GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

A

11 kV POWER CABLES

1

P-420-GS-9002A-01/02

420-GS-9002A

Steam Turbine Generator-A

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

VAC

6,500

2

P-420-GS-9002B-01/02

420-GS-9002B

Steam Turbine Generator-B

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

VAC

6,500

3

P-420-V-9002

420-V-9002

Essential Power Generator

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

VAC

3,000

4

P-420-TRF-0001A-01/02/03

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

420-TRF-0001A

11 / 6.6 kV Transformer A Substation-1 (Power Generation)

3

F

11,000

VAC

11,520

420-TRF-0001B

11 / 6.6 kV Transformer B Substation-1 (Power Generation)

3

F

11,000

VAC

11,520

5

P-420-TRF-0001B-01/02/03

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

6

P-900-SWG-0001

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

900-SWG-0001

11 kV Switchgear Infrastructure

3

F

11,000

VAC

2,223

7

P-900-TRF-0001

800-SWG-0001

11 kV Switchgear Infrastructure

900-TRF-0001

11 / 0.42 kV Transformer Infrastructure

3

F

11,000

VAC

2,400

1 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

211-SWG-0001

11 kV Switchgear Central Well Pad Substation

3

F

11,000

VAC

389

Volt

kW

8

P-211-SWG-0001

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

9

P-211-TRF-0001

211-SWG-0001

11 kV Switchgear Central Well Pad Substation

211-TRF-0001

11 / 0.42 kV Central Wellpad Transformer

3

F

11,000

VAC

384

10

P-211-SWG-0002

211-SWG-0001

11 kV Switchgear Central Well Pad Substation

212-SWG-0001

11 kV Switchgear East Well Pad Substation

3

F

11,000

VAC

384

11

P-212-SWG-0001

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

212-SWG-0001

11 kV Switchgear East Well Pad Substation

3

F

11,000

VAC

389

12

P-212-TRF-0001

212-SWG-0001

11 kV Switchgear East Well Pad Substation

212-TRF-0001

11 / 0.42 kV East Wellpad Transformer

3

F

11,000

VAC

384

13

P-710-SWG-0001

SWG823081 (PB-01S)

11 kV Switchgear Banyu Urip Main Gate House Area

710-SWG-0001

11 kV Switchgear Sales Gas Metering Substation

3

F

11,000

VAC

166

14

P-710-TRF-0001

710-SWG-0001

11 kV Switchgear Sales Gas Metering Substation

710-TRF-0001

11 / 0.42 kV Transformer Sales Gas Metering

3

F

11,000

VAC

120

2 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

B

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

6.6 kV POWER CABLES Substation-1 (Area 420 - Power Generation Substation)

1

P-420-TRF-0002A

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

420-TRF-0002A

6.6/0.4 kV Main Transformer

3

F

6,600

VAC

1,200

2

P-420-TRF-0002B

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

420-TRF-0002B

6.6/0.4 kV Main Transformer

3

F

6,600

VAC

1,200

3

P-420-TRF-0003A

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

420-TRF-0003A

6.6/0.4 kV Essential Transformer

3

F

6,600

VAC

1,536

4

P-420-TRF-0003B

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

420-TRF-0003B

6.6/0.4 kV Essential Transformer

3

F

6,600

VAC

1,536

Substation-2 (Area 231 - Train-A Substation) 5

P-231-SWG/MCC-0001A01/02

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-2 (Train-A)

3

F

6,600

VAC

4,840

6

P-231-SWG/MCC-0001B01/02

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-2 (Train-A)

3

F

6,600

VAC

4,840

3 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

7

P-231-TRF-0001A

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-2 (Train-A)

231-TRF-0001A

6.6/0.4 kV Transformer 1A Substation-2 (Train-A)

3

F

6,600

VAC

960

8

P-231-TRF-0001B

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-2 (Train-A)

231-TRF-0001B

6.6/0.4 kV Transformer 1B Substation-2 (Train-A)

3

F

6,600

VAC

960

9

P-231-TRF-0002A-01/02

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-2 (Train-A)

231-TRF-0002A

6.6/0.4 kV Transformer 2A Substation-2 (Train-A)

3

F

6,600

VAC

3,840

10

P-231-TRF-0002B-01/02

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-2 (Train-A)

231-TRF-0002B

6.6/0.4 kV Transformer 2B Substation-2 (Train-A)

3

F

6,600

VAC

3,840

Substation-3 (Area 280 - Train-B Substation) 11

P-280-SWG/MCC-0001A01/02

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

3

F

6,600

VAC

3,842

12

P-280-SWG/MCC-0001B01/02

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

3

F

6,600

VAC

3,842

13

P-280-TRF-0001A-01/02

280-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-3

280-TRF-0001A

6.6/0.4 kV Transformer A Substation3 (Train-B)

3

F

6,600

VAC

3,456

14

P-280-TRF-0001B-01/02

280-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-3

280-TRF-0001B

6.6/0.4 kV Transformer B Substation3 (Train-B)

3

F

6,600

VAC

3,456

4 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Substation-4 (Area 480 - Utility Substation) 15

P-480-SWG/MCC-0001 A

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

480-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-4 (Utility)

3

F

6,600

VAC

1,798

16

P-480-SWG/MCC-0001 B

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

480-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-4 (Utility)

3

F

6,600

VAC

1,798

17

P-480-TRF-0001A

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

480-TRF-0001A

6.6/0.4 kV Transformer Substation-4 (Utility)

3

F

6,600

VAC

768

18

P-480-TRF-0001B

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

480-TRF-0001B

6.6/0.4 kV Transformer Substation-4 (Utility)

3

F

6,600

VAC

768

Acid Gas Enrichment (AGE) Unit - Train A 19

P-280A-P-5001 A

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

280A-P-5001A

Lean Amine Pump-A (Train A)

3

M

6,600

VAC

200.00

20

P-280A-P-5001 B

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

280A-P-5001B

Lean Amine Pump-B (Train A)

3

M

6,600

VAC

200.00

Acid Gas Enrichment (AGE) Unit - Train B

5 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

21

P-280B-P-3001 A

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

280B-P-3001A

Lean Amine Pump-A (Train B)

3

M

6,600

VAC

200.00

22

P-280B-P-3001 B

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

280B-P-3001B

Lean Amine Pump-B (Train B)

3

M

6,600

VAC

200.00

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

410-P-9011

HP BWF Start-Up Pump

3

M

6,600

VAC

300.00

Boiler Feed Water (BFW) 23

P-410-P-9011

Instrument Air / Nitrogen Package 24

P-440-V-9001 A

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

440-V-9001 A

Instrument Air Compressor Package Motor A

3

M

6,600

VAC

355.00

25

P-440-V-9001 B

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

440-V-9001 B

Instrument Air Compressor Package Motor B

3

M

6,600

VAC

355.00

26

P-440-V-9001 C

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

440-V-9001 C

Instrument Air Compressor Package Motor C

3

M

6,600

VAC

355.00

6 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

C

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

0.4 kV POWER CABLES Inlet Separation Unit

1

P-221-E-9001-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-1

Inlet Cooler Fan 1

3

M

400

VAC

15.00

2

P-221-E-9001-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-2

Inlet Cooler Fan 2

3

M

400

VAC

15.00

3

P-221-E-9001-3

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-3

Inlet Cooler Fan 3

3

M

400

VAC

15.00

4

P-221-E-9001-4

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-4

Inlet Cooler Fan 4

3

M

400

VAC

15.00

5

P-221-E-9001-5

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-5

Inlet Cooler Fan 5

3

M

400

VAC

15.00

6

P-221-E-9001-6

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-6

Inlet Cooler Fan 6

3

M

400

VAC

15.00

7

P-221-E-9001-7

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-7

Inlet Cooler Fan 7

3

M

400

VAC

15.00

7 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

8

P-221-E-9001-8

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-8

Inlet Cooler Fan 8

3

M

400

VAC

15.00

Volt

kW

Produced Water Storage 9

P-222-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9001 A

Produced Water Transfer Pump A

3

M

400

VAC

5.50

10

P-222-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9001 B

Produced Water Transfer Pump B

3

M

400

VAC

5.50

11

P-222-P-9002 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9002 A

Pipeline Produced Water Transfer Pump A

3

M

400

VAC

75.00

12

P-222-P-9002 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9002 B

Pipeline Produced Water Transfer Pump B

3

M

400

VAC

75.00

13

P-222-P-9003

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9003

Skim Oil Pump

3

M

400

VAC

0.37

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

223-P-9001 A

Pipeline Condensate Transfer Pump A

3

M

400

VAC

37.00

Condensate Storage 14

P-223-P-9001 A

8 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

15

P-223-P-9001 B

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

223-P-9001 B

Pipeline Condensate Transfer Pump B

3

M

400

VAC

37.00

Volt

kW

Vapor Recovery Unit (VRU) 16

P-224-E-9001-1 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-1 A

VRU Intercooler-A (1st Stage) Fan-1

3

M

400

VAC

4.00

17

P-224-E-9001-2 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-2 A

VRU Intercooler-A (1st Stage) Fan-2

3

M

400

VAC

4.00

18

P-224-E-9001-1 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-1 B

VRU Intercooler-B (1st Stage) Fan-1

3

M

400

VAC

4.00

19

P-224-E-9001-2 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-2 B

VRU Intercooler-B (1st Stage) Fan-2

3

M

400

VAC

4.00

20

P-224-E-9002 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9002 A

VRU Intercooler-A (2nd Stage) Fan-1

3

M

400

VAC

1.50

21

P-224-E-9002 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9002 B

VRU Intercooler-B (2nd Stage) Fan-1

3

M

400

VAC

1.50

22

P-224-E-9003 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9003 A

VRU Intercooler-A (3rd Stage) Fan-1

3

M

400

VAC

2.20

9 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

23

P-224-E-9003 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9003 B

VRU Intercooler-B (3rd Stage) Fan-1

3

M

400

VAC

2.20

24

P-224-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-P-9001 A

VRU Knockout Pump A

3

M

400

VAC

0.37

25

P-224-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-P-9001 B

VRU Knockout Pump B

3

M

400

VAC

0.37

26

P-224-C-9001-01/02

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-C-9001

Driver Motor for VRU Compressor

3

M

400

VAC

160.00

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

231-P-9001

Methanol Injection Pump

3

M

400

VAC

3.00

Dew Point Control 27

P-231-P-9001

Condensate Stabilization 28

P-232-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-P-9001 A

Condensate Reflux Pump A

3

M

400

VAC

7.50

29

P-232-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-P-9001 B

Condensate Reflux Pump B

3

M

400

VAC

7.50

10 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

30

P-232-E-9001-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9001-1

Condensate Cooler Fan-1

3

M

400

VAC

4.00

31

P-232-E-9001-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9001-2

Condensate Cooler Fan-2

3

M

400

VAC

4.00

32

P-232-P-9002

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-P-9002

Condensate Stabilizer Recycle Liquid Pump

3

M

400

VAC

7.50

33

P-232-E-9003-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9003-1

Recycle Gas Compressor Cooler Fan-1

3

M

400

VAC

3.00

34

P-232-E-9003-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9003-2

Recycle Gas Compressor Cooler Fan-2

3

M

400

VAC

3.00

Ethylene Glycol (EG) Regeneration 35

P-233-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9001 A

EG Circulator Pump A

3

M

400

VAC

18.50

36

P-233-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9001 B

EG Circulator Pump B

3

M

400

VAC

18.50

37

P-233-P-9002 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9002 A

EG Reflux Pump A

3

M

400

VAC

0.37

11 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

38

P-233-P-9002 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9002 B

EG Reflux Pump B

3

M

400

VAC

0.37

39

P-233-P-9003 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9003 A

Produced Water Booster Pump A

3

M

400

VAC

0.75

40

P-233-P-9003 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9003 B

Produced Water Booster Pump B

3

M

400

VAC

0.75

41

P-233-P-9004

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9004

EG Makeup Pump

3

M

400

VAC

18.50

42

P-233-C-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-C-9001 A

EG Regeneration Overhead Gas Compressor A

3

M

400

VAC

75.00

43

P-233-C-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-C-9001 B

EG Regeneration Overhead Gas Compressor B

3

M

400

VAC

75.00

44

P-233-E-9005-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-E-9005-1

EG Regeneration Tower Cooler Fan-1

3

M

400

VAC

2.20

45

P-233-E-9005-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-E-9005-2

EG Regeneration Tower Cooler Fan-2

3

M

400

VAC

2.20

46

P-233-P-9005

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9005

Glycol Drain Return Pump

3

M

400

VAC

0.75

12 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Propylene - Refrigeration Unit 47

P-234-E-9001-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-1

Propylene Condenser Fan 1

3

M

400

VAC

7.50

48

P-234-E-9001-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-2

Propylene Condenser Fan 2

3

M

400

VAC

7.50

49

P-234-E-9001-3

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-3

Propylene Condenser Fan 3

3

M

400

VAC

7.50

50

P-234-E-9001-4

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-4

Propylene Condenser Fan 4

3

M

400

VAC

7.50

51

P-234-E-9001-5

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-5

Propylene Condenser Fan 5

3

M

400

VAC

7.50

52

P-234-E-9001-6

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-6

Propylene Condenser Fan 6

3

M

400

VAC

7.50

53

P-234-E-9001-7

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-6

Propylene Condenser Fan 7

3

M

400

VAC

7.50

54

P-234-E-9001-8

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-6

Propylene Condenser Fan 8

3

M

400

VAC

7.50

13 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

55

P-234-CA-9001-1 A

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-1 A

Propylene Compressor A (1st Stage) Auxiliary Load

3

M

400

VAC

45.00

56

P-234-CA-9001-2 A

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-2 A

Propylene Compressor A (2nd Stage) Auxiliary Load

3

M

400

VAC

45.00

57

P-234-CA-9001-1 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-1 B

Propylene Compressor B (1st Stage) Auxiliary Load

3

M

400

VAC

45.00

58

P-234-CA-9001-2 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-2 B

Propylene Compressor B (2nd Stage) Auxiliary Load

3

M

400

VAC

45.00

AGRU-A 59

P-240A-E-1001-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-1

Lean Solvent Air Cooler-A (AGRU A) #1

3

M

400

VAC

55.00

60

P-240A-E-1001-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-2

Lean Solvent Air Cooler-A (AGRU A) #2

3

M

400

VAC

55.00

61

P-240A-E-1001-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-3

Lean Solvent Air Cooler-A (AGRU A) #3

3

M

400

VAC

55.00

62

P-240A-E-1001-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-4

Lean Solvent Air Cooler-A (AGRU A) #4

3

M

400

VAC

55.00

14 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

63

P-240A-E-1001-5

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-5

Lean Solvent Air Cooler-A (AGRU A) #5

3

M

400

VAC

55.00

64

P-240A-E-1001-6

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-6

Lean Solvent Air Cooler-A (AGRU A) #6

3

M

400

VAC

55.00

65

P-240A-E-1001-7

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-7

Lean Solvent Air Cooler-A (AGRU A) #7

3

M

400

VAC

55.00

66

P-240A-E-1001-8

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-8

Lean Solvent Air Cooler-A (AGRU A) #8

3

M

400

VAC

55.00

67

P-240A-E-2001-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-1

Lean Solvent Air Cooler-B (AGRU A) #1

3

M

400

VAC

55.00

68

P-240A-E-2001-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-2

Lean Solvent Air Cooler-B (AGRU A) #2

3

M

400

VAC

55.00

69

P-240A-E-2001-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-3

Lean Solvent Air Cooler-B (AGRU A) #3

3

M

400

VAC

55.00

70

P-240A-E-2001-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-4

Lean Solvent Air Cooler-B (AGRU A) #4

3

M

400

VAC

55.00

71

P-240A-E-2001-5

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-5

Lean Solvent Air Cooler-B (AGRU A) #5

3

M

400

VAC

55.00

15 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

72

P-240A-E-2001-6

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-6

Lean Solvent Air Cooler-B (AGRU A) #6

3

M

400

VAC

55.00

73

P-240A-E-2001-7

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-7

Lean Solvent Air Cooler-B (AGRU A) #7

3

M

400

VAC

55.00

74

P-240A-E-2001-8

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-8

Lean Solvent Air Cooler-B (AGRU A) #8

3

M

400

VAC

55.00

75

P-240A-PA-1002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-1002

Auxiliary for HP Lean Solvent Pump 1 (Train A)

3

M

400

VAC

22.00

76

P-240A-PA-2002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-2002

Auxiliary for HP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

22.00

77

P-240A-PA-5003

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-5003

Auxiliary for HP Lean Solvent Pump 3 (Train A)

3

M

400

VAC

22.00

78

P-240A-P-1003 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1003A

Reflux Pump-1 A (Train A)

3

M

400

VAC

11.00

79

P-240A-P-1003 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1003B

Reflux Pump-1 B (Train A)

3

M

400

VAC

11.00

80

P-240A-P-2003 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2003A

Reflux Pump-2 A (Train A)

3

M

400

VAC

11.00

16 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

81

P-240A-P-2003 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2003B

Reflux Pump-2 B (Train A)

3

M

400

VAC

11.00

82

P-240A-P-5001

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-5001

Drained Solvent Pump (Stand-By) Train A

3

M

400

VAC

4.00

83

P-240A-P-5002

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-5002

Drained Hydrocarbon Pump (StandBy) Train A

3

M

400

VAC

2.20

84

P-240A-PA-1012

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-1012

Auxiliary for LP Lean Solvent Pump 1 (Train A)

3

M

400

VAC

4.00

85

P-240A-PA-2012

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-2012

Auxiliary for LP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

4.00

86

P-240A-PA-5012

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-5012

Auxiliary for LP Lean Solvent Pump 3 (Train A)

3

M

400

VAC

4.00

87

P-240A-PA-1001

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-1001

Auxiliary for Regenerator Lean Solvent Pump 1 (Train A)

3

M

400

VAC

5.50

88

P-240A-PA-2001

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-2001

Auxiliary for Regenerator Lean Solvent Pump 2 (Train A)

3

M

400

VAC

5.50

89

P-240A-PA-5004

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-5004

Auxiliary for Regenerator Lean Solvent Pump 3 (Train A)

3

M

400

VAC

5.50

17 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

90

P-240A-P-1006 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1006 A

Reboiler Condensate Pump-1A (Train A)

3

M

400

VAC

15.00

91

P-240A-P-1006 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1006 B

Reboiler Condensate Pump-1B (Train A)

3

M

400

VAC

15.00

92

P-240A-P-2006 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2006 A

Reboiler Condensate Pump-2A (Train A)

3

M

400

VAC

15.00

93

P-240A-P-2006 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2006 B

Reboiler Condensate Pump-2B (Train A)

3

M

400

VAC

15.00

94

P-240A-E-1004-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-1

Overhead Condenser-A (AGRU A) #1

3

M

400

VAC

55.00

95

P-240A-E-1004-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-2

Overhead Condenser-A (AGRU A) #2

3

M

400

VAC

55.00

96

P-240A-E-1004-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-3

Overhead Condenser-A (AGRU A) #3

3

M

400

VAC

55.00

97

P-240A-E-1004-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-4

Overhead Condenser-A (AGRU A) #4

3

M

400

VAC

55.00

98

P-240A-E-2004-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-1

Overhead Condenser-B (AGRU A) #1

3

M

400

VAC

55.00

18 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

P-240A-E-2004-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-2

Overhead Condenser-B (AGRU A) #2

3

M

400

VAC

55.00

100 P-240A-E-2004-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-3

Overhead Condenser-B (AGRU A) #3

3

M

400

VAC

55.00

101 P-240A-E-2004-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-4

Overhead Condenser-B (AGRU A) #4

3

M

400

VAC

55.00

102 P-240-P-9001 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240-P-9001A

AGRU Fresh Solvent Pump A

3

M

400

VAC

5.50

103 P-240-P-9001 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240-P-9001B

AGRU Fresh Solvent Pump B

3

M

400

VAC

5.50

104 P-240B-E-3001-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-1

Lean Solvent Air Cooler-A (AGRU B) #1

3

M

400

VAC

55.00

105 P-240B-E-3001-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-2

Lean Solvent Air Cooler-A (AGRU B) #2

3

M

400

VAC

55.00

106 P-240B-E-3001-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-3

Lean Solvent Air Cooler-A (AGRU B) #3

3

M

400

VAC

55.00

99

Volt

kW

AGRU-B

19 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

107 P-240B-E-3001-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-4

Lean Solvent Air Cooler-A (AGRU B) #4

3

M

400

VAC

55.00

108 P-240B-E-3001-5

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-5

Lean Solvent Air Cooler-A (AGRU B) #5

3

M

400

VAC

55.00

109 P-240B-E-3001-6

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-6

Lean Solvent Air Cooler-A (AGRU B) #6

3

M

400

VAC

55.00

110 P-240B-E-3001-7

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-7

Lean Solvent Air Cooler-A (AGRU B) #7

3

M

400

VAC

55.00

111 P-240B-E-3001-8

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-8

Lean Solvent Air Cooler-A (AGRU B) #8

3

M

400

VAC

55.00

112 P-240B-E-4001-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-1

Lean Solvent Air Cooler-B (AGRU B) #1

3

M

400

VAC

55.00

113 P-240B-E-4001-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-2

Lean Solvent Air Cooler-B (AGRU B) #2

3

M

400

VAC

55.00

114 P-240B-E-4001-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-3

Lean Solvent Air Cooler-B (AGRU B) #3

3

M

400

VAC

55.00

115 P-240B-E-4001-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-4

Lean Solvent Air Cooler-B (AGRU B) #4

3

M

400

VAC

55.00

20 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

116 P-240B-E-4001-5

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-5

Lean Solvent Air Cooler-B (AGRU B) #5

3

M

400

VAC

55.00

117 P-240B-E-4001-6

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-6

Lean Solvent Air Cooler-B (AGRU B) #6

3

M

400

VAC

55.00

118 P-240B-E-4001-7

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-7

Lean Solvent Air Cooler-B (AGRU B) #7

3

M

400

VAC

55.00

119 P-240B-E-4001-8

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-8

Lean Solvent Air Cooler-B (AGRU B) #8

3

M

400

VAC

55.00

120 P-240B-PA-3002

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-3002

Auxiliary for HP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

22.00

121 P-240B-PA-4002

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-4002

Auxiliary for HP Lean Solvent Pump 2 (Train B)

3

M

400

VAC

22.00

122 P-240B-PA-6003

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-6003

Auxiliary for HP Lean Solvent Pump 3 (Train B)

3

M

400

VAC

22.00

123 P-240B-P-3003 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3003A

Reflux Pump-1 A (Train B)

3

M

400

VAC

11.00

124 P-240B-P-3003 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3003 B

Reflux Pump-1 B (Train B)

3

M

400

VAC

11.00

21 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

125 P-240B-P-4003 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4003A

Reflux Pump-2 A (Train B)

3

M

400

VAC

11.00

126 P-240B-P-4003 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4003 B

Reflux Pump-2 B (Train B)

3

M

400

VAC

11.00

127 P-240B-P-6001

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-6001

Drained Solvent Pump (Stand-By) Train B

3

M

400

VAC

4.00

128 P-240B-P-6002

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-6002

Drained Hydrocarbon Pump (StandBy) Train B

3

M

400

VAC

2.20

127 P-240B-PA-3012

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-3012

Auxiliary for LP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

4.00

128 P-240B-PA-4012

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-4012

Auxiliary for LP Lean Solvent Pump 2 (Train B)

3

M

400

VAC

4.00

129 P-240B-PA-6012

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-6012

Auxiliary for LP Lean Solvent Pump 3 (Train B)

3

M

400

VAC

4.00

130 P-240B-PA-3001

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-3001

Auxiliary for Regenerator Lean Solvent Pump 1 (Train B)

3

M

400

VAC

5.50

131 P-240B-PA-4001

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-4001

Auxiliary for Regenerator Lean Solvent Pump 2 (Train B)

3

M

400

VAC

5.50

22 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

132 P-240B-PA-6004

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-6004

Auxiliary for Regenerator Lean Solvent Pump 3 (Train B)

3

M

400

VAC

5.50

133 P-240B-P-3006 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3006 A

Reboiler Condensate Pump-1 A (Train B)

3

M

400

VAC

15.00

134 P-240B-P-3006 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3006 B

Reboiler Condensate Pump-1 B (Train B)

3

M

400

VAC

15.00

135 P-240B-P-4006 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4006 A

Reboiler Condensate Pump-2 A (Train B)

3

M

400

VAC

15.00

136 P-240B-P-4006 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4006 B

Reboiler Condensate Pump-2 B (Train B)

3

M

400

VAC

15.00

137 P-240B-E-3004-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-1

Overhead Condenser-A (AGRU B) #1

3

M

400

VAC

55.00

138 P-240B-E-3004-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-2

Overhead Condenser-A (AGRU B) #2

3

M

400

VAC

55.00

139 P-240B-E-3004-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-3

Overhead Condenser-A (AGRU B) #3

3

M

400

VAC

55.00

140 P-240B-E-3004-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-4

Overhead Condenser-A (AGRU B) #4

3

M

400

VAC

55.00

23 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

141 P-240B-E-4004-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-1

Overhead Condenser-B (AGRU B) #1

3

M

400

VAC

55.00

142 P-240B-E-4004-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-2

Overhead Condenser-B (AGRU B) #2

3

M

400

VAC

55.00

143 P-240B-E-4004-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-3

Overhead Condenser-B (AGRU B) #3

3

M

400

VAC

55.00

144 P-240B-E-4004-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-4

Overhead Condenser-B (AGRU B) #4

3

M

400

VAC

55.00

145 P-250-P-9001 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9001 A

Sales Gas Dehy TEG Circulation Pump A

3

M

400

VAC

132.00

146 P-250-P-9001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9001 B

Sales Gas Dehy TEG Circulation Pump B

3

M

400

VAC

132.00

147 P-250-E-9001-1

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-E-9001-1

Sales Gas Dehy TEG Lean Cooler Fan-1

3

M

400

VAC

7.50

148 P-250-E-9001-2

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-E-9001-2

Sales Gas Dehy TEG Lean Cooler Fan-2

3

M

400

VAC

7.50

Volt

kW

Sales Gas Dehydration Unit

24 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

149 P-250-P-9002

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9002

Sales Gas Dehy TEG Supply Pump

3

M

400

VAC

7.50

150 P-250-P-9003

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9003

TEG Drain Vessel Pump

3

M

400

VAC

0.75

151 P-260-E-9001-1

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

260-E-9001-1

Sales Gas Compressor Discharge Cooler Fan 1

3

M

400

VAC

7.50

152 P-260-E-9001-2

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

260-E-9001-2

Sales Gas Compressor Discharge Cooler Fan 2

3

M

400

VAC

7.50

153 P-260-CA-9001 A

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

260-CA-9001 A

Sales Gas Compressor A Auxiliary Load

3

M

400

VAC

75.00

154 P-260-CA-9001 B

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

260-CA-9001 B

Sales Gas Compressor B Auxiliary Load

3

M

400

VAC

75.00

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1005

Wash Water Pump-1 at AGE Absorber (Train A)

3

M

400

VAC

7.50

Volt

kW

Sales Gas Compression

Acid Gas Enrichment (AGE) Unit - Train A 155 P-280A-P-1005

231-SWG/MCC-0004

25 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

156 P-280A-P-2005

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2005

Wash Water Pump-2 at AGE Absorber (Train A)

