PV ARRAY ON BUILDING "A1" ROOF

PV ARRAY ON BUILDING "A2" ROOF

PV ARRAY ON BUILDING "A3" ROOF

AC

AC

AC

PV INV.

PV INV.

10

3

PV INV.

10

3

REC METER

1

UTILITY-OWNED SERVICE TRANSFORMERS ST-1, ST-2, AND ST-3

PANEL "MA1"

TVSS

4

AC

400A MCB 120/240V

DISC. SW.

1-PHASE

3

REC METER

PANEL "A1-1"

PANEL "A1-2"

PANEL "A1-3"

PANEL "A1-4"

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

5

PANEL "MA2"

TVSS

PANEL "A2-1"

PANEL "A2-2"

PANEL "A2-3"

PANEL "A2-4"

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

4

AC

400A MCB 120/240V

DISC. SW.

1-PHASE

REC METER

5

4-METER UNIT LEVITON #6M204-CFG

PANEL "MA3"

TVSS

PANEL "A3-1"

PANEL "A3-2"

PANEL "A3-3"

PANEL "A3-4"

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

4

AC

400A MCB 120/240V

DISC. SW.

1-PHASE 5

4-METER UNIT LEVITON #6M204-CFG

4-METER UNIT LEVITON #6M204-CFG

8

8

8 8

8

8 8

8

8 8

8

2 6

7

10

8

6

TO ST-1

6

7

TO ST-2

7

TO ST-3

POWER RISER DIAGRAM - BUILDINGS A1, A2, & A3 SCALE: NONE

PV ARRAY ON BUILDING "B" ROOF

PV ARRAY ON BUILDING "C" ROOF

PV ARRAY ON BUILDING "D" ROOF

AC

AC

AC

PV INV.

PV INV.

10

3

PV INV.

10

3

REC METER

1

UTILITY-OWNED SERVICE TRANSFORMERS ST-4 AND ST-5

PANEL "MB"

TVSS

4

AC

300A MCB 120/240V

DISC. SW.

1-PHASE

PANEL "B-1"

PANEL "B-2"

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

5

10

3

REC METER

PANEL "MC"

TVSS

AC

400A MCB 120/240V

DISC. SW.

1-PHASE

REC METER

PANEL "C-1

PANEL "C-2"

PANEL "C-3"

PANEL "C-4"

PANEL "C-5"

PANEL "C-6"

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

4

5

2-METER UNIT LEVITON #6M202-CFG

PANEL "MD"

TVSS

PANEL "D-1"

PANEL "D-2"

PANEL "D-3"

PANEL "D-4"

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

125A MCB 120/240V 1-PHASE

4

AC

400A MCB 120/240V

DISC. SW.

1-PHASE 5

4-METER UNIT LEVITON #6M204-CFG

6-METER UNIT LEVITON #6L206-CFG

8

8

8

8

8

8 8 8

2

8 8

8 8

9

6

6

TO ST-4

7

6

TO ST-5

7

POWER RISER DIAGRAM - BUILDINGS B, C, & D

SERVICE GROUNDING SYSTEM GENERAL NOTES

TO ST-5

PHOTOVOLTAIC SYSTEM GENERAL NOTES:

SCALE: NONE

A. ALL CONDUCTORS USED FOR THE GROUNDING SYSTEM SHALL BE COPPER.

A

ALL PHOTOVOLTAIC (PV) SYSTEM COMPONENTS AND WIRING FOR EACH OF THE (7) BUILDINGS SHALL BE PROVIDED AND INSTALLED BY THE PV SYSTEM CONTRACTOR. NOTE: * PV SYSTEM CONTRACTOR IS REQUIRED TO OBTAIN INDEPENDENT PERMIT FROM THE AHJ PRIOR TO STARTING THEIR WORK.

B

THE PV SYSTEM CONTRACTOR SHALL REFER TO PV SERIES DRAWINGS FOR PV WORK REQUIRED. THE PV SERIES DRAWINGS SHALL BE ENGINEERED AND STAMPED BY A PROFESSIONAL PV SYSTEM DESIGN ENGINEER. COORDINATE ALL PV WORK WITH AFFORDABLE SOLAR, PH. (505) 944-4220).

C

ELECTRICAL CONTRACTOR SHALL PROVIDE A CONCEALED 3/4" CONDUIT WITH PULL WIRE FROM THE ROOF OF EACH BUILDING TO THE LOCATION OF THE ASSOCIATED BUILDING WALL MOUNTED PV EQUIPMENT. COORDINATE EXACT LOCATION WITH PV SYSTEM INSTALLER.

B. CONNECT THE GROUNDING SYSTEM TO THE FOUR FOLLOWING COMPONENTS: 1. BUILDING STEEL. 2. METAL U.G. COLD WATER PIPE. 3. CONCRETE ENCASED REBAR OR #4 COPPER UFER. 4. 10' GROUND RODS.

PV ARRAY ON BUILDING "M" ROOF

D. THE GROUNDING SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF ARTICLE 250 OF THE 2011 NEC, AND SHALL PROVIDE 5 OHMS OR LESS RESISTANCE TO GROUND. PROVIDE TEST REPORT VERIFYING RESISTANCE LEVEL IS IN COMPLIANCE WITH 5 OHM MAXIMUM.

ELECTRICAL KEYED NOTES: UTILITY-OWNED SERVICE TRANSFORMER WITH 120/240V, 1-PHASE SECONDARY. REFER TO ELECTRICAL SITE PLAN FOR LOCATION.

2

PRIMARY ELECTRICAL FEEDER TO UTILITY SERVICE POINT (BY EL PASO ELECTRIC (EPE), THE ELECTRIC UTILITY COMPANY).

3

PHOTOVOLTAIC (PV) EQUIPMENT PROVIDED AND INSTALLED BY OTHERS UNDER SEPARATE PERMIT AS PART OF THIS PROJECT. REFER TO PV-100 DRAWING BY AFFORDABLE SOLAR INCLUDED FOR REFERENCE. PROVIDE ONE 3/4" CONDUIT STUB-UP FROM METER / PANEL LOCATION TO ROOF FOR PV SYSTEM, COORDINATE EXACT LOCATION WITH PV SYSTEM INSTALLER.

4

METERING EQUIPMENT PER EPE REQUIREMENTS. VERIFY ALL METERING AND SERVICE REQUIREMENTS WITH EPE BLUE BOOK AND EPE REPRESENTATIVE PRIOR TO BEGINNING ANY ELECTRICAL WORK. CONTACT JERRY ORTEGA, PH. (575) 523-3614.

GROUNDING ELECTRODE CONDUCTOR SCHEDULE MAIN BONDING JUMPER

EQUIPMENT BONDING JUMPER

METALLIC PIPE CONDUCTOR

BUILDING STEEL CONDUCTOR

REBAR OR UFER CONDUCTOR

GROUND ROD CONDUCTOR

100A

#2

#8

#8

#8

#8

#8

#8

150A

#1/0

#6

#6

#6

#6

#6

#6

200A

#3/0

#4

#4

#4

#4

#4

#4

225A

#4/0

#2

#2

#2

#2

#2

#2

400A

500

#1/0

#1/0

#1/0

#1/0

#1/0

#1/0

600A

700

#2/0

#2/0

#2/0

#2/0

#2/0

#2/0

800A

1000

#3/0

#3/0

#2/0

#2/0

#2/0

#2/0

1000A

1200

#3/0

#3/0

#3/0

#3/0

#3/0

#3/0

1200A

1400

250KCMIL

250KCMIL

#3/0

#3/0

#3/0

AC

#3/0

UTILITY-OWNED SERVICE TRANSFORMER ST-4

N

COPPER SERVICE GROUNDING ELECTRODE CONDUCTOR, MINIMUM SIZE AS SHOWN ON GROUNDING ELECTRODE CONDUCTOR SCHEDULE

NEUTRAL BUS

AC

300A MCB 120/240V

DISC. SW.

GROUND BUS

1-PHASE

6

#6 CU NEUTRAL BUS

LANDLORD METERING UNIT TO READ INDIVIDUAL APARTMENT PANEL USAGE. INSTALL REQUIRED CT'S IN MAIN PANEL AND MAKE ALL FINAL CONNECTIONS PER MANUFACTURER'S RECOMMENDATIONS. LEVITON VERIFYE MINI-METER MULTIPLE UNIT (MMU) WITH MODHOPPER MODBUS/PULSE TRANSCEIVER, PULSE MODULE, EMB HUB, CT'S AND ALL FINAL CONNECTIONS REQUIRED FOR A COMPLETELY OPERATIONAL SYSTEM. ONE #1/0 BSD COPPER SERVICE GROUND IN 1/2" CONDUIT. REFER TO SERVICE GROUNDING DETAIL.

GROUND BUS BUILDING STEEL, NEC 250.52(2)

DRIVEN 5/8" X 10' COPPER CLAD GROUND ROD (SPACED 15' APART)

5

1

G

EQUIP. BONDING JUMPER, NEC 250.102(C)

4

INTERSYSTEM BONDING TERMINATION (IBT), NEC 250.94

9

SLAB REBAR OR #4 UFER GROUND, NEC 250.52(3)

6

2 COLD WATER PIPE, NEC 250.52(1)

SERVICE GROUNDING SYSTEM DIAGRAM

POWER RISER DIAGRAM - BUILDING M

SCALE: NONE

SCALE: NONE

LO

7

400A SERVICE FEEDER. 3 #500KCMIL CU IN 3" CONDUIT.

8

125A FEEDER. 3 #1 CU AND 1 #6 CU E.GR. IN 1.5" CONDUIT.

9

300A SERVICE FEEDER. 3 #350KCMIL CU IN 2.5" CONDUIT.

10

TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) DEVICE. LEVITON #52120-CM2. CONNECT TO PANEL PER MANUFACTURER'S RECOMMENDATIONS.

ARC I N IE

M EW

ME X I

A

PHASE BUSES

PANEL "MM"

TVSS

01/30/15 REVISION #1.

C

0

REC METER

PANELBOARD

N

MAIN BONDING JUMPER, NEC 250.28

10

3

MAIN SERVICE ENTRANCE EQUIPMENT

SERVICE FEEDER

1

PV INV.

N

EQUIV. SERVICE AMPACITY CU WIRE SIZE

G

1

SA

C. ANY SPLICING SHALL BE VIA CAD-WELD TYPE PROCESS.

18711

C

E

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

POWER RISER DIAGRAMS By: File: Plot Date:

AEC AEC-E-1.0-POWER RISER.DWG 2/12/2015 4:16:17 PM

Sheet

of

E-1.0

PROJECT GENERAL ELECTRICAL NOTES:

SERVICE SIZING CALCULATIONS - LOAD RECAP

SERVICE SIZING CALCULATIONS - LOAD RECAP

A

BLDGS A1 & A2 SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

BLDG A3 SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

TOTAL CONNECTED LOAD ON "MA1" (SAME FOR "MA2") 110.7 KVA

TOTAL CONNECTED LOAD ON "MA3": 111.2 KVA

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:

B

C

D

E

F G

H

I J

K

L

ALL DEVICES SHALL BE IVORY WITH COMPATIBLE PLASTIC PLATES, INSTALLED FOR ADA COMPLIANCE U.N.O. ALL TELEPHONE, DATA, SECURITY, CATV, SOUND AND INTERCOM LOW VOLTAGE SYSTEM ARE PROVIDED BY OTHERS. NOTE: * LOW VOLTAGE CONTRACTORS ARE REQUIRED TO OBTAIN INDEPENDENT PERMITS FROM THE AHJ PRIOR TO STARTING THEIR WORK UTILIZE "DEEP" 4-SQUARES WHERE REQUIRED TO COMPLY WITH NEC 314.6 EXTRA CONSIDERATION SHALL BE GIVEN TO BOXES SUPPLYING HOME-RUNS CONFIRM EXACT ROUGH-IN DIMENSIONS WITH ARCHITECTURAL DRAWINGS, KITCHEN EQUIPMENT, FURNITURE PLAN (IF AVAILABLE) AND SPECIALTY EQUIPMENT GENERAL CONTRACTOR TO SAW-CUT/REMOVE/PATCH EXISTING ARCHITECTURAL SURFACES INCLUDING BUT NOT LIMITED TO SLABS, WALLS AND ROOFS. SHARED NEUTRALS ARE NOT PERMISSIBLE U.N.O. CONDUCTOR TICK MARKS ARE SHOWN FOR CONVENIENCE ONLY, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL CONDUCTORS WHETHER SHOWN OR NOT INCLUDING "TRAVELERS" AS NECESSARY FOR COMPLETELY OPERATIONAL SYSTEMS.

