’’ should be obvious from the fact that the vector diagrams of the primary and secondary windings both resemble the letter Y. Each phase of the primary and secondary circuits is 120 electrical degrees out of phase with the other two phases. This is represented by angles of 120° between the legs of the primary Y and the secondary Y in the vector diagram. Each primary winding is magnetically linked to one secondary winding through a common core leg. Sets of windings that are magnetically linked are drawn parallel to each other in the vector diagram. In the Y-Y connection, each primary and secondary winding is connected to a neutral point. The neutral point may or may not be brought out to an external physical connection and the neutral may or may not be grounded.
A. Wye – Delta Transformer Connection
A. Wye – Delta Transformer Connection
There are times when a grounded Y-Δ transformer is used for no other purpose than to provide a good ground source in an otherwise ungrounded system. Take, for example, a distribution system supplied by a Δconnected (i.e., ungrounded) power source. If it is required to connect phase-toground loads to this system a grounding bank is connected to the system
A. Delta – Delta Transformer Connection
•
Type of three-phase electric power transformer design with Delta-connected windings on its primary and Delta connected windings on its secondary.
•
No neutral wire provision.
•
Either a single three-phase transformer, or built from three independent single-phase units.
•
Phase voltage = Line voltage Phase current = Line current / 1.732
•
Connection in three identical transformers are
symmetrical or balanced Currents & voltages in each of the phase are the
same and their relationship to the line voltages and currents are identical kVA rating of the bank = 1.732 x E x I Associated power in balanced three-phase loads =
1.732 x E x I kVA present in the transformers is equal to the kVA
delivered to the circuit
General Considerations for Transformer Connection Applications
General Considerations for Transformer Connection Applications • To
be
familiar
with
the
general
transformer characteristics is essential for the selection of the
appropriate
connection to meet a given service requirement.
The following are the transformer general characteristics: A. Ratio of kVA output to the kVA rating of
the bank B. Degree of Voltage Symmetry C. Voltage and Current Harmonics D. other operating peculiarities
A. Ratio of kVA output to the kVA rating of the bank Connection in three identical transformers are
symmetrical or balanced Currents & voltages in each of the phase are the
same and their relationship to the line voltages and currents are identical kVA rating of the bank = 1.732 x E x I Associated power in balanced three-phase loads =
1.732 x E x I kVA present in the transformers is equal to the kVA
delivered to the circuit
Thus, ratio of kVA load to the kVA present in the
bank is UNITY or equals to 1.0 This characteristic can be made as reference for
proper selection of transformer connections based on system kVA requirements
kVA output/kVA rating Ratio of various Transformer Connections
Transformer Connection Delta-Wye Wye-Delta Wye-Wye Delta-Delta
kVA output/kVA rating Ratio = 1.0 (100%)
< 1.0
Open-Delta
86.6%
T-type
86.6%
Zig-Zag
86.6%
B. Degree of Voltage Symmetry Another basis is the symmetry with respect to the
lines and with respect to the neutral Delta and Zig-zag:
voltage and current symmetry with respect to
the three lines and lines to neutral All other connections possess varying degrees of
dissymmetry; although three-phase load is balanced, introduce objectionable operating features such as: Unbalanced regulation Current distortion
Open-Delta and T : Dissymmetrical with respect to the three lines
and with respect to neutral Wye-Wye connection: Current dissymmetry between lines and neutral
Wye-Delta or Delta-Wye connection: Complete symmetry for all practical purposes is
maintained by the presence of the Delta
C. Voltage and Current Harmonics Open-Delta and T : introduces unbalanced regulation and third-
harmonic magnetizing currents in the circuit Wye –Wye : introduces third-harmonic voltage Current
dissymmetry
between
lines
and
neutral subjects parallel telephone circuits to serious interference subjects the system itself to dangerous overvoltages under certain conditions
Wye connection: Thus,
Wye-Wye connection neutral is not recommended
with
isolated
Balanced Three-phase Delta-Delta, Wye-Delta, &
Delta-Wye connection (equal and symmetrical windings and core): Do not introduce third harmonics and their multiples into the line Wave shapes of the magnetizing currents to
such banks are superior to the wave shapes of dissymmetrical banks
Paralleled banks of Three-phase Delta-Wye and
Wye-Delta (same rating): Fifth, seventh, seventeenth and nineteenth
harmonics = 180 degrees apart in phase Transformer magnetization line harmonics are
minimized.
Symmetry & Harmonic Characteristics and Effects
DeltaWye
WyeDelta
Delta Delta
WyeWye
Voltage symmetry to the three lines
Voltage symmetry to the lines to neutral
Current symmetry to the lines
Current symmetry to the lines to neutral
Current Dissymmetry between lines & neutral
OpenD elta
T
ZigZag
Dissymmetrical with respect to three lines and neutral
Unbalanced regulation
Introduces third-harmonic magnetizing currents
Introduces third-harmonic voltage
Serious interference to parallel telephone circuits
Dangerous system overvoltages
D. Other operating peculiarities Transformers having equal characteristics (rating and symmetry) such as the Delta-Wye, Wye-Delta, and Delta-Delta, other factors must be considered in order to select the appropriate connection type. Delta-Wye : Neutrals can be derived either for loading or
grounding Less expensive design in very high-voltage
(small line currents) systems since phase voltage = E / 1.732
Balanced three-phase loads equally divided
among the phases regardless of unequal or different impedances of banked transformers Unaffected by different transformer ratios However, when banking transformers having
widely different kVA ratings leads to disproportionate sharing of loads among the three phases.