3

M

400

VAC

7.50

157 P-280A-P-5005

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5005

Wash Water Pump-3 at AGE Absorber (Train A)

3

M

400

VAC

7.50

158 P-280A-P-1004

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1004

Regenerator Reflux Pump-1 (Train A)

3

M

400

VAC

15.00

159 P-280A-P-2004

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2004

Regenerator Reflux Pump-2 (Train A)

3

M

400

VAC

15.00

160 P-280A-P-5004

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5004

Regenerator Reflux Pump-3 (Train A)

3

M

400

VAC

15.00

161 P-280A-P-5002 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5002A

Solvent Sump Pump-A (Train A)

3

M

400

VAC

11.00

162 P-280A-P-5002 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5002B

Solvent Sump Pump-B (Train A)

3

M

400

VAC

11.00

163 P-280A-E-1002

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-1002

Regenerator Overhead Condenser 1 (Train A)

3

M

400

VAC

37.00

164 P-280A-E-2002

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-2002

Regenerator Overhead Condenser 2 (Train A)

3

M

400

VAC

37.00

26 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

165 P-280A-P-1008

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1008

Regenerator Bottoms Pump 1 (Train A)

3

M

400

VAC

75.00

166 P-280A-P-2008

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2008

Regenerator Bottoms Pump 2 (Train A)

3

M

400

VAC

75.00

167 P-280A-P-5008

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5008

Regenerator Bottoms Pump 3 (Train A)

3

M

400

VAC

75.00

168 P-280A-E-5001-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-1

Lean Amine Cooler (Train A) #1

3

M

400

VAC

37.00

169 P-280A-E-5001-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-2

Lean Amine Cooler (Train A) #2

3

M

400

VAC

37.00

170 P-280A-E-5001-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-3

Lean Amine Cooler (Train A) #3

3

M

400

VAC

37.00

171 P-280A-E-5001-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-4

Lean Amine Cooler (Train A) #4

3

M

400

VAC

37.00

172 P-280A-E-5001-5

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-5

Lean Amine Cooler (Train A) #5

3

M

400

VAC

37.00

173 P-280A-E-5001-6

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-6

Lean Amine Cooler (Train A) #6

3

M

400

VAC

37.00

27 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

174 P-280A-E-5001-7

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-7

Lean Amine Cooler (Train A) #7

3

M

400

VAC

37.00

175 P-280A-E-5001-8

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-8

Lean Amine Cooler (Train A) #8

3

M

400

VAC

37.00

176 P-280A-P-1003

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1003

Rich Amine Pump-1 at AGE Absorber (Train A)

3

M

400

VAC

110.00

177 P-280A-P-2003

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2003

Rich Amine Pump-2 at AGE Absorber (Train A)

3

M

400

VAC

110.00

178 P-280A-P-5003

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5003

Rich Amine Pump-3 at AGE Absorber (Train A)

3

M

400

VAC

110.00

179 P-280-P-9001 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280-P-9001A

Fresh Solvent Pump A (Train A)

3

M

400

VAC

5.50

180 P-280-P-9001 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280-P-9001B

Fresh Solvent Pump B (Train A)

3

M

400

VAC

5.50

181 P-280A-P-1006

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1006

Sour Water Pump-1 (Train A)

3

M

400

VAC

5.50

182 P-280A-P-2006

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2006

Sour Water Pump-2 (Train A)

3

M

400

VAC

5.50

28 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

183 P-280A-P-5006

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5006

Sour Water Pump-3 (Train A)

3

M

400

VAC

5.50

Volt

kW

Acid Gas Enrichment (AGE) Unit - Train B 184 P-280B-P-3005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3005

Wash Water Pump-1 at AGE Absorber (Train B)

3

M

400

VAC

11.00

185 P-280B-P-4005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4005

Wash Water Pump-2 at AGE Absorber (Train B)

3

M

400

VAC

11.00

186 P-280B-P-6005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6005

Wash Water Pump-3 at AGE Absorber (Train B)

3

M

400

VAC

11.00

187 P-280B-P-3004

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3004

Regenerator Reflux Pump-1 (Train B)

3

M

400

VAC

15.00

188 P-280B-P-4004

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4004

Regenerator Reflux Pump-2 (Train B)

3

M

400

VAC

15.00

189 P-280B-P-6004

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6004

Regenerator Reflux Pump-3 (Train B)

3

M

400

VAC

15.00

190 P-280B-P-6002 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6002A

Solvent Sump Pump-A (Train B)

3

M

400

VAC

11.00

29 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

191 P-280B-P-6002 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6002B

Solvent Sump Pump-B (Train B)

3

M

400

VAC

11.00

192 P-280B-E-3002

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-3002

Regenerator Overhead Condenser 1 (Train B)

3

M

400

VAC

37.00

193 P-280B-E-4002

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-4002

Regenerator Overhead Condenser 2 (Train B)

3

M

400

VAC

37.00

194 P-280B-P-3008

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3008

Regenerator Bottoms Pump-1 (Train B)

3

M

400

VAC

75.00

195 P-280B-P-4008

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4008

Regenerator Bottoms Pump-2 (Train B)

3

M

400

VAC

75.00

196 P-280B-P-6008

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6008

Regenerator Bottoms Pump-3 (Train B)

3

M

400

VAC

75.00

197 P-280B-E-6001-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-1

Lean Amine Cooler (Train B) #1

3

M

400

VAC

37.00

198 P-280B-E-6001-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-2

Lean Amine Cooler (Train B) #2

3

M

400

VAC

37.00

199 P-280B-E-6001-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-3

Lean Amine Cooler (Train B) #3

3

M

400

VAC

37.00

30 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

200 P-280B-E-6001-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-4

Lean Amine Cooler (Train B) #4

3

M

400

VAC

37.00

201 P-280B-E-6001-5

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-5

Lean Amine Cooler (Train B) #5

3

M

400

VAC

37.00

202 P-280B-E-6001-6

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-6

Lean Amine Cooler (Train B) #6

3

M

400

VAC

37.00

203 P-280B-E-6001-7

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-7

Lean Amine Cooler (Train B) #7

3

M

400

VAC

37.00

204 P-280B-E-6001-8

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-8

Lean Amine Cooler (Train B) #8

3

M

400

VAC

37.00

205 P-280B-P-3003-01/02

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3003

Rich Amine Pump-A at AGE Absorber (Train B)

3

M

400

VAC

110.00

206 P-280B-P-4003-01/02

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4003

Rich Amine Pump-B at AGE Absorber (Train B)

3

M

400

VAC

110.00

207 P-280B-P-6003-01/02

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6003

Rich Amine Pump-C at AGE Absorber (Train B)

3

M

400

VAC

110.00

208 P-280B-P-3006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3006

Sour Water Pump-A (Train B)

3

M

400

VAC

15.00

31 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

209 P-280B-P-4006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4006

Sour Water Pump-B (Train B)

3

M

400

VAC

15.00

210 P-280B-P-6006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6006

Sour Water Pump-C (Train B)

3

M

400

VAC

15.00

211 P-290-P-9002 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9002A

Sulfur Transfer Pump A

3

M

400

VAC

2.20

212 P-290-P-9002 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9002B

Sulfur Transfer Pump B

3

M

400

VAC

2.20

213 P-290-CA-9001 A

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

290-CA-9001A

Claus Air Blower A Auxiliary Load

3

M

400

VAC

7.50

214 P-290-CA-9001 B

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

290-CA-9001B

Claus Air Blower B Auxiliary Load

3

M

400

VAC

7.50

215 P-290-P-9001 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9001A

Sour Condensate Pump A

3

M

400

VAC

2.20

216 P-290-P-9001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9001B

Sour Condensate Pump B

3

M

400

VAC

2.20

Volt

kW

Sulfur Recovery Unit

32 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

217 P-290-P-9003 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9003A

Sulfur Handling Pump A

3

M

400

VAC

11.00

218 P-290-P-9003 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9003B

Sulfur Handling Pump B

3

M

400

VAC

11.00

219 P-290-P-9011 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9011A

LP Condensate Pump A

3

M

400

VAC

11.00

220 P-290-P-9011 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9011B

LP Condensate Pump B

3

M

400

VAC

11.00

221 P-310-P-9001 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9001A

Quench Water Pump-A

3

M

400

VAC

75.00

222 P-310-P-9001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9001B

Quench Water Pump-B

3

M

400

VAC

75.00

223 P-310-P-9002 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9002A

Wash Water Pump-A at TGU Absorber

3

M

400

VAC

11.00

224 P-310-P-9002 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9002B

Wash Water Pump-B at TGU Absorber

3

M

400

VAC

11.00

Volt

kW

Tail Gas Unit (TGU)

33 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

225 P-310-P-9003 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9003A

Rich Amine Pump-A at TGU Absorber

3

M

400

VAC

75.00

226 P-310-P-9003 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9003B

Rich Amine Pump-B at TGU Absorber

3

M

400

VAC

75.00

227 P-310-P-9004

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9004

Sour Water Drain Return Pump

3

M

400

VAC

2.20

228 P-310-E-9002-1

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-E-9002-1

Quench Water Air Cooler #1

3

M

400

VAC

30.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-E-9002-2

Quench Water Air Cooler #2

3

M

400

VAC

30.00

230 P-410-P-9001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9001A

BFW Transfer Pump-A

3

M

400

VAC

30.00

231 P-410-P-9001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9001B

BFW Transfer Pump-B

3

M

400

VAC

30.00

232 P-410-P-9003 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9003A

Steam Condensate Pump A

3

M

400

VAC

11.00

229 P-310-E-9002-2

Volt

kW

Boiler Feed Water (BFW)

34 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

233 P-410-P-9003 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9003B

Steam Condensate Pump B

3

M

400

VAC

11.00

234 P-410-P-9004 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9004A

Blowdown Pump A

3

M

400

VAC

18.50

235 P-410-P-9004 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9004B

Blowdown Pump B

3

M

400

VAC

18.50

236 P-410-P-9005 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9005A

LP BFW Pump A

3

M

400

VAC

37.00

237 P-410-P-9005 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9005B

LP BFW Pump B

3

M

400

VAC

37.00

238 P-410-E-9001-1

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9001-1

Steam Condenser Fan-1

3

M

400

VAC

11.00

239 P-410-E-9001-2

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9001-2

Steam Condenser Fan-2

3

M

400

VAC

11.00

240 P-410-TK-9002

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-TK-9002

Oxygen Scavenger Tank Mixer Motor

3

M

400

VAC

0.75

241 P-410-TK-9003

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-TK-9003

Neutralization Amine Tank Mixer Motor

3

M

400

VAC

0.75

35 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

242 P-410-TK-9004

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-TK-9004

Phosphate Solution Tank Mixer Motor

3

M

400

VAC

0.75

243 P-410-P-9008 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9008A

Oxygen Scavenger Pump Motor-A

3

M

400

VAC

0.75

244 P-410-P-9008 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9008B

Oxygen Scavenger Pump Motor-B

3

M

400

VAC

0.75

245 P-410-P-9009 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9009A

Neutralization Amine Pump Motor-A

3

M

400

VAC

1.10

246 P-410-P-9009 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9009B

Neutralization Amine Pump Motor-B

3

M

400

VAC

1.10

247 P-410-P-9010 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9010A

Phosphate Solution Pump Motor A

3

M

400

VAC

0.75

248 P-410-P-9010 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9010B

Phosphate Solution Pump Motor B

3

M

400

VAC

0.75

249 P-410-E-9002-1

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9002-1

Deaerator Steam Condenser Motor 1

3

M

400

VAC

30.00

250 P-410-E-9001-2

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9002-2

Deaerator Steam Condenser Motor 2

3

M

400

VAC

30.00

36 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

251 P-450-P-9004 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

450-P-9004 A

Raw Water Feed Pump A

3

M

400

VAC

45.00

252 P-450-P-9004 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

450-P-9004B

Raw Water Feed Pump B

3

M

400

VAC

45.00

253 P-460-P-9001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9001A

AGE Off-Gas K.O. Drum Pump-A

3

M

400

VAC

5.50

254 P-460-P-9001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9001B

AGE Off-Gas K.O. Drum Pump-B

3

M

400

VAC

5.50

255 P-460-P-9002 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9002A

TGU Off-Gas K.O. Drum Pump-A

3

M

400

VAC

5.50

256 P-460-P-9002 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9002B

TGU Off-Gas K.O. Drum Pump-B

3

M

400

VAC

5.50

257 P-460-EA-9001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001A

Thermal Oxidizer Air Blower A Auxiliary Load

3

M

400

VAC

11.00

Volt

kW

Water Treating

Thermal Oxidizer Unit

37 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

258 P-460-EA-9001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001B

Thermal Oxidizer Air Blower B Auxiliary Load

3

M

400

VAC

11.00

259 P-460-EA-9001 C

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001C

Thermal Oxidizer Air Blower C Auxiliary Load

3

M

400

VAC

11.00

260 P-460-EA-9001 D

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001D

Thermal Oxidizer Air Blower D Auxiliary Load

3

M

400

VAC

11.00

261 P-460-EA-9001 E

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001E

Thermal Oxidizer Air Blower E Auxiliary Load

3

M

400

VAC

11.00

262 P-470-P-9013 A-01/02

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

470-P-9013 A

HP Flare Knockout Drum Condensate Pump A

3

M

400

VAC

90.00

263 P-470-P-9013 B-01/02

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

470-P-9013 B

HP Flare Knockout Drum Condensate Pump B

3

M

400

VAC

90.00

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

475-P-9014 A

LP Flare Knockout Drum Condensate Pump A

3

M

400

VAC

75.00

Volt

kW

HP Flare System

LP Flare System 264 P-475-P-9014 A

38 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

475-P-9014 B

LP Flare Knockout Drum Condensate Pump B

3

M

400

VAC

75.00

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

480-P-9015

Diesel Pump

3

M

400

VAC

5.50

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

490-P-9008

Firewater Jockey Pump

3

M

400

VAC

18.50

268 P-510-P-9001

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

510-P-9001

Close Drain Pump

3

M

400

VAC

37.00

269 P-520-P-9001

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

520-P-9001

Open Drain Pump

3

M

400

VAC

5.50

265 P-475-P-9014 B

Volt

kW

Diesel Fuel 266 P-480-P-9015

Fire Water System 267 P-490-P-9008

Open and Close Drain System

GENERATOR DEG - Emergency Generator

39 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

420-V-9001

Emergency Generator

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

3

F

400

VAC

536

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-BCH-5001

Battery Charger Emergency Diesel Generator

3

F

400

VAC

2.20

211-V-9007

Backup Generator Well Pad Central

211-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad Central

3

F

400

VAC

240.00

211-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad Central

211-BCH-5001

Battery Charger Backup Diesel Generator Well Pad Central

3

F

400

VAC

2.20

211-TRF-0001

11 / 0.4 kV Central Well Pad Transformer

211-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad Central

3

F

400

VAC

160

212-V-9006

Backup Generator Well Pad East

212-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad East

3

F

400

VAC

240.00

212-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad East

212-BCH-5001

Battery Charger Backup Diesel Generator Well Pad East

3

F

400

VAC

2.20

270 P-420-V-9001-01/02/03

271 P-420-BCH-5001

Power

Volt

kW

Backup Generator - Well Pad Central 272 P-211-V-9007-01/02

273 P-211-BCH-5001

274 P-211-TRF-0002-01/02

Backup Generator - Well Pad East 275 P-212-V-9006-01/02/03

276 P-212-BCH-5001

40 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

212-TRF-0001

11 /0.42 kV East Well Pad Transformer

212-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad East

3

F

400

VAC

160

800-SWG/MCC-0002

400 VAC Switchgear/MCC Infrastructure

800-BCH-5001

Battery Charger Backup Diesel Generator Infrastructure

3

F

400

VAC

2.20

710-V-9003

Backup Generator Sales Gas Metering Station

710-SWG/MCC-0002

400 VAC Switchgear/MCC Sales Gas Metering Station

3

F

400

VAC

100.00

280 P-710-BCH-5001

710-SWG/MCC-0002

400 VAC Switchgear/MCC Sales Gas Metering Station

710-BCH-5001

Battery Charger Backup Diesel Generator Sales Gas Metering

3

F

400

VAC

2.20

281 P-710-TRF-0002

710-TRF-0001

11 / 0.42 kV Transformer Sales Gas Metering

410-SWG/MCC-0002

400 VAC Switchgear/MCC Sales Gas Metering Station

3

F

400

VAC

100.00

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1003

STG-A Lube Oil Clarifier Driver

3

M

400

VAC

1.50

277 P-212-TRF-0002

Volt

kW

Backup Generator - Infrastructure 278 P-800-BCH-5001

Backup Generator - Sales Gas Metering Station 279 P-710-V-9003

STG A - Main Generator A 282 P-420-P-1003

41 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

283 P-420-P-1001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1001A

STG-A Lube Oil Pump Driver-A

3

M

400

VAC

30.00

284 P-420-P-1001 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1001B

STG-A Lube Oil Pump Driver-B

3

M

400

VAC

30.00

285 P-420-P-1002 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1002A

STG-A Lube Oil Tank Mist SeparatorA

3

M

400

VAC

4.00

286 P-420-P-1002 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1002B

STG-A Lube Oil Tank Mist SeparatorB

3

M

400

VAC

4.00

287 P-420-P-1004

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1004

STG-A Jacking Oil Oump Driver

3

M

400

VAC

1.50

288 P-420-P-1005

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1005

STG-A Bearing Gear Driver

3

M

400

VAC

4.00

289 P-420-P-2003

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2003

STG-B Lube Oil Clarifier Driver

3

M

400

VAC

1.50

290 P-420-P-2001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2001A

STG-B Lube Oil Pump Driver-A

3

M

400

VAC

30.00

Volt

kW

STG B - Main Generator B

42 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

291 P-420-P-2001 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2001B

STG-B Lube Oil Pump Driver-B

3

M

400

VAC

30.00

292 P-420-P-2002 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2002A

STG-B Lube Oil Mist Separator-A

3

M

400

VAC

4.00

293 P-420-P-2002 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2002B

STG-B Lube Oil Mist Separator-B

3

M

400

VAC

4.00

294 P-420-P-2004

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2004

STG-B Jacking Oil Oump Driver

3

M

400

VAC

1.50

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2005

STG-B Bearing Gear Driver

3

M

400

VAC

4.00

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-E-4001

Radiator Fan Essential Generator

3

M

400

VAC

11.00

297 P-420-DPN-4001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DPN-4001

LCP Power Essential Generator

3

F

400

VAC

18.25

298 P-420-BCH-4001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-BCH-4001

Battery Charger Essential Generator

3

F

400

VAC

2.00

295 P-420-P-2005

Volt

kW

GEG+DEG - Essential Generator 296 P-420-E-4001

43 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Transformer Rectifier Unit (TRU) for Cathodic Protection 299 P-610-TRU-9001

420-SWG/MCC-0003

Main LV SWGR/MCC Substation-1 (Power Generation)

610-TRU-9001

Transformer Rectifier Unit (GPF Underground Pipeline)-1

3

F

400

VAC

3.50

300 P-620-TRU-9001

420-SWG/MCC-0003

Main LV SWGR/MCC Substation-1 (Power Generation)

620-TRU-9001

Transformer Rectifier Unit (GPF Underground Pipeline)-2

3

F

400

VAC

3.50

301 P-630-TRU-9001

420-SWG/MCC-0003

Main LV SWGR/MCC Substation-1 (Power Generation)

630-TRU-9001

Transformer Rectifier Unit (Sales Gas Metering Underground Pipeline)

3

F

400

VAC

3.50

420-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

64.00

SUBSTATION-1 (POWER GENERATION) 302 P-420-AC-UPS-0001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

303 P-420-AC-UPS-0001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

420-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

64.00

304 P-420-AC-UPS-0001 C

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

64.00

305 P-420-DC-UPS-0001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

13.78

44 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

306 P-420-DC-UPS-0001 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

13.78

307 P-420-HVAC-9001

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

420-HVAC-9001

HVAC Package for Substation-1

3

F

400

VAC

113.20

308 P-420-HVAC-9002

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-9002

HVAC Package for Substation-1

3

F

400

VAC

27.00

309 P-420-HVAC-9003

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-9003

HVAC Package for Substation-1

3

F

400

VAC

27.00

310 P-420-HVAC-9004

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

420-HVAC-9004

HVAC Package for Substation-1

3

F

400

VAC

27.00

311 P-420-HVAC-6010

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

420-HVAC-6010

HVAC Auxiliary for Substation 1

3

F

400

VAC

32.20

312 P-420-DPN-0001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DPN-0001

Distribution Panel Indoor Lighting Substation-1

3

F

400

VAC

14.00

313 P-420-DPN-0002

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

420-DPN-0002

Distribution Panel Outdoor Lighting Substation-1

3

F

400

VAC

46.00

45 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-1

3

F

400

VAC

7.20

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

900-WLO-001

Welding Receptacle #1

3

F

400

VAC

13.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

900-WLO-002

Welding Receptacle #2

3

F

400

VAC

13.00

Equipment Tag No.

Description

314 P-420-DPE-0001

315 P-900-WLO-001

316 P-900-WLO-002

Power

Volt

kW

SUBSTATION-2 (TRAIN A AREA) 317 P-231-AC-UPS-0001 A

231-SWG/MCC-0003

Main LV Switchgear/MCC Substation-2 (Train-A)

231-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

40.00

318 P-231-AC-UPS-0001 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

40.00

319 P-231-AC-UPS-0001 C

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

40.00

320 P-231-DC-UPS-0001 A

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

10.92

46 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

321 P-231-DC-UPS-0001 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

10.92

322 P-231-HVAC-9001-01/02

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9001

HVAC package for Substation 2

3

F

400

VAC

146.70

323 P-231-HVAC-9002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9002

HVAC package for Substation 2

3

F

400

VAC

34.00

324 P-231-HVAC-9003

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9003

HVAC package for Substation 2

3

F

400

VAC

34.00

325 P-231-HVAC-9004

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9004

HVAC package for Substation 2

3

F

400

VAC

34.00

326 P-231-HVAC-6010

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-6010

HVAC Auxiliary for Substation 2

3

F

400

VAC

45.00

327 P-231-DPN-0001

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DPN-0001

Distribution Panel Indoor Lighting Substation-2

3

F

400

VAC

11.90

328 P-231-DPN-0002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DPN-0002

Distribution Panel Outdoor Lighting Substation-2

3

F

400

VAC

93.30

47 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-2

3

F

400

VAC

12.50

330 P-900-WLO-003

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-003

Welding Receptacle #3

3

F

400

VAC

13.00

331 P-900-WLO-004

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-004

Welding Receptacle #4

3

F

400

VAC

13.00

332 P-900-WLO-007

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-007

Welding Receptacle #7

3

F

400

VAC

13.00

333 P-900-WLO-008

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-008

Welding Receptacle #8

3

F

400

VAC

13.00

Equipment Tag No.

Description

329 P-231-DPE-0001

Volt

kW

SUBSTATION-3 (TRAIN-B AREA) 334 P-280-AC-UPS-0001 A

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

32.00

335 P-280-AC-UPS-0001 B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

32.00

336 P-280-AC-UPS-0001 C

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

32.00

48 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

337 P-280-DC-UPS-0001 A

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

8.06

338 P-280-DC-UPS-0001 B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

8.06

339 P-290-HVAC-9001A-01/02

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-9001A

HVAC package for Substation 3

3

F

400

VAC

224.20

340 P-290-HVAC-9001B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-9001B

HVAC package for Substation 3

3

F

400

VAC

71.00

341 P-290-HVAC-9001B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-9001B

HVAC package for Substation 3

3

F

400

VAC

71.00

342 P-290-HVAC-6010

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-6010

HVAC Auxiliary for Substation 3

3

F

400

VAC

83.00

343 P-280-DPN-0001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DPN-0001

Distribution Panel Indoor Lighting Substation-3

3

F

400

VAC

9.80

49 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

344 P-280-DPN-0002

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DPN-0002

Distribution Panel Outdoor Lighting Substation-3

3

F

400

VAC

58.00

345 P-280-DPE-0001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-3

3

F

400

VAC

15.00

346 P-900-WLO-005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

900-WLO-005

Welding Receptacle #5

3

F

400

VAC

13.00

347 P-900-WLO-006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

900-WLO-006

Welding Receptacle #6

3

F

400

VAC

13.00

Volt

kW

SUBSTATION-4 (UTILITY AREA) 348 P-480-AC-UPS-0001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

32.00

349 P-480-AC-UPS-0001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

32.00

350 P-480-AC-UPS-0001 C

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

32.00

50 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

351 P-480-DC-UPS-0001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

5.46

352 P-480-DC-UPS-0001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

5.46

353 P-480-HVAC-9001A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-9001A

HVAC package for Substation 4

3

F

400

VAC

112.70

354 P-480-HVAC-9001B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-9001B

HVAC package for Substation 4

3

F

400

VAC

34.00

355 P-480-HVAC-9001C

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-9001C

HVAC package for Substation 4

3

F

400

VAC

34.00

356 P-480-HVAC-9003

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-6010

HVAC Auxiliary for Substation 4

3

F

400

VAC

45.00

357 P-480-DPN-0001

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DPN-0001

Distribution Panel Indoor Lighting Substation-4

3

F

400

VAC

8.00

358 P-480-DPN-0002

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DPN-0002

Distribution Panel Outdoor Lighting Substation-4

3

F

400

VAC

57.35

51 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

359 P-480-DPE-0001

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-4

3

F

400

VAC

5.60

Equipment Tag No.

Description

480-SWG/MCC-0002

Volt

kW

INSTRUMENT BUILDING (280B-B-9001) 360 P-280A-HVAC-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-9001

HVAC package for Instrument Building Train-A

3

F

400

VAC

27.00

361 P-280A-HVAC-9002

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-9002

HVAC package for Instrument Building Train-A

3

F

400

VAC

27.00

362 P-280A-HVAC-9003

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-9003

HVAC package for Instrument Building Train-A

3

F

400

VAC

27.00

363 P-280A-HVAC-6010

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-6010

HVAC Aux for Instrument Building Train-A

3

F

400

VAC

86.00

364 P-280B-HVAC-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-9001

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

365 P-280B-HVAC-9002

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-9002

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

52 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

366 P-280B-HVAC-9003

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-9003

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

367 P-280B-HVAC-6010

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-6010

HVAC Aux for Instrument Building Train-B

3

F

400

VAC

86.00

368

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

HOLD (NOTE-5)

Instrument Panel (Train-A)

3

F

400

VAC

20.00

369

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

HOLD (NOTE-5)

Instrument Panel (Train-B)

3

F

400

VAC

20.00

370 P-280A-LPN-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-A)

280A-LPN-9001

Distribution Panel Indoor Lighting & Small Power Instrument Building 280A

3

F

400

VAC

2.10

371 P-280B-LPN-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-LPN-9001

Distribution Panel Indoor Lighting & Small Power Instrument Building 280B

3

F

400

VAC

2.10

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-AC-UPS-0001 A

230 VAC UPS System - Feeder A Control Room

3

F

400

VAC

48.00

Volt

kW

CONTROL BUILDING 372 P-450-AC-UPS-0001 A

53 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

373 P-450-AC-UPS-0001 B

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-AC-UPS-0001 B

230 VAC UPS System - Feeder B Control Room

3

F

400

VAC

48.00

374 P-450-AC-UPS-0001 C

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass Control Room

3

F

400

VAC

48.00

375 P-450-HVAC-9001

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-9001

AHU DX

3

F

400

VAC

11.00

376 P-450-HVAC-9002

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-9002

AHU DX

3

F

400

VAC

2.20

377 P-450-HVAC-6010

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-6010

Air Conditioner Cassette Type (Total = 14 unit)

3

F

400

VAC

29.35

378 P-450-HVAC-6020

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-6020

Electric Duct Heater

3

F

400

VAC

106.03

379 P-450-HVAC-6030

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-6030

AC Auxiliary

3

F

400

VAC

6.30

380 P-900-LPN-4103

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

900-LPN-4103

Lighting (Indoor Control Room)

3

F

400

VAC

30.20

54 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

INFRASTRUCTURE SUBSTATION INFRASTRUCTURE 381 P-800-AC-UPS-0001 A

800-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

800-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

40.00

382 P-800-AC-UPS-0001 B

800-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

800-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

40.00

383 P-800-AC-UPS-0001 C

800-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

800-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

40.00

384 P-800-HVAC-1001

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-HVAC-1001

HVAC package for Infrastructure Substation

3

F

400

VAC

34.00

385 P-800-HVAC-1002

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-HVAC-1002

HVAC package for Infrastructure Substation

3

F

400

VAC

34.00

386 P-800-HVAC-1003

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-HVAC-1003

HVAC package for Infrastructure Substation

3

F

400

VAC

34.00

387 P-800-HVAC-6010

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-HVAC-6010

HVAC Auxiliary for Infrastructure Substation

3

F

400

VAC

45.00

55 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9021-01

Distribution Panel Indoor Lighting & Small Power Infrastructure Substation

3

F

400

VAC

6.20

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9021-02

Distribution Panel Outdoor Lighting Infrastructure Substation

3

F

400

VAC

41.25

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9021-03

Distribution Panel Emergency Lighting Infrastructure Substation

3

F

400

VAC

10.80

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9001A-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

900-DPN-9001B-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

900-DPN-9001C-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

3

F

400

VAC

3.80

3

F

400

VAC

3.60

Equipment Tag No.

