5- Basics Of Fault Calculation

  • Uploaded by: harish
  • 0
  • 0
  • January 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View 5- Basics Of Fault Calculation as PDF for free.

More details

  • Words: 4,926
  • Pages: 109
Loading documents preview...
Power System Protection Date: 6th March 2010 Venue: L&T, Manapakkam, Chennai

Steady State Fault Analysis Dr. G. Pradeep Kumar

What is Fault Analysis? Fault Analysis 

Analysis of a power system 



during and after a fault

Involves computation of voltages and currents under the fault conditions.

© Protection Engineering And Research Laboratories

2

Why Fault Analysis? Fault Analysis 

Important to understand what happens in the system as a result of a fault

© Protection Engineering And Research Laboratories

3

Why Fault Analysis? Study the effects of fault 

How high will the current go?



Will the voltage rise above a limit or fall below a limit?

© Protection Engineering And Research Laboratories

4

Why Fault Analysis? Ensure Ratings 

Use calculated voltage and current values 

Ensure that load and short circuit ratings of the plant are not exceeded



For proper selection of switchgear

© Protection Engineering And Research Laboratories

5

Why Fault Analysis? Selection of Switchgear 

Rating of a breaker 

Current it has to carry under normal conditions 



Continuous rating

Current flowing immediately after the fault occurs 



Short time withstand

Current which the breaker must interrupt 

Breaking capacity

© Protection Engineering And Research Laboratories

6

Why Fault Analysis? Selection of Switchgear 

Calculated fault voltages and currents 

Verify that the breaking capacity is not exceeded



Short time withstand is not exceeded

© Protection Engineering And Research Laboratories

7

Why Fault Analysis? Protection System Design 

Fault detection 

In which system parameters will the change due to fault be reflected more?

combination of both ??

Voltage

© Protection Engineering And Research Laboratories

Current

8

Why Fault Analysis? Protection System Design 

Fault detection 

Fault voltages and currents calculated at various system locations 

Select most suitable relay characteristics for fault detection

© Protection Engineering And Research Laboratories

10

Why Fault Analysis? Software Packages 

Software packages can do it - why bother? 

Understanding what is happening is important 

Eg. In a Δ-Y transformer for a single phase fault on the Y-side, why fault current in two phases on the Δ- side.



Spot check on the computer results 



Catch data entry errors

Easier for simpler systems

© Protection Engineering And Research Laboratories

15

How to Perform Fault Analysis? Computations 

Steady state analysis 

Solved by algebraic equations



Does not mean system is static



System may be fast changing



This is like taking a set of photographs of the system behavior under certain specified conditions 

Algebraic equations are much easier to solve!

© Protection Engineering And Research Laboratories

17

Per-unit Systems Definition

A is any quantity 

A per unit quantity is a “normalized” quantity with respect to a chosen base value.



Any quantity can be converted to a selected base quantity of the same dimension. 

Per unit quantities are dimensionless

© Protection Engineering And Research Laboratories

20

Per-unit Systems Per-unit Applied to Power Systems 



Power system quantities that are represented in per unit are: 

Voltage



Current



Impedance



Apparent power

All of these are completely described by only two of them 

Sufficient to choose only two base quantities

© Protection Engineering And Research Laboratories

21

Per-unit Systems Per-unit Applied to Power Systems 

Generally the two chosen base quantities are, 

Apparent power (SB)



Voltage (VB)



Equipment ratings are usually given in MVA and kV



Other two base quantities (ZB, IB) can be fixed as follows:

© Protection Engineering And Research Laboratories

22

Per-unit Systems Per-unit Calculations 

Converting from actual values to per unit

© Protection Engineering And Research Laboratories

23

Per-unit Systems Per-unit Calculations 

Change of Base: 