17.57 KVA X 4 X .45 DEMAND FACTOR = 31.63 KVA

17.57 KVA X 4 X .45 DEMAND FACTOR = 31.63 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 38.0 KVA (158A).

DESIGN LOAD = DEMAND LOAD + HOUSE LOAD + FUTURE 20%: 38.5 KVA (160A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SHORT-CIRCUIT CALCULATIONS

SHORT-CIRCUIT CALCULATIONS

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A (USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA, RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A (USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA, RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

ELECTRICAL SYMBOL LEGEND (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

SYMBOL

DESCRIPTION

SYMBOL

CONDUIT, NEW WORK.

2'X4' LAY-IN LIGHTING FIXTURE (TROFFER), TYPE INDICATED BY LETTER. SHADING AND "EM" INDICATES LIGHTING FIXTURE SUPPLIED WITH EMERGENCY BATTERY PACK.

A

HIDDEN OR BURIED.

DESCRIPTION

AE

HOME-RUN CONDUIT.

1'X4' SURFACE MOUNTED LIGHTING FIXTURE.

CONDUCTOR TICK MARKS: GROUND, NEUTRAL, PHASE, SWITCHED, AND ISOLATED GROUND RESPECTIVELY.

1'X4' RECESSED (FLANGED) MOUNTED LIGHTING FIXTURE.

EXISTING CONDUIT.

2'X2' LAY-IN LIGHTING FIXTURE (TROFFER).

FLEXIBLE CONDUIT.

FLUORESCENT STRIP FIXTURE.

CONDUIT TURNING DOWN.

LINEAR PENDANT MOUNTED LIGHTING FIXTURE, LENGTH AS INDICATED.

CONDUIT TURNING UP.

WALL BRACKET LIGHTING FIXTURE.

CONDUIT CAP/STUB-OUT.

POLE MOUNTED AREA LIGHTING FIXTURE, SINGLE-HEAD.

J

CEILING JUNCTION BOX

RECESSED DOWNLIGHT FIXTURE.

J

WALL JUNCTION BOX

SURFACE MOUNTED DRUM TYPE LIGHTING FIXTURE.

#

DUPLEX RECEPTACLE OUTLET, 18"AFF. # INDICATES CIRCUIT.

BOLLARD LIGHTING FIXTURE.

GFCI

GFCI PROTECTED DUPLEX RECEPTACLE. RECEPTACLES WITH TRIP RESET SHALL BE IN READILY ACCESSIBLE LOCATION. SLAVE GFCI-PROTECTED RECEPTACLE (NEC 422.52) FOR ELECTRIC DRINKING FOUNTAIN (EDF) CONCEALED WITHIN CASE.

EX

PROVIDE GFCI-TYPE RECEPTACLES WITHIN 6' OF ANY SINK, IN KITCHENS, BATHROOMS, LAUNDRY AREAS AND OUTDOORS PER NEC 210.8.

FLUSH IN-GROUND LIGHTING FIXTURE.

SERVICE SIZING CALCULATIONS - LOAD RECAP

SERVICE SIZING CALCULATIONS - LOAD RECAP

BLDG B SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

BLDG C SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

TOTAL CONNECTED LOAD ON "MB": 56.7 KVA

TOTAL CONNECTED LOAD ON "MC": 155.0 KVA

QUADPLEX RECEPTACLE, 18" AFF TO CENTER.

EXTERIOR WALL SCONCE LIGHTING FIXTURE.

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (2) UNITS:

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (6) UNITS:

GROUND FAULT CIRCUIT INTERRUPTER (GFCI) DUPLEX RECEPTACLE WITH WEATHER-RESISTANT COVER.

STEP LIGHT LIGHTING FIXTURE.

17.57 KVA X 2 X 1.0 DEMAND FACTOR = 35.14 KVA

17.57 KVA X 6 X .44 DEMAND FACTOR = 46.38 KVA

SPLIT-WIRED DUPLEX RECEPTACLE

PENDANT HUNG CYLINDER-TYPE LIGHTING FIXTURE.

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 42.17 KVA (176A).

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 55.66 KVA (232A).

DUPLEX RECEPTACLE WITH BUILT-IN USB CHARGER OUTLET.

STANCHION MOUNTED SIGN-LIGHTER FIXTURE.

EXTERIOR LIGHTING SHALL COMPLY WITH THE LAS CRUCES OUTDOOR LIGHTING ORDINANCE AND THE NEW MEXICO NIGHT SKY PROTECTION ACT.

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SPECIAL RECEPTACLE, TYPE AS NOTED.

TWIN-EYE EMERGENCY LIGHTING UNIT WITH BATTERY BACK-UP.

ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2011 NEC, 2011 NMEC, AND APPLICABLE CODES AND ORDINANCES ADOPTED BY THE CITY OF LAS CRUCES. REFERENCE WEB SITE:

SHORT-CIRCUIT CALCULATIONS

SHORT-CIRCUIT CALCULATIONS

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A (USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA, RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A (USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA, RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

Sa

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

S

PROVIDE AFCI PROTECTION IN DWELLING UNITS PER NEC 210.12. ELECTRICAL DEVICE INSTALLATION SHALL COMPLY WITH ACCESSIBILITY CODES ADOPTED FOR NEW MEXICO. SPECIFICALLY; MOUNT APPLICABLE SWITCHES, RECEPTACLES, AND ENVIRONMENTAL CONTROLS SO THAT THEY ARE MOUNTED WITH THE TOP OF THE DEVICE NO HIGHER THAN 48 INCHES ABOVE FINISHED FLOOR (AFF) AND THE BOTTOM OF THE DEVICE NO LOWER THAN 15 INCHES AFF. ELECTRICAL DEVICES ABOVE COUNTERTOP (AC) OR OTHER OBSTRUCTION SHOULD COMPLY WITH ICC/ANSI 117.1-2003 SECTION 308.

FIRE ALARM SYMBOL LEGEND (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

SYMBOL

DESCRIPTION FIRE ALARM CONTROL PANEL (FACP). FIRE ALARM MANUAL PULL STATION.

SURFACE MOUNTED PANELBOARD, REFER TO ASSOCIATED PANEL SCHEDULE. FLUSH MOUNTED PANELBOARD, REFER TO ASSOCIATED PANEL SCHEDULE. SINGLE-POLE WALL SWITCH. SUBSCRIPT, IF USED, DESIGNATES CONTROL OF PARTICULAR LIGHTING FIXTURES.

FIRE PROTECTION SPRINKLER SYSTEM POST INDICATOR VALVE (PIV). AHJ

AUTHORITY HAVING JURISDICTION.

EXIT SIGN, DOUBLE-FACED, DIRECTIONAL ARROWS INDICATED. COMBO EXIT SIGN/EMERGENCY TWIN-EYE UNIT. PADDLE FAN, WITH OR WITHOUT LIGHT PER LUMINAIRE SCHEDULE. J-BOX WITH FLEXIBLE CONDUIT CONNECTION TO LAY-IN LIGHTING FIXTURES. NON-FUSED DISCONNECT SWITCH, NEMA 3R IF OUTSIDE, AMPS / POLES INDICATED. FUSED DISCONNECT SWITCH, NEMA 3R IF OUTSIDE, AMPS/ POLES / FUSE SIZE INDICATED.

THREE-WAY SWITCH

4

FOUR-WAY SWITCH

WR

WEATHER-RESISTANT SWITCH

K

KEY-OPERATED SWITCH

D

DIMMER SWITCH, 1200W MINIMUM WATTAGE.

T

CONTROL / LOW VOLTAGE TRANSFORMER.

TT

MECHANICALLY WOUND TWIST-TIMER SWITCH OR ELECTRONIC TIME SWITCH.

T

POWER TRANSFORMER.

T

THERMAL SWITCH.

2

MOTOR, HP SIZE AS INDICATED, "F" = FRACTIONAL HORSEPOWER.

OC

OCCUPANCY SENSOR SWITCH.

EC

EVAPORATIVE COOLER SWITCH.

SERVICE SIZING CALCULATIONS - LOAD RECAP

S

BLDGS D SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

BLDG M SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

S

TOTAL CONNECTED LOAD ON "MD": 111.6 KVA

TOTAL CONNECTED LOAD ON "MM": 45.6 KVA

S

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:

CODE DEMAND LOAD PER NEC 220.40: SERVICE LOAD CALCULATION:

S

17.57 KVA X 4 X 0.45 DEMAND FACTOR = 31.63 KVA

DEMAND LOAD = 44.7 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 38.0 KVA (158A).

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 53.6 KVA (224A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SHORT-CIRCUIT CALCULATIONS

SHORT-CIRCUIT CALCULATIONS

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A (USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA, RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A (USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA, RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

S

S

J

60/3 60/3/45

DOOR OPERATOR PUSH-PAD UNIT (ADA COMPLIANT).

CATV OUTLET PTZ STA

B

E

OH

OVERHEAD PRIMARY ELECTRICAL LINE.

E UG

PRIMARY ELECTRICAL UNDERGROUND FEEDER.

E.GR.

EQUIPMENT GROUND.

U.N.O.

UNLESS NOTED OTHERWISE.

SURVEILLANCE CAMERA, PTZ = PAN, TILT, ZOOM, WEATHERRESISTANT AT EXTERIOR; STA = STATIONARY.

AFF

ABOVE FINISH FLOOR.

DOORBELL SYSTEM PUSHBUTTON.

AC

ABOVE COUNTER.

DOORBELL/CHIME.

WR

WEATHER-RESITANT.

PHOTOCELL. B-2

OWNER FURNISHED, CONTRACTOR INSTALLED.

O.F.C.I.

COMBINATION VOICE/DATA OUTLET, UP 18" U.N.O. EXTEND 3/4" CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING. FLUSH CEILING VOICE/DATA OUTLET. EXTEND 3/4"C. WITH PULL STRING TO CEILING. FLUSH FLOOR VOICE/DATA OUTLET. EXTEND 3/4"C. WITH PULL STRING TO CEILING. TV

BARE SOFT-DRAWN.

BSD

THERMOSTAT

T

FIRE ALARM TAMPER SWITCH. FIRE ALARM FLOW SWITCH.

EXIT SIGN, SINGLE FACE INDICATED BY SHADED QUADRANT.

3

S

FIRE ALARM HEAT DETECTOR. FIRE ALARM DUCT SMOKE DETECTOR.

EXTERIOR WALL MOUNTED EMERGENCY LIGHTING UNIT WITH BATTERY BACK-UP. TRACK MOUNTED LIGHTING ASSEMBLY, ONE FIXTURE HEAD INDICATED.

CEILING MOUNTED DUPLEX RECEPTACLE.