Delta-Delta: No neutrals available for loading or grounding Less expensive design in very large current
(low-voltage) since phase current = I / 1.732 Balanced three-phase loads unequal division of
loads among the phases when banking with different transformer impedances When
banking transformers having widely different kVA ratings leads to proportionate sharing of loads among the three phases.
Advantages & Disadvantages of Each Transformer Connection
A. Delta-Wye Transformer Connection advantages •
•
One of the major advantages of the ∆-Y connection is that it provides harmonic suppression. Recall that the magnetizing current must contain odd harmonics for the induced voltages to be sinusoidal. In the ∆-Y connection, however, the third harmonic currents, being equal in amplitude and in phase with each other, are able to circulate around the path formed by the ∆-connected winding.
A. Delta-Wye Transformer Connection advantages •
Another important advantage of the ∆-Y connection is that it provides ground current isolation between the primary and secondary circuits. Assuming that the neutral of the Yconnected secondary circuit is grounded, a load connected phase-to-neutral or a phase-to-ground fault produces two equal and opposite currents in two phases in the primary circuit without any neutral ground current in the primary circuit.
A. Wye - Wye Transformer Connection advantages
•The primary and secondary circuits are in phase; i.e., there are no phase angle displacements introduced by the Y-Y connection. This is an important advantage when transformers are used to interconnect systems of different voltages in a cascading manner. •Since the phase-to-neutral voltage is only 57.7% of the phase-to phase voltage, the windings of a Y-Y transformer require fewer turns to produce the same level of excitation in the core compared to windings connected across the phases.
A. Wye - Wye Transformer Connection advantages
•If the neutral end of a Y-connected winding is grounded, then there is an opportunity to use reduced levels of insulation at the neutral end of the winding. A winding that is connected across the phases requires full insulation throughout the winding. •A Y-Y transformer may be constructed as an autotransformer, with the possibility of great cost savings compared to the two-winding transformer construction.
A. Wye - Wye Transformer Connection disadvantages •
The presence of third (and other zero-sequence) harmonics at an ungrounded neutral can cause overvoltage conditions at light load. When constructing a Y-Y transformer using single-phase transformers connected in a bank, the measured line-to-neutral voltages are not 57.7% of the system phase-to-phase voltage at no-load but are about 68% and diminish very rapidly as the bank is loaded.
A. Wye - Wye Transformer Connection disadvantages
. Under certain circumstances, a Y-Y connected threephase transformer can produce severe tank overheating that can quickly destroy the transformer. This usually occurs with an open phase on the primary circuit and load on the secondary.
A. Wye - Wye Transformer Connection disadvantages
. Severe over-voltages due to Series resonance between the third harmonic magnetizing reactance of the transformer and line to-ground capacitance. . If a phase-to-ground fault occurs on the primary circuit with the primary neutral grounded, then the phase-toneutral voltage on the un-faulted phases increases to 173% of the normal voltage. This would almost certainly result in over-excitation of the core, with greatly increased magnetizing currents and core losses.
A. Wye - Wye Transformer Connection disadvantages
• If the neutrals of the primary and secondary are both brought out, then a phase-to-ground fault on the secondary circuit causes neutral fault current to flow in the primary circuit. Ground protection relaying in the neutral of the primary circuit may then operate for faults on the secondary circuit. •The obvious remedy for some of the disadvantages of the Y-Y transformer connection would be to simply solidly ground both the primary and secondary neutrals. In fact, this is standard practice for virtually all Y-Y transformers in systems designed by utility companies.
A. Wye - Wye Transformer Connection disadvantages
•Unfortunately, solidly grounding the neutrals alone does not solve the problem of tank overheating, ferroresonance, and operating primary ground protection during secondary faults.
A. Advantages of Delta-Delta or Ungrounded
Wye-Delta Connection:
•More economical transformer installation for smaller three-phase service with some single-phase loads is possible. •The load is isolated from ground faults on the utility side.
•DG would not typically feed utility-side ground faults except when resonance occurs. •Ungrounded interconnection can be provided for inverter-based systems requiring it.
A. Disadvantages of Delta-Delta or Ungrounded
Wye-Delta Connection:
•Utility-side SLG faults are difficult to detect. •Utility arresters are subjected to high steady-state over-voltages if islanded on an SLG fault. This is true for delta-wye connections as well. •These connections are highly susceptible to ferroresonance in cable-fed installations.
•There are more restrictions on switching for utility maintenance.
RECOMMENDATIONS
Select the proper kVA output to kVA rating ratio
that is appropriate requirements.
for
your
system
kVA
Evaluate if system loads can tolerate voltage and
current dissymmetry which can lead to unbalanced regulation, current distortion and interference in other systems (i.e. telephone circuits and other communication systems) Evaluate if system loads are composed mostly of
non-linear loads which can produce undesired system harmonics.
Check if there are presence of line-to-neutral loads
which necessitates neutral connection from the transformer. Evaluate if system can tolerate voltage and current
harmonics which can easily damage sensitive electronic equipment, etc. Evaluate
if system can not tolerate power interruption due to single-line-to-ground faults (SLG) due to critical opportunity loss or loss of lives such as in some areas of Healthcare facilities and hospitals
Evaluate if neutral system ground is necessary for
easier ground fault detection in the system in order to avoid electrical fires due to arcing ground faults (i.e. hazardous areas, petro-chem facilities, wood manufacturing plants, etc.) Last but not the least, don’t forget about the
bottomline:
PRACTICAL ECONOMICS
THE END!! Thank you for listening!!