Often require to convert per unit values from one base to another 

Most equipment impedances are given in its own MVA and kV base



Need to be converted to a common base when solving a network

© Protection Engineering And Research Laboratories

24

Per-unit Systems Per-unit Calculations

A is any quantity 

Basically we, 

Multiply the old per unit value by the old base to get back the actual value



Then divide by new base to get the new per unit value

© Protection Engineering And Research Laboratories

25

Per-unit Systems Per-unit Calculations – Example Problem T1 G

50 + j100 ohms

ΔY 

Generator: 15 MVA, 13.8 kV, x = 0.15 pu



Load 1: 10 MVA at 0.9 pf lead



T1: 25 MVA, 13.2/161 kV, x = 0.10 pu



T2: 15 MVA, 161/13.8 kV, x = 0.10 pu



Load 2: 4 MVA at 0.8 pf lag

T2 YΔ

Load 1 Load 2

If the load bus voltage is 15.18 kV, find the voltage at the generator terminals, Vg.

© Protection Engineering And Research Laboratories

29

Per-unit Systems Calculations – using per unit system 

Choose an MVA base

25 MVA T1

15 MVA T2

10 MVA Load 1

G

Load 2

15 MVA

4 MVA Choose an MVA base of 15

© Protection Engineering And Research Laboratories

30

Per-unit Systems Calculations – using per unit system 

Choose a kV base at any part of the system and fix the kV bases at different sections of the system

13.2/161 kV

161/13.8 kV

T1

T2

13.2 kV

G

Load 1 Load 2

13.8 kV 13.2 kV

161 kV

13.8 kV

Choose a kV base of 161 kV at the transmission line

© Protection Engineering And Research Laboratories

31

Per-unit Systems Calculations – using per unit system 

MVAB = 15

Chosen bases T1

T2

G

Load 1 Load 2

kVB = 13.2

kVB = 161

© Protection Engineering And Research Laboratories

kVB = 13.8

32

Per-unit Systems Calculations – using per unit system 

Convert all impedances to pu in the chosen bases

© Protection Engineering And Research Laboratories

33

Per-unit Systems Calculations – using per unit system 

Solve the network to obtain required voltages & currents in pu Load bus voltage

Load 1 current

© Protection Engineering And Research Laboratories

34

Per-unit Systems Calculations – using per unit system 

Solve the network to obtain required voltages & currents in pu Load 2 current

© Protection Engineering And Research Laboratories

35

Per-unit Systems Calculations – using per unit system 

Solve the network to obtain required voltages & currents in pu Total load current

© Protection Engineering And Research Laboratories

36

Per-unit Systems Calculations – using per unit system 

Solve the network to obtain required voltages & currents in pu Generator terminal voltage

© Protection Engineering And Research Laboratories

37

Per-unit Systems Calculations – using per unit system 

Convert the pu values back to actual values

The generator terminal voltage is 14.623 ∠8.540 kV

© Protection Engineering And Research Laboratories

38

Per-unit Systems Advantages 

Name plate details 

Manufacturers usually specify impedance of the equipment in per unit or percent

pu ?

© Protection Engineering And Research Laboratories

39

Per-unit Systems Advantages 

Relative strength of different parts of the system on the same scale 

E.g. Currents in two parts of the system with a few transformers in between cannot be compared directly