Description

388 P-900-DPN-9021-01

389 P-900-DPN-9021-02

390 P-900-DPN-9021-03

Power

Volt

kW

Buildings Lighting and Socket Outlet Distribution Board 1

900-DPN-9001A-01

2

900-DPN-9001B-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

3

900-DPN-9001C-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9001D-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

900-DPN-9002-01

Distribution Panel Indoor Lighting & Small Power Guard House Building

4

900-DPN-9001D-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

5

900-DPN-9002-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

56 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

900-DPN-9003-01

Distribution Panel Indoor Lighting & Small Power Security Gate House

3

F

400

VAC

3.20

900-DPN-9004-01

Distribution Panel Indoor Lighting Administration Building

3

F

400

VAC

12.40

3

F

400

VAC

35.00

Volt

kW

6

P-900-DPN-9003-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

7

P-900-DPN-9004-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9004-02

Distribution Panel Small Power Administration Building

900-DPN-9004-03

Distribution Panel Indoor Lighting & Small Power Telcom Building

3

F

400

VAC

3.80

3

F

400

VAC

2.80

8

P-900-DPN-9004-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

9

P-900-DPN-9004-03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-01

Distribution Panel Indoor Lighting Fire Emegency Station

900-DPN-9005-02

Distribution Panel Small Power Fire Emegency Station

3

F

400

VAC

9.50

3

F

400

VAC

10.00

10

P-900-DPN-9005-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

11

P-900-DPN-9005-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-03

Distribution Panel Indoor Lighting Office Building

900-DPN-9005-04

Distribution Panel Small Power Office Building

3

F

400

VAC

44.50

900-DPN-9005-05

Distribution Panel Indoor Lighting Laboratory Building

3

F

400

VAC

7.35

12

P-900-DPN-9005-03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

13

P-900-DPN-9005-04

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

14

P-900-DPN-9005-05

57 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

900-DPN-9005-06

Distribution Panel Small Power Laboratory Building

3

F

400

VAC

21.00

900-DPN-9007-01

Distribution Panel Lighting & Small Power Mosque

3

F

400

VAC

8.00

3

F

400

VAC

6.20

Volt

kW

15

P-900-DPN-9005-06

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

16

P-900-DPN-9007-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9009-01

Distribution Panel Indoor Lighting Kitchen & Dining Hall

900-DPN-9009-02

Distribution Panel Indoor Lighting Kitchen & Dining Hall

3

F

400

VAC

11.00

3

F

400

VAC

6.40

17

P-900-DPN-9009-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

18

P-900-DPN-9009-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9011-01

Distribution Panel Lighting & Small Power Laundry Center Building

900-DPN-9011-02

Distribution Panel Indoor Lighting Medical Center Building

3

F

400

VAC

8.00

3

F

400

VAC

12.00

19

P-900-DPN-9011-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

20

P-900-DPN-9011-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9011-03

Distribution Panel Small Power Medical Center Building

900-DPN-9012A-01

Distribution Panel Indoor Lighting Dormitory Operator & Staff

3

F

400

VAC

22.40

900-DPN-9012A-02

Distribution Panel Small Power Dormitory Operator & Staff

3

F

400

VAC

99.00

21

P-900-DPN-9011-03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

22

P-900-DPN-9012A-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

23

P-900-DPN-9012A-02

58 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

900-DPN-9012B-01

Distribution Panel Indoor Lighting Dormitory Field Superintendent

3

F

400

VAC

12.82

900-DPN-9012B-02

Distribution Panel Small Power Dormitory Field Superintendent

3

F

400

VAC

54.50

3

F

400

VAC

20.00

Volt

kW

24

P-900-DPN-9012B-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

25

P-900-DPN-9012B-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9013-01

Distribution Panel Indoor Lighting Sport Hall & Multipurpose Building

900-DPN-9013-02

Distribution Panel Small Power Sport Hall & Multipurpose Building

3

F

400

VAC

60.50

3

F

400

VAC

30.00

26

P-900-DPN-9013-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

27

P-900-DPN-9013-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9014-01

Distribution Panel Indoor Lighting Operation Warehouse Building

900-DPN-9014-02

Distribution Panel Small Power Operation Warehouse Building

3

F

400

VAC

31.50

3

F

400

VAC

1.70

28

P-900-DPN-9014-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

29

P-900-DPN-9014-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9015-01

Distribution Panel Indoor Lighting & Small Power Vehicle Fuel Station Shelter

900-DPN-9016-01

Distribution Panel Indoor Lighting Operation Maintenance Building

3

F

400

VAC

38.00

900-DPN-9016-02

Distribution Panel Small Power Operation Maintenance Building

3

F

400

VAC

39.00

30

P-900-DPN-9015-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

31

P-900-DPN-9016-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

32

P-900-DPN-9016-02

59 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

33

P-900-DPN-9017-01

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

400VAC Switchgear/MCC Infrastructure

900-DPN-9017-01

Distribution Panel Indoor Lighting & Small Power Chemical Storage Building

3

F

400

VAC

20.00

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9001

Distribution Panel Air Conditioning Guard House

3

F

400

VAC

3.54

900-HVAC-9002A

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

900-HVAC-9002B

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

3

F

400

VAC

7.06

Equipment Tag No.

Description

800-SWG/MCC-0002

Volt

kW

Buildings Air Conditioned Distribution Board 34

P-900-HVAC-9001

35

P-900-HVAC-9002A

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

36

P-900-HVAC-9002B

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9002C

Distribution Panel Air Conditioning Gate House

900-HVAC-9002D

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

3

F

400

VAC

10.66

3

F

400

VAC

28.90

37

P-900-HVAC-9002C

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

38

P-900-HVAC-9002D

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9003

Distribution Panel Air Conditioning Security Gate House

900-HVAC-9004

Distribution Panel Air Conditioning Telcom Building

39

P-900-HVAC-9003

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

40

P-900-HVAC-9004

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

60 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

900-HVAC-9005

Distribution Panel Air Conditioning Fire Emergency Station

3

F

400

VAC

32.00

900-HVAC-9007

Distribution Panel Air Conditioning Mosque

3

F

400

VAC

58.00

3

F

400

VAC

93.73

Volt

kW

41

P-900-HVAC-9005

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

42

P-900-HVAC-9007

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9008

Distribution Panel Air Conditioning Administration Building

900-HVAC-9009

Distribution Panel Air Conditioning Kitchen & Dinning Hall Building

3

F

400

VAC

34.85

3

F

400

VAC

23.98

43

P-900-HVAC-9008-01/02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

44

P-900-HVAC-9009

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9010

Distribution Panel Air Conditioning Medical Center Building

900-HVAC-9011

Distribution Panel Air Conditioning Laundry Center Building

3

F

400

VAC

19.00

3

F

400

VAC

21.51

45

P-900-HVAC-9010

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

46

P-900-HVAC-9011

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9012A

Distribution Panel Air Conditioning Dormitory Operator & Staff

900-HVAC-9012B

Distribution Panel Air Conditioning Dormitory Field Superintendent

3

F

400

VAC

11.52

900-HVAC-9013

Distribution Panel Air Conditioning Sport Hall & Multipurposed Building

3

F

400

VAC

50.63

47

P-900-DPN-9012A

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

48

P-900-DPN-9012B

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

49

P-900-HVAC-9013

61 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

900-HVAC-9014

Distribution Panel Air Conditioning Operation Warehouse Building

3

F

400

VAC

66.68

900-HVAC-9016

Distribution Panel Air Conditioning Operation Maintenance Building

3

F

400

VAC

42.27

3

F

400

VAC

53.65

Volt

kW

50

P-900-HVAC-9014-01/02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

51

P-900-HVAC-9016-01/02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9017

Distribution Panel Air Conditioning Chemical Storage Building

900-HVAC-9016

Distribution Panel Air Conditioning Operation Warehouse Building

3

F

400

VAC

66.68

3

F

400

VAC

37.74

52

P-900-HVAC-9017-01/02/03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

53

P-900-HVAC-9016-01/02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9019

Distribution Panel Air Conditioning Office Building

54

P-900-HVAC-9019

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

55

P-900-HVAC-9020

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9020

Distribution Panel Air Conditioning Laboratory Building

3

F

400

VAC

40.08

CENTRAL WELL PAD 56

P-211-P-9001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-P-9001

Potable Water Pump

3

M

400

VAC

0.37

57

P-211-P-9004

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-P-9004

Close Drain Pump

3

M

400

VAC

18.50

62 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

58

P-211-UPS-0001 A

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

24.00

59

P-211-UPS-0001 B

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

24.00

60

P-211-UPS-0001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-UPS-0001

230 VAC UPS System - Bypass

3

F

400

VAC

24.00

61

P-211-HVAC-9001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-9001

HVAC package for Central Wellpad Substation

3

F

400

VAC

27.00

62

P-211-HVAC-9002

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-9002

HVAC package for Central Wellpad Substation

3

F

400

VAC

27.00

63

P-211-HVAC-9003

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-9003

HVAC package for Central Wellpad Substation

3

F

400

VAC

27.00

64

P-211-HVAC-6010

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-6010

HVAC Auxiliry for Central Wellpad Substation

3

F

400

VAC

33.00

63 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

65

P-211-DPN-0001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPN-0001

Flare Package

3

F

400

VAC

3.00

66

P-211-DPN-0002

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPN-0002

Distribution Panel Outdoor Lighting Central Wellpad

3

F

400

VAC

24.22

67

P-211-DPN-0003

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPN-0003

Distribution Panel Indoor Lighting Central Wellpad

3

F

400

VAC

3.70

68

P-211-DPE-0001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPE-0001

Distribution Panel Emergency Outdoor Lighting Central Wellpad

3

F

400

VAC

7.27

EAST WELL PAD 69

P-212-P-9001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-P-9001

Potable Water Pump

3

M

400

VAC

0.37

70

P-212-P-9004

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-P-9004

Close Drain Pump

3

M

400

VAC

45.00

71

P-212-UPS-1004 A

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-UPS-1004 A

230 VAC UPS System - Feeder A

3

F

400

VAC

24.00

64 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

72

P-212-UPS-1004 B

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-UPS-1004 B

230 VAC UPS System - Feeder B

3

F

400

VAC

24.00

73

P-212-UPS-1004

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-UPS-1004

230 VAC UPS System - Bypass

3

F

400

VAC

24.00

74

P-212-HVAC-9001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-9001

HVAC package for East Wellpad Substation

3

F

400

VAC

27.00

75

P-212-HVAC-9002

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-9002

HVAC package for East Wellpad Substation

3

F

400

VAC

27.00

76

P-212-HVAC-9003

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-9003

HVAC package for East Wellpad Substation

3

F

400

VAC

27.00

77

P-212-HVAC-6010

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-6010

HVAC package for East Wellpad Substation

3

F

400

VAC

33.00

78

P-212-DPN-1001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPN-1001

Flare Package

3

F

400

VAC

3.00

79

P-212-DPN-1002

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPN-1002

Distribution Panel Outdoor Lighting East Wellpad

3

F

400

VAC

36.00

65 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

80

P-212-DPN-1003

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPN-1003

Distribution Panel Indoor Lighting East Wellpad

3

F

400

VAC

3.70

81

P-212-DPE-0001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPE-0001

Distribution Panel Emergency Outdoor Lighting East Wellpad

3

F

400

VAC

9.60

SALES GAS METERING STATION 82

P-710-P-9001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-P-9001

Potable Water Pump

3

M

400

VAC

0.37

83

P-710-V-9004

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-V-9004

Instrument Air Compressor

3

M

400

VAC

11.00

84

P-710-AC-UPS-1001 A

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-AC-UPS-1001 A

Gas Metering 230VAC UPS System Feeder A

3

F

400

VAC

24.00

85

P-710-AC-UPS-1001 B

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-AC-UPS-1001 B

Gas Metering 230VAC UPS System Feeder B

3

F

400

VAC

24.00

86

P-710-AC-UPS-1001 C

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-AC-UPS-1001 C

Gas Metering 230VAC UPS System Bypass

3

F

400

VAC

24.00

66 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

87

P-710-HVAC-7101

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-HVAC-7101

Metering Station Building HVAC

3

F

400

VAC

5.20

88

P-710-HVAC-7102

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-HVAC-7102

Metering Station Building HVAC

3

F

400

VAC

5.20

89

P-710-HVAC-7103

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-HVAC-7103

Metering Station Building HVAC

3

F

400

VAC

5.20

90

P-710-HVAC-6010

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-HVAC-6010

Metering Station Building HVAC Auxiliary

3

F

400

VAC

5.20

91

P-710-DPN-1003

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-DPN-1003

Distribution Panel Indoor Lighting East Wellpad

3

F

400

VAC

16.43

92

P-710-DPN-2001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-SO-001

Metering Station Building Socket Outlet

3

F

400

VAC

5.00

93

P-710-DPN-1002

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-DPN-1002

Distribution Panel Indoor Lighting East Wellpad

3

F

400

VAC

29.00

94

P-710-DPE-0001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-DPE-0001

Distribution Panel Emergency Outdoor Lighting East Wellpad

3

F

400

VAC

7.00

67 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

95

P-710-LPR-1001

D

230 V POWER CABLES

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-SO-002

Metering Station Welding Outlet

3

F

400

VAC

13.00

(NOTE-4)

Motor Space Heater (Continuous) GPF (Qty=73 ea)

1

M

230

VAC

0.23

(NOTE-4)

Motor Space Heater (Intermittent) GPF (Qty=6 ea)

1

M

230

VAC

0.23

(NOTE-4)

Motor Space Heater (Stand-by) GPF (Qty=105 ea)

1

M

230

VAC

0.23

211-SH-1001

Space Heater for Close Drain Pump Central Wellpad

1

M

230

VAC

0.20

Volt

kW

Space Heater 1

(NOTE-4)

420-SWG/MCC-0004

2

(NOTE-4)

420-SWG/MCC-0004

3

(NOTE-4)

420-SWG/MCC-0004

4

P-211-SH-1001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation)

68 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

5

P-212-SH-1001

420-SWG/MCC-0004

6

P-420-SH-1011

420-SWG/MCC-0004

7

P-420-SH-2011

420-SWG/MCC-0004

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

212-SH-1001

Space Heater for Close Drain Pump East Wellpad

1

M

230

VAC

0.20

420-SH-1011

STG-A Space Heater

1

M

230

VAC

2.25

420-SH-2011

STG-B Space Heater

1

M

230

VAC

2.25

Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation)

Volt

kW

230VAC UPS SUBSTATION-1 (POWER GENERATION) 8

P-420-UCP-SG-0001A

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-UCP-SG-0001A

UCP STG-A

1

F

210

VAC

1.00

9

P-420-BCH-1001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-BCH-1001

Battery Charger STG-A

1

F

210

VAC

1.00

10

P-420-UCP-4001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-UCP-4001

UCP Essential Generator

1

F

210

VAC

1.00

11

P-420-BCH-4001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-BCH-4001

Battery Charger Essential Generator

1

F

210

VAC

1.00

12

P-420-VCB-0001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-VCB-0001

Motor Charging VCB for 420-SWG-0001

1

M

210

VAC

1.80

69 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

13

P-420-VCB-0002

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-VCB-0002

Motor Charging VCB for 420-SWG-0002

1

M

210

VAC

3.00

Volt

kW

14

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O

1

F

210

VAC

0.50

15

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

1.00

16

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

ECMS NETWORK SERVER

1

F

210

VAC

1.00

17

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

ECMS PRINTER

1

F

210

VAC

0.50

18

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

LCP STG-A

1

F

210

VAC

1.00

19

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O

1

F

210

VAC

0.70

20

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O

1

F

210

VAC

0.20

21

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

LOAD SHEDDING PANEL-A

1

F

210

VAC

1.00

70 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

22

P-420-DPE-0002

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-1

1

F

210

VAC

7.20

Equipment Tag No.

Description

Volt

kW

23

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

TELECOM CABINET

1

F

210

VAC

1.00

24

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

HP BOILER CABINET

1

F

210

VAC

1.00

25

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

LP BOILER CABINET

1

F

210

VAC

1.00

26

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

MAIN ECMS-A PANEL

1

F

210

VAC

1.50

27

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

28

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

FACP CABINET

1

F

210

VAC

0.50

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-UCP-SG-0001B

UCP STG-B

1

F

210

VAC

1.00

29

P-420-UCP-SG-0001B

71 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

30

P-420-BCH-2001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-BCH-2001

Battery Charger STG-B

1

F

210

VAC

1.00

31

P-420-UCP-0001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-UCP-0001

UCP Emergency Diesel Generator

1

F

210

VAC

1.00

32

P-420-BCH-5001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-BCH-5001

Battery Charger Emergency Generator

1

F

210

VAC

0.50

33

P-420-VCB-0003

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-VCB-0003

Motor Charging VCB for 420-SWG-0003

1

M

210

VAC

0.30

34

P-420-VCB-0004

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-VCB-0004

Motor Charging VCB for 420-SWG-0004

1

M

210

VAC

0.50

35

P-420-VCB-0005

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-VCB-0005

Motor Charging VCB for 420-SWG-0005

1

M

210

VAC

0.30

36

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O

1

F

210

VAC

0.50

37

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O

1

F

210

VAC

0.70

38

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O

1

F

210

VAC

0.20

72 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

39

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

ECMS OPC SERVER

1

F

210

VAC

1.00

40

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LCP STG-B

1

F

210

VAC

1.00

41

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LCP ESSENTIAL GEN

1

F

210

VAC

1.00

42

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

ECMS WORK STATION

1

F

210

VAC

1.00

43

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

ECMS NETWORK SWITCH

1

F

210

VAC

0.20

44

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LOAD SHEDDING PANEL-B

1

F

210

VAC

1.00

45

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

TELECOM CABINET

1

F

210

VAC

1.00

46

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

HP BOILER CABINET

1

F

210

VAC

1.00

47

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LP BOILER CABINET

1

F

210

VAC

1.00

73 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

48

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

MAIN ECMS-B PANEL

1

F

210

VAC

1.50

49

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

SUBSTATION-2 (TRAIN A AREA) 50

P-231-VCB-0001

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

231-VCB-0001

Motor Charging VCB : 231-SWG-0001

1

M

210

VAC

2.20

51

P-231-VCB-0002

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

231-VCB-0002

Motor Charging ACB : 231-SWG-0002

1

M

210

VAC

0.30

52

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

53

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

0.40

54

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

55

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

74 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

56

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

57

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

58

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

59

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

VRU LCP

1

F

210

VAC

0.50

60

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

61

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

RECYLE GAS COMPRESSOR LCP

1

F

210

VAC

0.50

62

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

HP/LP A FLARE LCP

1

F

210

VAC

1.00

63

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

SALES GAS COMPRESSOR LCP

1

F

210

VAC

1.00

64

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

TEG LCP

1

F

210

VAC

0.50

75 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

65

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

SRU LCP

1

F

210

VAC

0.50

66

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

TGU LCP

1

F

210

VAC

0.50

67

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

UPS DB at Instrument Building 280A-B-9001

1

F

210

VAC

3.50

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

231-VCB-0003

Motor Charging VCB : 231-SWG-0003

1

M

210

VAC

0.50

68

P-231-VCB-0003

69

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

70

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

71

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

VRU LCP

1

F

210

VAC

0.50

72

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

ECMS WORKSTATION

1

F

210

VAC

0.50

76 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

73

74

75

76

HOLD (NOTE-5)

P-231-DPE-0001 HOLD (NOTE-5)

P-231-VCB-0004

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.20

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

231-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-2

1

F

210

VAC

8.80

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

231-VCB-0004

Motor Charging VCB : 231-SWG-0004

1

M

210

VAC

0.30

Volt

kW

77

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

78

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

79

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

80

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

81

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

RECYLE GAS COMPRESSOR LCP

1

F

210

VAC

0.50

77 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

82

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

SALES GAS COMPRESSOR LCP

1

F

210

VAC

1.00

83

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

TEG LCP

1

F

210

VAC

0.50

84

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

SRU LCP

1

F

210

VAC

0.50

85

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

TGU LCP

1

F

210

VAC

0.50

SUBSTATION-3 (TRAIN-B AREA) 86

P-280-VCB-0001

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

280-VCB-0001

Motor Charging VCB 280-SWG-0001

1

M

210

VAC

1.40

87

P-280-VCB-0002

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

280-VCB-0002

Motor Charging ACB : 280-SWG-0002

1

M

210

VAC

0.50

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

280-HVAC-9001

HVAC CONTROL PANEL

1

F

210

VAC

1.00

88

89

HOLD (NOTE-5) C-280-HVAC-9001

78 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

90

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

91

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

92

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL (280A-B9001)

1

F

210

VAC

0.50

93

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

94

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

95

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.20

96

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

UPS DB at Instrument Building 280B-B-9001

1

F

210

VAC

3.50

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

280-VCB-0003

Motor Charging VCB : 280-SWG-0003

1

M

210

VAC

0.30

97

P-280-VCB-0003

79 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

98

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL (280A-B9001)

1

F

210

VAC

0.50

99

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

100

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

101

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

ECMS WORKSTATION

1

F

210

VAC

0.50

102

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.80

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

280-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-3

1

F

210

VAC

10.40

103 P-280-DPE-0001

104

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

105

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

106

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

80 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

108 P-480-VCB-0001

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

480-VCB-0001

Motor Charging VCB 480-SWG-0001

1

M

210

VAC

2.00

109 P-480-VCB-0001

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

480-VCB-0001

Motor Charging ACB : 480-SWG-0002

1

M

210

VAC

0.30

107

HOLD (NOTE-5)

Volt

kW

SUBSTATION-4 (UTILITY AREA)

110

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

111

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

1.00

112

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

113

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

INSTRUMENT AIR COMPRESSORA LCP

1

F

210

VAC

1.00

114

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

INSTRUMENT AIR COMPRESSORB LCP

1

F

210

VAC

1.00

81 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

115

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

INSTRUMENT AIR COMPRESSORC LCP

1

F

210

VAC

1.00

116

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

117

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

480-DPE-0001

Distribution Panel Emergency Outdoor Lighting Substation-4

1

F

210

VAC

4.00

118 P-480-DPE-0001

119

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

120

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

121

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.20

122

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

82 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

123

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

AIR MANAGER LCP

1

F

210

VAC

0.50

124

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

125

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

126

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

127

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

ECMS WORKSTATION

1

F

210

VAC

0.50

128

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

1.00

129

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

INSTRUMENT AIR DRYER-A LCP

1

F

210

VAC

1.00

130

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

INSTRUMENT AIR DRYER-B LCP

1

F

210

VAC

1.00

131

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

INSTRUMENT AIR DRYER-C LCP

1

F

210

VAC

1.00

83 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

132

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

FIRE WATER PANEL BATTERY CHARGER-A

1

F

210

VAC

1.00

133

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

FIRE WATER PANEL BATTERY CHARGER-B

1

F

210

VAC

1.00

134

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

135

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

TELECOM CABINET

1

F

210

VAC

1.00

136

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

137

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

CONTROL BUILDING 138

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

PCS SYSTEM CABINET

1

F

210

VAC

1.00

139

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

SIS SYSTEM CABINET

1

F

210

VAC

0.50

84 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

140

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

F&G SYSTEM CABINET

1

F

210

VAC

0.20

141

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

142

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

LDS SYSTEM COMPUTER

1

F

210

VAC

0.65

143

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

OFFICE APPLICATION COMPUTER

1

F

210

VAC

0.65

144

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

MM SERVER

1

F

210

VAC

0.65

145

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

PROCESS MONITORING COMP

1

F

210

VAC

0.65

146

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

RTS SERVER

1

F

210

VAC

0.65

147

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

FO BACKBONE PATCH PANEL

1

F

210

VAC

2.00

148

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

MOM SYSTEM CABINET 2

1

F

210

VAC

0.65

85 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

149

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

SOE WORKSTATION

1

F

210

VAC

0.65

150

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

F&G MONITOR WORKSTATION

1

F

210

VAC

0.40

151

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

FIRE STATION MONITOR

1

F

210

VAC

0.40

152

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

0.60

153

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

ECMS-A PANEL

1

F

210

VAC

0.50

154

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

ECMS-A WORKSTATION

1

F

210

VAC

0.65

155

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

CWE SYSTEM CABINET

1

F

210

VAC

1.00

156

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

MOM SYSTEM CABINET 1

1

F

210

VAC

1.00

157

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

1.00

86 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

158

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

OPERATOR TRAINING SYSTEM CABINET

1

F

210

VAC

0.60

159

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PCS SYSTEM CABINET

1

F

210

VAC

1.00

160

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

SIS SYSTEM CABINET

1

F

210

VAC

0.50

161

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

F&G SYSTEM CABINET

1

F

210

VAC

0.20

162

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

163

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CCTV SERVER

1

F

210

VAC

0.65

164

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

EDMS SERVER

1

F

210

VAC

1.30

165

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

MIS BACK-UP SERVER

1

F

210

VAC

0.65

87 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

166

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

APMS SERVER

1

F

210

VAC

0.65

167

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

EPMS SERVER

1

F

210

VAC

0.65

168

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

HISTORIAN OPC SERVER

1

F

210

VAC

1.30

169

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PRINTER

1

F

210

VAC

0.69

170

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

FO BACKBONE PATCH PANEL

1

F

210

VAC

1.00

171

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CCTV SYSTEM

1

F

210

VAC

1.50

172

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CCTV MONITOR

1

F

210

VAC

0.80

173

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PAGA STATION

1

F

210

VAC

0.40

174

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PCS PLASMA TV

1

F

210

VAC

1.87

88 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

175

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

MOM SYSTEM CABINET 2

1

F

210

VAC

0.65

176

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

1.60

177

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

SIS CONSOLE

1

F

210

VAC

0.30

178

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

F&G CONSOLE

1

F

210

VAC

0.30

179

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

ECMS-B PANEL

1

F

210

VAC

0.50

180

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PCS EWS

1

F

210

VAC

0.40

181

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

ESD/F&G EWS

1

F

210

VAC

0.40

182

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

AMS EWS

1

F

210

VAC

0.40

183

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CWE SYSTEM CABINET

1

F

210

VAC

1.00

89 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

184

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

MOM SYSTEM CABINET 1

1

F

210

VAC

1.00

185

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

OPERATOR TRAINING SYSTEM CABINET

1

F

210

VAC

0.60

186

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

1.00

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

900-DPE-0001

Distribution Panel Emergency Outdoor Lighting Central Wellpad

1

F

210

VAC

10.80

188 P-900-SWG/MCC-0001 A

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

900-SWG/MCC-0001

11 kV Switchgear Infrastructure Substation (BUS A)