SERVICE SIZING CALCULATIONS - LOAD RECAP

FIRE ALARM STROBE UNIT.

EXTERIOR WALLPACK LIGHTING FIXTURE.

FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE.

S

FIRE ALARM AUDIO/STROBE UNIT.

FIRE ALARM SMOKE DETECTOR.

EDF

GROUND FAULT CIRCUIT INTERRUPTER.

GFCI

MECHANICAL UNIT TAG (EXAMPLE: BOILER B-2 INDICATED), SEE MECHANICAL EQUIPMENT SCHEDULE.

1

C

E

ON

01/30/15 REVISION #1.

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

ELECTRICAL SYMBOL LEGEND By: File: Plot Date:

AEC AEC-E-2.0-SYMBOL LEGEND.DWG 2/12/2015 4:18:04 PM

Sheet

of

E-2.0

1

C

E

ON

01/30/15 REVISION #1.

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

PANEL SCHEDULES By: File: Plot Date:

AEC AEC-E-3.0-PANEL SCHEDULES.DWG 2/12/2015 4:19:37 PM

Sheet

of

E-3.0

ELECTRICAL KEYED NOTES:

ST-1

PASEO DEL ORO CR

1

1

UTILITY-OWNED SERVICE TRANSFORMER (ST) WITH 120/240V, 1-PHASE SECONDARY, REFER TO POWER RISER DIAGRAM. VERIFY ALL SERVICE REQUIREMENTS WITH EL PASO ELECTRIC (EPE) PRIOR TO BEGINNING ANY ELECTRICAL WORK.

2

TELEPHONE TERMINAL BACKBOARD (TTB).

3

EXTEND 4" PVC TELEPHONE SERVICE CONDUIT TO SERVICE PEDESTAL. VERIFY SERVICE LOCATION AND REQUIREMENTS WITH CENTURYLINK PRIOR TO ANY INSTALLATION OR TRENCHING WORK.

4

SECONDARY SERVICE FEEDER BY ELECTRICAL CONTRACTOR, REFER TO POWER RISER DIAGRAM.

5

SERVICE ENTRANCE GEAR, REFER TO POWER RISER DIAGRAM.

6

CONNECT FIRE ALARM DEVICES AT FIRE RISER ROOM TO FIRE ALARM CONTROL PANEL (FACP) IN BUILDING "M", SEE POWER PLAN FOR THIS BUILDING. REFER TO FIRE ALARM SYSTEM DIAGRAM AND FIRE ALARM GENERAL NOTES ON SHEET EM-1.0.

7

TELEPHONE SERVICE PEDESTAL.

8

MAIN TELEPHONE SERVICE DEMARC CABINET, REFER TO TELEPHONE RISER DIAGRAM.

9

TELEPHONE CABINET, REFER TO TELEPHONE RISER DIAGRAM.

10

EXISTING EPE-OWNED OVERHEAD 3-PHASE PRIMARY POWER LINE TO REMAIN.

11

EXISTING EPE-OWNED POWER POLE TO REMAIN.

12

CATV TERMINAL CABINET, FURNISHED BY COMCAST, INSTALLED BY ELECTRICAL CONTRACTOR.

13

2" PVC CATV SERVICE CONDUIT PER COMCAST REQUIREMENTS. VERIFY SERVICE POINT AND CONDUIT ROUTING WITH COMCAST REPRESENTATIVE PRIOR TO ANY INSTALLATION OR TRENCHING WORK.

14

CATV SERVICE PEDESTAL.

15

PRIMARY UNDERGROUND ELECTRICAL FEEDER BY EL PASO ELECTRIC.

16

PHOTOVOLTAIC (PV) REC METER AND INVERTER SHALL BE LOCATED ADJACENT TO SERVICE ENTRANCE EQUIPMENT, REFER TO POWER RISER DIAGRAM ON SHEET E1.0.

17

PV PANELS SHALL BE INSTALLED ON THE ROOF OF THIS BUILDING, REFER TO SHEET PV-1.00 FOR QUANTITY, LOCATION, AND ELECTRICAL CHARACTERISTICS.

18

THIS APARTMENT UNIT IS FOR THE HEARING IMPAIRED.

19

THIS APARTMENT UNIT IS FULLY ACCESSIBLE FOR THE PHYSICALLY CHALLENGED.

20

FIRE ALARM CONTROL PANEL, REFER TO SHEET EM-1.0.

16

"MA1"

EXISTING TRANSFORMER

5 9

T

12

4

EXISTING TELE. PED.

15 TYP 6 UNIT 115

18 17

BUILDING A1 2-STORY (4 APTS)

17

T R U O LD C

BUILDING A3 2-STORY (4 APTS)

E V I R D R E L G EN

6 16

ST-3

"MA3"

1

15 TYP

5

T

9

4 12

15 TYP

GO

15 TYP 15 TYP

6

2 17

BUILDING A2 2-STORY (4 APTS)

ST-5

6

1

ST-4 1 2

4

6

4

T

TS FS

4

T

TS FS

4 7 EXISTING TELE. PED.

16 "MB" 5

17

18

UNIT 106

UNIT 103

19

19

9

BUILDING M (OFFICE / LAUNDRY)

UNIT 107

16 "MC" 5

6

12

9

5

"MA2" 16

5 "MM" 16

8 4

1

12

ST-2

TS FS

9

17

12

BUILDING D 2-STORY (4 APTS)

BUILDING C 2-STORY (6 APTS)

BUILDING B 2-STORY (2 APTS)

20 12

12

17

17

TS FS

9

5 "MD" 16

14

6

T 13

CATV T

10

10

11 3

PP

PP 10

ELKS DRIVE

1 ONE 4" PVC CONDUIT W/PULL STRING TO CENTURYLINK PEDESTAL.

NORTH

2 ONE BARE # 6 SOLID CU TO TO INTERSYSTEM BONDING TERMINAL (IBT).

ELECTRICAL SITE PLAN

3 CENTURYLINK DEMARK, E.C. TO PROVIDE CIRCLE AW #420 NEMA 3R ENCLOSURE WITH BACKBOARD.

1" = 20'-0"

4 E.C. PROVIDED 24X24X12 NEMA 3R J-BOX WITH PLYWOOD BACKBOARD AND LOCKING COVER. 5 DIRECT BURY TELEPHONE DISTRIBUTION CABLE.

2

03/04/15 REVISION #2, RELOCATE ST-5.

6 LIGHTNING PROTECTION.

1

01/30/15 REVISION #1.

7 CAT 5E PVC COATED TELEPHONE CABLING AND SINGLE PORT TERMINATION PLATE TO EACH PHONE OUTLET.

N

2 ONE BARE # 6 SOLID CU TO TO INTERSYSTEM BONDING TERMINAL (IBT).

7

7

7

7

7

7

4

4

4

4

4

4

3

2

6

6 5

6

6

6

6

C

3

3

3

3

3

3

CCTV CAB.

CCTV CAB.

CCTV CAB.

CCTV CAB.

CCTV CAB.

CCTV CAB.

3

CCTV PEDESTAL

CCTV CAB. 4

2

5 5

1

NI E

ME X I C EW

18711

4 2" PVC CONDUIT WITH PULL STRING.

2" C.

TEL. CAB.

ARCI

3 COMCAST PROVIDED CABINET.

TTB BLDG. M

TELEPHONE PEDESTAL

M

0

8 TYPICAL VOICE/DATA (PHONE) OUTLET, FURNISHED BY E.C.

LO

GA

1 ONE 2" PVC CONDUIT W/PULL STRING TO COMCAST PEDESTAL.

SA

11

1

5

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC.

4 4

5

E

ON

4 4

5

4

TELEPHONE RISER DIAGRAM

CATV RISER DIAGRAM

SCALE: NONE

SCALE: NONE

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Paseo Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

ELECTRICAL SITE PLAN By: File: Plot Date:

AEC AEC-SITE-ES-1.0.DWG 3/4/2015 1:54:37 PM

Sheet

of

ES-1.0

PASEO DEL ORO CR 2

BUILDING A1 (4 APTS)

BUILDING A3 (4 APTS)

GO

ENGL

E V I R ER D

T R U O LD C

TYP 3

1 2

BUILDING A2 (4 APTS)

2

2

BUILDING M (OFFICE / LAUNDRY)

BUILDING B (2 APTS)

BUILDING D (4 APTS)

BUILDING C (6 APTS) 3 TYP

3 TYP

NORTH

ELKS DRIVE

ELECTRICAL SITE LIGHTING PLAN

1" = 20'-0"

ELECTRICAL KEYED NOTES:

IECC LIGHTING COMPLIANCE - SITE LIGHTING THE SITE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC). REFERENCE SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS

1

EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL/TIMECLOCK CONTROLS. USE #10 WIRING THROUGHOUT ENTIRE RUN.

2

PARKING LOT FIXTURE ON 12' POLE, REFER TO POLE BASE MOUNTING DETAIL.

3

REFER TO ASSOCIATED BUILDING ELECTRICAL PLAN FOR CIRCUITING TO THIS LIGHTING FIXTURE.

505.6 - EXTERIOR LIGHTING 1.

TABLE 505.6.2(1) - EXTERIOR LIGHTING ZONES: THIS PROJECT SITE IS CLASSIFIED AS LIGHTING ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS DISTRICT.

2.

TABLE 505.6.2(2) - LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS:

BASE SITE ALLOWANCE: 600W PARKING AREAS AND DRIVES: 0.06 W/SF WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF SPECIAL FEATURE AREAS: 0.14 W/SF STAIRWAYS: 1.0 W/SF MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR THE SITE: 2,140W. ACTUAL EXTERIOR LIGHTING LOAD = 1,026W. THIS BUILDING COMPLIES WITH THE MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE. FINISHED GRADE

C

E

TO BRANCH CIRCUIT PER PLAN

TO EXTERIOR LIGHTS

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

LIGHTING CONTROL DIAGRAM

POLE BASE MOUNTING DETAIL

SCALE: NONE

SCALE: NONE

ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Paseo Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

ELECTRICAL SITE LIGHTING PLAN By: File: Plot Date:

AEC AEC-SITE-ES-1.1 SITE LIGHTING.DWG 2/12/2015 4:22:10 PM

Sheet

of

ES-1.1

PASEO DEL ORO CR 16 TYP 0.1

SB

0.1

SA

5.9

10.4

10.0

4.4

0.1

SA

2.9 0.2

1.6

SA

0.3

SA

0.7 0.2

0.4

0.1

0.7

SA SA

1.3

0.0

BUILDING A3 (4 APTS)

0.0

1.4

0.0

TYP 17

E V I R D R E L ENG

SA

0.0

1.5

SA

1.6

T R U O C D L O G

BUILDING A1 (4 APTS)

0.9

0.0 0.0

1.1 0.0 0.8

SA

0.1

SA

0.5

0.1

0.4 0.3

3.5

3.4

8.8

SA15.1 8.9 15.0 18.7 SA

0.3 3.0 1.1

0.1 0.1

SA

0.1

0.3

0.0

0.3

0.0

SA

0.4

0.0

0.6

6

SE

SC

3.7

SC

MM-7 1.3

0.8

SE

1.0

BUILDING A2 (4 APTS)

1.0

SA 1.5

2.7

SC

0.0

10.3

SE

SC

SB

0.2

9.4

0.4

SB

0.3

8.2

0.4 0.0

0.5

0.8 0.6

0.2 0.9 2.3

6.9 10.9 11.5 SA 7.7 4.1

1.1 0.3 0.2

0.1 0.1

0.1

0.0 0.0 0.0 0.0 0.0

0.0

0.0 0.0

0.1 0.1

0.0

0.0 0.0

0.0 0.0

0.0 0.0

0.0

0.0

0.0 0.1

0.2 0.2 0.2

0.1

0.0 0.0

0.0 0.0 0.1

0.7 1.4

0.2

2.4 3.9 0.2

1.5 1.7

SA

0.0

2.5

0.0

6.5

0.3

2

SA

0.0

9.6

0.0

8.8

0.6

1.5 1.2 0.9

0.0

SA

0.5

0.1

BUILDING M (OFFICE / LAUNDRY)

6.6

0.0

0.0

0.0

0.0

1.0

SA SA

BUILDING B (2 APTS)

SD

SD

SA

SA

0.3

SA

BUILDING C (6 APTS)

SD

0.8

BUILDING D (4 APTS)

0.5

SD

0.5

SD SA

SD

0.2

17 TYP 17 TYP

SA

0.1

SA

SA

0.4

SA

SA

SA

SA

0.3 0.2

0.1 0.1 0.0 0.1 0.0 0.0 0.0 0.0 0.0

0.0 0.0

0.0 0.0 0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

NORTH

ELKS DRIVE

ELECTRICAL SITE LIGHTING LUMENS CALC

1" = 20'-0"

Luminaire Schedule Symbol

Qty

Label

Arrangement

Total Lamp Lumens

LLF

Description

34

SA

SINGLE

N.A.