Per unit gives the relative values directly

Actual values

© Protection Engineering And Research Laboratories

PU values

40

Classification of Faults Power System Faults Symmetrical

Shunt Faults

Unsymmetrical

Shunt Faults

Series Faults

Three-phase

Single-line to gnd

Unequal Series

3-phase to gnd

phase-to-phase

One line open

2-phase to gnd

Two lines open

© Protection Engineering And Research Laboratories

52

Classification of Faults Balanced or Symmetrical Faults 

Three phase faults



System remains balanced even after the fault



Per-phase analysis can be done 



the easiest fault to analyze

Generally the most severe fault a b c

a b c 3-phase

© Protection Engineering And Research Laboratories

3 phase - ground

53

Classification of Faults Un-balanced or Un-symmetrical Faults 



Un-balanced situation 

Unbalanced load



Any other unsymmetrical condition

System becomes unbalanced 

Single phase representation is not valid 



Per phase analysis CANNOT be done

Further classified into 

Shunt faults



Series faults

© Protection Engineering And Research Laboratories

54

Classification of Faults Shunt Faults 

Unbalance is between phases or between phase and neutral



Causes 

Insulation breakdown



Lightning discharges and other over-voltages



Mechanical damage

a b c

a b c

a b c e

e Single-line to ground

© Protection Engineering And Research Laboratories

Line to line

Double-line to ground

55

Classification of Faults Series Faults 

Unbalance in the line impedances



Doesn’t involve ground or inter-connection between the phases



Causes 

Broken conductor



Operation of fuses



Maloperation of single phase circuit breakers

a b c

za zb zc

Unequal series Impedances

© Protection Engineering And Research Laboratories

a b c

a b c One line open

Two lines open

56

Classification of Faults Other Faults 

Cross-country faults

a

a'

b

b'

c

c'

e

e

© Protection Engineering And Research Laboratories

57

Classification of Faults Other Faults 

Faults between adjacent parallel lines

© Protection Engineering And Research Laboratories

58

Classification of Faults Other Faults 

Open-circuit + Single-line to ground fault

a b c e

© Protection Engineering And Research Laboratories

59

Classification of Faults Other Faults 

Changing fault in cable - evolving faults

a

a c

b

© Protection Engineering And Research Laboratories

a c

b

c b

60

Reactance of Synch. Machines Transients Caused by Synchronous Generator 

Consider only this ac component 

The amplitude of the ac component is given by,

Where E – Internal voltage or no-load voltage Xd – steady-state reactance, Xd’ – transient reactance, Xd” – sub-transient reactance Td’ – transient decay time constant, Td” – sub-transient decay time constant

© Protection Engineering And Research Laboratories

61

Reactance of Synch. Machines Transients Caused by Synchronous Generator 

The ac component of the current waveform 

Has three components

Steady-state component

Sub-transient component

Transient component

© Protection Engineering And Research Laboratories

62

Reactance of Synch. Machines Transients Caused by Synchronous Generator 

Transient and sub-transient currents 

decay at different rates over the sub-transient and transient period



Reduces to negligible values after a few cycles 

The sub-transient component first



The transient component next

© Protection Engineering And Research Laboratories

63

Reactance of Synch. Machines Sub Heading here

i(t)

t (sec) © Protection Engineering And Research Laboratories

64

Reactance of Synch. Machines Sub Heading here

Steady-state component

i(t)

t (sec) © Protection Engineering And Research Laboratories

65

Reactance of Synch. Machines Sub Heading here

Transient component

i(t)

t (sec) © Protection Engineering And Research Laboratories

66

Reactance of Synch. Machines Sub Heading here Sub-transient component

i(t)

t (sec) © Protection Engineering And Research Laboratories

67

Reactance of Synch. Machines Transients Caused by Synchronous Generator 

The time after a fault occurs can be divided into 3 periods 

Sub-transient – 2 to 3 cycles after the fault 



Transient – 10 to 15 cycles after the fault 



Characterized by the transient reactance Xd’

Steady-state – > 20 cycles after the fault 



Characterized by the sub-transient reactance Xd”

Characterized by the steady-state reactance Xd

Xd” < Xd’ < Xd

© Protection Engineering And Research Laboratories

68

Reactance of Synch. Machines Transients Caused by Synchronous Generator 

rms value of the steady current I 



rms value of the transient current I’ 



I’rms = Erms/Xd’

rms value of the sub-transient current I” 



Irms = Erms/Xd

I”rms= Erms/Xd”

I”rms > I’rms > Irms 

Since Xd” < Xd’ < Xd

© Protection Engineering And Research Laboratories

69

Transients due to Faults Symmetrical and Un-Symmetrical Fault Currents 

When to consider unsymmetrical ? 