1

F

210

VAC

0.50

189 P-900-BCH-5001 A

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

900-BCH-5001 A

Back-Up Genset Charger

1

F

210

VAC

0.75

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

900-SWG/MCC-0002 A

400 VAC Switchgear/MCC Infrastructure Substation (BUS A)

1

F

210

VAC

1.00

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

INFRASTRUCTURE AREA SUBSTATION 187 P-900-DPE-0001

190 P-900-SWG/MCC-0002 A

191

HOLD (NOTE-5)

90 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

192

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

ECMS Workstation

1

F

210

VAC

0.50

193

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

2.00

194

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

HOLD (NOTE-5)

Telecom UPS DB

1

F

210

VAC

13.40

195 P-900-BCH-5001 B

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

900-BCH-5001

Back-Up Genset Charger

1

F

210

VAC

0.75

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

900-SWG/MCC-0002 B

400 VAC Switchgear/MCC Infrastructure Substation (BUS B)

1

F

210

VAC

1.00

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

900-SWG/MCC-0001 B

11 kV Switchgear Infrastructure Substation (BUS B)

1

F

210

VAC

0.50

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

2.00

196 P-900-SWG/MCC-0002 B

197

HOLD (NOTE-5)

198 P-900-SWG/MCC-0001 B

199

HOLD (NOTE-5)

91 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

200

HOLD (NOTE-5)

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

2.00

Volt

kW

CENTRAL WELLPAD SUBSTATION 201

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

0.50

202

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

203

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.50

204 P-211-SWG/MCC-0002

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-SWG-MCC-0002 A

400 VAC Switchgear/MCC Well Pad Central (BUS A)

1

F

210

VAC

1.00

205 P-211-ECMS-0001 A

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-ECMS-0001 A

ECMS Panel

1

F

210

VAC

0.50

206 P-211-ECMS-0002

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

P-211-ECMS-0002

ECMS PC

1

F

210

VAC

0.50

207 P-211-SWG/MCC-0001

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-SWG-MCC-0001 A

11 kV Switchgear Central Well Pad Substation (BUS A)

1

F

210

VAC

0.50

92 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

208 P-211-BCH-0001 A

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-BCH-0001

Back-Up Genset Charger

1

F

210

VAC

0.75

Volt

kW

209

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

210

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

211

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.30

212 P-211-SWG-MCC-0002 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-SWG-MCC-0002 B

400 VAC Switchgear/MCC Well Pad Central (BUS B)

1

F

210

VAC

0.75

213 P-211-ECMS-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-ECMS-0001 B

ECMS Panel

1

F

210

VAC

0.50

214 P-211-SWG-MCC-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-SWG-MCC-0001 B

11 kV Switchgear Central Well Pad Substation (BUS B)

1

F

210

VAC

0.50

215 P-211-DPE-0001

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-DPE-0001

Distribution Panel Emergency Outdoor Lighting Central Wellpad

1

F

210

VAC

5.60

93 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

216 P-211-DPN-1001

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-DPN-1001

FLARE PANEL

1

F

210

VAC

0.50

217 C-211-HVAC-9004

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-HVAC-9004

HVAC CONTROL PANEL

1

F

210

VAC

0.50

Volt

kW

EAST WELLPAD SUBSTATION 218

HOLD (NOTE-5)

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

219

HOLD (NOTE-5)

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

220

HOLD (NOTE-5)

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.30

221 P-212-SWG-MCC-0002 A

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-SWG-MCC-0002 A

400 VAC Switchgear/MCC East Well Pad Substation (BUS A)

1

F

210

VAC

0.75

222 P-212-ECMS-0001 A

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-ECMS-0001 A

ECMS Panel

1

F

210

VAC

0.50

223 P-212-ECMS-0002

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-ECMS-0002

ECMS PC

1

F

210

VAC

0.50

94 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-SWG-MCC-0001 A

11 kV Switchgear East Well Pad Substation (BUS A)

1

F

210

VAC

0.50

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-BCH-0001

Back-Up Genset Charger

1

F

210

VAC

0.75

Equipment Tag No.

Description

224 P-212-SWG-MCC-0001 A

225 P-212-BCH-0001 A

Volt

kW

226

HOLD (NOTE-5)

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

227

HOLD (NOTE-5)

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

228

HOLD (NOTE-5)

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.30

229 P-212-SWG-MCC-0002 B

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

212-SWG-MCC-0002 B

400 VAC Switchgear/MCC East Well Pad Substation (BUS B)

1

F

210

VAC

0.75

230 P-212-ECMS-0001 B

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

212-ECMS-0001 B

ECMS Panel

1

F

210

VAC

0.50

231 P-212-SWG-MCC-0001 B

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

212-SWG-MCC-0001 B

11 kV Switchgear East Well Pad Substation (BUS B)

1

F

210

VAC

0.50

95 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

212-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

212-DPE-0001

Distribution Panel Emergency Outdoor Lighting East Wellpad

1

F

210

VAC

9.60

233 P-212-DPN-1001

212-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

212-DPN-1001

FLARE PANEL

1

F

210

VAC

0.50

234 C-212-HVAC-9004

212-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

212-HVAC-9004

HVAC CONTROL PANEL

1

F

210

VAC

0.50

Equipment Tag No.

Description

232 P-212-DPE-0001

Volt

kW

SALES GAS METERING SUBSTATION 235

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

236

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.40

237

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Flow Computer System

1

F

210

VAC

1.80

238

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Laser Jet Printer

1

F

210

VAC

0.50

239

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Sales Gas Ccmputer

1

F

210

VAC

0.70

96 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

240

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

ECMS PC

1

F

210

VAC

0.50

241

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

242 P-710-BCH-5001 A

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

710-BCH-5001

Back-Up Genset Charger

1

F

210

VAC

0.75

243 P-710-SWG/MCC-0002 A

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

710-SWG/MCC-0002A

400 VAC Switchgear/MCC Sales Gas Metering Substation (BUS A)

1

F

210

VAC

0.50

244 P-710-SWG-0001 A

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

710-SWG-0001A

11 kV Switchgear Sales Gas Metering Substation (BUS A)

1

F

210

VAC

0.50

245

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

246

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.40

247

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

Dot Maztrix Printer

1

F

210

VAC

0.10

97 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

248

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

Flow Computer System

1

F

210

VAC

1.80

249

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

250 P-710-UCP-5001

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-UCP-5001

Back-Up Genset UCP

1

F

210

VAC

0.75

251 P-710-DPE-0001

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-DPE-0001

Distribution Panel Emergency Outdoor Lighting Sales Gas Metering

1

F

210

VAC

4.00

252 C-710-HVAC-9004

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-HVAC-9004

HVAC CONTROL PANEL

1

F

210

VAC

0.50

253 P-710-SWG/MCC-0002 B

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-SWG/MCC-0002B

400 VAC Switchgear/MCC Sales Gas Metering Substation (BUS B)

1

F

210

VAC

0.50

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-SWG-0001B

11 kV Switchgear Sales Gas Metering Substation (BUS B)

1

F

210

VAC

0.50

254 P-710-SWG-0001 B

98 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

E

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

DC POWER CABLES DC UPS SUBSTATION-1 (POWER GENERATION)

1

C-420-SWG/MCC-0001A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0001A

11 kV Switchgear: 420-SWG-0001A

1

F

108

VDC

1.00

2

C-420-SWG/MCC-0001B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0001B

11 kV Switchgear: 420-SWG-0001B

1

F

108

VDC

1.00

3

C-420-SWG/MCC-0003A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0003A

400 VAC MCC : 420-MCC-0003A

1

F

108

VDC

1.00

4

C-420-SWG/MCC-0003B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0003B

400 VAC MCC : 420-MCC-0003B

1

F

108

VDC

1.00

5

C-420-SWG/MCC-0005A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0005A

400 VAC MCC : 420-MCC-0005A

1

F

108

VDC

1.00

6

C-420-SWG/MCC-0004A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0004A

400 VAC MCC : 420-MCC-0004A

1

F

108

VDC

1.00

7

C-420-SWG/MCC-0004B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0004B

400 VAC MCC : 420-MCC-0004B

1

F

108

VDC

1.00

99 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

8

C-420-SWG/MCC-0005B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0005B

400 VAC MCC : 420-MCC-0005B

1

F

108

VDC

1.00

9

C-420-SWG/MCC-0002A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0002A

6,6 kV Switchgear: 420-SWG-0002A

1

F

108

VDC

1.00

10

C-420-SWG/MCC-0002B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0002B

6,6 kV Switchgear: 420-SWG-0002B

1

F

108

VDC

1.00

11

C-420-TRF-0001A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0001A

TRAFO 420-TRF-0001A

1

F

108

VDC

0.10

12

C-420-TRF-0001B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0001B

TRAFO 420-TRF-0001B

1

F

108

VDC

0.10

13

C-420-TRF-0002A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0002A

TRAFO 420-TRF-0002A

1

F

108

VDC

0.10

14

C-420-TRF-0002B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0002B

TRAFO 420-TRF-0002B

1

F

108

VDC

0.10

15

C-420-TRF-0003A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0003A

TRAFO 420-TRF-0003A

1

F

108

VDC

0.10

16

C-420-TRF-0003B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0003B

TRAFO 420-TRF-0003B

1

F

108

VDC

0.10

100 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

SUBSTATION-2 (TRAIN-A AREA) 17

C-231-SWG/MCC-0001A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-2 (Train-A)

1

F

108

VDC

1.00

18

C-231-SWG/MCC-0001B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-2 (Train-A)

1

F

108

VDC

1.00

19

C-231-SWG/MCC-0002A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0002 (BUS A)

400 VAC Switchgear / MCC LV 2A Substation-2 (Train-A)

1

F

108

VDC

1.00

20

C-231-SWG/MCC-0002B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0002 (BUS B)

400 VAC Switchgear / MCC LV 2B Substation-2 (Train-A)

1

F

108

VDC

1.00

21

C-231-SWG/MCC-0003A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0003 (BUS A)

400 VAC Switchgear / MCC LV 3A Substation-2 (Train-A)

1

F

108

VDC

1.00

22

C-231-SWG/MCC-0003B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0003 (BUS B)

400 VAC Switchgear / MCC LV 3B Substation-2 (Train-A)

1

F

108

VDC

1.00

23

C-231-SWG/MCC-0004A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0004 (BUS A)

400 VAC Switchgear / MCC LV 4A Substation-2 (Train-A)

1

F

108

VDC

1.00

24

C-231-SWG/MCC-0004B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0004 (BUS B)

400 VAC Switchgear / MCC LV 4B Substation-2 (Train-A)

1

F

108

VDC

1.00

101 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

25

C-231-TRF-0001A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0001A

TRAFO 231-TRF-0001A

1

F

108

VDC

0.10

26

C-231-TRF-0001B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0001B

TRAFO 231-TRF-0001B

1

F

108

VDC

0.10

27

C-231-TRF-0002A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0002A

TRAFO 231-TRF-0002A

1

F

108

VDC

0.10

28

C-231-TRF-0002B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0002B

TRAFO 231-TRF-0002B

1

F

108

VDC

0.10

SUBSTATION-3 (TRAIN-B AREA) 29

C-280-SWG/MCC-0001A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0001A

6,6 kV Switchgear: 280-SWG-0001A

1

F

108

VDC

1.00

30

C-280-SWG/MCC-0001B

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0001B

6,6 kV Switchgear: 280-SWG-0001B

1

F

108

VDC

1.00

31

C-280-SWG/MCC-0002A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0002A

400 VAC MCC : 280-MCC-0002A

1

F

108

VDC

1.00

32

C-280-SWG/MCC-0002B

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0002B

400 VAC MCC : 280-MCC-0002B

1

F

108

VDC

1.00

102 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

33

C-280-SWG/MCC-0003A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0003A

400 VAC MCC : 280-MCC-0003A

1

F

108

VDC

1.00

34

C-280-SWG/MCC-00013

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0003B

400 VAC MCC : 280-MCC-0003B

1

F

108

VDC

1.00

35

C-280-TRF-0001A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-TRF-0001A

TRAFO 280-TRF-0001A

1

F

108

VDC

0.10

36

C-280-TRF-0001B

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-TRF-0001B

TRAFO 280-TRF-0001B

1

F

108

VDC

0.10

SUBSTATION-4 (UTILITY AREA) 37

C-480-SWG/MCC-0001A

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0001A

6,6 kV Switchgear: 480-SWG-0001A

1

F

108

VDC

1.00

38

C-480-SWG/MCC-0001B

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0001B

6,6 kV Switchgear: 480-SWG-0001B

1

F

108

VDC

1.00

39

C-480-SWG/MCC-0002A

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0002A

400 VAC MCC : 480-MCC-0002A

1

F

108

VDC

1.00

40

C-480-SWG/MCC-0002B

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0002B

400 VAC MCC : 480-MCC-0002B

1

F

108

VDC

1.00

103 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

41

C-480-TRF-0001A

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-TRF-0001A

TRAFO 480-TRF-0001A

1

F

108

VDC

0.10

42

C-480-TRF-0001B

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-TRF-0001B

TRAFO 480-TRF-0001B

1

F

108

VDC

0.10

BATTERY RACK FOR UPS GPF 230 VAC UPS 43

P-420-BAT-0001 A-01/02

420-AC-UPS-0001 A

Substation-1 230 VAC UPS System Feeder A

420-BAT-0001 A

Battery Rack for Substation-1 230 VAC UPS System - Feeder A

1

F

220

VDC

61.04

44

P-420-BAT-0001 B-01/02

420-AC-UPS-0001 B

Substation-1 230 VAC UPS System Feeder B

420-BAT-0001 B

Battery Rack for Substation-1 230VAC UPS System - Feeder B

1

F

220

VDC

61.04

45

P-231-BAT-0001 A

231-AC-UPS-0001 A

Substation-2 230 VAC UPS System Feeder A

231-BAT-0001 A

Battery Rack for Substation-2 230 VAC UPS System - Feeder A

1

F

220

VDC

25.43

46

P-231-BAT-0001 B

231-AC-UPS-0001 B

Substation-2 230VAC UPS System Feeder B

231-BAT-0001 B

Battery Rack for Substation-2 230VAC UPS System - Feeder B

1

F

220

VDC

25.43

47

P-280-BAT-0001 A

280-AC-UPS-0001 A

Substation-3 230VAC UPS System Feeder A

280-BAT-0001 A

Battery Rack for Substation-3 230 VAC UPS System - Feeder A

1

F

220

VDC

27.88

104 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

48

P-280-BAT-0001 B

280-AC-UPS-0001 B

Substation-3 230VAC UPS System Feeder B

280-BAT-0001 B

Battery Rack for Substation-3 230VAC UPS System - Feeder B

1

F

220

VDC

27.88

49

P-480-BAT-0001 A

480-AC-UPS-0001 A

Substation-4 230 VAC UPS System Feeder A

480-BAT-0001 A

Battery Rack for Substation-4 230 VAC UPS System - Feeder A

1

F

220

VDC

27.88

50

P-480-BAT-0001 B

480-AC-UPS-0001 B

Substation-4 230 VAC UPS System Feeder B

480-BAT-0001 B

Battery Rack for Substation-4 230VAC UPS System - Feeder B

1

F

220

VDC

27.88

51

P-410-BAT-0001 A-01/02

410-AC-UPS-0001 A

Control Building 230 VAC UPS System - Feeder A

410-BAT-0001 A

Battery Rack for Control Building 230 VAC UPS System - Feeder A

1

F

220

VDC

53.10

52

P-410-BAT-0001 B-01/02

410-AC-UPS-0001 B

Control Building 230 VAC UPS System - Feeder B

410-BAT-0001 B

Battery Rack for Control Building 230VAC UPS System - Feeder B

1

F

220

VDC

53.10

53

P-800-BAT-0001 A-01/02

800-AC-UPS-0001 A

Infrastructure 230 VAC UPS System Feeder A

800-BAT-0001 A

Battery Rack for Infrastructure 230 VAC UPS System - Feeder A

1

F

220

VDC

53.10

54

P-800-BAT-0001 B-01/02

800-AC-UPS-0001 B

Infrastructure 230 VAC UPS System Feeder B

800-BAT-0001 B

Battery Rack for Infrastructure 230VAC UPS System - Feeder B

1

F

220

VDC

53.10

55

P-211-BAT-0001 A

211-AC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 A

Battery Rack for Central Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

105 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

56

P-211-BAT-0001 B

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 B

Battery Rack for Central Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

Volt

kW

230 VAC UPS System Central Wellpad (Bus-B) 57

P-212-BAT-0001 A

212-UPS-1004 A

230 VAC UPS System Central Wellpad (Bus-B)

212-BAT-0001 A

Battery Rack for East Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

58

P-212-BAT-0001 B

212-UPS-1004 B

230 VAC UPS System Central Wellpad (Bus-B)

212-BAT-0001 B

Battery Rack for East Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

230 VAC UPS System Central Wellpad (Bus-B) 59 P-710-BAT-1001 A

710-AC-UPS-1001 A

230 VAC UPS System Central Wellpad (Bus-B)

710-BAT-1001 A

Battery Rack for Gas Metering 230 VAC UPS System - Feeder A

1

F

220

VDC

20.44

60 P-710-BAT-1001 B

710-AC-UPS-1001 B

230 VAC UPS System Central Wellpad (Bus-B)

710-BAT-1001 B

Battery Rack for Gas Metering 230VAC UPS System - Feeder B

1

F

220

VDC

20.44

230 VAC UPS System Central Wellpad (Bus-B) 230 VAC UPS System Central Wellpad (Bus-B)

GPF 110 VDC UPS 61

P-420-BAT-0002A

420-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

420-BAT-0002 A

Battery Rack for Substation-1 110 VDC UPS System - Feeder A

1

F

110

VDC

20.35

62

P-420-BAT-0002 B

420-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

420-BAT-0002 B

Battery Rack for Substation-1 110VDC UPS System - Feeder B

1

F

110

VDC

20.35

106 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

63

P-231-BAT-0002 A

231-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

231-BAT-0002 A

Battery Rack for Substation-2 110 VDC UPS System - Feeder A

1

F

110

VDC

16.48

64

P-231-BAT-0002 B

231-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

231-BAT-0002 B

Battery Rack for Substation-2 110VDC UPS System - Feeder B

1

F

110

VDC

16.48

65

P-280-BAT-0002 A

280-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

280-BAT-0002 A

Battery Rack for Substation-3 110 VDC UPS System - Feeder A

1

F

110

VDC

12.72

66

P-280-BAT-0002 B

280-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

280-BAT-0002 B

Battery Rack for Substation-3 110VDC UPS System - Feeder B

1

F

110

VDC

12.72

67

P-480-BAT-0002 A

480-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

480-BAT-0002 A

Battery Rack for Substation-4 110 VDC UPS System - Feeder A

1

F

110

VDC

8.85

68

P-480-BAT-0002 B

480-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

480-BAT-0002 B

Battery Rack for Substation-4 110VDC UPS System - Feeder B

1

F

110

VDC

8.85

230 VAC UPS System Central Wellpad (Bus-B) 230 VAC UPS System Central Wellpad (Bus-B)

WELLPAD 230 VAC UPS 69

P-211-BAT-0001 A

211-AC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 A

Battery Rack for Central Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

70

P-211-BAT-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 B

Battery Rack for Central Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

107 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

71

P-212-BAT-0001 A

212-AC-UPS-0001 A

East Wellpad 230 VAC UPS System Feeder A

212-BAT-0001 A

Battery Rack for East Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

72

P-212-BAT-0001 B

212-AC-UPS-0001 B

East Wellpad 230VAC UPS System Feeder B

212-BAT-0001 B

Battery Rack for East Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

F

TYPICAL LIGHTING & SMALL POWER CABLES TYPICAL OUTDOOR LIGHTINGS

1

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Distribution Panel Outdoor Lighting

(NOTE-6)

400W Normal HPS Floodlight

3

F

400

VAC

25.60

2

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Distribution Panel Emergency Outdoor Lighting

(NOTE-6)

400W Emergency HPS Floodlight

3

F

400

VAC

0.40

3

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Distribution Panel Outdoor Lighting

(NOTE-6)

150W Normal HPS Wellglass

3

F

400

VAC

0.15

4

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Distribution Panel Outdoor Lighting

(NOTE-6)

250W HPS Streetlight

3

F

400

VAC

0.25

108 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

TYPICAL INDOOR LIGHTING 5

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Distribution Panel Indoor Lighting

(NOTE-6)

2x36 W Normal Fluorescent Light

1

F

230

VAC

0.07

6

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Distribution Panel Emergency Outdoor Lighting

(NOTE-6)

2x36 W Emergency Fluorescent Light (Muster Point)

1

F

230

VAC

0.07

OUTER PERIMETER LIGHTING (For One (1) Loop Perimeter Lighting Cable) 7

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (16 ea)

3

F

400

VAC

4.00

8

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (14 ea)

3

F

394

VAC

3.50

9

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (12 ea)

3

F

394

VAC

3.00

10

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (10 ea)

3

F

392

VAC

2.50

11

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (8 ea)

3

F

391

VAC

2.00

109 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

12

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (6 ea)

3

F

389

VAC

1.50

13

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (4 ea)

3

F

388

VAC

1.00

14

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outdoor Lighting and Small Power

(NOTE-6)

250W Normal HPS Floodlight (2 ea)

3

F

386

VAC

0.50

3

F

400

VAC

4.40

G

TIE-IN BANYU URIP

Distribution Board Helipad

900-DPN-9002-02

Distribution Panel Indoor Lighting & Small Power Guard House-Banyu Urip

1

P-620-LPN-0001

HOLD (NOTE-5)

2

HOLD (NOTE-5)

900-DPN-9002-02

Distribution Panel Indoor Lighting & Small Power Guard House-Banyu Urip

HOLD (NOTE-5)

Indoor Lighting Fluoroscent 2x36 W

1

F

230

VAC

0.07

3

HOLD (NOTE-5)

900-DPN-9002-02

Distribution Panel Indoor Lighting & Small Power Guard House-Banyu Urip

HOLD (NOTE-5)

Air Conditioning

1

F

230

VAC

1.50

110 of 522

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

4

HOLD (NOTE-5)

900-DPN-9002-02

Distribution Panel Indoor Lighting & Small Power Guard House-Banyu Urip

HOLD (NOTE-5)

Outdoor Lighting Floodlight 2x400 W

1

F

230

VAC

1.60

5

HOLD (NOTE-5)

900-DPN-9002-02

Distribution Panel Indoor Lighting & Small Power Guard House-Banyu Urip

HOLD (NOTE-5)

Socket Outlet

1

F

230

VAC

1.20

6

HOLD (NOTE-5)

UPDP826551

UPS Distribution Board PB-24 of Banyu Urip

HOLD (NOTE-5)

PCS System

1

F

230

VAC

5.00

7

HOLD (NOTE-5)

UPDP826551

UPS 230V AC Distribution Board A/B

HOLD (NOTE-5)

PCS System (Redundant)

1

F

230

VAC

0.95

8

HOLD (NOTE-5)

UPDP826551

UPS 230V AC Distribution Board A/B

HOLD (NOTE-5)

CWS Workstation

1

F

230

VAC

0.657

9

HOLD (NOTE-5)

UPDP826551

UPS 230V AC Distribution Board A/B

HOLD (NOTE-5)

Flow Comp System

1

F

230

VAC

0.51

111 of 522

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

Notes : 1. Short Circuit Values (kA) in Column AI are based on ETAP simulated short circuit at each of load end (user) 2. CSA of cable (Smin) are based on the following : ISC x √t

a.) For MV Feeder, Smin of cable determined by formulas : Smin =

k

b.) For 6600 V Motor, Smin determined by Let-through Energy of Protection Device as per Appendix-E c.) For 400 V Motor, Smin determined by Let-through Energy of Protection Device as per Appendix-F d.) For 400 V Feeder, Smin determined by Let-through Energy of Protection Device as per Appendix-G e.) For 230V Cable, Smin determined by Let-through Energy of Protection Device as per Appendix-H (Merlin Gerin C60N for Feeder and C60H for Motor) 3. Sizing cable of switchgear is based on maximum load of switchgear plus 15% contingency and 20% growth allowance of load 112 of 522

3 Ph / 1 Ph

F/M

Volt

kW

GAS DEVELOPMENT

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

4. This is only general calculation of Cable for Space Heater (for motor rated > 5.5 kW). For the complete list of Space Heater cable can be seen in the Doc. No. JTB-SF-E-LST-900-00013~00018, Electrical Cable 5. The Cable Tag Number shall be verifired in the detail engineering phase. 6. The calculation of typical lighting & small power cable in this document are used as an general sizing only. The total number of lighting fixtures will sum in the Electrical MTO.