0.930

RAB # SLIM26YWPC

3

SB

SINGLE

N.A.

0.930

RAB # SLIM26YWPC-ON 12 FT POLE

4

SC

SINGLE

N.A.

0.930

BK LIGHTING # BQL-LED-E36A9-WHP

3

SD

SINGLE

1200

0.930

VOLUME # V8853-6 WHITE

3

SE

SINGLE

1200

0.930

VOLUME # V8853-6 WHITE

Calculation Summary: Lighting levels calculated by point-to-point method using AGi32 software Label

CalcType

Units

Avg

Max

Min

Avg/Min

Max/Min

PARKING_Top

Illuminance

Fc

0.38

7.0

0.0

N.A.

N.A.

SIDEWALK AROUND SITE_Top

Illuminance

Fc

0.30

2.5

0.0

N.A.

N.A.

C

E

SIDEWALK INTERIOR SITE_1_Top

Illuminance

Fc

1.96

13.0

0.0

N.A.

N.A.

SIDEWALK INTERIOR SITE_Top

Illuminance

Fc

2.04

18.8

0.0

N.A.

N.A.

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Paseo Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

ELECTRICAL SITE LIGHTING LUMENS CALC By:

AEC

AEC-SITE-ES-1.2 SITE LIGHTING LUMEN CALCS.DWG File: Plot Date:

2/12/2015 4:23:16 PM

Sheet

of

ES-1.2

GENERAL NOTES:

DECK

A

REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS. ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

B

BUILDING A1 WITH APARTMENTS 111, 112, 113, AND 114 IS SHOWN ON THIS SHEET, BUILDINGS A2 AND A3 ARE SIMILAR BUILDINGS. APARTMENT NUMBERS ARE 107, 108, 109, 110 FOR BUILDING A2, AND 115, 116, 117, 118 FOR BUILDING A3.

6 MECH. 101

6

6

STORAGE 109

CU-3

DECK

2

2

APARTMENT 114 (UNIT STYLE "3")

APARTMENT 111 (UNIT STYLE "3")

MECH. 101

STORAGE 109

TO APT. 111

5

TO APT. 113

TO APT. 112

ELECTRICAL KEYED NOTES:

2

CU-3

5

MECH. 101

BEDROOM 2 111

5

CU-3

DECK

STAIRS 101

2 STORAGE 109

APARTMENT 113 (UNIT STYLE "3")

HALLWAY 113

APARTMENT 112 (UNIT STYLE "3")

BEDROOM 2 111

BEDROOM 2 111

BATH 112 STAIRS 101

STAIRS 101

HALLWAY 113

HALLWAY 113

BATH 112

BEDROOM 3 114

BEDROOM 3 114

NORTH

NORTH

SECOND FLOOR ELECTRICAL PLAN - BUILDINGS A1, A2, A3

1/8"=1'-0"

REFER TO ENLARGED UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN FOR WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

2

REFER TO ENLARGED UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN FOR WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

3

MAIN DISTRIBUTION / HOUSE PANEL FOR BUILDING A1, SIMILAR FOR PANELS "MA2" AND "MA3" WHICH SERVE BUILDINGS A2 AND A3 RESPECTIVELY. REFER TO POWER RISER DIAGRAM.

4

TYPICAL POWER PANEL FOR STYLE "3" APARTMENTS, REFER TO ASSOCIATED PANEL SCHEDULE.

5

EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6

INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3 #12 TO CIRCUIT BREAKER INDICATED IN PANEL "MA" AND MAKE ALL FINAL POWER CONNECTIONS.

7

EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN OPERATION.

8

NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO CIRCUIT BREAKER IN PANEL "MA" AND MAKE ALL FINAL POWER CONNECTIONS.

9

CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

10

REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EXTERIOR LIGHTING FIXTURE.

BATH 112

BEDROOM 3 114

ROOF ELECTRICAL PLAN - BUILDINGS A1, A2, A3

1

1/8"=1'-0"

IECC LIGHTING COMPLIANCE THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS AS FOLLOWS: 1.

PORCH

505.2.2.2 - LIGHTING CONTROLS:

A.

THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.

2.

TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A MULTI-FAMILY DWELLING TO 0.7 W/SF.

APARTMENT 114 (UNIT STYLE "3")

TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

PORCH

1 APARTMENT 111 (UNIT STYLE "3")

LIVING 102

STORAGE 108

1

1

APARTMENT 113 (UNIT STYLE "3")

APARTMENT 112 (UNIT STYLE "3")

LIVING 102

STORAGE 108 KITCHEN 107

3.

PORCH

1

BUILDINGS "A1", "A2", AND "A3" AREA IS 5,368 SQ FT, TOTAL ALLOWABLE WATTAGE IS 3,758W. INTERIOR LIGHTING LOAD = 3,200W. THIS MULTIFAMILY DWELLING BUILDING HAS AN LPD OF 0.60W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

PORCH

STORAGE 108

(APARTMENTS 107, 115)

LIVING 102

STORAGE 108

DINING 103

KITCHEN 107

DINING 103

10 TYP

TYP 10 LAUNDRY 104

KITCHEN 107

DINING 103

KITCHEN 107

DINING 103

4 PANEL "A3"

LAUNDRY 104

PANEL "MA1" 3

4 PANEL "A3" LAUNDRY 104

LAUNDRY 104

BATH 1 105

BATH 1 105

BASE SITE ALLOWANCE: 600W PARKING AREAS AND DRIVES: 0.06 W/SF WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF SPECIAL FEATURE AREAS: 0.14 W/SF MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

LIVING 102

BEDROOM 1 106

4 PANEL "A3"

BEDROOM 1 106

4 PANEL "A3"

8 TYP

EUH-1

FS TS

9 RISER -

S

BEDROOM 1 106

BATH 1 105

BEDROOM 1 106

BATH 1 105

7

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDGS "A1, "A2, & "A3": 240W. ACTUAL EXTERIOR LIGHTING LOAD = 168W. THIS BUILDING COMPLIES WITH THE MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE. NORTH

NORTH

KEY PLAN

1/8"=1'-0"

1

NTS

01/30/15 REVISION #1.

M

ARCI

NI E

ME X I C EW

0

N

LO

GA

SA

GROUND FLOOR ELECTRICAL PLAN - BUILDINGS A1, A2, A3

18711

C

E

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

BUILDINGS A1, A2, & A3 ELECTRICAL PLAN By: File: Plot Date:

AEC AEC-A-EA-1.0.DWG 2/12/2015 4:24:29 PM

Sheet

of

EA-1.0

GENERAL NOTES: A 6

6

CU-3

CU-3

5

5

TO APT. 106

TO APT. 105

2

2

APARTMENT 206 (UNIT STYLE "3")

APARTMENT 205 (UNIT STYLE "3")

REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS. ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

ELECTRICAL KEYED NOTES: 1

REFER TO ENLARGED UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN FOR WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

2

REFER TO ENLARGED UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN FOR WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

3

MAIN DISTRIBUTION /HOUSE PANEL FOR THIS BUILDING, REFER TO POWER RISER DIAGRAM.

4

TYPICAL POWER PANEL FOR STYLE "3" APARTMENTS, REFER TO ASSOCIATED PANEL SCHEDULE.

5

EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6

INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3 #12 TO CIRCUIT BREAKER INDICATED IN PANEL "MB" AND MAKE ALL FINAL POWER CONNECTIONS.

7

EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN OPERATION.

8

NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO CIRCUIT BREAKER IN PANEL "MB" AND MAKE ALL FINAL POWER CONNECTIONS.

9

CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

10

REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EXTERIOR LIGHTING FIXTURE.

BUILDING B ROOF

NORTH

ROOF ELECTRICAL PLAN - BUILDING B

NORTH

1/8"=1'-0"

SECOND FLOOR ELECTRICAL PLAN - BUILDING B

1/8"=1'-0"

IECC LIGHTING COMPLIANCE THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS AS FOLLOWS: 1.

505.2.2.2 - LIGHTING CONTROLS:

A.

THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.

2.

PORCH

PORCH

1

1

APARTMENT 106 (UNIT STYLE "3")

APARTMENT 105 (UNIT STYLE "3")

TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A MULTIFAMILY DWELLING TO 0.7 W/SF.

BUILDING "B" AREA IS 2,684 SQ FT, TOTAL ALLOWABLE WATTAGE IS 1,879W. INTERIOR LIGHTING LOAD = 1600W. THIS MULTIFAMILY DWELLING BUILDING HAS AN LPD OF 0.60W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD. 3.

TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W PARKING AREAS AND DRIVES: 0.06 W/SF WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF SPECIAL FEATURE AREAS: 0.14 W/SF MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

PANEL "MB" 3 EUH-1

FS TS

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "B": 240W. S TYP 10

RISER -

8 TYP 7

NORTH NORTH

1

NTS

01/30/15 REVISION #1.

M

ARCI

NI E

GA

LO

ME X I C EW

0

N

FIRST FLOOR ELECTRICAL PLAN - BUILDING B

KEY PLAN

1/8"=1'-0"

SA

ACTUAL EXTERIOR LIGHTING LOAD = 168W. THIS BUILDING COMPLIES WITH THE MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

18711

C

E

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

BUILDING B ELECTRICAL PLAN By: File: Plot Date:

AEC AEC-B-EB-1.0.DWG 2/12/2015 4:25:13 PM

Sheet

of

EB-1.0

GENERAL NOTES: A

TO APT. 204 6

5

CU-4

CU-4

CU-4

5

CU-4

TO APT. 203

5

5

5

TO APT. 104

TO APT. 103

TO APT. 102

CU-4

MECH. 101

DECK

2

2

2

APARTMENT 204 (UNIT STYLE "2")

APARTMENT 203 (UNIT STYLE "2")

APARTMENT 202 (UNIT STYLE "2")

TO APT. 202 LIVING ROOM 102

LIVING ROOM 102

LIVING ROOM 102

DN

BUILDING C ROOF

BATH 104

KITCHEN 109

BATH 104

KITCHEN 109

LINEN 108

LINEN 108

PANTRY 107

PANTRY 107

PANTRY 107

4 PANEL "A2"

PANEL "A2" 4

BEDROOM 2 106

BEDROOM 2 106 BEDROOM 1 105

BEDROOM 2 106

BEDROOM 1 105

NORTH

SECOND FLOOR ELECTRICAL PLAN - BUILDING C

1/8"=1'-0"

THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.