Circuit breaker rating

Unsymmetrical currents usually ignored 

Assumed that it will decay fast

© Protection Engineering And Research Laboratories

70

Transmission Lines & Cables Representation of Transmission Lines & Cables 



Practical transmission lines 

Not spaced equilaterally



May not be transposed

The errors due to this are considered minimal 

Lines are taken to be symmetrical

© Protection Engineering And Research Laboratories

71

Transmission Lines & Cables Representation of Transmission Lines & Cables 

Distributed model of lines

L

R

L

R

C

L C

G

© Protection Engineering And Research Laboratories

R

L C

G

R C

G

G

72

Transmission Lines & Cables Representation of Transmission Lines & Cables 

Shunt branches are ignored for short circuit calculations

L

R

L

R

© Protection Engineering And Research Laboratories

L

R

L

R

73

Transmission Lines & Cables Representation of Transmission Lines & Cables 

A lumped parameter model is used 

Entire line lumped into a single impedance XL

RL

RL = the total resistance of the line XL = 2ᴨf×LLine, where LLine - is the total inductance of the line

© Protection Engineering And Research Laboratories

74

Transmission Lines & Cables Representation of Transmission Lines & Cables 

Represented by a series impedance 

Resistance equal to the total resistance of the line/cable



Reactance equal to the total series reactance of the line/cable

ZL

© Protection Engineering And Research Laboratories

75

Transformers Two Winding Transformer Equivalent Circuit I1

XL1

R1

XL2

I’2= I2/n

R2

I2

n = N1/N2

I0

V1

Xm

Rc

E2=E1/n

E1

N1



Winding resistance & Leakage reactance

Secondary side impedance 



N2

Primary side impedance 



V2

Winding resistance & Leakage reactance

Magnetizing branch

© Protection Engineering And Research Laboratories

76

Transformers Two Winding Transformer Equivalent Circuit I1

XL1

n2XL2

R1

Xm

Rc

V’2=nV2

N1



n = N1/N2

n2R2

I0 V1

I’2= I2/n

N2

Referring the secondary impedances to the primary side

© Protection Engineering And Research Laboratories

77

Transformers Two Winding Transformer Equivalent Circuit I1

XL1

R1

n2XL2

I’2= I2/n

n = N1/N2

n2R2 V’2=nV2

V1

N1



N2

Magnetizing impedance is very large compared to the leakage reactance 

Can be ignored without much error

© Protection Engineering And Research Laboratories

78

Transformers Two Winding Transformer Equivalent Circuit I1

XL1

n2XL2

I’2= I2/n

V’2=nV2

V1

N1



n = N1/N2

N2

The winding resistances are very small 

Can be safely neglected

© Protection Engineering And Research Laboratories

79

Transformers Two Winding Transformer Equivalent Circuit n = N1/N2

XT = XL1 + n2XL2

N1



N2

The primary & secondary leakage reactances can be lumped together 

Single reactance, XT



Obtained from the short circuit test of the transformer

© Protection Engineering And Research Laboratories

80

Transformers Two Winding Transformer Equivalent Circuit XTpu = XL1pu + XL2pu



n = N1/N2

Per unit equivalent diagram 

Total reactance is sum of the per unit reactance of the two windings

© Protection Engineering And Research Laboratories

81

Transformers Representation of Two Winding Transformers 

Represented by a series reactance 

Equal to the leakage impedance of the transformer



Obtained from the short circuit testing of the transformer

P

S

P

XTpu

S

Transformer

© Protection Engineering And Research Laboratories

82

Transformers Representation of Three Winding Transformers 

Each winding is represented by its own leakage reactance 



XP, XS, XT

Magnetizing impedance represented by the parallel branch ZM

Transformer

P

S

T

P

XP-pu

ZM-pu

XS-pu S XT-pu T N

© Protection Engineering And Research Laboratories

83

Transformers Representation of Three Winding Transformers 

Magnetizing impedance is very large 

Usually ignored

Transformer

P

S

P

XP-pu

XS-pu S XT-pu

T

T N

© Protection Engineering And Research Laboratories

84

Transformers Representation of Autotransformers 

The HV & LV windings are represented by the leakage reactances XH & XL



Magnetizing impedance represented by the parallel branch ZM

Autotransformer

H

L

H

XH-pu

XL-pu L

ZM-pu N