Legends: Vin (Voltage Source) Vd% (Voltage dropn in %) Vd max %(Voltage drop max in %)

IFL (Full Load current (Amp)) R (Cable resistance (ohm/1000 meter at 90 ºC)) X (Cable reactance (ohm/1000 meter at 50 Hz))

Cos  (Load steady state power factor )

Sin φ

Cos β (Load starting power factor)

Lmax (Maximum Cable Length (m))

L (Cable Length (m))

Ist (Motor Starting Current (Amp))

113 of 522

=Sqrt (1-Cos² φ))

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

11 kV Switchgear Substation-1 (Power Generation)

3

F

11 kV Switchgear Substation-1 (Power Generation)

3

11 / 6.6 kV Transformer A Substation-1 (Power Generation)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

6,500

7,471

1.00

0.87

0.49

N/A

392.14

N/A

2

3/C -

185

mm²

0.1281

0.095

748

0.56

418.8

11,000

VAC

6,500

7,471

1.00

0.87

0.49

N/A

392.14

N/A

2

3/C -

185

mm²

0.1281

0.095

748

0.56

418.8

F

11,000

VAC

3,000

3,448

1.00

0.87

0.49

N/A

180.99

N/A

1

3/C -

150

mm²

0.16

0.098

332

0.56

185.9

3

F

11,000

VAC

11,520

14,400

1.00

0.80

0.60

N/A

755.80

N/A

3

3/C -

300

mm²

0.0799

0.089

1446

0.56

809.7

11 / 6.6 kV Transformer B Substation-1 (Power Generation)

3

F

11,000

VAC

11,520

14,400

1.00

0.80

0.60

N/A

755.80

N/A

3

3/C -

300

mm²

0.0799

0.089

1446

0.56

809.7

11 kV Switchgear Infrastructure

3

F

11,000

VAC

2,223

2,779

1.00

0.80

0.60

N/A

145.86

N/A

1

3/C -

95

mm²

0.247

0.105

263

0.56

147.2

11 / 0.42 kV Transformer Infrastructure

3

F

11,000

VAC

2,400

3,000

1.00

0.80

0.60

N/A

157.46

N/A

1

3/C -

120

mm²

0.197

0.102

298

0.56

166.8

114 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

11 kV Switchgear Central Well Pad Substation

3

F

11,000

11 / 0.42 kV Central Wellpad Transformer

3

F

11 kV Switchgear East Well Pad Substation

3

11 kV Switchgear East Well Pad Substation

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

389

486

1.00

0.80

0.60

N/A

25.53

N/A

1

3/C -

70

mm²

0.343

0.111

220

0.56

123.2

11,000

VAC

384

480

1.00

0.80

0.60

N/A

25.19

N/A

1

3/C -

35

mm²

0.669

0.123

154

0.56

86.2

F

11,000

VAC

384

480

1.00

0.80

0.60

N/A

25.19

N/A

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

3

F

11,000

VAC

389

486

1.00

0.80

0.60

N/A

25.53

N/A

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

11 / 0.42 kV East Wellpad Transformer

3

F

11,000

VAC

384

480

1.00

0.80

0.60

N/A

25.19

N/A

1

3/C -

35

mm²

0.669

0.115

154

0.56

86.2

11 kV Switchgear Sales Gas Metering Substation

3

F

11,000

VAC

166

207

1.00

0.80

0.60

N/A

12.60

N/A

1

3/C -

25

mm²

0.927

0.13

129

0.56

72.2

11 / 0.42 kV Transformer Sales Gas Metering

3

F

11,000

VAC

120

150

1.00

0.80

0.60

N/A

12.60

N/A

1

3/C -

25

mm²

0.927

0.13

129

0.56

72.2

115 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

6.6/0.4 kV Main Transformer

3

F

6,600

6.6/0.4 kV Main Transformer

3

F

6.6/0.4 kV Essential Transformer

3

6.6/0.4 kV Essential Transformer

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1,200

1,500

1.00

0.80

0.60

N/A

131.22

N/A

1

3/C -

95

mm²

0.247

0.099

263

0.56

147.2

6,600

VAC

1,200

1,500

1.00

0.80

0.60

N/A

131.22

N/A

1

3/C -

95

mm²

0.247

0.099

263

0.56

147.2

F

6,600

VAC

1,536

1,920

1.00

0.80

0.60

N/A

167.96

N/A

1

3/C -

150

mm²

0.16

0.093

332

0.56

185.9

3

F

6,600

VAC

1,536

1,920

1.00

0.80

0.60

N/A

167.96

N/A

1

3/C -

150

mm²

0.16

0.093

332

0.56

185.9

6.6 kV Switchgear / MCC MV 1A Substation-2 (Train-A)

3

F

6,600

VAC

4,840

6,050

1.00

0.80

0.60

N/A

529.20

N/A

2

3/C -

300

mm²

0.0799

0.084

964

0.56

539.8

6.6 kV Switchgear / MCC MV 1B Substation-2 (Train-A)

3

F

6,600

VAC

4,840

6,050

1.00

0.80

0.60

N/A

529.20

N/A

2

3/C -

300

mm²

0.0799

0.084

964

0.56

539.8

116 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

6.6/0.4 kV Transformer 1A Substation-2 (Train-A)

3

F

6,600

6.6/0.4 kV Transformer 1B Substation-2 (Train-A)

3

F

6.6/0.4 kV Transformer 2A Substation-2 (Train-A)

3

6.6/0.4 kV Transformer 2B Substation-2 (Train-A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

960

1,200

1.00

0.80

0.60

N/A

104.97

N/A

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

6,600

VAC

960

1,200

1.00

0.80

0.60

N/A

104.97

N/A

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

F

6,600

VAC

3,840

4,800

1.00

0.80

0.60

N/A

419.89

N/A

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

3

F

6,600

VAC

3,840

4,800

1.00

0.80

0.60

N/A

419.89

N/A

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

6.6 kV Switchgear/MCC Substation-3 (Train-B)

3

F

6,600

VAC

3,842

4,802

1.00

0.80

0.60

N/A

420.10

N/A

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

6.6 kV Switchgear/MCC Substation-3 (Train-B)

3

F

6,600

VAC

3,842

4,802

1.00

0.80

0.60

N/A

420.10

N/A

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

6.6/0.4 kV Transformer A Substation3 (Train-B)

3

F

6,600

VAC

3,456

4,320

1.00

0.80

0.60

N/A

377.90

N/A

2

3/C -

185

mm²

0.1281

0.09

748

0.56

418.8

6.6/0.4 kV Transformer B Substation3 (Train-B)

3

F

6,600

VAC

3,456

4,320

1.00

0.80

0.60

N/A

377.90

N/A

2

3/C -

185

mm²

0.1281

0.09

748

0.56

418.8

117 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

6.6 kV Switchgear / MCC MV 2A Substation-4 (Utility)

3

F

6,600

6.6 kV Switchgear / MCC MV 2B Substation-4 (Utility)

3

F

6.6/0.4 kV Transformer Substation-4 (Utility)

3

6.6/0.4 kV Transformer Substation-4 (Utility)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1,798

2,248

1.00

0.80

0.60

N/A

196.62

N/A

1

3/C -

185

mm²

0.1281

0.09

374

0.56

209.4

6,600

VAC

1,798

2,248

1.00

0.80

0.60

N/A

196.62

N/A

1

3/C -

185

mm²

0.1281

0.09

374

0.56

209.4

F

6,600

VAC

768

960

1.00

0.80

0.60

N/A

83.98

N/A

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

3

F

6,600

VAC

768

960

1.00

0.80

0.60

N/A

83.98

N/A

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

Lean Amine Pump-A (Train A)

3

M

6,600

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

Lean Amine Pump-B (Train A)

3

M

6,600

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

118 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Amine Pump-A (Train B)

3

M

6,600

Lean Amine Pump-B (Train B)

3

M

HP BWF Start-Up Pump

3

Instrument Air Compressor Package Motor A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

6,600

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

M

6,600

VAC

300.00

340.91

0.952

0.88

0.47

0.50

31.33

203.62

1

3/C -

25

mm²

0.927

0.13

129

0.56

72.2

3

M

6,600

VAC

355.00

403.41

0.957

0.88

0.47

0.50

36.87

239.69

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

Instrument Air Compressor Package Motor B

3

M

6,600

VAC

355.00

403.41

0.957

0.88

0.47

0.50

36.87

239.69

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

Instrument Air Compressor Package Motor C

3

M

6,600

VAC

355.00

403.41

0.957

0.88

0.47

0.50

36.87

239.69

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.2

119 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Inlet Cooler Fan 1

3

M

400

Inlet Cooler Fan 2

3

M

Inlet Cooler Fan 3

3

Inlet Cooler Fan 4

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Inlet Cooler Fan 5

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Inlet Cooler Fan 6

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Inlet Cooler Fan 7

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

120 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Inlet Cooler Fan 8

3

M

400

Produced Water Transfer Pump A

3

M

Produced Water Transfer Pump B

3

Pipeline Produced Water Transfer Pump A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

Pipeline Produced Water Transfer Pump B

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

Skim Oil Pump

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Pipeline Condensate Transfer Pump A

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

121 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Pipeline Condensate Transfer Pump B

3

M

400

VRU Intercooler-A (1st Stage) Fan-1

3

M

VRU Intercooler-A (1st Stage) Fan-2

3

VRU Intercooler-B (1st Stage) Fan-1

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

VRU Intercooler-B (1st Stage) Fan-2

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

VRU Intercooler-A (2nd Stage) Fan-1

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

VRU Intercooler-B (2nd Stage) Fan-1

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

VRU Intercooler-A (3rd Stage) Fan-1

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

122 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

VRU Intercooler-B (3rd Stage) Fan-1

3

M

400

VRU Knockout Pump A

3

M

VRU Knockout Pump B

3

Driver Motor for VRU Compressor

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

3

M

400

VAC

160.00

179.78

0.961

0.89

0.46

0.50

270.01

1755.09

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

Methanol Injection Pump

3

M

400

VAC

3.00

3.49

0.851

0.86

0.51

0.50

5.92

38.46

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Condensate Reflux Pump A

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Condensate Reflux Pump B

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

123 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Condensate Cooler Fan-1

3

M

400

Condensate Cooler Fan-2

3

M

Condensate Stabilizer Recycle Liquid Pump

3

Recycle Gas Compressor Cooler Fan-1

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

3.00

3.49

0.851

0.86

0.51

0.50

5.92

38.46

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Recycle Gas Compressor Cooler Fan-2

3

M

400

VAC

3.00

3.49

0.851

0.86

0.51

0.50

5.92

38.46

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

EG Circulator Pump A

3

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

EG Circulator Pump B

3

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

EG Reflux Pump A

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

124 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

EG Reflux Pump B

3

M

400

Produced Water Booster Pump A

3

M

Produced Water Booster Pump B

3

EG Makeup Pump

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

3

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

EG Regeneration Overhead Gas Compressor A

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

EG Regeneration Overhead Gas Compressor B

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

EG Regeneration Tower Cooler Fan-1

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

EG Regeneration Tower Cooler Fan-2

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Glycol Drain Return Pump

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

125 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Propylene Condenser Fan 1

3

M

400

Propylene Condenser Fan 2

3

M

Propylene Condenser Fan 3

3

Propylene Condenser Fan 4

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Propylene Condenser Fan 5

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Propylene Condenser Fan 6

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Propylene Condenser Fan 7

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Propylene Condenser Fan 8

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

126 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Propylene Compressor A (1st Stage) Auxiliary Load

3

M

400

Propylene Compressor A (2nd Stage) Auxiliary Load

3

M

Propylene Compressor B (1st Stage) Auxiliary Load

3

Propylene Compressor B (2nd Stage) Auxiliary Load

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Lean Solvent Air Cooler-A (AGRU A) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-A (AGRU A) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-A (AGRU A) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-A (AGRU A) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

127 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Solvent Air Cooler-A (AGRU A) #5

3

M

400

Lean Solvent Air Cooler-A (AGRU A) #6

3

M

Lean Solvent Air Cooler-A (AGRU A) #7

3

Lean Solvent Air Cooler-A (AGRU A) #8

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-B (AGRU A) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-B (AGRU A) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-B (AGRU A) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-B (AGRU A) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Lean Solvent Air Cooler-B (AGRU A) #5

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

128 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Solvent Air Cooler-B (AGRU A) #6

3

M

400

Lean Solvent Air Cooler-B (AGRU A) #7

3

M

Lean Solvent Air Cooler-B (AGRU A) #8

3

Auxiliary for HP Lean Solvent Pump 1 (Train A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

Auxiliary for HP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

Auxiliary for HP Lean Solvent Pump 3 (Train A)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

Reflux Pump-1 A (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Reflux Pump-1 B (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Reflux Pump-2 A (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

129 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Reflux Pump-2 B (Train A)

3

M

400

Drained Solvent Pump (Stand-By) Train A

3

M

Drained Hydrocarbon Pump (StandBy) Train A

3

Auxiliary for LP Lean Solvent Pump 1 (Train A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Auxiliary for LP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Auxiliary for LP Lean Solvent Pump 3 (Train A)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Auxiliary for Regenerator Lean Solvent Pump 1 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Auxiliary for Regenerator Lean Solvent Pump 2 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Auxiliary for Regenerator Lean Solvent Pump 3 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

130 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Reboiler Condensate Pump-1A (Train A)

3

M

400

Reboiler Condensate Pump-1B (Train A)

3

M

Reboiler Condensate Pump-2A (Train A)

3

Reboiler Condensate Pump-2B (Train A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Overhead Condenser-A (AGRU A) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-A (AGRU A) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-A (AGRU A) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-A (AGRU A) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-B (AGRU A) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

131 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Overhead Condenser-B (AGRU A) #2

3

M

400

Overhead Condenser-B (AGRU A) #3

3

M

Overhead Condenser-B (AGRU A) #4

3

AGRU Fresh Solvent Pump A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

AGRU Fresh Solvent Pump B

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Lean Solvent Air Cooler-A (AGRU B) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-A (AGRU B) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-A (AGRU B) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

132 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Solvent Air Cooler-A (AGRU B) #4

3

M

400

Lean Solvent Air Cooler-A (AGRU B) #5

3

M

Lean Solvent Air Cooler-A (AGRU B) #6

3

Lean Solvent Air Cooler-A (AGRU B) #7

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-A (AGRU B) #8

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-B (AGRU B) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-B (AGRU B) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-B (AGRU B) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Solvent Air Cooler-B (AGRU B) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

133 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Solvent Air Cooler-B (AGRU B) #5

3

M

400

Lean Solvent Air Cooler-B (AGRU B) #6

3

M

Lean Solvent Air Cooler-B (AGRU B) #7

3

Lean Solvent Air Cooler-B (AGRU B) #8

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Auxiliary for HP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

1

3/C -

35

mm²

0.6690

0.0753

122

0.60

73.2

Auxiliary for HP Lean Solvent Pump 2 (Train B)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

1

3/C -

35

mm²

0.6690

0.0753

122

0.60

73.2

Auxiliary for HP Lean Solvent Pump 3 (Train B)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

1

3/C -

35

mm²

0.6690

0.0753

122

0.60

73.2

Reflux Pump-1 A (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Reflux Pump-1 B (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

134 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Reflux Pump-2 A (Train B)

3

M

400

Reflux Pump-2 B (Train B)

3

M

Drained Solvent Pump (Stand-By) Train B

3

Drained Hydrocarbon Pump (StandBy) Train B

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Auxiliary for LP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Auxiliary for LP Lean Solvent Pump 2 (Train B)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Auxiliary for LP Lean Solvent Pump 3 (Train B)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Auxiliary for Regenerator Lean Solvent Pump 1 (Train B)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Auxiliary for Regenerator Lean Solvent Pump 2 (Train B)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

135 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Auxiliary for Regenerator Lean Solvent Pump 3 (Train B)

3

M

400

Reboiler Condensate Pump-1 A (Train B)

3

M

Reboiler Condensate Pump-1 B (Train B)

3

Reboiler Condensate Pump-2 A (Train B)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Reboiler Condensate Pump-2 B (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Overhead Condenser-A (AGRU B) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-A (AGRU B) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-A (AGRU B) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Overhead Condenser-A (AGRU B) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

136 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Overhead Condenser-B (AGRU B) #1

3

M

400

Overhead Condenser-B (AGRU B) #2

3

M

Overhead Condenser-B (AGRU B) #3

3

Overhead Condenser-B (AGRU B) #4

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Sales Gas Dehy TEG Circulation Pump A

3

M

400

VAC

132.00

150.00

0.954

0.88

0.47

0.50

226.95

1475.15

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

Sales Gas Dehy TEG Circulation Pump B

3

M

400

VAC

132.00

150.00

0.954

0.88

0.47

0.50

226.95

1475.15

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

Sales Gas Dehy TEG Lean Cooler Fan-1

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Sales Gas Dehy TEG Lean Cooler Fan-2

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

137 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Sales Gas Dehy TEG Supply Pump

3

M

400

TEG Drain Vessel Pump

3

M

Sales Gas Compressor Discharge Cooler Fan 1

3

Sales Gas Compressor Discharge Cooler Fan 2

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Sales Gas Compressor A Auxiliary Load

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Sales Gas Compressor B Auxiliary Load

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Wash Water Pump-1 at AGE Absorber (Train A)

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

138 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Wash Water Pump-2 at AGE Absorber (Train A)

3

M

400

Wash Water Pump-3 at AGE Absorber (Train A)

3

M

Regenerator Reflux Pump-1 (Train A)

3

Regenerator Reflux Pump-2 (Train A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Regenerator Reflux Pump-3 (Train A)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Solvent Sump Pump-A (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Solvent Sump Pump-B (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Regenerator Overhead Condenser 1 (Train A)

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

Regenerator Overhead Condenser 2 (Train A)

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

139 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Regenerator Bottoms Pump 1 (Train A)

3

M

400

Regenerator Bottoms Pump 2 (Train A)

3

M

Regenerator Bottoms Pump 3 (Train A)

3

Lean Amine Cooler (Train A) #1

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Lean Amine Cooler (Train A) #2

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Lean Amine Cooler (Train A) #3

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Lean Amine Cooler (Train A) #4

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Lean Amine Cooler (Train A) #5

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Lean Amine Cooler (Train A) #6

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

140 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Amine Cooler (Train A) #7

3

M

400

Lean Amine Cooler (Train A) #8

3

M

Rich Amine Pump-1 at AGE Absorber (Train A)

3

Rich Amine Pump-2 at AGE Absorber (Train A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

1

3/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

1

3/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

Rich Amine Pump-3 at AGE Absorber (Train A)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

1

3/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

Fresh Solvent Pump A (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Fresh Solvent Pump B (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Sour Water Pump-1 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Sour Water Pump-2 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

141 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Sour Water Pump-3 (Train A)

3

M

400

Wash Water Pump-1 at AGE Absorber (Train B)

3

M

Wash Water Pump-2 at AGE Absorber (Train B)

3

Wash Water Pump-3 at AGE Absorber (Train B)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Regenerator Reflux Pump-1 (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Regenerator Reflux Pump-2 (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Regenerator Reflux Pump-3 (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Solvent Sump Pump-A (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

142 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Solvent Sump Pump-B (Train B)

3

M

400

Regenerator Overhead Condenser 1 (Train B)

3

M

Regenerator Overhead Condenser 2 (Train B)

3

Regenerator Bottoms Pump-1 (Train B)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

Regenerator Bottoms Pump-2 (Train B)

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

Regenerator Bottoms Pump-3 (Train B)

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

Lean Amine Cooler (Train B) #1

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Amine Cooler (Train B) #2

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Amine Cooler (Train B) #3

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

143 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Lean Amine Cooler (Train B) #4

3

M

400

Lean Amine Cooler (Train B) #5

3

M

Lean Amine Cooler (Train B) #6

3

Lean Amine Cooler (Train B) #7

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Lean Amine Cooler (Train B) #8

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

Rich Amine Pump-A at AGE Absorber (Train B)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

Rich Amine Pump-B at AGE Absorber (Train B)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

Rich Amine Pump-C at AGE Absorber (Train B)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

Sour Water Pump-A (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

144 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Sour Water Pump-B (Train B)

3

M

400

Sour Water Pump-C (Train B)

3

M

Sulfur Transfer Pump A

3

Sulfur Transfer Pump B

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Claus Air Blower A Auxiliary Load

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Claus Air Blower B Auxiliary Load

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Sour Condensate Pump A

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Sour Condensate Pump B

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

145 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Sulfur Handling Pump A

3

M

400

Sulfur Handling Pump B

3

M

LP Condensate Pump A

3

LP Condensate Pump B

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Quench Water Pump-A

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

Quench Water Pump-B

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

Wash Water Pump-A at TGU Absorber

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Wash Water Pump-B at TGU Absorber

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

146 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Rich Amine Pump-A at TGU Absorber

3

M

400

Rich Amine Pump-B at TGU Absorber

3

M

Sour Water Drain Return Pump

3

Quench Water Air Cooler #1

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

Quench Water Air Cooler #2

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

BFW Transfer Pump-A

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

BFW Transfer Pump-B

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Steam Condensate Pump A

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

147 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Steam Condensate Pump B

3

M

400

Blowdown Pump A

3

M

Blowdown Pump B

3

LP BFW Pump A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

LP BFW Pump B

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

Steam Condenser Fan-1

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Steam Condenser Fan-2

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Oxygen Scavenger Tank Mixer Motor

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Neutralization Amine Tank Mixer Motor

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

148 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Phosphate Solution Tank Mixer Motor

3

M

400

Oxygen Scavenger Pump Motor-A

3

M

Oxygen Scavenger Pump Motor-B

3

Neutralization Amine Pump Motor-A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

3

M

400

VAC

1.10

1.29

0.802

0.85

0.53

0.50

2.33

15.14

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Neutralization Amine Pump Motor-B

3

M

400

VAC

1.10

1.29

0.802

0.85

0.53

0.50

2.33

15.14

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Phosphate Solution Pump Motor A

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Phosphate Solution Pump Motor B

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Deaerator Steam Condenser Motor 1

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

Deaerator Steam Condenser Motor 2

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

149 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Raw Water Feed Pump A

3

M

400

Raw Water Feed Pump B

3

M

AGE Off-Gas K.O. Drum Pump-A

3

AGE Off-Gas K.O. Drum Pump-B

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.4

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

TGU Off-Gas K.O. Drum Pump-A

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

TGU Off-Gas K.O. Drum Pump-B

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Thermal Oxidizer Air Blower A Auxiliary Load

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

150 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Thermal Oxidizer Air Blower B Auxiliary Load

3

M

400

Thermal Oxidizer Air Blower C Auxiliary Load

3

M

Thermal Oxidizer Air Blower D Auxiliary Load

3

Thermal Oxidizer Air Blower E Auxiliary Load

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

HP Flare Knockout Drum Condensate Pump A

3

M

400

VAC

90.00

100.00

0.951

0.90

0.44

0.50

151.77

986.53

2

3/C -

95

mm²

0.2470

0.0711

422

0.60

253.2

HP Flare Knockout Drum Condensate Pump B

3

M

400

VAC

90.00

100.00

0.951

0.90

0.44

0.50

151.77

986.53

2

3/C -

95

mm²

0.2470

0.0711

422

0.60

253.2

LP Flare Knockout Drum Condensate Pump A

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

151 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

LP Flare Knockout Drum Condensate Pump B

3

M

400

Diesel Pump

3

M

Firewater Jockey Pump

3

Close Drain Pump

Open Drain Pump

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

152 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

3

F

400

Battery Charger Emergency Diesel Generator

3

F

400 VAC Switchgear/MCC Well Pad Central

3

Battery Charger Backup Diesel Generator Well Pad Central

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

536

670.00

1.00

0.80

0.60

N/A

967.06

N/A

5

4/C -

300

mm²

0.0799

0.0835

1980

0.60

1188.

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

F

400

VAC

240.00

300.00

1.00

0.80

0.60

N/A

433.01

N/A

2

4/C -

300

mm²

0.0799

0.0835

792

0.60

475.2

3

F

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400 VAC Switchgear/MCC Well Pad Central

3

F

400

VAC

160

200

1.00

0.80

0.60

N/A

288.68

N/A

2

4/C -

150

mm²

0.16

0.0843

542

0.60

325.2

400 VAC Switchgear/MCC Well Pad East

3

F

400

VAC

240.00

300.00

1.00

0.80

0.60

N/A

433.01

N/A

3

4/C -

300

mm²

0.0799

0.0835

1188

0.60

712.8

Battery Charger Backup Diesel Generator Well Pad East

3

F

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

153 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

400 VAC Switchgear/MCC Well Pad East

3

F

400

Battery Charger Backup Diesel Generator Infrastructure

3

F

400 VAC Switchgear/MCC Sales Gas Metering Station

3

Battery Charger Backup Diesel Generator Sales Gas Metering

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

160

200

1.00

0.80

0.60

N/A

288.68

N/A

1

4/C -

240

mm²

0.0984

0.0842

538

0.60

322.8

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

F

400

VAC

100.00

125.00

1.00

0.80

0.60

N/A

180.42

N/A

1

4/C -

185

mm²

0.1281

0.0851

304

0.60

182.4

3

F

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400 VAC Switchgear/MCC Sales Gas Metering Station

3

F

400

VAC

100.00

200.00

1.00

0.80

0.60

N/A

180.42

N/A

1

4/C -

120

mm²

0.197

0.0839

346

0.60

207.6

STG-A Lube Oil Clarifier Driver

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

154 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

STG-A Lube Oil Pump Driver-A

3

M

400

STG-A Lube Oil Pump Driver-B

3

M

STG-A Lube Oil Tank Mist SeparatorA

3

STG-A Lube Oil Tank Mist SeparatorB

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

STG-A Jacking Oil Oump Driver

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

STG-A Bearing Gear Driver

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

STG-B Lube Oil Clarifier Driver

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

STG-B Lube Oil Pump Driver-A

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

155 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

STG-B Lube Oil Pump Driver-B

3

M

400

STG-B Lube Oil Mist Separator-A

3

M

STG-B Lube Oil Mist Separator-B

3

STG-B Jacking Oil Oump Driver

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

STG-B Bearing Gear Driver

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Radiator Fan Essential Generator

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

LCP Power Essential Generator

3

F

400

VAC

18.25

20.28

0.913

0.90

0.44

N/A

32.06

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

Battery Charger Essential Generator

3

F

400

VAC

2.00

2.11

1.000

0.95

0.31

N/A

3.04

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

156 of 522

Amp

ss)

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Transformer Rectifier Unit (GPF Underground Pipeline)-1

3

F

400

Transformer Rectifier Unit (GPF Underground Pipeline)-2

3

F

Transformer Rectifier Unit (Sales Gas Metering Underground Pipeline)

3

230 VAC UPS System - Feeder A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.50

4.38

0.950

0.80

0.60

N/A

6.65

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

400

VAC

3.50

4.38

0.950

0.80

0.60

N/A

6.65

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

F

400

VAC

3.50

4.38

0.950

0.80

0.60

N/A

6.65

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

3

F

400

VAC

64.00

80.00

0.900

0.80

0.60

N/A

128.30

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

230 VAC UPS System - Feeder B

3

F

400

VAC

64.00

80.00

0.900

0.80

0.60

N/A

128.30

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

230 VAC UPS System - Bypass

3

F

400

VAC

64.00

80.00

0.900

0.80

0.60

N/A

128.30

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

110 VDC UPS System - Feeder A

3

F

400

VAC

13.78

17.23

0.900

0.80

0.60

N/A

27.62

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

157 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

110 VDC UPS System - Feeder B

3

F

400

HVAC Package for Substation-1

3

F

HVAC Package for Substation-1

3

HVAC Package for Substation-1

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

13.78

17.23

0.900

0.80

0.60

N/A

27.62

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

400

VAC

113.20

141.50

1.000

0.80

0.60

N/A

204.24

N/A

1

4/C -

240

mm²

0.0984

0.0842

351

0.60

210.6

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

HVAC Package for Substation-1

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

HVAC Auxiliary for Substation 1

3

F

400

VAC

32.20

40.25

1.000

0.80

0.60

N/A

58.10

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Indoor Lighting Substation-1

3

F

400

VAC

14.00

16.47

0.950

0.85

0.53

N/A

25.02

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Outdoor Lighting Substation-1

3

F

400

VAC

46.00

54.12

0.950

0.85

0.53

N/A

82.22

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

158 of 522

Amp

ss)

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Emergency Outdoor Lighting Substation-1

3

F

400

Welding Receptacle #1

3

F

Welding Receptacle #2

3

230 VAC UPS System - Feeder A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.20

8.47

0.950

0.85

0.53

N/A

12.87

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

3

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

230 VAC UPS System - Feeder B

3

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

230 VAC UPS System - Bypass

3

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

110 VDC UPS System - Feeder A

3

F

400

VAC

10.92

13.65

0.900

0.80

0.60

N/A

21.89

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

159 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

110 VDC UPS System - Feeder B

3

F

400

HVAC package for Substation 2

3

F

HVAC package for Substation 2

3

HVAC package for Substation 2

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

10.92

13.65

0.900

0.80

0.60

N/A

21.89

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

146.70

183.38

1.000

0.80

0.60

N/A

264.68

N/A

2

4/C -

120

mm²

0.197

0.0839

480

0.60

288.0

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC package for Substation 2

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC Auxiliary for Substation 2