MECH. 101

PORCH

4

TYPICAL POWER PANEL FOR STYLE "2" APARTMENTS, REFER TO ASSOCIATED PANEL SCHEDULE.

5

EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6

INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3 #12 TO CIRCUIT BREAKER INDICATED IN HOUSE PANEL "MC" AND MAKE ALL FINAL POWER CONNECTIONS.

7

EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN OPERATION.

8

NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO CIRCUIT BREAKER IN HOUSE PANEL "MC" AND MAKE ALL FINAL POWER CONNECTIONS.

9

TYPICAL POWER PANEL FOR STYLE "1" APARTMENTS, REFER TO ASSOCIATED PANEL SCHEDULE.

10

CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

11

REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EXTERIOR LIGHTING FIXTURE.

TS MECH. 101

PORCH

EUH-1

APARTMENT 104 (UNIT STYLE "1")

1

APARTMENT 103 (UNIT STYLE "1")

BEDROOM 1 102

STORAGE 110

STORAGE 111

1

1

TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A MULTIFAMILY DWELLING BUILDING TO 0.7 W/SF.

LIVING 109

BEDROOM 1 102

APARTMENT 102 (UNIT STYLE "1")

LIVING 109

STORAGE 110

BEDROOM 1 102

STORAGE 110

LINEN 103

UP

TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W PARKING AREAS AND DRIVES: 0.06 W/SF WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF SPECIAL FEATURE AREAS: 0.14 W/SF MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

MECH. 101

STORAGE 111

INTERIOR LIGHTING LOAD = 3,650W. THIS MULTIFAMILY DWELLING BUILDING HAS AN LPD OF 0.62W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD. 3.

MAIN DISTRIBUTION / HOUSE PANEL FOR THIS BUILDING, REFER TO POWER RISER DIAGRAM.

STORAGE 111

LIVING 109

BUILDING "C" AREA IS 5,910 SQ FT, TOTAL ALLOWABLE WATTAGE IS 4,137W.

3

S FS S PORCH

A.

REFER TO ENLARGED UNIT STYLE "2" - ELECTRICAL PLAN FOR WORK REQUIRED IN THIS DWELLING UNIT.

RISER -

THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS AS FOLLOWS: 505.2.2.2 - LIGHTING CONTROLS:

2

10

IECC LIGHTING COMPLIANCE

1.

REFER TO ENLARGED UNIT STYLE "1" - ELECTRICAL PLAN FOR WORK REQUIRED IN THIS DWELLING UNIT.

BEDROOM 1 105

NORTH

1/8"=1'-0"

1

BATH 104

LINEN 108

4 PANEL "A2"

2.

ELECTRICAL KEYED NOTES:

DN

KITCHEN 109

ROOF ELECTRICAL PLAN - BUILDING C

MECH. 101

DECK

DINING 108

BATH 104

LAUNDRY 105

7

DINING 108

BATH 104

UP

DINING 108

LAUNDRY 105

9 PANEL "A1"

LAUNDRY 105

PANEL "A1" 9

KITCHEN 107

7

KITCHEN 107 BEDROOM 2 106

BATH 104

9 PANEL "A1"

PANEL "MC" 3

KITCHEN 107

BEDROOM 2 106

BEDROOM 2 106

8 TYP

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "C": 360W. ACTUAL EXTERIOR LIGHTING LOAD = 112W. THIS BUILDING COMPLIES WITH THE MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

11 TYP

7

NORTH NORTH

GROUND FLOOR ELECTRICAL PLAN - BUILDING C

KEY PLAN

1/8"=1'-0"

1

NTS

01/30/15 REVISION #1.

M

ARCI

NI E

GA

LO

ME X I C EW

0

N

CU-4

MECH. 101

DECK

6

SA

5

6

REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS. ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

18711

C

E

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

BUILDING C ELECTRICAL PLAN By: File: Plot Date:

AEC AEC-C-EC-1.0.DWG 2/12/2015 4:26:17 PM

Sheet

of

EC1.0

GENERAL NOTES: A

1

1

APARTMENT 200 (UNIT STYLE "4")

APARTMENT 201 (UNIT STYLE "4")

REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS. ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

4 PANEL "A4"

PANEL "A4" 4

ELECTRICAL KEYED NOTES: 6

5

5

CU-4

1

REFER TO ENLARGED UNIT STYLE "4" - ELECTRICAL PLAN FOR WORK REQUIRED IN THIS DWELLING UNIT.

2

NOT USED.

3

MAIN DISTRIBUTION / HOUSE PANEL FOR THIS BUILDING, REFER TO POWER RISER DIAGRAM.

4

TYPICAL POWER PANEL FOR STYLE "4" APARTMENTS, REFER TO ASSOCIATED PANEL SCHEDULE.

5

EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6

INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3 #12 TO CIRCUIT BREAKER INDICATED IN PANEL "MD" AND MAKE ALL FINAL POWER CONNECTIONS.

7

EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN OPERATION.

8

NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO CIRCUIT BREAKER IN PANEL "MD" AND MAKE ALL FINAL POWER CONNECTIONS.

9

CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

10

REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EXTERIOR LIGHTING FIXTURE.

6

CU-4

CU-4

TO APT. 200 BUILDING D ROOF

5

CU-4

TO APT. 201

5

TO APT. 101

TO APT. 100

DN

ELECTRICAL PLAN - BUILDING D ROOF

1/8"=1'-0"

ELECTRICAL PLAN - BUILDING D SECOND FLOOR

1/8"=1'-0"

NORTH

NORTH

IECC LIGHTING COMPLIANCE THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS AS FOLLOWS: 1.

505.2.2.2 - LIGHTING CONTROLS:

A.

THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.

2.

TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A MULTIFAMILY DWELLING TO 0.7 W/SF.

7

1

APARTMENT 100 (UNIT STYLE "4")

APARTMENT 101 (UNIT STYLE "4")

PANEL "MD" 3

4 PANEL "A4"

PANEL "A4" 4 9

RISER -

EUH-1

BUILDING "D" AREA IS 5,444 SQ FT, TOTAL ALLOWABLE WATTAGE IS 3,811W.

1

S

FS TS

INTERIOR LIGHTING LOAD = 3200W. THIS MULTIFAMILY DWELLING BUILDING HAS AN LPD OF 0.59W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD. 3.

TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W PARKING AREAS AND DRIVES: 0.06 W/SF WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF SPECIAL FEATURE AREAS: 0.14 W/SF MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

NORTH

KEY PLAN

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "D": 240W.

1

NTS

01/30/15 REVISION #1.

7

UP

ARC I N IE

M

ME X I

A

EW

C

0

N

LO

G

SA

ACTUAL EXTERIOR LIGHTING LOAD = 140W. THIS BUILDING COMPLIES WITH THE MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

18711

C

E

10 TYP 8 TYP

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419

ELECTRICAL PLAN - BUILDING D FIRST FLOOR

1/8"=1'-0" NORTH

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

BUILDING D ELECTRICAL PLAN By: File: Plot Date:

AEC AEC-D-ED1.0.DWG 2/12/2015 4:27:19 PM

Sheet

of

ED1.0

GENERAL NOTES:

IECC LIGHTING COMPLIANCE THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS AS FOLLOWS: 1.

505.2.2.2 - LIGHTING CONTROLS:

A.

THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.

2.

TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN AN OFFICE BUILDING TO 1.0 W/SF.

SS

SA

A

A

A.

ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL CODE (NEC).

B.

NFPA 72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2 / HOUSEHOLD FIRE WARNING EQUIPMENT GOVERNS; SPECIFICALLY 2-2.1.1.1 AND 2-2.3.

C.

EACH DWELLING UNIT HAS SINGLE STATION ALARM DEVICE(S) WHICH ALARMS IN THAT DWELLING UNIT ONLY.

D.

LOCATION OF DWELLING UNIT RECEPTACLES IS GOVERNED BY NEC 210.52; SPECIFIC ATTENTION IS DIRECTED TO EXHIBIT 210.24 AND 210.26.

E.

LOCATIONS OF ALL DWELLING UNIT PANELBOARDS SHALL BE FIELD IDENTIFIED AND THE LOCATIONS FIELD APPROVED BY THE ARCHITECT PRIOR TO ANY ELECTRICAL SYSTEMS ROUGH-IN.

F.

LUMINAIRE AND CEILING PADDLE FAN LOCATIONS SHALL BE FIELD LOCATED BY ARCHITECT PRIOR TO ANY BRANCH CIRCUIT INSTALLATION.

G.

LOCATION OF DEVICES MAY BE ALTERED WITHIN NEC PARAMETERS AND ONLY WITH ARCHITECT WRITTEN APPROVAL.

H.

ALL 120V, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES.

A

BUILDING "M" AREA IS 1,344 SQ FT, TOTAL ALLOWABLE WATTAGE IS 1,344W. INTERIOR LIGHTING LOAD = 1,300W. THIS OFFICE/COMMONS BUILDING HAS AN LPD OF 0.97W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

23

A

20

9

A

TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

B GREAT ROOM 101

B

9

18

ELECTRICAL KEYED NOTES:

BASE SITE ALLOWANCE: 600W PARKING AREAS AND DRIVES: 0.06 W/SF WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF SPECIAL FEATURE AREAS: 0.14 W/SF MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

A

A

A

1

GFCI PROTECTED DUPLEX RECEPTACLE, 6" ABOVE COUNTERTOP WITH MAJOR AXIS HORIZONTAL. SPACE RECEPTACLES PER NEC 210.52(C)(1) FOR EVERY WALL COUNTERTOP SPACE 12" OR WIDER.

2

GFCI PROTECTED DUPLEX RECEPTACLE, INSTALL 42" AFF.

3

INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF DISPOSER.

4

INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF DISHWASHER.

5

INSTALL RECEPTACLE WITH MAJOR AXIS HORIZONTAL, 6" ABOVE COUNTERTOP.

6

WEATHER-RESISTANT, GFCI-PROTECTED RECEPTACLE, REFER TO SYMBOL LEGEND. INSTALL 24" AFF.

7

DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 42" AFF.

8

COORDINATE EXACT LOCATION OF PANEL WITH ARCHITECT/OWNER PRIOR TO ROUGH-IN.

9

CEILING PADDLE FAN WITH LIGHT KIT, PROVIDE J-BOX AND SUPPORT FOR FAN PER NEC 314.27(D).

10

CEILING FAN (CF) CONTROL SWITCH, MAKE ALL FINAL LIGHTING AND FAN CONTROL CONNECTIONS TO ASSOCIATED CEILING FAN UNIT.

11

DEDICATED RECEPTACLE FOR MICROWAVE, INSTALL 6" ABOVE COUNTERTOP. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT HEIGHT/LOCATION.

10 MAILBOXES

SA

25

A

S

SA

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "M": 360W. SA

ACTUAL EXTERIOR LIGHTING LOAD = 182W. THIS BUILDING COMPLIES WITH THE MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

S SS S

19

E

A A

F 18

RESTROOM 2 106

20

D

22

F

C

C

C

19

F

D

A

E

21

CU-M

A E

RESTROOM 1 105

SA

S SS

S

SS SA

SA

26

NORTH

ELECTRICAL PLAN - BUILDING M ROOF (PARTIAL)

1/4"=1'-0" NORTH

LIGHTING PLAN - BUILDING M

FIRE ALARM GENERAL NOTES: A

THE FIRE ALARM CONTRACTOR SHALL EMPLOY THE SERVICES OF A NICET 3 (OR BETTER) FIRE ALARM DESIGNER AND SHALL PROCESS SHOP DRAWINGS FOR APPROVAL BY THE FIRE MARSHAL. ALL DEVICES REQUIRED BY CODE AND/OR THE AHJ, WHETHER OR NOT SHOWN ON THIS DRAWING, SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR AND SHALL BE INSTALLED AT NO ADDITIONAL COST.