© Protection Engineering And Research Laboratories

85

Transformers Representation of Autotransformers 

Magnetizing impedance is very large 

Usually ignored

Autotransformer

H

L

H

XH-pu

XL-pu L

N

© Protection Engineering And Research Laboratories

86

Transformers Representation of Autotransformers 

Represented by a single leakage reactance 



XH & XL lumped together

Same as two winding transformer

Autotransformer

H

L

H

XHL-pu

L

N

© Protection Engineering And Research Laboratories

87

Transformers Representation of Autotransformers with Tertiary Delta Winding 

The HV & LV windings are represented by the leakage reactances XH & XL



The tertiary delta winding is represented by its leakage reactance XT



Magnetizing impedance is ignored

Autotransformer

H

L

∆ T

© Protection Engineering And Research Laboratories

H

XH-pu

XL-pu L XT-pu T N

88

Synchronous Machines Representation of a Synchronous Generator 

An unloaded generator is represented by the no-load phase to neutral voltage in series with the appropriate reactance

Xg +

Eg -

© Protection Engineering And Research Laboratories

89

Synchronous Machines Representation of a Synchronous Generator 

Appropriate reactance is considered 

depends on time-period is of interest

Xg = Xd” or Xd’ or Xd +

Eg -

© Protection Engineering And Research Laboratories

90

Synchronous Machines Representation of a Synchronous Generator 

For fault currents immediately after the fault (typically 2-5 cycles) 

Use sub-transient reactance 



Eg: Instantaneous protection setting calculations

For fault currents few cycles after the fault (typically 25 cycles) 

Use transient reactance 

Eg: Time delayed protections such as generator back-up impedance protection



For sustained fault currents 

Use steady-state reactance 

Eg: Power swing calculations

© Protection Engineering And Research Laboratories

91

Synchronous Machines Representation of a Synchronous Motor 

When short-circuited, 

No more electric energy supplied to it



Still keeps rotating for some time 

Inertia of its rotor and connected load



Field remains energized



Starts acting like a generator

© Protection Engineering And Research Laboratories

92

Synchronous Machines Representation of a Synchronous Motor 

Synchronous motor behaves like a generator 



Especially larger capacity motors 



Contributes current to the fault

Contribution to fault current is significant

This current decays with time 

Stored energy is dissipated



Rotor starts slowing down

© Protection Engineering And Research Laboratories

93

Synchronous Machines Representation of a Synchronous Motor 

Contribution from small capacity motors 



Neglected – not included in fault calculations

Contribution from large motors 

Usually considered only if the sub-transient fault current is calculated

© Protection Engineering And Research Laboratories

94

Synchronous Machines Representation of a Synchronous Motor 

Usually modeled as a voltage behind Xd”

Xm = Xd”

Typical values from IEEE standard 399 



+



Em

2 - 6 poles

8 - 14 poles 

-



Xd” = 20%

≥ 16 poles 

© Protection Engineering And Research Laboratories

Xd” = 15%

Xd” = 28%

95

Transients due to Faults Representation of a Induction Motor 

When fault occurs 

Input power to motor is cut



Energy stored in the motor contributes to the fault



Contribution decays with time 



Typical decay rate - 100 to 150 ms

Modeled like the synchronous motor 

Voltage behind an impedance

© Protection Engineering And Research Laboratories

96

Transients due to Faults Representation of a Induction Motor 

Small Motors 

Contribution from small motors are negligible



Not considered for fault calculations



Motors of ratings < 35kW considered as small motors

© Protection Engineering And Research Laboratories

97

Transients due to Faults Representation of a Induction Motor Modeled as a voltage behind an impedance





Xm = Xd”

Large Motors > 35kW 

Xd” is approximately equal to the locked rotor reactance

+

Em -



Typical value can be used when exact values not known 

Typical value Xd” = 16.7% (IEEE Standard 399)

© Protection Engineering And Research Laboratories

98

Summary Synchronous Motors

Xm = Xd”