3

F

400

VAC

45.00

56.25

1.000

0.80

0.60

N/A

81.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

Distribution Panel Indoor Lighting Substation-2

3

F

400

VAC

11.90

14.00

1.000

0.85

0.53

N/A

20.21

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Outdoor Lighting Substation-2

3

F

400

VAC

93.30

109.76

1.000

0.85

0.53

N/A

158.43

N/A

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

160 of 522

Amp

ss)

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Emergency Outdoor Lighting Substation-2

3

F

400

Welding Receptacle #3

3

F

Welding Receptacle #4

3

Welding Receptacle #7

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

12.50

14.71

1.000

0.85

0.53

N/A

21.23

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

Welding Receptacle #8

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

230 VAC UPS System - Feeder A

3

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

230 VAC UPS System - Feeder B

3

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

230 VAC UPS System - Bypass

3

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

161 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

110 VDC UPS System - Feeder A

3

F

400

110 VDC UPS System - Feeder B

3

F

HVAC package for Substation 3

3

HVAC package for Substation 3

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

8.06

10.08

0.900

0.80

0.60

N/A

16.16

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

8.06

10.08

0.900

0.80

0.60

N/A

16.16

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

F

400

VAC

224.20

280.25

1.000

0.80

0.60

N/A

404.51

N/A

2

4/C -

240

mm²

0.0984

0.0842

702

0.60

421.2

3

F

400

VAC

71.00

88.75

1.000

0.80

0.60

N/A

128.10

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

HVAC package for Substation 3

3

F

400

VAC

71.00

88.75

1.000

0.80

0.60

N/A

128.10

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

HVAC Auxiliary for Substation 3

3

F

400

VAC

83.00

103.75

1.000

0.80

0.60

N/A

149.75

N/A

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

Distribution Panel Indoor Lighting Substation-3

3

F

400

VAC

9.80

11.53

1.000

0.85

0.53

N/A

16.64

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

162 of 522

Amp

ss)

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Outdoor Lighting Substation-3

3

F

400

Distribution Panel Emergency Outdoor Lighting Substation-3

3

F

Welding Receptacle #5

3

Welding Receptacle #6

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

58.00

68.24

0.950

0.85

0.53

N/A

103.67

N/A

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

400

VAC

15.00

17.65

1.000

0.85

0.53

N/A

25.47

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

230 VAC UPS System - Feeder A

3

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

230 VAC UPS System - Feeder B

3

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

230 VAC UPS System - Bypass

3

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

163 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

110 VDC UPS System - Feeder A

3

F

400

110 VDC UPS System - Feeder B

3

F

HVAC package for Substation 4

3

HVAC package for Substation 4

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.46

6.83

0.900

0.80

0.60

N/A

10.95

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

5.46

6.83

0.900

0.80

0.60

N/A

10.95

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

F

400

VAC

112.70

132.59

0.900

0.85

0.53

N/A

212.64

N/A

1

4/C -

300

mm²

0.0799

0.0835

396

0.60

237.6

3

F

400

VAC

34.00

40.00

0.900

0.85

0.53

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC package for Substation 4

3

F

400

VAC

34.00

40.00

0.900

0.85

0.53

N/A

64.15

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC Auxiliary for Substation 4

3

F

400

VAC

45.00

52.94

0.900

0.85

0.53

N/A

84.90

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

Distribution Panel Indoor Lighting Substation-4

3

F

400

VAC

8.00

9.41

1.000

0.85

0.53

N/A

13.58

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Outdoor Lighting Substation-4

3

F

400

VAC

57.35

67.47

1.000

0.85

0.53

N/A

97.39

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

164 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Emergency Outdoor Lighting Substation-4

3

F

400

HVAC package for Instrument Building Train-A

3

F

HVAC package for Instrument Building Train-A

3

HVAC package for Instrument Building Train-A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.60

6.59

1.000

0.85

0.53

N/A

9.51

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

HVAC Aux for Instrument Building Train-A

3

F

400

VAC

86.00

107.50

1.000

0.80

0.60

N/A

155.16

N/A

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

165 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

HVAC package for Instrument Building Train-B

3

F

400

HVAC Aux for Instrument Building Train-B

3

F

Instrument Panel (Train-A)

3

Instrument Panel (Train-B)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

400

VAC

86.00

107.50

1.000

0.80

0.60

N/A

155.16

N/A

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

F

400

VAC

20.00

23.53

0.900

0.85

0.53

N/A

37.74

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

3

F

400

VAC

20.00

23.53

0.90

0.85

0.53

N/A

37.74

N/A

1

4/C -

25

mm²

0.9270

0.0908

101

0.60

60.6

Distribution Panel Indoor Lighting & Small Power Instrument Building 280A

3

F

400

VAC

2.10

2.47

1.000

0.85

0.53

N/A

3.57

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Indoor Lighting & Small Power Instrument Building 280B

3

F

400

VAC

2.10

2.47

1.000

0.85

0.53

N/A

3.57

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

230 VAC UPS System - Feeder A Control Room

3

F

400

VAC

48.00

60.00

0.900

0.80

0.60

N/A

96.23

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

166 of 522

Amp

ss)

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

230 VAC UPS System - Feeder B Control Room

3

F

400

230 VAC UPS System - Bypass Control Room

3

F

AHU DX

3

AHU DX

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

48.00

60.00

0.900

0.80

0.60

N/A

96.23

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

400

VAC

48.00

60.00

0.900

0.80

0.60

N/A

96.23

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

F

400

VAC

11.00

12.94

0.900

0.85

0.53

N/A

20.75

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

3

F

400

VAC

2.20

2.59

0.900

0.85

0.53

N/A

4.15

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Air Conditioner Cassette Type (Total = 14 unit)

3

F

400

VAC

29.35

34.53

0.900

0.85

0.53

N/A

55.38

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

Electric Duct Heater

3

F

400

VAC

106.03

124.74

0.900

0.85

0.53

N/A

200.05

N/A

2

4/C -

70

mm²

0.343

0.0864

356

0.60

213.6

AC Auxiliary

3

F

400

VAC

6.30

7.41

0.900

0.85

0.53

N/A

11.89

N/A

2

4/C -

6

mm²

3.93

0.098

92

0.60

55.2

Lighting (Indoor Control Room)

3

F

400

VAC

30.20

35.53

0.950

0.85

0.53

N/A

53.98

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

167 of 522

Amp

ss)

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

230 VAC UPS System - Feeder A

3

F

400

230 VAC UPS System - Feeder B

3

F

230 VAC UPS System - Bypass

3

HVAC package for Infrastructure Substation

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC package for Infrastructure Substation

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC package for Infrastructure Substation

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

HVAC Auxiliary for Infrastructure Substation

3

F

400

VAC

45.00

56.25

1.000

0.80

0.60

N/A

81.19

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

168 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Indoor Lighting & Small Power Infrastructure Substation

3

F

400

Distribution Panel Outdoor Lighting Infrastructure Substation

3

F

Distribution Panel Emergency Lighting Infrastructure Substation

3

Distribution Panel Indoor Lighting & Small Power Gate House Building

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

6.20

6.53

1.000

0.95

0.31

N/A

9.42

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

41.25

43.42

1.000

0.95

0.31

N/A

62.67

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

F

400

VAC

10.80

11.37

1.000

0.95

0.31

N/A

16.41

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

Distribution Panel Indoor Lighting & Small Power Guard House Building

3

F

400

VAC

3.60

3.79

1.000

0.95

0.31

N/A

5.47

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

169 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Indoor Lighting & Small Power Security Gate House

3

F

400

Distribution Panel Indoor Lighting Administration Building

3

F

Distribution Panel Small Power Administration Building

3

Distribution Panel Indoor Lighting & Small Power Telcom Building

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.20

3.37

1.000

0.95

0.31

N/A

4.86

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

400

VAC

12.40

13.05

1.000

0.95

0.31

N/A

18.84

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

F

400

VAC

35.00

36.84

1.000

0.95

0.31

N/A

53.18

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

Distribution Panel Indoor Lighting Fire Emegency Station

3

F

400

VAC

2.80

2.95

1.000

0.95

0.31

N/A

4.25

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Small Power Fire Emegency Station

3

F

400

VAC

9.50

10.00

1.000

0.95

0.31

N/A

14.43

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Indoor Lighting Office Building

3

F

400

VAC

10.00

10.53

1.000

0.95

0.31

N/A

15.19

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Small Power Office Building

3

F

400

VAC

44.50

46.84

1.000

0.95

0.31

N/A

67.61

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

Distribution Panel Indoor Lighting Laboratory Building

3

F

400

VAC

7.35

7.74

1.000

0.95

0.31

N/A

11.17

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

170 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Small Power Laboratory Building

3

F

400

Distribution Panel Lighting & Small Power Mosque

3

F

Distribution Panel Indoor Lighting Kitchen & Dining Hall

3

Distribution Panel Indoor Lighting Kitchen & Dining Hall

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

21.00

22.11

1.000

0.95

0.31

N/A

31.91

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

400

VAC

8.00

8.42

1.000

0.95

0.31

N/A

12.15

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

F

400

VAC

6.20

6.53

1.000

0.95

0.31

N/A

9.42

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

3

F

400

VAC

11.00

11.58

1.000

0.95

0.31

N/A

16.71

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

Distribution Panel Lighting & Small Power Laundry Center Building

3

F

400

VAC

6.40

6.74

1.000

0.95

0.31

N/A

9.72

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

Distribution Panel Indoor Lighting Medical Center Building

3

F

400

VAC

8.00

8.42

1.000

0.95

0.31

N/A

12.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

Distribution Panel Small Power Medical Center Building

3

F

400

VAC

12.00

12.63

1.000

0.95

0.31

N/A

18.23

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Indoor Lighting Dormitory Operator & Staff

3

F

400

VAC

22.40

23.58

1.000

0.95

0.31

N/A

34.03

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

Distribution Panel Small Power Dormitory Operator & Staff

3

F

400

VAC

99.00

104.21

1.000

0.95

0.31

N/A

150.41

N/A

1

4/C -

300

mm²

0.0799

0.0835

396

0.60

237.6

171 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Indoor Lighting Dormitory Field Superintendent

3

F

400

Distribution Panel Small Power Dormitory Field Superintendent

3

F

Distribution Panel Indoor Lighting Sport Hall & Multipurpose Building

3

Distribution Panel Small Power Sport Hall & Multipurpose Building

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

12.82

13.49

1.000

0.95

0.31

N/A

19.48

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

400

VAC

54.50

57.37

1.000

0.95

0.31

N/A

82.80

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

F

400

VAC

20.00

21.05

1.000

0.95

0.31

N/A

30.39

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

3

F

400

VAC

60.50

63.68

1.000

0.95

0.31

N/A

91.92

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

Distribution Panel Indoor Lighting Operation Warehouse Building

3

F

400

VAC

30.00

31.58

1.000

0.95

0.31

N/A

45.58

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

Distribution Panel Small Power Operation Warehouse Building

3

F

400

VAC

31.50

33.16

1.000

0.95

0.31

N/A

47.86

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Indoor Lighting & Small Power Vehicle Fuel Station Shelter

3

F

400

VAC

1.70

1.79

1.000

0.95

0.31

N/A

2.58

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Indoor Lighting Operation Maintenance Building

3

F

400

VAC

38.00

40.00

1.000

0.95

0.31

N/A

57.74

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

Distribution Panel Small Power Operation Maintenance Building

3

F

400

VAC

39.00

41.05

1.000

0.95

0.31

N/A

59.25

N/A

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

172 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Indoor Lighting & Small Power Chemical Storage Building

3

F

400

Distribution Panel Air Conditioning Guard House

3

F

Distribution Panel Air Conditioning Gate House

3

Distribution Panel Air Conditioning Gate House

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

20.00

21.05

1.000

0.95

0.31

N/A

30.39

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

400

VAC

3.54

3.73

1.000

0.95

0.31

N/A

5.38

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

3

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Air Conditioning Security Gate House

3

F

400

VAC

10.66

12.54

1.000

0.85

0.53

N/A

18.10

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Air Conditioning Telcom Building

3

F

400

VAC

28.90

34.00

1.000

0.85

0.53

N/A

49.07

N/A

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

173 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Air Conditioning Fire Emergency Station

3

F

400

Distribution Panel Air Conditioning Mosque

3

F

Distribution Panel Air Conditioning Administration Building

3

Distribution Panel Air Conditioning Kitchen & Dinning Hall Building

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

32.00

37.65

1.000

0.85

0.53

N/A

54.34

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

400

VAC

58.00

61.05

1.000

0.95

0.31

N/A

88.12

N/A

1

4/C -

240

mm²

0.0984

0.0842

351

0.60

210.6

F

400

VAC

93.73

110.27

1.000

0.85

0.53

N/A

159.16

N/A

2

4/C -

185

mm²

0.1281

0.0851

608

0.60

364.8

3

F

400

VAC

34.85

41.00

1.000

0.85

0.53

N/A

59.18

N/A

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

Distribution Panel Air Conditioning Medical Center Building

3

F

400

VAC

23.98

28.21

1.000

0.85

0.53

N/A

40.72

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Air Conditioning Laundry Center Building

3

F

400

VAC

19.00

22.35

1.000

0.85

0.53

N/A

32.26

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

Distribution Panel Air Conditioning Dormitory Operator & Staff

3

F

400

VAC

21.51

25.31

1.000

0.85

0.53

N/A

36.53

N/A

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.4

Distribution Panel Air Conditioning Dormitory Field Superintendent

3

F

400

VAC

11.52

13.55

1.000

0.85

0.53

N/A

19.56

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Air Conditioning Sport Hall & Multipurposed Building

3

F

400

VAC

50.63

59.56

1.000

0.85

0.53

N/A

85.97

N/A

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

174 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Air Conditioning Operation Warehouse Building

3

F

400

Distribution Panel Air Conditioning Operation Maintenance Building

3

F

Distribution Panel Air Conditioning Chemical Storage Building

3

Distribution Panel Air Conditioning Operation Warehouse Building

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

66.68

78.45

1.000

0.85

0.53

N/A

113.23

N/A

2

4/C -

240

mm²

0.0984

0.0842

702

0.60

421.2

400

VAC

42.27

49.73

1.000

0.85

0.53

N/A

71.78

N/A

2

4/C -

185

mm²

0.1281

0.0851

608

0.60

364.8

F

400

VAC

53.65

63.12

1.000

0.85

0.53

N/A

91.10

N/A

3

4/C -

150

mm²

0.16

0.0843

813

0.60

487.8

3

F

400

VAC

66.68

78.45

1.000

0.85

0.53

N/A

113.23

N/A

2

4/C -

240

mm²

0.0984

0.0842

702

0.60

421.2

Distribution Panel Air Conditioning Office Building

3

F

400

VAC

37.74

39.73

1.000

0.95

0.31

N/A

57.34

N/A

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

Distribution Panel Air Conditioning Laboratory Building

3

F

400

VAC

40.08

42.19

1.000

0.95

0.31

N/A

60.90

N/A

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

Potable Water Pump

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Close Drain Pump

3

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

175 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

230 VAC UPS System - Feeder A

3

F

400

230 VAC UPS System - Feeder B

3

F

230 VAC UPS System - Bypass

3

HVAC package for Central Wellpad Substation

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

3

F

400

VAC

27.00

31.76

1.000

0.85

0.53

N/A

45.85

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

HVAC package for Central Wellpad Substation

3

F

400

VAC

27.00

31.76

1.000

0.85

0.53

N/A

45.85

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

HVAC package for Central Wellpad Substation

3

F

400

VAC

27.00

31.76

1.000

0.85

0.53

N/A

45.85

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

HVAC Auxiliry for Central Wellpad Substation

3

F

400

VAC

33.00

38.82

1.000

0.85

0.53

N/A

56.04

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

176 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Flare Package

3

F

400

Distribution Panel Outdoor Lighting Central Wellpad

3

F

Distribution Panel Indoor Lighting Central Wellpad

3

Distribution Panel Emergency Outdoor Lighting Central Wellpad

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.00

3.49

1.000

0.86

0.51

N/A

5.04

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

24.22

30.28

1.000

0.80

0.60

N/A

43.70

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

F

400

VAC

3.70

4.63

1.000

0.80

0.60

N/A

6.68

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

3

F

400

VAC

7.27

9.08

1.000

0.80

0.60

N/A

13.11

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Potable Water Pump

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Close Drain Pump

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

230 VAC UPS System - Feeder A

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

177 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

230 VAC UPS System - Feeder B

3

F

400

230 VAC UPS System - Bypass

3

F

HVAC package for East Wellpad Substation

3

HVAC package for East Wellpad Substation

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

F

400

VAC

27.00

31.76

1.000

0.85

0.53

N/A

45.85

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

3

F

400

VAC

27.00

31.76

1.000

0.85

0.53

N/A

45.85

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

HVAC package for East Wellpad Substation

3

F

400

VAC

27.00

31.76

1.000

0.85

0.53

N/A

45.85

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

HVAC package for East Wellpad Substation

3

F

400

VAC

33.00

38.82

1.000

0.85

0.53

N/A

56.04

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Flare Package

3

F

400

VAC

3.00

3.49

1.000

0.86

0.51

N/A

5.04

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Outdoor Lighting East Wellpad

3

F

400

VAC

36.00

45.00

1.000

0.80

0.60

N/A

64.95

N/A

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.2

178 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Indoor Lighting East Wellpad

3

F

400

Distribution Panel Emergency Outdoor Lighting East Wellpad

3

F

Potable Water Pump

3

Instrument Air Compressor

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.70

4.63

1.000

0.80

0.60

N/A

6.68

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

9.60

12.00

1.000

0.80

0.60

N/A

17.32

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

Gas Metering 230VAC UPS System Feeder A

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Gas Metering 230VAC UPS System Feeder B

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Gas Metering 230VAC UPS System Bypass

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

179 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Metering Station Building HVAC

3

F

400

Metering Station Building HVAC

3

F

Metering Station Building HVAC

3

Metering Station Building HVAC Auxiliary

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.20

6.50

1.000

0.80

0.60

N/A

9.38

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

400

VAC

5.20

6.50

1.000

0.80

0.60

N/A

9.38

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

F

400

VAC

5.20

6.50

1.000

0.80

0.60

N/A

9.38

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

3

F

400

VAC

5.20

6.50

1.000

0.80

0.60

N/A

9.38

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Indoor Lighting East Wellpad

3

F

400

VAC

16.43

19.33

1.000

0.85

0.53

N/A

27.90

N/A

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.6

Metering Station Building Socket Outlet

3

F

400

VAC

5.00

6.25

1.000

0.80

0.60

N/A

9.02

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

Distribution Panel Indoor Lighting East Wellpad

3

F

400

VAC

29.00

36.25

1.000

0.80

0.60

N/A

52.32

N/A

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.6

Distribution Panel Emergency Outdoor Lighting East Wellpad

3

F

400

VAC

7.00

8.24

1.000

0.85

0.53

N/A

11.89

N/A

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.6

180 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Metering Station Welding Outlet

3

F

400

Motor Space Heater (Continuous) GPF (Qty=73 ea)

1

M

Motor Space Heater (Intermittent) GPF (Qty=6 ea)

1

Motor Space Heater (Stand-by) GPF (Qty=105 ea) Space Heater for Close Drain Pump Central Wellpad

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

230

VAC

0.23

0.23

0.95

0.98

0.20

0.50

1.07

6.98

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

230

VAC

0.23

0.23

0.95

0.98

0.20

0.50

1.07

6.98

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

M

230

VAC

0.23

0.23

0.95

0.98

0.20

0.50

1.07

6.98

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

M

230

VAC

0.20

0.20

0.95

1.00

0.00

0.50

0.92

5.95

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

181 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Space Heater for Close Drain Pump East Wellpad

1

M

230

STG-A Space Heater

1

M

STG-B Space Heater

1

UCP STG-A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.20

0.21

1.00

0.95

0.31

0.50

0.92

5.95

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

230

VAC

2.25

2.25

0.900

1.00

0.00

0.50

10.87

70.65

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

M

230

VAC

2.25

2.25

0.900

1.00

0.00

0.50

10.87

70.65

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Battery Charger STG-A

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

UCP Essential Generator

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Battery Charger Essential Generator

1

F

210

VAC

1.00

1.05

1.000

0.95

0.31

N/A

5.01

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Motor Charging VCB for 420-SWG-0001

1

M

210

VAC

1.80

1.80

0.900

1.00

0.00

0.50

9.52

61.90

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

182 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Motor Charging VCB for 420-SWG-0002

1

M

210

PCS REMOTE I/O

1

F

HVAC CONTROL PANEL

1

ECMS NETWORK SERVER

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.00

3.00

0.900

1.00

0.00

0.50

15.87

103.17

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

ECMS PRINTER

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

LCP STG-A

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

SIS REMOTE I/O

1

F

210

VAC

0.70

0.70

0.900

1.00

0.00

N/A

3.70

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F&G REMOTE I/O

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

LOAD SHEDDING PANEL-A

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

183 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Emergency Outdoor Lighting Substation-1

1

F

210

TELECOM CABINET

1

F

HP BOILER CABINET

1

LP BOILER CABINET

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.20

7.20

0.900

1.00

0.00

N/A

38.10

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

MAIN ECMS-A PANEL

1

F

210

VAC

1.50

1.50

0.900

1.00

0.00

N/A

7.94

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FACP CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

UCP STG-B

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

184 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Battery Charger STG-B

1

F

210

UCP Emergency Diesel Generator

1

F

Battery Charger Emergency Generator

1

Motor Charging VCB for 420-SWG-0003

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.50

0.60

0.842

0.84

0.00

N/A

3.37

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Motor Charging VCB for 420-SWG-0004

1

M

210

VAC

0.50

0.50

0.900

1.00

0.00

0.50

2.65

17.20

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Motor Charging VCB for 420-SWG-0005

1

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS REMOTE I/O

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

SIS REMOTE I/O

1

F

210

VAC

0.70

0.70

0.900

1.00

0.00

N/A

3.70

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F&G REMOTE I/O

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

185 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

ECMS OPC SERVER

1

F

210

LCP STG-B

1

F

LCP ESSENTIAL GEN

1

ECMS WORK STATION

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

ECMS NETWORK SWITCH

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

LOAD SHEDDING PANEL-B

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

TELECOM CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

HP BOILER CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

LP BOILER CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

186 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

MAIN ECMS-B PANEL

1

F

210

PAGA CABINET

1

F

Motor Charging VCB : 231-SWG-0001

1

Motor Charging ACB : 231-SWG-0002

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.50

1.50

0.900

1.00

0.00

N/A

7.94

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

210

VAC

2.20

2.20

0.900

1.00

0.00

0.50

11.64

75.66

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

1

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

HVAC CONTROL PANEL

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

187 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

SIS REMOTE I/O PANEL

1

F

210

F&G REMOTE I/O PANEL

1

F

PAGA CABINET

1

VRU LCP

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

RECYLE GAS COMPRESSOR LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

HP/LP A FLARE LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

SALES GAS COMPRESSOR LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

TEG LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

188 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

SRU LCP

1

F

210

TGU LCP

1

F

UPS DB at Instrument Building 280A-B-9001

1

Motor Charging VCB : 231-SWG-0003

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

210

VAC

3.50

3.50

0.900

1.00

0.00

N/A

18.52

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

1

M

210

VAC

0.50

0.50

0.900

1.00

0.00

0.50

2.65

17.20

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

VRU LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

ECMS WORKSTATION

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

189 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

NETWORK SWITCH

1

F

210

Distribution Panel Emergency Outdoor Lighting Substation-2

1

F

SIS REMOTE I/O PANEL

1

Motor Charging VCB : 231-SWG-0004

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

8.80

8.80

0.900

1.00

0.00

N/A

46.56

N/A

1

2/C -

35

mm²

0.6690

0.0753

122

0.60

73.2

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FACP PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

RECYLE GAS COMPRESSOR LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

190 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

SALES GAS COMPRESSOR LCP

1

F

210

TEG LCP

1

F

SRU LCP

1

TGU LCP

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

Motor Charging VCB 280-SWG-0001

1

M

210

VAC

1.40

1.40

0.900

1.00

0.00

0.50

7.41

48.15

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Motor Charging ACB : 280-SWG-0002

1

M

210

VAC

0.50

0.50

0.900

1.00

0.00

0.50

2.65

17.20

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

HVAC CONTROL PANEL

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

191 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

ECMS PANEL

1

F

210

PAGA CABINET

1

F

SIS REMOTE I/O PANEL (280A-B9001)

1

F&G REMOTE I/O PANEL

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

NETWORK SWITCH

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

UPS DB at Instrument Building 280B-B-9001

1

F

210

VAC

3.50

3.50

0.900

1.00

0.00

N/A

18.52

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Motor Charging VCB : 280-SWG-0003

1

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

192 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

SIS REMOTE I/O PANEL (280A-B9001)

1

F

210

F&G REMOTE I/O PANEL

1

F

ECMS PANEL

1

ECMS WORKSTATION

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

NETWORK SWITCH

1

F

210

VAC

0.80

0.80

0.900

1.00

0.00

N/A

4.23

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Distribution Panel Emergency Outdoor Lighting Substation-3

1

F

210

VAC

10.40

10.40

0.900

1.00

0.00

N/A

55.03

N/A

1

2/C -

35

mm²

0.6690

0.0753

122

0.60

73.2

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

193 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

FACP PANEL

1

F

210

Motor Charging VCB 480-SWG-0001

1

M

Motor Charging ACB : 480-SWG-0002

1

PCS REMOTE I/O PANEL

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

2.00

2.00

0.900

1.00

0.00

0.50

10.58

68.78

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

HVAC CONTROL PANEL

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

ECMS PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

INSTRUMENT AIR COMPRESSORA LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

INSTRUMENT AIR COMPRESSORB LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

194 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

INSTRUMENT AIR COMPRESSORC LCP

1

F

210

SIS REMOTE I/O PANEL

1

F

F&G REMOTE I/O PANEL

1

Distribution Panel Emergency Outdoor Lighting Substation-4

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

4.00

4.00

0.900

1.00

0.00

N/A

21.16

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

NETWORK SWITCH

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FACP PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

195 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

AIR MANAGER LCP

1

F

210

SIS REMOTE I/O PANEL

1

F

F&G REMOTE I/O PANEL

1

ECMS PANEL

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS WORKSTATION

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FACP PANEL

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

INSTRUMENT AIR DRYER-A LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

INSTRUMENT AIR DRYER-B LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

INSTRUMENT AIR DRYER-C LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

196 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

FIRE WATER PANEL BATTERY CHARGER-A

1

F

210

FIRE WATER PANEL BATTERY CHARGER-B

1

F

PCS REMOTE I/O PANEL

1

TELECOM CABINET

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS SYSTEM CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

SIS SYSTEM CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

197 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

F&G SYSTEM CABINET

1

F

210

FACP PANEL

1

F

LDS SYSTEM COMPUTER

1

OFFICE APPLICATION COMPUTER

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

MM SERVER

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PROCESS MONITORING COMP

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

RTS SERVER

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FO BACKBONE PATCH PANEL

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

MOM SYSTEM CABINET 2

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

198 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

SOE WORKSTATION

1

F

210

F&G MONITOR WORKSTATION

1

F

FIRE STATION MONITOR

1

HVAC CONTROL PANEL

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.60

0.60

0.900

1.00

0.00

N/A

3.17

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS-A PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS-A WORKSTATION