B

ALL DEVICES SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE LOCATED AND APPROPRIATELY U.L. LISTED WHENEVER APPLICABLE.

C

SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 36" OF ANY AIR REGISTER (SUPPLY OR RETURN).

D

PULL STATIONS: PULL STATIONS ARE REQUIRED AT EVERY EXTERIOR MEANS OF EGRESS. MOUNT 3'-5" - 4'-5" TO CENTER OF DEVICE, LOCATE WITHIN 5' OF EXTERIOR DOOR. MAXIMUM TRAVEL BETWEEN PULL STATIONS IS 200 '.

E

WALL MOUNTED STROBES AND HORN/STROBES SHALL BE LOCATED SO THE ENTIRE LENS IS BETWEEN 80" AND 96" AFF

F

IN CORRIDORS STROBES AND HORN/STROBES SHALL BE LOCATED WITHIN 15'-0" OF THE END OF THE CORRIDOR AND NOT MORE THAN 100'-0" APART.

1/4"=1'-0"

T

F

INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT.

V 23

17 G

24 FIRE ALARM CONTROL PANEL (FACP), REFER TO FIRE ALARM SYSTEM DIAGRAM.

INSTALL MONITOR MODULES AT EACH FLOW AND TAMPER SWITCH (INCLUDING DAMPERS AND P.I.V.'S). VERIFY LOCATIONS WITH MECHANICAL AND FIRE SPRINKLER DRAWINGS PRIOR TO INSTALLATION.

25

INSTALL DUCT DETECTORS ON THE RETURN SIDE OF ALL AIR HANDLING UNITS RATED OVER 2000 CFM. COORDINATE OPERATING VOLTAGE PRIOR TO INSTALLATION. DUCT DETECTORS SHALL BE FURNISHED BY FIRE ALARM CONTRACTOR AND INSTALLED BY MECHANICAL CONTRACTOR.

I

ELECTRICAL CONTRACTOR SHALL INSTALL ALL 3/4" CONDUIT REQUIRED FOR FIRE ALARM SYSTEM. ALL CONDUIT SHALL BE RED OR HAVE RED BANDING EVERY 5'-0". BUSH ALL EXPOSED CONDUIT ENDS.

J

ALL CONDITIONS THAT APPLY SHALL COMPLY WITH NFPA 72.

K

FIRE ALARM SYSTEM SHALL HAVE A MINIMUM 1 YEAR WARRANTY ON ALL PARTS AND INSTALLATION. UPON COMPLETION OF INSTALLATION AND TRAINING THE CONTRACTOR SHALL GIVE THE OWNER A COMPLETE COPY OF THE FIRE ALARM PROGRAMMING MANUAL (INCLUDING PASSWORDS).

L

FIRE ALARM CONTRACTOR SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE AND UPON REQUEST DEMONSTRATE AT LEAST 3 PAST PROJECTS OF SIMILAR SCALE AND SCOPE. CONTRACTOR SHALL PROVIDE 24 HOUR EMERGENCY RESPONSE SERVICES DURING THE WARRANTY PERIOD AT NO ADDITIONAL COST TO THE OWNER. INSTALLER SHALL BE RESPONSIBLE FOR CABLING, TERMINATIONS, PROGRAMMING, ETC... "PARTS & SMARTS" JOINT VENTURES ARE UNACCEPTABLE.

26 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EXTERIOR LIGHTING FIXTURE.

12 CO

17

M

FIRE ALARM CONTRACTOR SHALL HAVE 20 CALENDAR DAYS FROM NOTICE OF AWARD TO PRODUCE JOB SPECIFIC SHOP DRAWINGS AND SUBMIT THEM TO THE FIRE MARSHAL FOR APPROVAL.

N

SMOKE DETECTORS IN RESIDENCES SHALL BE INSTALLED PER NFPA 72. SMOKE DETECTORS WITH INTEGRAL ALARM SHALL BE LOCATED IN EACH BEDROOM, OUTSIDE EACH SLEEPING AREA, AND ON EVERY FLOOR LEVEL. THE SMOKE DETECTORS SHALL BE INTERCONNECTED SO THAT WHEN ONE SOUNDS, THEY ALL SOUND.

SOLAR PANEL (BY OTHERS, INSTALLED BY PHOTOVOLTAIC SYSTEM INSTALLER). REFER TO SHEET PV-1.00.

6

F 5 T

NORTH

T

CONNECT AUTO-DIALER TO TTB, PROGRAM EMER. CALL NUMBER PER OWNER'S INSTRUCTION

T

DIAGRAM IS SCHEMATIC ONLY, NOT ALL DEVICES SHOWN NECESSARILY USED

KEY PLAN

11

F

NTS

17 5

1

3

16

01/30/15 REVISION #1.

F

E.O.L. 5

EF2 16

5

F

5

E.O.L.

12

1

4

CO

INITIATING CIRCUIT

E.O.L.

AUTO-DIALER

5

16

24

PANEL "MM"

E.O.L.

IWH1

F

SCALE: NONE

F

13

F

15

C

ON

SU LT IN G

E

S N G INC. R I N E E

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

NORTH

POWER PLAN - BUILDING M

FM

PO BOX 93024 Albuquerque, NM 87199 505-856-3419

14

TO DEDICATED CIRCUIT MM-11, PROVIDE CODE REQUIRED LOCK-OUT CLIP AT CIRCUIT BREAKER

FIRE ALARM SYSTEM DIAGRAM

18711

1

EF2

14

NI E

ME X I C EW

5

16

INTERFACE RELAY TO VARIOUS NON-ADDRESSABLE DEVICES SUCH AS TAMPER AND FLOW SWITCHES AT ALL (7) BUILDINGS, REFER TO SITE PLAN.

1

ARCI

7

5

INDICATING CIRCUIT ADDRESSABLE SYSTEM WITH BATTERIES

M

0

F

LO

GA

FIRE ALARM CONTROL PANEL (FACP)

N

H

52" PADDLE FAN BY THE BIG ASS FAN COMPANY, MODEL K3127-A2 WITH L.E.D. MODULE.

SA

3.

9

A

1/4"=1'-0"

ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

BUILDING M ELECTRICAL PLANS By: File: Plot Date:

AEC AEC-M-EM-1.0.DWG 2/12/2015 4:28:17 PM

Sheet

of

EM-1.0

GENERAL NOTES: F2

19

IWH1

3

F2

19

3

A.

ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL CODE (NEC).

B.

PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA 72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND 2-2.3.

C.

EACH DWELLING UNIT HAS SINGLE STATION ALARM DEVICE(S) WHICH ALARMS IN THAT DWELLING UNIT ONLY.

D.

THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC 210.52.

E.

LOCATIONS OF ALL DWELLING UNIT PANELBOARDS SHALL BE FIELD APPROVED BY THE ARCHITECT PRIOR TO ANY ELECTRICAL SYSTEMS ROUGH-IN.

F.

LUMINAIRE AND CEILING PADDLE FAN LOCATIONS SHALL BE FIELD APPROVED BY THE ARCHITECT PRIOR TO ANY BRANCH CIRCUIT INSTALLATION.

G.

DEVICE LOCATION AS SHOWN ON DRAWINGS IS SOMEWHAT SCHEMATIC AND MAY BE ALTERED WITHIN NEC PARAMETERS AND AS FIELD CONDITIONS REQUIRE. ANY DEVICE RELOCATION GREATER THAN 12" REQUIRES ARCHITECT'S WRITTEN APPROVAL.

H.

ALL 120V, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES.

I.

PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20 AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

IWH1

EF3

MECH 101

BATH 104

T

S

T

F

MECH. 101

23

V

2

V

V

F

S

BEDROOM 2 106

T

BATH 104

EF3

23

22

17

17

LIVING ROOM 102

22 LAUNDRY 105

BEDROOM 1 102

F PORCH

26 (UNIT 103 ONLY) T

S

D

V

20

18

S

LIVING 109

SS SS

18 7

S

BEDROOM 1 105

17

20

DECK

25

LINEN 108

PANEL "A2" 9

PANTRY 107

11

7

6

17

LAUNDRY 103

W/D

17

W

26 (UNIT 106 ONLY)

V

F

PANEL "A1" 9

S T

SS

2

LINEN 103

6

DINING 110

6

17

5

24 KITCHEN 107

12

21

7

5

DINING 108

2

ELECTRICAL KEYED NOTES:

4

25

2

24

8

KITCHEN 109

1

4

.

BEDROOM 2 106

8

2

11

SS 6

21 STORAGE 111

T

6

SPLIT-WIRED RECEPTACLE, CONNECT TOP HALF OF DUPLEX RECEPTACLE FOR SWITCH CONTROL.

3

V

6

1

6

STORAGE 110

1

4

INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF DISPOSER.

5

INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF DISHWASHER.

6

INSTALL KITCHEN COUNTERTOP RECEPTACLE HORIZONTALLY, 6" ABOVE COUNTERTOP (AC). SPACE RECEPTACLES PER NEC 210.52(C)(1) FOR EVERY WALL COUNTERTOP SPACE 12" OR WIDER.

7

WEATHER-RESISTANT, GFCI-PROTECTED RECEPTACLE, REFER TO SYMBOL LEGEND. INSTALL 24" AFF.

8

POWER J-BOX FOR CONNECTION TO RANGE HOOD.

9

TYPICAL APARTMENT PANEL FOR THIS UNIT STYLE, REFER TO ASSOCIATED PANEL SCHEDULE.

10

NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO CIRCUIT BREAKER IN ASSOCIATED APARTMENT PANEL AND MAKE ALL FINAL POWER CONNECTIONS.

11

DOOR CHIME, INSTALL 6'-6" AFF TO CENTER. CONNECT ASSOCIATED BELL SYSTEM 24V TRANSFORMER TO NEAREST UNSWITCHED 120V RECEPTACLE CIRCUIT AND MAKE ALL FINAL POWER AND CONTROL CONNECTIONS.

12

DOOR CHIME SYSTEM PUSH BUTTON (SUPPLIED AS PART OF DOOR CHIME PACKAGE).

13

CEILING PADDLE FAN WITH LIGHT KIT, PROVIDE J-BOX AND SUPPORT FOR FAN PER NEC 314.27(D).

14

FAN SPEED CONTROL SWITCH FURNISHED WITH CEILING PADDLE FAN, MAKE ALL FINAL CONTROL CONNECTIONS TO ASSOCIATED FAN (CONTROL LIGHTING INDEPENDENTLY AS SHOWN).

15

DEDICATED RECEPTACLE FOR MICROWAVE, INSTALL IN CASEWORK. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT HEIGHT/LOCATION.

16

ALL DWELLING UNIT 120V, 15 AND 20A RECEPTACLES SHALL BE TAMPER-RESISTANT.