Xg = Xd” or Xd’ or Xd

+ Em

Induction Motors

Synchronous Generators

Xm = Xd”

+

+

-

Eg

Em

-

Typical Xd” = 16.7%

-

Trans. Lines & Cables ZL Autotransformer with ∆ tertiary

Three-winding transformer

P

XP-pu

2-wdg txfr & Auto-txfr XT-pu

© Protection Engineering And Research Laboratories

XS-pu S

H

XH-pu

XL-pu L XT-pu

XT-pu T

T

N

N

99

Analysis of Symmetrical Faults

Introduction Symmetrical Faults 

As we saw earlier 

These are three-phase faults



System remains balanced



Per-phase analysis can be done

© Protection Engineering And Research Laboratories

101

Introduction Procedure 

In the given network replace … 

Transformers with their leakage reactances



Transmission lines with their series impedance  All shunt connections are neglected



Load impedances are neglected  Much larger than the network components



Synchronous machines represented by  No load-voltage behind Xd” or Xd’ 

Depends on time period of interest

© Protection Engineering And Research Laboratories

102

Introduction Procedure (contd.) 

Express voltage and impedances in per unit



Reduce the network



Solve for 

Fault current



Current through each branch



Bus voltages

© Protection Engineering And Research Laboratories

103

Single Source System Problem 1 T1

G

50 + j100 ohms

ΔY



Generator: 15 MVA, 13.8 kV, xd” = 0.15 pu



Load: 10 MVA at 0.9 pf lead



T1: 25 MVA, 13.2/161 kV, x = 0.10 pu



T2: 15 MVA, 161/13.8 kV, x = 0.10 pu

T2

Load



For a three-phase fault at the load bus, find the symmetrical current fed into the fault

© Protection Engineering And Research Laboratories

104

Single Source System Problem 1 - Per-unit equivalent

MVA base = 15 kV base of 161 kV at the transmission line

0.0289 + j0.0579

G j0.06

j0.1639

j0.06

j0.1

0.0289 + j0.0579

j0.1

j0.1639 +

IF”

1.045 © Protection Engineering And Research Laboratories

105

Single Source System Problem 1 - Reduced equivalent circuit 0.0289 + j0.0579

G j0.1639

j0.06

j0.1

0.0289 + j0.3818 + 1.045

IF” -

© Protection Engineering And Research Laboratories

106

Single Source System Problem 1 - Fault current calculation 0.0289 + j0.0579

G j0.1639

j0.06

j0.1

0.0289 + j0.3818

IF" =

+ 1.045

IF” -

1.045 = 0.206 " j2.7214 pu 0.0289 + j0.3818

IF" = 2.7292# " 85.67 0 pu

! © Protection Engineering And Research Laboratories

107

Single Source System Problem 1 - Fault current calculation 0.0289 + j0.0579

G j0.1639

j0.06

j0.1

0.0289 + j0.3818

IBase =

+ 1.045

IF” -

MVA B 15 = kA = 627.55 A 3 " kVB 3 "13.8

IF" = 2.7292 " 627.55 = 1712.72# $ 85.67 0 A

! © Protection Engineering And Research Laboratories

108

Single Source System Problem 1 - Solution T1

T2

ΔY



Load

G

Fault current = 1712.72 ∠-85.670 A

© Protection Engineering And Research Laboratories

109

Three-phase Systems Unbalanced 3 Phase system

Va

Vc

Vb Its Sequence Components POSITIVE SEQUENCE

NEGATIVE SEQUENCE

Vb2

Vc1 1200

1200 1200

Vb1

ZERO SEQUENCE

1200

Va1

Vc2

© Protection Engineering And Research Laboratories

Va0

1200

Vb0

1200

Va2

Vc0

126

Three-phase Systems Points to note Vc1

Vb2 1200

Va1

1200

Vc2

Vb1



1200

1200

1200 Positive Sequence

1200

Va0 Vb0 Vc0

Va2 Negative Sequence

Zero Sequence

There is no direct relationship between the magnitude or angles of Va0, Va1 and Va2.