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

CWE SYSTEM CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

MOM SYSTEM CABINET 1

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

PAGA CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

199 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

OPERATOR TRAINING SYSTEM CABINET

1

F

210

PCS SYSTEM CABINET

1

F

SIS SYSTEM CABINET

1

F&G SYSTEM CABINET

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.60

0.60

0.900

1.00

0.00

N/A

3.17

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FACP PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

CCTV SERVER

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

EDMS SERVER

1

F

210

VAC

1.30

1.30

0.900

1.00

0.00

N/A

6.88

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

MIS BACK-UP SERVER

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

200 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

APMS SERVER

1

F

210

EPMS SERVER

1

F

HISTORIAN OPC SERVER

1

PRINTER

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

1.30

1.30

0.900

1.00

0.00

N/A

6.88

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

1

F

210

VAC

0.69

0.69

0.900

1.00

0.00

N/A

3.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

FO BACKBONE PATCH PANEL

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

CCTV SYSTEM

1

F

210

VAC

1.50

1.50

0.900

1.00

0.00

N/A

7.94

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

CCTV MONITOR

1

F

210

VAC

0.80

0.80

0.900

1.00

0.00

N/A

4.23

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PAGA STATION

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS PLASMA TV

1

F

210

VAC

1.87

1.87

0.900

1.00

0.00

N/A

9.87

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

201 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

MOM SYSTEM CABINET 2

1

F

210

NETWORK SWITCH

1

F

SIS CONSOLE

1

F&G CONSOLE

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

210

VAC

1.60

1.60

0.900

1.00

0.00

N/A

8.47

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS-B PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

PCS EWS

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ESD/F&G EWS

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

AMS EWS

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

CWE SYSTEM CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

202 of 522

Amp

A

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

MOM SYSTEM CABINET 1

1

F

210

OPERATOR TRAINING SYSTEM CABINET

1

F

PAGA CABINET

1

Distribution Panel Emergency Outdoor Lighting Central Wellpad

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

210

VAC

0.60

0.60

0.900

1.00

0.00

N/A

3.17

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

1

F

210

VAC

10.80

10.80

0.900

1.00

0.00

N/A

57.14

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

11 kV Switchgear Infrastructure Substation (BUS A)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Back-Up Genset Charger

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC Infrastructure Substation (BUS A)

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

203 of 522

Amp

B

B

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

ECMS Workstation

1

F

210

F&G REMOTE I/O PANEL

1

F

Telecom UPS DB

1

Back-Up Genset Charger

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

F

210

VAC

13.40

13.40

0.900

1.00

0.00

N/A

70.90

N/A

1

2/C -

35

mm²

0.6690

0.0753

122

0.60

73.2

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC Infrastructure Substation (BUS B)

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

11 kV Switchgear Infrastructure Substation (BUS B)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

NETWORK SWITCH

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

204 of 522

Amp

A

A

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

F&G REMOTE I/O PANEL

1

F

210

Telecom Cabinet

1

F

RTU/SCADA Cabinet

1

Flow Comp Cabinet

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC Well Pad Central (BUS A)

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS PC

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

11 kV Switchgear Central Well Pad Substation (BUS A)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

205 of 522

Amp

B

B

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Back-Up Genset Charger

1

F

210

Telecom Cabinet

1

F

RTU/SCADA Cabinet

1

Flow Comp Cabinet

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC Well Pad Central (BUS B)

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

11 kV Switchgear Central Well Pad Substation (BUS B)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Distribution Panel Emergency Outdoor Lighting Central Wellpad

1

F

210

VAC

5.60

5.60

0.900

1.00

0.00

N/A

29.63

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

206 of 522

Amp

A

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

FLARE PANEL

1

F

210

HVAC CONTROL PANEL

1

F

Telecom Cabinet

1

RTU/SCADA Cabinet

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Flow Comp Cabinet

1

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC East Well Pad Substation (BUS A)

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS PC

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

207 of 522

Amp

A

B

B

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

11 kV Switchgear East Well Pad Substation (BUS A)

1

F

210

Back-Up Genset Charger

1

F

Telecom Cabinet

1

RTU/SCADA Cabinet

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Flow Comp Cabinet

1

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC East Well Pad Substation (BUS B)

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

11 kV Switchgear East Well Pad Substation (BUS B)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

208 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Distribution Panel Emergency Outdoor Lighting East Wellpad

1

F

210

FLARE PANEL

1

F

HVAC CONTROL PANEL

1

Telecom Cabinet

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

9.60

9.60

0.900

1.00

0.00

N/A

50.79

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

RTU/SCADA Cabinet

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Flow Computer System

1

F

210

VAC

1.80

1.80

0.900

1.00

0.00

N/A

9.52

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Laser Jet Printer

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Sales Gas Ccmputer

1

F

210

VAC

0.70

0.70

0.900

1.00

0.00

N/A

3.70

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

209 of 522

Amp

A

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

ECMS PC

1

F

210

ECMS Panel

1

F

Back-Up Genset Charger

1

400 VAC Switchgear/MCC Sales Gas Metering Substation (BUS A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

11 kV Switchgear Sales Gas Metering Substation (BUS A)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Telecom Cabinet

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

RTU/SCADA Cabinet

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Dot Maztrix Printer

1

F

210

VAC

0.10

0.10

0.900

1.00

0.00

N/A

0.53

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

210 of 522

Amp

B

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Flow Computer System

1

F

210

ECMS Panel

1

F

Back-Up Genset UCP

1

Distribution Panel Emergency Outdoor Lighting Sales Gas Metering

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.80

1.80

0.900

1.00

0.00

N/A

9.52

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

210

VAC

4.00

4.00

0.900

1.00

0.00

N/A

21.16

N/A

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

HVAC CONTROL PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

400 VAC Switchgear/MCC Sales Gas Metering Substation (BUS B)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

11 kV Switchgear Sales Gas Metering Substation (BUS B)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

211 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

A

11 kV Switchgear: 420-SWG-0001A

1

F

108

B

11 kV Switchgear: 420-SWG-0001B

1

F

A

400 VAC MCC : 420-MCC-0003A

1

B

400 VAC MCC : 420-MCC-0003B

A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400 VAC MCC : 420-MCC-0005A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

A

400 VAC MCC : 420-MCC-0004A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

B

400 VAC MCC : 420-MCC-0004B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

212 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

B

400 VAC MCC : 420-MCC-0005B

1

F

108

A

6,6 kV Switchgear: 420-SWG-0002A

1

F

B

6,6 kV Switchgear: 420-SWG-0002B

1

TRAFO 420-TRF-0001A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

TRAFO 420-TRF-0001B

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

TRAFO 420-TRF-0002A

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

TRAFO 420-TRF-0002B

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

TRAFO 420-TRF-0003A

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

TRAFO 420-TRF-0003B

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

213 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

6.6 kV Switchgear / MCC MV 1A Substation-2 (Train-A)

1

F

108

6.6 kV Switchgear / MCC MV 1B Substation-2 (Train-A)

1

F

400 VAC Switchgear / MCC LV 2A Substation-2 (Train-A)

1

400 VAC Switchgear / MCC LV 2B Substation-2 (Train-A)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400 VAC Switchgear / MCC LV 3A Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400 VAC Switchgear / MCC LV 3B Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400 VAC Switchgear / MCC LV 4A Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

400 VAC Switchgear / MCC LV 4B Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

214 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

TRAFO 231-TRF-0001A

1

F

108

TRAFO 231-TRF-0001B

1

F

TRAFO 231-TRF-0002A

1

TRAFO 231-TRF-0002B

A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

6,6 kV Switchgear: 280-SWG-0001A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

B

6,6 kV Switchgear: 280-SWG-0001B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

A

400 VAC MCC : 280-MCC-0002A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

B

400 VAC MCC : 280-MCC-0002B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

215 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

A

400 VAC MCC : 280-MCC-0003A

1

F

108

B

400 VAC MCC : 280-MCC-0003B

1

F

TRAFO 280-TRF-0001A

1

TRAFO 280-TRF-0001B

A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

6,6 kV Switchgear: 480-SWG-0001A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

B

6,6 kV Switchgear: 480-SWG-0001B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

A

400 VAC MCC : 480-MCC-0002A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

B

400 VAC MCC : 480-MCC-0002B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

216 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

TRAFO 480-TRF-0001A

1

F

108

TRAFO 480-TRF-0001B

1

F

Battery Rack for Substation-1 230 VAC UPS System - Feeder A

1

Battery Rack for Substation-1 230VAC UPS System - Feeder B

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

220

VDC

61.04

61.04

0.800

1.00

0.00

N/A

346.80

N/A

2

2/C -

185

mm²

0.1281

0.0720

608

0.60

364.8

1

F

220

VDC

61.04

61.04

0.800

1.00

0.00

N/A

346.80

N/A

2

2/C -

185

mm²

0.1281

0.0720

608

0.60

364.8

Battery Rack for Substation-2 230 VAC UPS System - Feeder A

1

F

220

VDC

25.43

25.43

0.800

1.00

0.00

N/A

144.50

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

Battery Rack for Substation-2 230VAC UPS System - Feeder B

1

F

220

VDC

25.43

25.43

0.800

1.00

0.00

N/A

144.50

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

Battery Rack for Substation-3 230 VAC UPS System - Feeder A

1

F

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

217 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Battery Rack for Substation-3 230VAC UPS System - Feeder B

1

F

220

Battery Rack for Substation-4 230 VAC UPS System - Feeder A

1

F

Battery Rack for Substation-4 230VAC UPS System - Feeder B

1

Battery Rack for Control Building 230 VAC UPS System - Feeder A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

F

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

1

F

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

Battery Rack for Control Building 230VAC UPS System - Feeder B

1

F

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

Battery Rack for Infrastructure 230 VAC UPS System - Feeder A

1

F

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

Battery Rack for Infrastructure 230VAC UPS System - Feeder B

1

F

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

Battery Rack for Central Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

218 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Battery Rack for Central Wellpad 230VAC UPS System - Feeder B

1

F

220

Battery Rack for East Wellpad 230 VAC UPS System - Feeder A

1

F

Battery Rack for East Wellpad 230VAC UPS System - Feeder B

1

Battery Rack for Gas Metering 230 VAC UPS System - Feeder A

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

1

F

220

VDC

20.44

20.44

0.800

1.00

0.00

N/A

116.11

N/A

1

2/C -

95

mm² 0.2470 0.0711

211

0.60

126.6

Battery Rack for Gas Metering 230VAC UPS System - Feeder B

1

F

220

VDC

20.44

20.44

0.800

1.00

0.00

N/A

116.11

N/A

1

2/C -

95

mm² 0.2470 0.0711

211

0.60

126.6

Battery Rack for Substation-1 110 VDC UPS System - Feeder A

1

F

110

VDC

20.35

20.35

0.800

1.00

0.00

N/A

231.20

N/A

1

2/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

Battery Rack for Substation-1 110VDC UPS System - Feeder B

1

F

110

VDC

20.35

20.35

0.800

1.00

0.00

N/A

231.20

N/A

1

2/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

219 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Battery Rack for Substation-2 110 VDC UPS System - Feeder A

1

F

110

Battery Rack for Substation-2 110VDC UPS System - Feeder B

1

F

Battery Rack for Substation-3 110 VDC UPS System - Feeder A

1

Battery Rack for Substation-3 110VDC UPS System - Feeder B

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

16.48

16.48

0.800

1.00

0.00

N/A

187.30

N/A

1

2/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

110

VDC

16.48

16.48

0.800

1.00

0.00

N/A

187.30

N/A

1

2/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

F

110

VDC

12.72

12.72

0.800

1.00

0.00

N/A

144.50

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

1

F

110

VDC

12.72

12.72

0.800

1.00

0.00

N/A

144.50

N/A

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

Battery Rack for Substation-4 110 VDC UPS System - Feeder A

1

F

110

VDC

8.85

8.85

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Battery Rack for Substation-4 110VDC UPS System - Feeder B

1

F

110

VDC

8.85

8.85

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Battery Rack for Central Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Battery Rack for Central Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

220 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Battery Rack for East Wellpad 230 VAC UPS System - Feeder A

1

F

220

Battery Rack for East Wellpad 230VAC UPS System - Feeder B

1

F

400W Normal HPS Floodlight

3

400W Emergency HPS Floodlight

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

F

400

VAC

25.60

26.12

0.950

0.98

0.20

N/A

39.69

N/A

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

3

F

400

VAC

0.40

0.41

0.950

0.98

0.20

N/A

0.62

N/A

1

4/C -

2.5

mm²

9.45

0.1086

29

0.60

17.4

150W Normal HPS Wellglass

3

F

400

VAC

0.15

0.15

0.950

0.98

0.20

N/A

0.23

N/A

1

4/C -

2.5

mm²

9.45

0.1086

29

0.60

17.4

250W HPS Streetlight

3

F

400

VAC

0.25

0.26

0.950

0.98

0.20

N/A

0.39

N/A

1

4/C -

2.5

mm²

9.45

0.1086

29

0.60

17.4

221 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

2x36 W Normal Fluorescent Light

1

F

230

2x36 W Emergency Fluorescent Light (Muster Point)

1

F

250W Normal HPS Floodlight (16 ea)

3

250W Normal HPS Floodlight (14 ea)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.07

0.07

0.900

1.00

0.00

N/A

0.35

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

230

VAC

0.07

0.07

0.900

1.00

0.00

N/A

0.35

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

400

VAC

4.00

4.00

0.900

1.00

0.00

N/A

6.42

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

3

F

394

VAC

3.50

3.50

0.900

1.00

0.00

N/A

5.70

N/A

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.6

250W Normal HPS Floodlight (12 ea)

3

F

394

VAC

3.00

3.00

0.900

1.00

0.00

N/A

4.89

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

250W Normal HPS Floodlight (10 ea)

3

F

392

VAC

2.50

2.50

0.900

1.00

0.00

N/A

4.09

N/A

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.6

250W Normal HPS Floodlight (8 ea)

3

F

391

VAC

2.00

2.00

0.900

1.00

0.00

N/A

3.28

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

222 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

250W Normal HPS Floodlight (6 ea)

3

F

389

250W Normal HPS Floodlight (4 ea)

3

F

250W Normal HPS Floodlight (2 ea)

3

Distribution Panel Indoor Lighting & Small Power Guard House-Banyu Urip

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.50

1.50

0.900

1.00

0.00

N/A

2.47

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

388

VAC

1.00

1.00

0.900

1.00

0.00

N/A

1.65

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

386

VAC

0.50

0.50

0.900

1.00

0.00

N/A

0.83

N/A

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

3

F

400

VAC

4.40

5.00

0.912

0.88

0.47

N/A

7.91

N/A

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.4

Indoor Lighting Fluoroscent 2x36 W

1

F

230

VAC

0.07

0.09

0.900

0.80

0.60

N/A

0.43

N/A

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

Air Conditioning

1

F

230

VAC

1.50

1.88

0.900

0.80

0.60

N/A

9.06

N/A

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

223 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

To Description

3 Ph / 1 Ph

F/M

Outdoor Lighting Floodlight 2x400 W

1

F

230

Socket Outlet

1

F

PCS System

1

PCS System (Redundant)

Volt

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.60

2.00

0.710

0.80

0.60

N/A

12.25

N/A

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

230

VAC

1.20

1.50

0.710

0.80

0.60

N/A

9.19

N/A

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.4

F

230

VAC

5.00

5.68

0.912

0.88

0.47

N/A

27.09

N/A

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

1

F

230

VAC

0.95

0.95

0.900

1.00

0.00

N/A

4.59

N/A

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.6

CWS Workstation

1

F

230

VAC

0.657

0.657

0.900

1.00

0.00

N/A

3.17

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

Flow Comp System

1

F

230

VAC

0.51

0.51

0.900

1.00

0.00

N/A

2.46

N/A

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.2

224 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

To Description

3 Ph / 1 Ph

F/M

Volt

kW

kVA

p.u

p.u

ISC x √t k

0N for Feeder and C60H for Motor)

of load 225 of 522

p.u

p.u

Amp

Amp

No.of Run

Impedace Type

Current Carrying Capaci CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY Load Data Voltage No. Equip System, Phase Type Vin

Power



Cos φ

Sin φ

Selected Cable

Cos β (Start)

IFL

Ist

To Description

3 Ph / 1 Ph

F/M

Volt

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

No.of Run

Impedace Type R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

eater cable can be seen in the Doc. No. JTB-SF-E-LST-900-00013~00018, Electrical Cable Schedule.

mber of lighting fixtures will sum in the Electrical MTO.

ate

wer

Sin φ

=Sqrt (1-Cos² φ))

Lmax (Maximum Cable Length (m)) Ist (Motor Starting Current (Amp))

n (Quantity of cables in parallel per phase)

AG (Above Ground Installation)

 (Efficiency)

UG (Under Ground Installation)

Isc (Short circuit current )

226 of 522

Current Carrying Capaci CCC

Corretion Factor

Derate

Amp

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

A

11 kV POWER CABLES

1

P-420-GS-9002A-01/02

420-GS-9002A

Steam Turbine Generator-A

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

VAC

6,500

2

P-420-GS-9002B-01/02

420-GS-9002B

Steam Turbine Generator-B

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

VAC

6,500

3

P-420-V-9002

420-V-9002

Essential Power Generator

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

3

F

11,000

VAC

3,000

4

P-420-TRF-0001A-01/02/03

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

420-TRF-0001A

11 / 6.6 kV Transformer A Substation-1 (Power Generation)

3

F

11,000

VAC

11,520

420-TRF-0001B

11 / 6.6 kV Transformer B Substation-1 (Power Generation)

3

F

11,000

VAC

11,520

5

P-420-TRF-0001B-01/02/03

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

6

P-800-SWG-0001

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

800-SWG-0001

11 kV Switchgear Infrastructure

3

F

11,000

VAC

2,223

7

P-800-TRF-0001

800-SWG-0001

11 kV Switchgear Infrastructure

800-TRF-0001

11 / 0.42 kV Transformer Infrastructure

3

F

11,000

VAC

2,400

227 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

211-SWG-0001

11 kV Switchgear Central Well Pad Substation

3

F

11,000

VAC

389

Volt

kW

8

P-211-SWG-0001

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

9

P-211-TRF-0001

211-SWG-0001

11 kV Switchgear Central Well Pad Substation

211-TRF-0001

11 / 0.42 kV Central Wellpad Transformer

3

F

11,000

VAC

384

10

P-211-SWG-0002

211-SWG-0001

11 kV Switchgear Central Well Pad Substation

212-SWG-0001

11 kV Switchgear East Well Pad Substation

3

F

11,000

VAC

384

11

P-212-SWG-0001

420-SWG/MCC-0001

11 kV Switchgear Substation-1 (Power Generation)

212-SWG-0001

11 kV Switchgear East Well Pad Substation

3

F

11,000

VAC

389

12

P-212-TRF-0001

212-SWG-0001

11 kV Switchgear East Well Pad Substation

212-TRF-0001

11 / 0.42 kV East Wellpad Transformer

3

F

11,000

VAC

384

13

P-710-SWG-0001

SWG823081 (PB-01S)

11 kV Switchgear Banyu Urip Main Gate House Area

710-SWG-0001

11 kV Switchgear Sales Gas Metering Substation

3

F

11,000

VAC

166

14

P-710-TRF-0001

710-SWG-0001

11 kV Switchgear Sales Gas Metering Substation

710-TRF-0001

11 / 0.42 kV Transformer Sales Gas Metering

3

F

11,000

VAC

120

B

6.6 kV POWER CABLES Substation-1 (Area 420 - Power Generation Substation) 228 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

1

P-420-TRF-0002A

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

420-TRF-0002A

6.6/0.4 kV Main Transformer

3

F

6,600

VAC

1,200

2

P-420-TRF-0002B

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

420-TRF-0002B

6.6/0.4 kV Main Transformer

3

F

6,600

VAC

1,200

3

P-420-TRF-0003A

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

420-TRF-0003A

6.6/0.4 kV Essential Transformer

3

F

6,600

VAC

1,536

4

P-420-TRF-0003B

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

420-TRF-0003B

6.6/0.4 kV Essential Transformer

3

F

6,600

VAC

1,536

Substation-2 (Area 231 - Train-A Substation) 5

P-231-SWG/MCC-0001A01/02

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-2 (Train-A)

3

F

6,600

VAC

4,840

6

P-231-SWG/MCC-0001B01/02

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-2 (Train-A)

3

F

6,600

VAC

4,840

7

P-231-TRF-0001A

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-2 (Train-A)

231-TRF-0001A

6.6/0.4 kV Transformer 1A Substation-2 (Train-A)

3

F

6,600

VAC

960

8

P-231-TRF-0001B

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-2 (Train-A)

231-TRF-0001B

6.6/0.4 kV Transformer 1B Substation-2 (Train-A)

3

F

6,600

VAC

960

229 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

9

P-231-TRF-0002A-01/02

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-2 (Train-A)

231-TRF-0002A

6.6/0.4 kV Transformer 2A Substation-2 (Train-A)

3

F

6,600

VAC

3,840

10

P-231-TRF-0002B-01/02

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-2 (Train-A)

231-TRF-0002B

6.6/0.4 kV Transformer 2B Substation-2 (Train-A)

3

F

6,600

VAC

3,840

Substation-3 (Area 280 - Train-B Substation) 11

P-280-SWG/MCC-0001A01/02

420-SWG/MCC-0002 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

3

F

6,600

VAC

3,842

12

P-280-SWG/MCC-0001B01/02

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

3

F

6,600

VAC

3,842

13

P-280-TRF-0001A-01/02

280-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-3

280-TRF-0001A

6.6/0.4 kV Transformer A Substation3 (Train-B)

3

F

6,600

VAC

3,456

14

P-280-TRF-0001B-01/02

280-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-3

280-TRF-0001B

6.6/0.4 kV Transformer B Substation3 (Train-B)

3

F

6,600

VAC

3,456

6.6 kV Switchgear / MCC MV 1A Substation-1 (Power Generation)

480-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 2A Substation-4 (Utility)

3

F

6,600

VAC

1,798

Substation-4 (Area 480 - Utility Substation) 15

P-480-SWG/MCC-0001 A

420-SWG/MCC-0002 (BUS A)

230 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

16

P-480-SWG/MCC-0001 B

420-SWG/MCC-0002 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-1 (Power Generation)

480-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 2B Substation-4 (Utility)

3

F

6,600

VAC

1,798

17

P-480-TRF-0001A

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

480-TRF-0001A

6.6/0.4 kV Transformer Substation-4 (Utility)

3

F

6,600

VAC

768

18

P-480-TRF-0001B

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

480-TRF-0001B

6.6/0.4 kV Transformer Substation-4 (Utility)

3

F

6,600

VAC

768

DELETEP-224-C-9001-3 A

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-3 A

VRU Compressor (3rd Stage) MotorA

3

M

6,600

VAC

300.00

DELETEP-224-C-9001-3 B

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-3 B

VRU Compressor (3rd Stage) MotorB

3

M

6,600

VAC

300.00

DELETEP-224-C-9001-4 A

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-4 A

VRU Compressor (4th Stage) MotorA

3

M

6,600

VAC

750.00

DELETEP-224-C-9001-4 B

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-4 B

VRU Compressor (4th Stage) MotorB

3

M

6,600

VAC

750.00

Vapor Recovery Unit (VRU)

Acid Gas Enrichment (AGE) Unit - Train A

231 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

19

P-280A-P-5001 A

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

280A-P-5001A

Lean Amine Pump-A (Train A)

3

M

6,600

VAC

200.00

20

P-280A-P-5001 B

231-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-2 (Train-A)

280A-P-5001B

Lean Amine Pump-B (Train A)

3

M

6,600

VAC

200.00

Acid Gas Enrichment (AGE) Unit - Train B 21

P-280B-P-3001 A

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

280B-P-3001A

Lean Amine Pump-A (Train B)

3

M

6,600

VAC

200.00

22

P-280B-P-3001 B

280-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-3 (Train-B)

280B-P-3001B

Lean Amine Pump-B (Train B)

3

M

6,600

VAC

200.00

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

410-P-9011

HP BWF Start-Up Pump

3

M

6,600

VAC

300.00

6.6 kV Switchgear/MCC Substation-4 (Utility)

440-V-9001 A

Instrument Air Compressor Package Motor A

3

M

6,600

VAC

355.00

Boiler Feed Water (BFW) 23

P-410-P-9011

Instrument Air / Nitrogen Package 24

P-440-V-9001 A

480-SWG/MCC-0001

232 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

25

P-440-V-9001 B

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

440-V-9001 B

Instrument Air Compressor Package Motor B

3

M

6,600

VAC

355.00

26

P-440-V-9001 C

480-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

440-V-9001 C

Instrument Air Compressor Package Motor C

3

M

6,600

VAC

355.00

410-SWG/MCC-0001

6.6 kV Switchgear/MCC Substation-4 (Utility)

490-P-9007

Firewater Pump - Electric

3

M

6,600

VAC

300.00

Fire Water System DELETED P-490-P-9007

C

0.4 kV POWER CABLES Inlet Separation Unit

1

P-221-E-9001-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-1

Inlet Cooler Fan 1

3

M

400

VAC

15.00

2

P-221-E-9001-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-2

Inlet Cooler Fan 2

3

M

400

VAC

15.00

233 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

3

P-221-E-9001-3

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-3

Inlet Cooler Fan 3

3

M

400

VAC

15.00

4

P-221-E-9001-4

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-4

Inlet Cooler Fan 4

3

M

400

VAC

15.00

5

P-221-E-9001-5

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-5

Inlet Cooler Fan 5

3

M

400

VAC

15.00

6

P-221-E-9001-6

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-6

Inlet Cooler Fan 6

3

M

400

VAC

15.00

7

P-221-E-9001-7

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-7

Inlet Cooler Fan 7

3

M

400

VAC

15.00

8

P-221-E-9001-8

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

221-E-9001-8

Inlet Cooler Fan 8

3

M

400

VAC

15.00

Produced Water Storage 9

P-222-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9001 A

Produced Water Transfer Pump A

3

M

400

VAC

5.50

10

P-222-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9001 B

Produced Water Transfer Pump B

3

M

400

VAC

5.50

234 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

11

P-222-P-9002 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9002 A

Pipeline Produced Water Transfer Pump A

3

M

400

VAC

75.00

12

P-222-P-9002 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9002 B

Pipeline Produced Water Transfer Pump B

3

M

400

VAC

75.00

13

P-222-P-9003

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

222-P-9003

Skim Oil Pump

3

M

400

VAC

0.37

Condensate Storage 14

P-223-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

223-P-9001 A

Pipeline Condensate Transfer Pump A

3

M

400

VAC

37.00

15

P-223-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

223-P-9001 B

Pipeline Condensate Transfer Pump B

3

M

400

VAC

37.00

DELETEP-224-C-9001-1 A-01/02

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-1 A

VRU Compressor (1st Stage) MotorA

3

M

0

VAC

132.00

DELETEP-224-C-9001-1 B-01/02

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-1 B

VRU Compressor (1st Stage) MotorB

3

M

0

VAC

132.00

Vapor Recovery Unit (VRU)