17

120V COMBINATION SMOKE DETECTOR/

12

1

UNIT STYLE "1" - ELECTRICAL PLAN

19

23

12

S

T

3

E

SD

B

F

S

V

17

F

S

17 T

B V

S

SS S

22

25 7

BEDROOM 3 114

17

14

17 17

24

S

MECH. 110

11

H

V

DECK

B

W

S

S

S

T

V

26 (UNITS 106, 107, 115 ONLY)

18 LIVING

T

17

HALLWAY 113

17

T

EF1

BATH 112

BEDROOM 2 111

IWH1

20 D

1/4"=1'-0"

F4

PORCH

E

2

UNIT STYLE "2" - ELECTRICAL PLAN

1/4"=1'-0"

F3

PANEL "A4" 9

19

V

IWH1

17

STAIRS 101

STORAGE 109

3

DINING

23

G

SS

SS

H

F

T

1

EF3

EF3

8

C

V

DINING 103

F B

22

23

SS

1/4"=1'-0"

20

2

G

W

DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 42" AFF

D

EF3

LAUNDRY 104

2 6

6

4

UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN

6

B

F

25 11

K 24

SS 21

5

S

9 PANEL "A3"

6

S LIVING 102

UNIT STYLE "4" - ELECTRICAL PLAN

26 (UNITS 106, 107, 115 ONLY)

12

4

BATH 1 105

17

3

T

V

5

18

17

1/4"=1'-0"

4

KITCHEN 107

7 T PORCH

V

BEDROOM 1 106

21

8

S

B 1

01/30/15 REVISION #1.

6 STORAGE 108

6 6

1

UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN

6

5

1/4"=1'-0" C

E

ON

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

TYPICAL UNIT ELECTRICAL PLANS By: File: Plot Date:

AEC AEC-EU-1.0 UNIT PLANS.DWG 2/12/2015 4:29:14 PM

Sheet

of

EU-1.0

SECTION 26 0500- BASIC ELECTRICAL MATERIALS AND METHODS

SECTION 26 0533 - RACEWAYS AND BOXES

PART 1 GENERAL

PART 1 GENERAL

1.1 RELATED DOCUMENTS A The Contractor shall make a thorough field investigation of all work described above and shown on the contract drawings prior to submitting a bid on this project to ensure the bid is complete and comprehensive. 1.2 SUMMARY A This Section includes the following electrical materials and methods: 1. Building wire, connectors, and splices for branch circuits and feeders. 2. Supporting devices for electrical components. B Furnish all labor and materials necessary for complete electrical service to all equipment which requires electric connections installed as part of this project. Provide temporary electric power of sufficient capacity to allow construction. 1.3 ELECTRICAL SPECIFICATION INDEX 26 0500 - Basic Electrical Materials and Methods 26 0533 - Raceways and Boxes 26 2416 - Panelboards 26 2726 - Wiring Devices 26 2816 - Enclosed Switches and Circuit Breakers 1.4 SUBMITTALS A General: Electrical submittals shall be provided. The Contractor shall provide submittal information for: 1. Panelboards 2. Safety switches 3. Fuses 4. Light Fixtures 5. Occupancy Sensors (Controls) 6. Fire Alarm 1.5 QUALITY ASSURANCE A Comply with the 2011 edition of NFPA 70 (NEC) for components and installation. 1.6 DRAWINGS A All drawings included in the Contract Documents are to be considered as part of the work. Architectural drawings shall take precedence over electrical drawings. B As-built drawings: During project construction, the Contractor shall maintain an accurate record of the installation of all electrical work, carefully noting any deviations from the contract drawings. Upon project completion, the Contractor shall transfer all as-built information to a single neat and legible drawing set. C Upon completion of the fire alarm system installation, the contractor shall give the owner a complete copy of the fire alarm programming manual (including passwords).

2.2 BUILDING WIRE A Description: Single conductor, copper. Solid conductor for No. 10 AWG and smaller; stranded conductor for larger than No. 10 AWG. 2.3 SUPPORTING DEVICES A Channel and angle support systems, hangers, anchors, sleeves, brackets, fabricated items, and fasteners are designed to provide secure support from the building structure for electrical components. 1. Material: Steel, except as otherwise indicated, protected from corrosion with zinc coating or with treatment of equivalent corrosion resistance using approved alternative finish or inherent material characteristics. 2. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel, except as otherwise indicated. B Steel channel supports have 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least 1 surface. 1. Fittings and accessories mate and match with channels and are from the same manufacturer. C Nonmetallic Channel and Angle Systems: Structural-grade, factory-formed, fiberglass-resin channels and angles with 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least one surface. 1. Fittings and accessories shall mate with channels or angles and be of the same manufacturer. 2. Fitting and Accessory Material: Same as channels, except metal items may be stainless steel. 2.4 ELECTRICAL IDENTIFICATION A Color code all wiring as follows: For 120/240V: Phase A-Black; Phase B-Red; Neutral-White; Ground-Green. 2.5 TOUCH-UP PAINT

A Safety switches, fuses, enclosed circuit breakers.

1.2 SUBMITTALS

QUALITY ASSURANCE A Comply with the 2011 National Electrical Code (NEC) for installation.

PART 2 PRODUCTS 2.1 COATINGS

1.2 SUBMITTALS

A Submit the following: 1. Catalog data: Submit catalog data describing each type panelboard, accessory item, and component specified. Include data substantiating that materials comply with specified requirements.

A Provide products with zinc coating or with treatment of equivalent corrosion resistance. 2.2 ELECTRICAL METALLIC TUBING AND FITTINGS (EMT) A Furnish galvanized electrical metallic tubing (EMT) that meets the requirements of UL797 Electrical Metallic Tubing, NEMA C80.3 - Steel Electrical Metallic Tubing (EMT). B Furnish compression or set-screw type fittings that meet the requirements of UL514B - Fittings for Conduit and Outlet Boxes, and ANSI/NEMA FB1 - Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit and Cable Assemblies. Furnish insulated throat connectors.

A Comply with the 2011 National Electrical Code (NEC) for installation. PART 2

2.4 OUTLET BOXES A Provide outlet boxes selected for specific installations using the guidance in NEMA OS 3, Selection and Installation Guidelines for Electrical Outlet Boxes, and the requirements of this Selection. B For dry locations provide galvanized steel outlet boxes that comply with UL Standard 514-A Metallic Outlet Boxes and ANSI/NEMA OS1 - Sheet-Steel Outlet Boxes, Device Boxes, Device Boxes, Covers, and Box Supports. C For damp or wet locations and for surface-mounted RMC or IMC raceways systems, provide outlet boxes that comply with UL Standard 498 and 514, ANSI/NEMA FB1. 2.5 PULL AND JUNCTION BOXES A For dry locations in clean, non-contaminated environments use galvanized sheet steel pull and junction boxes that comply with UL Standard 50 Type 1 and the NEC as to size and construction. Use boxes not less than 4 inches square x 1-1/2 inches deep with screw-secured covers. Provide larger boxes as required by the number and size of conduits and conductors. B For damp or wet, non-corrosive locations, in conduit runs 1 inch trade size and larger, provide galvanized sheet-steel pull and junction boxes and covers that comply with UL 50 Type 3R. PART 3 EXECUTION 3.1 EXAMINATION A Examine surfaces to receive raceways and boxes for compliance with installation tolerances and other conditions affecting performance of the raceway system. Do not proceed with installation until unsatisfactory conditions have been corrected. 3.2 GENERAL A Install raceways and boxes according to NECA 1 Standard Practices for Good Workmanship in Electrical Construction. B Raceway termination points and box locations shown on the Drawings are in approximate locations unless dimensioned. Verify locations before rough-in. C Ground and bond raceways and boxes as required by the NEC. D Support raceways and boxes in accordance with the NEC. Arrange raceways and boxes to maintain headroom and present a neat, workmanlike appearance. 3.3 CONDUIT INSTALLATION A For wiring systems less than 1000 volts use conduit materials in accordance with the NEC. B Use 3/4-inch or larger conduit to enclose multiple conductors larger than 12 AWG. For home-run circuits, conduit shall be a minimum of 3/4". C Conceal conduits within walls, floors and ceilings. D Install insulating bushing or connectors with an insulated throat to protect conductors or cables at conduit terminations. E Join nonmetallic conduit using cement as recommended by manufacturer. F Install plastic-coated RMC and fittings according to the NEC and manufacturer's instructions. Use only fittings approved for use with that material. Patch all nicks and scrapes in PVC coating after installing conduits. G Do not use RNC 90 degree elbows larger than 3 inch trade size; use plastic-coated RMC, tape-wrapped RMC, or tape-wrapped IMC for 3-1/2 inch trade size and larger 90 degree elbows. H Maintain the following minimum clearances between conduit and surfaces with temperatures exceeding 104 degrees F (40 degrees C): 1. 6" at perpendicular crossings, 12" between parallel runs. I Install pull string in all empty and spare conduits. J Any conduit run below slab on grade shall be a minimum of 6" below slab.

PRODUCTS

2.1 PANELBOARDS, GENERAL REQUIREMENTS A Provide panelboard cabinets for flush or surface mounted as indicated on the Drawings. 1. Furnish NEMA Type 1 enclosures, except where the Drawings indicate the following enclosure requirements: NEMA 3R - Raintight B Provide trim fronts that meet the strength and rigidity requirements of UL 50. 1. Fronts for flush panels shall overlap boxes at least 1 inch. 2. Fronts shall have ANSI 49 medium gray enamel. 3. For NEMA 1 panelboards, provide fronts with hinged trim construction having a piano hinge down one side. The front shall contain a smaller lockable door, which when open, shall provide access to all conductors and wiring terminals. 4. Provide a metal panelboard directory frame mounted inside the panelboard door. C Panelboard phase and neutral bus shall be copper. D Provide copper equipment ground bus that is adequate for feeder and branch circuit equipment ground conductors. Bond ground bus to cabinet. E Provide thermal-magnetic circuit breakers that meet the requirements of UL 489 Molded Case Circuit Breakers and NEMA AB 1 Molded Case Circuit Breakers and Molded Case Switches. 2.2 LIGHTING AND APPLIANCE PANELBOARDS A Provide lighting and appliance branch circuit panelboards as indicated on the Drawings. B Lighting and appliance branch circuit panelboards enclosures shall be not less than 20 inches or more than 26 inches in width. C Manufacturers: 1. Cutler-Hammer: PRL3a (480Y/277V) and PRL1a and PRL2a (208Y/120V or 120/240V). 2. General Electric: Spectra (480Y/277V) and AQ (208Y/120V or 120/240V). 3. Siemens: P2 (480Y/277V) and P1 (208Y/120V or 120/240V). 4. Square D: I-Line (480Y/277V) and NQOD (208Y/120V or 120/240V). 2.3 LIGHTING AND APPLIANCE LOAD CENTERS A B C D

Provide lighting and appliance branch circuit load centers as indicated on the Drawings. Load centers identified for use as service equipment are to be labeled for this application. A directory label shall be provided with circuits identified as indicated on the schedule. Bus bar connections to the branch circuit breakers shall be the distributed phase type and shall accept plug on circuit breakers. E Manufacturers: 1 Cutler Hammer, General Electric, Siemens or Square D PART 3 EXECUTION

PART 3 - EXECUTION 3.1 EQUIPMENT INSTALLATION REQUIREMENTS A Where components and equipment are indicated to be installed, the term "install" includes all work, materials, and associated accessories necessary to obtain a completely operational system. B Install items level, plumb, and parallel and perpendicular to other building systems and components, except where otherwise indicated. 3.2 WIRING METHODS A Feeders: Type THHN/THWN, in copper conductor, RHW or XHHW in aluminum conductor, in raceway, except as otherwise indicated. Branch Circuits: Type THHN/THWN, in raceway or type MC Cable or type NM, NMC or NMS where allowed by NEC and State of New Mexico codes. B Type MC cable shall be acceptable where in compliance with current NEC. C Upsize circuits and feeders as necessary to limit overall voltage drop to the furthest outlet on a branch circuit to 5% maximum. 3.3 ELECTRICAL SUPPORTING METHODS A Damp Locations and Outdoors: Hot-dip galvanized materials. B Dry Locations: Steel materials. C Strength of Supports: Adequate to carry all present and future loads, times and safety factor of at least 4; 200-lb-minimum design load. 3.4 INSTALLATION A Install conductors according to manufacturer's written instructions and NECA's "Standard of Installation". Coordinate special systems work with Owner and Cabling Contractor. B Conductor Splices: Keep to the minimum possible. C Install devices to securely and permanently fasten and support electrical components. D Raceway Supports: Comply with NFPA 70 and the following requirements: 1. Conform to manufacturer's recommendations for selecting and installing supports. E Fire stopping: Apply to cable and raceway penetrations of fire-rated floor and wall assemblies. Perform fire stopping to reestablish the original fire-resistance rating of the assembly at the penetration. F Fastening: Unless otherwise indicated, securely fasten electrical items and their supporting Install identification devices where required. 1. Install labels where indicated and at locations for best convenience of viewing.