Similarly no direct relationship between the magnitude or angles of Vb0, Vb1 and Vb2

or Vc0, Vc1 and Vc2.

© Protection Engineering And Research Laboratories

127

Three-phase Systems Points to note Vb2

Vc1

Va0 1200

1200

Va1

1200 1200

Vc2

Vb1 Positive Sequence



1200

1200

Va2

Negative Sequence

Vb0 Vc0 Zero Sequence

The magnitude and the angles of Va0, Va1 and Va2 are determined by the system conditions.

© Protection Engineering And Research Laboratories

128

Symmetrical Transmission Line Sequence Impedances

a

Z0

+ Van0

I0

a’

a +

_ n

Zero

+

Va’n’0

_ n’

Z1

Van1

a’

I1

a +

_ n

© Protection Engineering And Research Laboratories

Positive

+

Va’n’1

_ n’

Z2

Van2

a’

I2

+ Va’n’2

_

_ n

Negative

n’

142

Star/star - Both Neutrals Grounded A



IA



N1:N2

N C B I0

P

3ZN

IC



a

Ia

n

ZN

⦁ ⦁

IN



Zn

In

IB

Ib

b

Ic

ZT

3Zn

V0’

Q

V0

P

I1

ZT

V1’

Reference Bus

Zero © Protection Engineering And Research Laboratories

I1

Q

V1 Reference Bus

Positive

P

I2

c ZT

I2

V2’

Q

V2 Reference Bus

Negative 143

Star/star - Ungrounded Neutral A



IA

N C B I0

P

3ZN

IC





N1:N2

a

Ia

n

ZN

⦁ ⦁

IN



Zn= ∞

IB

Ib

b

Ic

ZT

V0’

Q

V0

P

I1

ZT

V1’

Reference Bus

Zero © Protection Engineering And Research Laboratories

I1

Q

V1 Reference Bus

Positive

P

I2

c ZT

I2

V2’

Q

V2 Reference Bus

Negative 144

Delta/delta - Pu Sequence Circuit N1:N2

A

Ia

IA



P



Q

C

IC





Transformer

I0

ZT

V0’



⦁ ⦁



Vab

Ib Ic

IB

B

P

VAB

Q

V0

P

I1

ZT

V1’

Reference Bus

Zero © Protection Engineering And Research Laboratories

I1

Q

V1 Reference Bus

Positive

a

P

I2

ZT

b c I2

V2’

Q

V2 Reference Bus

Negative 145

Star/delta - Neutral Grounded A



P

Per-unit Sequence Ckt. P V0’

Q

V0

B

P

IC







N C

ZT

Ia

VAN

Q

Transformer

I0 3ZN

N1:N2



IA

VN

ZN

Vab





IN

Ib Ic

IB

IA1

ZT

1∠30˚:1

VA1

Ia1

Q

Va1

P

IA1

ZT

1∠-30˚:1

Ia1

VA1

© Protection Engineering And Research Laboratories

Positive

b c

Q

Va1

Reference Bus

Zero

a

Negative 146

Star/delta - Neutral Ungrounded A



P

Per-unit Sequence Ckt. P V0’

Q

V0

B

P

IC





N C

ZT

Ia

VAN

Q

Transformer

I0

N1:N2



IA



Vab





Ib Ic

IB

IA1

ZT

1∠30˚:1

VA1

Ia1

Q

Va1

P

IA1

ZT

1∠-30˚:1

Ia1

VA1

© Protection Engineering And Research Laboratories

Positive

b c

Q

Va1

Reference Bus

Zero

a

Negative 147

Synchronous Machines 

Positive & Negative sequence circuits 



n

Grounding has no effect

Zero sequence impedance 

Grounding impedance is included



Ungrounded generators - no path for zero sequence

XG1

I1

n

a +

XG2

I2

V1 _

Positive

n

n

© Protection Engineering And Research Laboratories

Negative

a +

V1 _

n

3ZN

gnd

XG0

I0

a +

V0 _

Zero 148

Sequence Networks Positive Sequence Network T1

T2

Load

G ZE

(Dyn1) ΔY

YY ZF

Equivalent Positive Sequence Network ZT1(1)