A Install outlet boxes with centers at the following heights unless noted otherwise on the Drawings: 1. Receptacles, general use duplex type: 18 inches to center of j-box above finished floor (AFF). 2. Voice/data outlets: 18 inches AFF to center. 3. Light switches: center 44 inches AFF to center and within 6 inches of door frame. 4. Thermostats: center 44 inches AFF to center. 5. Fire alarm audible/visible alarm devices: center of strobe light 80 inches AFF or 6 inches below the ceiling, whichever is lower. 6. Fire alarm pull stations: center 44 inches AFF to center. B Install a multi-gang box where more than one device is mounted together. Do not use sectional type boxes. Mount multiple controls as close together as possible and in-line with each other. Where shown within two feet of each other, group voice/data outlets and receptacles together. C Install box with plaster ring for single or multiple device outlets. D Use flush mounted outlet boxes in finished areas. F Install a blank cover plate on each outlet box in which no device is installed. 3.6 CLEANING A Clean interior of boxes to remove dust, debris, and other material. B Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer. C Repair damage to paint finishes with matching touch-up paint. END OF SECTION 26 0533

PART 2 PRODUCTS 2.1 SAFETY SWITCHES A Provide NRTL-listed, NEMA KS 1 Type HD safety switches with ratings and number of poles as indicated on the Drawings. Use Type HD for switches rated 100A and above. B Provide safety switches for use as service equipment that are NRTL labeled for the application. C Provide enclosure type in accordance with NEMA ratings as required by the conditions of use. D For fusible safety switches provide rejection clip designed to accommodate NEMA FU 1, Class R. E Furnish each safety switch with an equipment ground bar. F Furnish a neutral bar for each safety switch used on a circuit that includes a grounded "neutral" conductor. G Provide each safety switch with a factory-installed cover-mounted viewing window positioned over the blades to allow visual verification of ON-OFF status. H Provide auxiliary electrical interlock switches with safety switches as indicated on the Drawings or as required by the application. 2.2 FUSES A Provide NRTL-listed, NEMA FU 1 Class R fuses for fusible safety switches as indicated on the Drawings or required by the manufacturer of served equipment. B Provide a lime green spare fuse cabinet with "Fuses" stenciled in OSHA purple. Cabinet shall be sized to hold one set of (2) fuses of each size used on this project. 2.3 ENCLOSED CIRCUIT BREAKERS A Provide NRTL-listed, NEMA AB 1 enclosed molded-case circuit breakers with ratings and number of poles and indicated on the Drawings. PART 3 EXECUTION 3.1 EXAMINATION A Examine surfaces to receive safety switches and enclosed circuit breakers for compliance with installation tolerances and other conditions affecting performance of the product. Do not proceed with installation until unsatisfactory conditions have been corrected.

A Install safety switches and enclosed circuit breakers where indicated on the Drawings and according to manufacturer's instructions, NECA 1, and the NEC. Have the manufacturer's installation instruction available at the construction site.

3.2 INSTALLATION A Install panelboards where indicated on the Drawings and according to manufacturer's installation instructions. B Ground and bond panelboards as required by NEC.

B Install each safety switch and enclosed circuit breaker so the interlock bypass will be accessible. C Provide supports and seismic anchorage in accordance with the manufacturer's installation instructions. D Ground and bond safety switches and enclosed circuit breakers as required by NEC.

C At all flush panelboards install four 1-inch spare conduits, extend to above accessible ceiling space. D Home-run conduits (all conduits connected to a panel) shall be a minimum of 3/4 inch. 3.3 IDENTIFICATION A Provide typewritten circuit directories for each branch circuit panel board. Revise directories to reflect ANY field circuiting changes. B Provide plastic nameplates for power panels. Nameplate to include panel designation, voltage, and phase, e.g. PANEL "MM" / 120/240V / 1-PHASE. 3.4 FIELD QUALITY CONTROL A Clean, inspect, test, and energize installed panelboards in accordance with NECA 407. B After completing installation, cleaning, and testing, touch-up any scratches to match finish. END OF SECTION 26 2916

SECTION 26 2726 - WIRING DEVICES PART 1 GENERAL 1.1 SUMMARY A. SECTION INCLUDES 1. Receptacles, Snap switches, Dimmer switches, Wall plates, Multi-outlet assemblies. 1.2 QUALITY ASSURANCE A. Furnish products listed and labeled by a nationally recognized testing laboratory (NRTL) for the

E Install conduits as required in Section 26 0533 Raceways and Boxes for Electrical Systems. F Install conductors as follows: 1. Use compression type lugs to connect all service feeders. 2. Tighten electrical connectors and terminals to the manufacturer's published torque tightening values. Where manufacturer's torque values are not indicated, use those specified in UL 486A. G Install fuses in fusible safety switches as indicated on the Drawings or as required to match installed motor or load characteristics. H Install spare fuse cabinet in main electrical room or alternate location as shown on Drawings. 3.3 IDENTIFICATION A Identify safety switches and enclosed circuit breakers with unit name and circuit number. 3.4 FIELD QUALITY CONTROL A Clean interior and exterior of safety switches and enclosed circuit breakers. B Verify that ratings for safety switches and enclosed circuit breakers match values indicated on the Drawings. END OF SECTION 26 2816

PART 2 PRODUCTS 2.1 RECEPTACLES A. 120V convenience duplex receptacles connected to general use branch circuits: Provide straight-blade NEMA 5-15R, 15A, duplex receptacles. Use "Decora" style, ivory-colored receptacles. B. 120V ground fault circuit interrupter (GFCI) receptacles: Provide straight-blade NEMA 5-15R, 15A, feed-through type, self-testing GFCI, duplex receptacles that meet the requirements of UL Standard 943, Ground Fault Circuit Interrupters. C. 120V exterior duplex receptacles: Provide GFCI type with integral weather-resistant (WR) cover D. Dedicated duplex receptacles: Provide 20A rated device. 2.4

SNAP SWITCHES A. Provide single pole, double pole, three-way, four-way and pilot handle snap switches as indicated on the Drawings. Use "Decora" style, ivory-colored switches. B. Switches shall be rated 20A, 120-277 volts AC, back and side wired, screw pressure terminal, quiet type AC switch with yoke grounding screw. 2.5 WALLBOX DIMMING CONTROLS A. Dimmer wattage rating shall exceed connected load by 10 percent minimum, contractor shall verify load indicated on the Drawings matches actual fixtures/lamps supplied. 2.6 WALL PLATES A. For flush mounted interior receptacles and wall switches, provide compatible nylon cover plate, ivory in color.

1

PART 3 EXECUTION 3.1 PREPARATION A. Verify outlet boxes are installed at proper locations and heights. 3.2 A. B. C. D. E. F.

3.4

3.8 TOUCH-UP PAINT A Thoroughly clean damaged areas and provide primer, intermediate, and finish coats. 3.5 END OF SECTION 26 0500

B Provide safety switches and circuit breaks that are listed and labeled by a Nationally Recognized Testing Laboratory (NRTL) for the application, installation condition, and the environment in which installed. C Comply with the following standards as applicable: 1. NEMA AB 1 (UL 489) Molded Case Circuit Breakers, Molded Case Switches, and Circuit Breaker Enclosures; UL 50 - Enclosures for Electrical Equipment.

3.1 EXAMINATION A Examine surfaces to receive panelboards for compliance with installation tolerances and other instructions, NECA 407, and the NEC.

3.5 CUTTING AND PATCHING A Cut, channel, chase, and drill floors, walls partitions, ceilings, and other surfaces necessary for electrical installations. Perform cutting by skilled mechanics of the trades involved. B General Contractor shall repair disturbed surfaces to match adjacent undisturbed surfaces. 3.6 TESTING A Perform complete testing on all systems to ensure proper operation. 3.7 TRAINING A Instruct Owner's personnel in the proper operation of electrical systems.

A Comply with the 2011 National Electrical Code (NEC) for components and installation.

3.2 INSTALLATION

3.5 OUTLET BOX INSTALLATION

A For Equipment: Provided by equipment manufacturer and selected to match equipment finish. B For Non-equipment Surfaces: Matching type and color of undamaged, existing adjacent finish.

1. Product Data: Submit manufacturer's technical data for each type of safety switch and enclosed circuit breaker.

2. Provide galvanized steel cabinets constructed according to UL 50 requirements.

2.3 FLEXIBLE METAL CONDUIT AND FITTINGS A Furnish galvanized steel flexible metal conduit that meets the requirements of UL1 - Flexible Metal Electrical Conduit.

A Submit the following:

1.3 QUALITY ASSURANCE

1.3 QUALITY ASSURANCE

PART 2 - PRODUCTS 2.1 EQUIPMENT REQUIREMENTS A The electrical equipment connections on the drawings are based on specific equipment and models. Any additional costs resulting from any changes in equipment furnished will be the complete responsibility of the Division furnishing the equipment. B Fuses shall be dual element Buss Fusetrins unless noted otherwise. C Safety switches rated 100A and above shall be heavy-duty rated.

1.1 SECTION INCLUDES

A Power panelboards

A Conduits and fittings B Outlet boxes

SECTION 26 2816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 GENERAL

PART 1 GENERAL 1.1 SECTION INCLUDES

1.1 SECTION INCLUDES

1.2

SECTION 26 2416 - PANELBOARDS

INSTALLATION Install devices plumb, level, and secure. All duplex receptacles in dwelling units shall be tamper-resistant in accordance with NEC 406.12. All duplex receptacles in dwelling units shall be AFCI protected in accordance with NEC 210.12. All duplex receptacles within 6' of a sink or bathtub/shower stall, in bathrooms, in garages, and in laundry area shall be GFCI protected in accordance with NEC 210.8. Install wall plates on each switch, receptacle, and blank outlet after painting is complete. Install GFCI-protected slave receptacle for electric drinking fountains (EDF) per NEC 422.52 concealed within EDF cabinet.

IDENTIFICATION A. Identify wiring devices with circuit number written on back of cover plate using permanent ink pen. FIELD QUALITY CONTROL A. Operate each switch and receptacle at least six times with circuit energized. END OF SECTION 26 2726

C

E

ON

01/30/15 REVISION #1.

SU LT IN G

S N G INC. R I N E E

PO BOX 93024 Albuquerque, NM 87199 505-856-3419 ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION.

Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico PROJECT ARCHITECT:

Project #:

BOB HALL, AIA

Date:

IDA-14-01-P DECEMBER 22, 2014

ELECTRICAL SPECIFICATIONS By: File: Plot Date:

AEC AEC-ESP-1.0-SPECS.DWG 2/12/2015 4:30:57 PM

Sheet

of

ESP-1.0

THIS SHEET INCLUDED FOR REFERENCE