ZLine(1)

ZT2(1)

F1

1:1∠-300

ZG(1) + Eg

1:1∠-300 -

© Protection Engineering And Research Laboratories

Reference bus

N1 149

Sequence Networks Negative Sequence Network T1

T2

Load

G ZE

(Dyn1) ΔY

YY ZF

Equivalent Negative Sequence Network ZT1(2)

ZG(2)

ZLine(2)

ZT2(2)

F2

1:1∠300

1:1∠300

N2 © Protection Engineering And Research Laboratories

150

Sequence Networks Zero Sequence Network T1

T2

Load

G ZE

ΔY

YY ZF

Equivalent Zero Sequence Network ZT1(0)

ZLine(0)

ZT2(0)

F0

ZG(0)

3ZE

G0 © Protection Engineering And Research Laboratories

151

Inter-connection of seq. networks Power System Network – Before Fault T1

T2

G

ZE

YY

ΔY

Positive Sequence Network

Load

Negative Sequence Network

Z1

Z2

Zero Sequence Network Z0

+ Vf © Protection Engineering And Research Laboratories

152

Inter-connection of seq. networks Power System Network – Before Fault 

Positive Sequence 



Voltage source is present  Positive sequence currents flow

Negative and Zero Sequence 

No negative and zero sequence sources 

No Negative and zero sequence currents

Positive Sequence Network

Negative Sequence Network

Z1

Z2

i1

i2=0

Zero Sequence Network Z0

+ Vf

i0=0

© Protection Engineering And Research Laboratories

153

Inter-connection of seq. networks Faulted Power System T1

T2

Load

G

ZE

YY

ΔY

ZF

Sequence circuits for a fault at the load bus Z1

F1

Z2

F2

Z0

F0

+ Vf -

N1

© Protection Engineering And Research Laboratories

N2

N0 154

Inter-connection of seq. networks Faulted Power System– Redrawn sequence circuits Z1 Vf

+

-

+

I1

V1 -

Z2 I2

+

N1 F2

V2 -

Z0 +

I0

F1

N2 F0

V0 -

N0

© Protection Engineering And Research Laboratories

155

Single Line to Ground Fault Inter-connection of Sequence Networks Z1 Vf

+

-

+

I1

F1

V1 N1

Z2 I2

F2 +

V2 -

Z0 +

I0

3 × ZF N2 F0

V0 N0

© Protection Engineering And Research Laboratories

156

Three Phase Fault Inter-connection of sequence networks Z1 Vf

+

-

+

I1

F1 ZF

V1 N1

Z2 I2

F2 +

V2 -

Z0 +

I0

ZF

 Fault impedance to ground Zg  No effect on the fault

N2

current

F0 ZF + 3Zg

V0 N0

© Protection Engineering And Research Laboratories

170

Analysis of Un-Symmetrical Faults Three Phase vs. Single Phase Fault Level 

Three phase faults are generally the most severe ones 



Three phase fault level is the highest

However, sometimes 

Single phase fault levels can be higher than 3-phase 

Solidly grounded systems



On the Y-grounded side of Δ-Y-grounded transformer banks

© Protection Engineering And Research Laboratories

171

Analysis of Un-Symmetrical Faults Three Phase vs. Single Phase Fault Level 

Consider the following system with fault as shown

T G ΔY

© Protection Engineering And Research Laboratories

ZF

172

Analysis of Un-Symmetrical Faults Three Phase vs. Single Phase Fault Level 

Hence for the system shown …

G

T1 ΔY

Single-phase fault current

ZF

If Z0 < Z1, then Three-phase fault current

© Protection Engineering And Research Laboratories

1-φ fault level > 3-

φ fault level

173

Related Documents

5 Algebra Basics
February 2021 0
Basics Of Compressor
February 2021 0
Basics Of Ship Resistance
February 2021 0

More Documents from "api-27176519"