235 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

16

P-224-E-9001-1 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-1 A

VRU Intercooler-A (1st Stage) Fan-1

3

M

400

VAC

4.00

17

P-224-E-9001-2 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-2 A

VRU Intercooler-A (1st Stage) Fan-2

3

M

400

VAC

4.00

18

P-224-E-9001-1 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-1 B

VRU Intercooler-B (1st Stage) Fan-1

3

M

400

VAC

4.00

19

P-224-E-9001-2 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9001-2 B

VRU Intercooler-B (1st Stage) Fan-2

3

M

400

VAC

4.00

DELETEP-224-C-9001-2 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-2 A

VRU Compressor (2nd Stage) MotorA

3

M

0

VAC

75.00

DELETEP-224-C-9001-2 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-C-9001-2 B

VRU Compressor (2nd Stage) MotorB

3

M

0

VAC

75.00

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9002 A

VRU Intercooler-A (2nd Stage) Fan-1

3

M

400

VAC

1.50

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9002-2 A

VRU Intercooler-A (2nd Stage) Fan-2

3

M

0

VAC

1.10

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9002 B

VRU Intercooler-B (2nd Stage) Fan-1

3

M

400

VAC

1.50

20

P-224-E-9002 A

DELETEP-224-E-9002-2 A

21

P-224-E-9002 B

236 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

DELETEP-224-E-9002-2 B

22

P-224-E-9003 A

DELETEP-224-E-9003-2 A

23

P-224-E-9003 B

DELETEP-224-E-9003-2 B

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9002-2 B

VRU Intercooler-B (2nd Stage) Fan-2

3

M

0

VAC

1.10

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9003 A

VRU Intercooler-A (3rd Stage) Fan-1

3

M

400

VAC

2.20

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9003-2 A

VRU Intercooler-A (3rd Stage) Fan-2

3

M

0

VAC

2.20

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9003 B

VRU Intercooler-B (3rd Stage) Fan-1

3

M

400

VAC

2.20

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-E-9003-2 B

VRU Intercooler-B (3rd Stage) Fan-2

3

M

0

VAC

2.20

Volt

kW

24

P-224-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-P-9001 A

VRU Knockout Pump A

3

M

400

VAC

0.37

25

P-224-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-P-9001 B

VRU Knockout Pump B

3

M

400

VAC

0.37

26

P-224-C-9001-01/02

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

224-C-9001

Driver Motor for VRU Compressor

3

M

400

VAC

160.00

Dew Point Control 237 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

27

P-231-P-9001

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

231-P-9001

Methanol Injection Pump

3

M

400

VAC

3.00

Volt

kW

Condensate Stabilization 28

P-232-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-P-9001 A

Condensate Reflux Pump A

3

M

400

VAC

7.50

29

P-232-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-P-9001 B

Condensate Reflux Pump B

3

M

400

VAC

7.50

30

P-232-E-9001-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9001-1

Condensate Cooler Fan-1

3

M

400

VAC

4.00

31

P-232-E-9001-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9001-2

Condensate Cooler Fan-2

3

M

400

VAC

4.00

32

P-232-P-9002

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-P-9002

Condensate Stabilizer Recycle Liquid Pump

3

M

400

VAC

7.50

33

P-232-E-9003-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9003-1

Recycle Gas Compressor Cooler Fan-1

3

M

400

VAC

3.00

34

P-232-E-9003-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

232-E-9003-2

Recycle Gas Compressor Cooler Fan-2

3

M

400

VAC

3.00

238 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Ethylene Glycol (EG) Regeneration 35

P-233-P-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9001 A

EG Circulator Pump A

3

M

400

VAC

18.50

36

P-233-P-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9001 B

EG Circulator Pump B

3

M

400

VAC

18.50

37

P-233-P-9002 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9002 A

EG Reflux Pump A

3

M

400

VAC

0.37

38

P-233-P-9002 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9002 B

EG Reflux Pump B

3

M

400

VAC

0.37

39

P-233-P-9003 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9003 A

Produced Water Booster Pump A

3

M

400

VAC

0.75

40

P-233-P-9003 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9003 B

Produced Water Booster Pump B

3

M

400

VAC

0.75

41

P-233-P-9004

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9004

EG Makeup Pump

3

M

400

VAC

18.50

42

P-233-C-9001 A

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-C-9001 A

EG Regeneration Overhead Gas Compressor A

3

M

400

VAC

75.00

239 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

43

P-233-C-9001 B

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-C-9001 B

EG Regeneration Overhead Gas Compressor B

3

M

400

VAC

75.00

44

P-233-E-9005-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-E-9005-1

EG Regeneration Tower Cooler Fan-1

3

M

400

VAC

2.20

45

P-233-E-9005-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-E-9005-2

EG Regeneration Tower Cooler Fan-2

3

M

400

VAC

2.20

46

P-233-P-9005

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

233-P-9005

Glycol Drain Return Pump

3

M

400

VAC

0.75

Propylene - Refrigeration Unit 47

P-234-E-9001-1

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-1

Propylene Condenser Fan 1

3

M

400

VAC

7.50

48

P-234-E-9001-2

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-2

Propylene Condenser Fan 2

3

M

400

VAC

7.50

49

P-234-E-9001-3

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-3

Propylene Condenser Fan 3

3

M

400

VAC

7.50

50

P-234-E-9001-4

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-4

Propylene Condenser Fan 4

3

M

400

VAC

7.50

240 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

51

P-234-E-9001-5

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-5

Propylene Condenser Fan 5

3

M

400

VAC

7.50

52

P-234-E-9001-6

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-6

Propylene Condenser Fan 6

3

M

400

VAC

7.50

53

P-234-E-9001-7

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-6

Propylene Condenser Fan 7

3

M

400

VAC

7.50

54

P-234-E-9001-8

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

234-E-9001-6

Propylene Condenser Fan 8

3

M

400

VAC

7.50

55

P-234-CA-9001-1 A

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-1 A

Propylene Compressor A (1st Stage) Auxiliary Load

3

M

400

VAC

45.00

56

P-234-CA-9001-2 A

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-2 A

Propylene Compressor A (2nd Stage) Auxiliary Load

3

M

400

VAC

45.00

57

P-234-CA-9001-1 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-1 B

Propylene Compressor B (1st Stage) Auxiliary Load

3

M

400

VAC

45.00

58

P-234-CA-9001-2 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

234-CA-9001-2 B

Propylene Compressor B (2nd Stage) Auxiliary Load

3

M

400

VAC

45.00

AGRU-A 241 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

59

P-240A-E-1001-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-1

Lean Solvent Air Cooler-A (AGRU A) #1

3

M

400

VAC

55.00

60

P-240A-E-1001-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-2

Lean Solvent Air Cooler-A (AGRU A) #2

3

M

400

VAC

55.00

61

P-240A-E-1001-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-3

Lean Solvent Air Cooler-A (AGRU A) #3

3

M

400

VAC

55.00

62

P-240A-E-1001-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-4

Lean Solvent Air Cooler-A (AGRU A) #4

3

M

400

VAC

55.00

63

P-240A-E-1001-5

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-5

Lean Solvent Air Cooler-A (AGRU A) #5

3

M

400

VAC

55.00

64

P-240A-E-1001-6

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-6

Lean Solvent Air Cooler-A (AGRU A) #6

3

M

400

VAC

55.00

65

P-240A-E-1001-7

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-7

Lean Solvent Air Cooler-A (AGRU A) #7

3

M

400

VAC

55.00

66

P-240A-E-1001-8

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1001-8

Lean Solvent Air Cooler-A (AGRU A) #8

3

M

400

VAC

55.00

67

P-240A-E-2001-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-1

Lean Solvent Air Cooler-B (AGRU A) #1

3

M

400

VAC

55.00

242 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

68

P-240A-E-2001-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-2

Lean Solvent Air Cooler-B (AGRU A) #2

3

M

400

VAC

55.00

69

P-240A-E-2001-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-3

Lean Solvent Air Cooler-B (AGRU A) #3

3

M

400

VAC

55.00

70

P-240A-E-2001-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-4

Lean Solvent Air Cooler-B (AGRU A) #4

3

M

400

VAC

55.00

71

P-240A-E-2001-5

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-5

Lean Solvent Air Cooler-B (AGRU A) #5

3

M

400

VAC

55.00

72

P-240A-E-2001-6

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-6

Lean Solvent Air Cooler-B (AGRU A) #6

3

M

400

VAC

55.00

73

P-240A-E-2001-7

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-7

Lean Solvent Air Cooler-B (AGRU A) #7

3

M

400

VAC

55.00

74

P-240A-E-2001-8

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2001-8

Lean Solvent Air Cooler-B (AGRU A) #8

3

M

400

VAC

55.00

75

P-240A-PA-1002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-1002

Auxiliary for HP Lean Solvent Pump 1 (Train A)

3

M

400

VAC

22.00

76

P-240A-PA-2002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-2002

Auxiliary for HP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

22.00

243 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

77

P-240A-PA-5003

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-5003

Auxiliary for HP Lean Solvent Pump 3 (Train A)

3

M

400

VAC

22.00

78

P-240A-P-1003 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1003A

Reflux Pump-1 A (Train A)

3

M

400

VAC

11.00

79

P-240A-P-1003 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1003B

Reflux Pump-1 B (Train A)

3

M

400

VAC

11.00

80

P-240A-P-2003 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2003A

Reflux Pump-2 A (Train A)

3

M

400

VAC

11.00

81

P-240A-P-2003 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2003B

Reflux Pump-2 B (Train A)

3

M

400

VAC

11.00

82

P-240A-P-5001

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-5001

Drained Solvent Pump (Stand-By) Train A

3

M

400

VAC

4.00

83

P-240A-P-5002

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-5002

Drained Hydrocarbon Pump (StandBy) Train A

3

M

400

VAC

2.20

84

P-240A-PA-1012

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-1012

Auxiliary for LP Lean Solvent Pump 1 (Train A)

3

M

400

VAC

4.00

85

P-240A-PA-2012

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-2012

Auxiliary for LP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

4.00

244 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

86

P-240A-PA-5012

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-5012

Auxiliary for LP Lean Solvent Pump 3 (Train A)

3

M

400

VAC

4.00

87

P-240A-PA-1001

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-1001

Auxiliary for Regenerator Lean Solvent Pump 1 (Train A)

3

M

400

VAC

5.50

88

P-240A-PA-2001

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-2001

Auxiliary for Regenerator Lean Solvent Pump 2 (Train A)

3

M

400

VAC

5.50

89

P-240A-PA-5004

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

240A-PA-5004

Auxiliary for Regenerator Lean Solvent Pump 3 (Train A)

3

M

400

VAC

5.50

90

P-240A-P-1006 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1006 A

Reboiler Condensate Pump-1A (Train A)

3

M

400

VAC

15.00

91

P-240A-P-1006 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-1006 B

Reboiler Condensate Pump-1B (Train A)

3

M

400

VAC

15.00

92

P-240A-P-2006 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2006 A

Reboiler Condensate Pump-2A (Train A)

3

M

400

VAC

15.00

93

P-240A-P-2006 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-P-2006 B

Reboiler Condensate Pump-2B (Train A)

3

M

400

VAC

15.00

94

P-240A-E-1004-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-1

Overhead Condenser-A (AGRU A) #1

3

M

400

VAC

55.00

245 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

95

P-240A-E-1004-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-2

Overhead Condenser-A (AGRU A) #2

3

M

400

VAC

55.00

96

P-240A-E-1004-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-3

Overhead Condenser-A (AGRU A) #3

3

M

400

VAC

55.00

97

P-240A-E-1004-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-1004-4

Overhead Condenser-A (AGRU A) #4

3

M

400

VAC

55.00

98

P-240A-E-2004-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-1

Overhead Condenser-B (AGRU A) #1

3

M

400

VAC

55.00

99

P-240A-E-2004-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-2

Overhead Condenser-B (AGRU A) #2

3

M

400

VAC

55.00

100 P-240A-E-2004-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-3

Overhead Condenser-B (AGRU A) #3

3

M

400

VAC

55.00

101 P-240A-E-2004-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240A-E-2004-4

Overhead Condenser-B (AGRU A) #4

3

M

400

VAC

55.00

102 P-240-P-9001 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240-P-9001A

AGRU Fresh Solvent Pump A

3

M

400

VAC

5.50

103 P-240-P-9001 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

240-P-9001B

AGRU Fresh Solvent Pump B

3

M

400

VAC

5.50

246 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

104 P-240B-E-3001-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-1

Lean Solvent Air Cooler-A (AGRU B) #1

3

M

400

VAC

55.00

105 P-240B-E-3001-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-2

Lean Solvent Air Cooler-A (AGRU B) #2

3

M

400

VAC

55.00

106 P-240B-E-3001-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-3

Lean Solvent Air Cooler-A (AGRU B) #3

3

M

400

VAC

55.00

107 P-240B-E-3001-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-4

Lean Solvent Air Cooler-A (AGRU B) #4

3

M

400

VAC

55.00

108 P-240B-E-3001-5

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-5

Lean Solvent Air Cooler-A (AGRU B) #5

3

M

400

VAC

55.00

109 P-240B-E-3001-6

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-6

Lean Solvent Air Cooler-A (AGRU B) #6

3

M

400

VAC

55.00

110 P-240B-E-3001-7

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-7

Lean Solvent Air Cooler-A (AGRU B) #7

3

M

400

VAC

55.00

111 P-240B-E-3001-8

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3001-8

Lean Solvent Air Cooler-A (AGRU B) #8

3

M

400

VAC

55.00

Volt

kW

AGRU-B

247 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

112 P-240B-E-4001-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-1

Lean Solvent Air Cooler-B (AGRU B) #1

3

M

400

VAC

55.00

113 P-240B-E-4001-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-2

Lean Solvent Air Cooler-B (AGRU B) #2

3

M

400

VAC

55.00

114 P-240B-E-4001-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-3

Lean Solvent Air Cooler-B (AGRU B) #3

3

M

400

VAC

55.00

115 P-240B-E-4001-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-4

Lean Solvent Air Cooler-B (AGRU B) #4

3

M

400

VAC

55.00

116 P-240B-E-4001-5

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-5

Lean Solvent Air Cooler-B (AGRU B) #5

3

M

400

VAC

55.00

117 P-240B-E-4001-6

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-6

Lean Solvent Air Cooler-B (AGRU B) #6

3

M

400

VAC

55.00

118 P-240B-E-4001-7

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-7

Lean Solvent Air Cooler-B (AGRU B) #7

3

M

400

VAC

55.00

119 P-240B-E-4001-8

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4001-8

Lean Solvent Air Cooler-B (AGRU B) #8

3

M

400

VAC

55.00

120 P-240B-PA-3002

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-3002

Auxiliary for HP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

22.00

248 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

121 P-240B-PA-4002

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-4002

Auxiliary for HP Lean Solvent Pump 2 (Train B)

3

M

400

VAC

22.00

122 P-240B-PA-6003

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-6003

Auxiliary for HP Lean Solvent Pump 3 (Train B)

3

M

400

VAC

22.00

123 P-240B-P-3003 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3003A

Reflux Pump-1 A (Train B)

3

M

400

VAC

11.00

124 P-240B-P-3003 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3003 B

Reflux Pump-1 B (Train B)

3

M

400

VAC

11.00

125 P-240B-P-4003 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4003A

Reflux Pump-2 A (Train B)

3

M

400

VAC

11.00

126 P-240B-P-4003 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4003 B

Reflux Pump-2 B (Train B)

3

M

400

VAC

11.00

127 P-240B-P-6001

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-6001

Drained Solvent Pump (Stand-By) Train B

3

M

400

VAC

4.00

128 P-240B-P-6002

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-6002

Drained Hydrocarbon Pump (StandBy) Train B

3

M

400

VAC

2.20

127 P-240B-PA-3012

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-3012

Auxiliary for LP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

4.00

249 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

128 P-240B-PA-4012

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-4012

Auxiliary for LP Lean Solvent Pump 2 (Train B)

3

M

400

VAC

4.00

129 P-240B-PA-6012

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-6012

Auxiliary for LP Lean Solvent Pump 3 (Train B)

3

M

400

VAC

4.00

130 P-240B-PA-3001

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-3001

Auxiliary for Regenerator Lean Solvent Pump 1 (Train B)

3

M

400

VAC

5.50

131 P-240B-PA-4001

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-4001

Auxiliary for Regenerator Lean Solvent Pump 2 (Train B)

3

M

400

VAC

5.50

132 P-240B-PA-6004

280-SWG/MCC-0002

Essential LV SWGR/MCC Substation-3 (Train-B)

240B-PA-6004

Auxiliary for Regenerator Lean Solvent Pump 3 (Train B)

3

M

400

VAC

5.50

133 P-240B-P-3006 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3006 A

Reboiler Condensate Pump-1 A (Train B)

3

M

400

VAC

15.00

134 P-240B-P-3006 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-3006 B

Reboiler Condensate Pump-1 B (Train B)

3

M

400

VAC

15.00

135 P-240B-P-4006 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4006 A

Reboiler Condensate Pump-2 A (Train B)

3

M

400

VAC

15.00

136 P-240B-P-4006 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-P-4006 B

Reboiler Condensate Pump-2 B (Train B)

3

M

400

VAC

15.00

250 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

137 P-240B-E-3004-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-1

Overhead Condenser-A (AGRU B) #1

3

M

400

VAC

55.00

138 P-240B-E-3004-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-2

Overhead Condenser-A (AGRU B) #2

3

M

400

VAC

55.00

139 P-240B-E-3004-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-3

Overhead Condenser-A (AGRU B) #3

3

M

400

VAC

55.00

140 P-240B-E-3004-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-3004-4

Overhead Condenser-A (AGRU B) #4

3

M

400

VAC

55.00

141 P-240B-E-4004-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-1

Overhead Condenser-B (AGRU B) #1

3

M

400

VAC

55.00

142 P-240B-E-4004-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-2

Overhead Condenser-B (AGRU B) #2

3

M

400

VAC

55.00

143 P-240B-E-4004-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-3

Overhead Condenser-B (AGRU B) #3

3

M

400

VAC

55.00

144 P-240B-E-4004-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

240B-E-4004-4

Overhead Condenser-B (AGRU B) #4

3

M

400

VAC

55.00

Sales Gas Dehydration Unit 251 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

145 P-250-P-9001 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9001 A

Sales Gas Dehy TEG Circulation Pump A

3

M

400

VAC

132.00

146 P-250-P-9001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9001 B

Sales Gas Dehy TEG Circulation Pump B

3

M

400

VAC

132.00

147 P-250-E-9001-1

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-E-9001-1

Sales Gas Dehy TEG Lean Cooler Fan-1

3

M

400

VAC

7.50

148 P-250-E-9001-2

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-E-9001-2

Sales Gas Dehy TEG Lean Cooler Fan-2

3

M

400

VAC

7.50

DELETEP-250-E-9001-3

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-E-9001-3

Sales Gas Dehy TEG Lean Cooler Fan-3

3

M

0

VAC

15.00

DELETEP-250-E-9001-4

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-E-9001-4

Sales Gas Dehy TEG Lean Cooler Fan-4

3

M

0

VAC

15.00

149 P-250-P-9002

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9002

Sales Gas Dehy TEG Supply Pump

3

M

400

VAC

7.50

150 P-250-P-9003

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

250-P-9003

TEG Drain Vessel Pump

3

M

400

VAC

0.75

Sales Gas Compression 252 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

151 P-260-E-9001-1

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

260-E-9001-1

Sales Gas Compressor Discharge Cooler Fan 1

3

M

400

VAC

7.50

152 P-260-E-9001-2

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

260-E-9001-2

Sales Gas Compressor Discharge Cooler Fan 2

3

M

400

VAC

7.50

DELETEP-260-E-9001-3

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

260-E-9001-3

Sales Gas Compressor Discharge Cooler Fan 3

3

M

0

VAC

30.00

DELETEP-260-E-9001-4

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

260-E-9001-4

Sales Gas Compressor Discharge Cooler Fan 4

3

M

0

VAC

30.00

153 P-260-CA-9001 A

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

260-CA-9001 A

Sales Gas Compressor A Auxiliary Load

3

M

400

VAC

75.00

154 P-260-CA-9001 B

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

260-CA-9001 B

Sales Gas Compressor B Auxiliary Load

3

M

400

VAC

75.00

Volt

kW

Acid Gas Enrichment (AGE) Unit - Train A 155 P-280A-P-1005

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1005

Wash Water Pump-1 at AGE Absorber (Train A)

3

M

400

VAC

7.50

156 P-280A-P-2005

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2005

Wash Water Pump-2 at AGE Absorber (Train A)

3

M

400

VAC

7.50

253 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

157 P-280A-P-5005

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5005

Wash Water Pump-3 at AGE Absorber (Train A)

3

M

400

VAC

7.50

158 P-280A-P-1004

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1004

Regenerator Reflux Pump-1 (Train A)

3

M

400

VAC

15.00

159 P-280A-P-2004

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2004

Regenerator Reflux Pump-2 (Train A)

3

M

400

VAC

15.00

160 P-280A-P-5004

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5004

Regenerator Reflux Pump-3 (Train A)

3

M

400

VAC

15.00

161 P-280A-P-5002 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5002A

Solvent Sump Pump-A (Train A)

3

M

400

VAC

11.00

162 P-280A-P-5002 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5002B

Solvent Sump Pump-B (Train A)

3

M

400

VAC

11.00

163 P-280A-E-1002

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-1002

Regenerator Overhead Condenser 1 (Train A)

3

M

400

VAC

37.00

164 P-280A-E-2002

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-2002

Regenerator Overhead Condenser 2 (Train A)

3

M

400

VAC

37.00

165 P-280A-P-1008

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1008

Regenerator Bottoms Pump 1 (Train A)

3

M

400

VAC

75.00

254 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

166 P-280A-P-2008

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2008

Regenerator Bottoms Pump 2 (Train A)

3

M

400

VAC

75.00

167 P-280A-P-5008

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5008

Regenerator Bottoms Pump 3 (Train A)

3

M

400

VAC

75.00

168 P-280A-E-5001-1

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-1

Lean Amine Cooler (Train A) #1

3

M

400

VAC

37.00

169 P-280A-E-5001-2

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-2

Lean Amine Cooler (Train A) #2

3

M

400

VAC

37.00

170 P-280A-E-5001-3

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-3

Lean Amine Cooler (Train A) #3

3

M

400

VAC

37.00

171 P-280A-E-5001-4

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-4

Lean Amine Cooler (Train A) #4

3

M

400

VAC

37.00

172 P-280A-E-5001-5

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-5

Lean Amine Cooler (Train A) #5

3

M

400

VAC

37.00

173 P-280A-E-5001-6

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-6

Lean Amine Cooler (Train A) #6

3

M

400

VAC

37.00

174 P-280A-E-5001-7

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-7

Lean Amine Cooler (Train A) #7

3

M

400

VAC

37.00

255 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

175 P-280A-E-5001-8

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-E-5001-8

Lean Amine Cooler (Train A) #8

3

M

400

VAC

37.00

176 P-280A-P-1003

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1003

Rich Amine Pump-1 at AGE Absorber (Train A)

3

M

400

VAC

110.00

177 P-280A-P-2003

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2003

Rich Amine Pump-2 at AGE Absorber (Train A)

3

M

400

VAC

110.00

178 P-280A-P-5003

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5003

Rich Amine Pump-3 at AGE Absorber (Train A)

3

M

400

VAC

110.00

179 P-280-P-9001 A

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280-P-9001A

Fresh Solvent Pump A (Train A)

3

M

400

VAC

5.50

180 P-280-P-9001 B

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280-P-9001B

Fresh Solvent Pump B (Train A)

3

M

400

VAC

5.50

181 P-280A-P-1006

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-1006

Sour Water Pump-1 (Train A)

3

M

400

VAC

5.50

182 P-280A-P-2006

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-2006

Sour Water Pump-2 (Train A)

3

M

400

VAC

5.50

183 P-280A-P-5006

231-SWG/MCC-0004

Main LV Switchgear/MCC Substation-2 (Train-A)

280A-P-5006

Sour Water Pump-3 (Train A)

3

M

400

VAC

5.50

256 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Acid Gas Enrichment (AGE) Unit - Train B 184 P-280B-P-3005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3005

Wash Water Pump-1 at AGE Absorber (Train B)

3

M

400

VAC

11.00

185 P-280B-P-4005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4005

Wash Water Pump-2 at AGE Absorber (Train B)

3

M

400

VAC

11.00

186 P-280B-P-6005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6005

Wash Water Pump-3 at AGE Absorber (Train B)

3

M

400

VAC

11.00

187 P-280B-P-3004

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3004

Regenerator Reflux Pump-1 (Train B)

3

M

400

VAC

15.00

188 P-280B-P-4004

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4004

Regenerator Reflux Pump-2 (Train B)

3

M

400

VAC

15.00

189 P-280B-P-6004

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6004

Regenerator Reflux Pump-3 (Train B)

3

M

400

VAC

15.00

190 P-280B-P-6002 A

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6002A

Solvent Sump Pump-A (Train B)

3

M

400

VAC

11.00

191 P-280B-P-6002 B

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6002B

Solvent Sump Pump-B (Train B)

3

M

400

VAC

11.00

257 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

192 P-280B-E-3002

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-3002

Regenerator Overhead Condenser 1 (Train B)

3

M

400

VAC

37.00

193 P-280B-E-4002

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-4002

Regenerator Overhead Condenser 2 (Train B)

3

M

400

VAC

37.00

194 P-280B-P-3008

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3008

Regenerator Bottoms Pump-1 (Train B)

3

M

400

VAC

75.00

195 P-280B-P-4008

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4008

Regenerator Bottoms Pump-2 (Train B)

3

M

400

VAC

75.00

196 P-280B-P-6008

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6008

Regenerator Bottoms Pump-3 (Train B)

3

M

400

VAC

75.00

197 P-280B-E-6001-1

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-1

Lean Amine Cooler (Train B) #1

3

M

400

VAC

37.00

198 P-280B-E-6001-2

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-2

Lean Amine Cooler (Train B) #2

3

M

400

VAC

37.00

199 P-280B-E-6001-3

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-3

Lean Amine Cooler (Train B) #3

3

M

400

VAC

37.00

200 P-280B-E-6001-4

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-4

Lean Amine Cooler (Train B) #4

3

M

400

VAC

37.00

258 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

201 P-280B-E-6001-5

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-5

Lean Amine Cooler (Train B) #5

3

M

400

VAC

37.00

202 P-280B-E-6001-6

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-6

Lean Amine Cooler (Train B) #6

3

M

400

VAC

37.00

203 P-280B-E-6001-7

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-7

Lean Amine Cooler (Train B) #7

3

M

400

VAC

37.00

204 P-280B-E-6001-8

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-E-6001-8

Lean Amine Cooler (Train B) #8

3

M

400

VAC

37.00

205 P-280B-P-3003-01/02

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3003

Rich Amine Pump-A at AGE Absorber (Train B)

3

M

400

VAC

110.00

206 P-280B-P-4003-01/02

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4003

Rich Amine Pump-B at AGE Absorber (Train B)

3

M

400

VAC

110.00

207 P-280B-P-6003-01/02

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6003

Rich Amine Pump-C at AGE Absorber (Train B)

3

M

400

VAC

110.00

208 P-280B-P-3006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-3006

Sour Water Pump-A (Train B)

3

M

400

VAC

15.00

209 P-280B-P-4006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-4006

Sour Water Pump-B (Train B)

3

M

400

VAC

15.00

259 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

280B-P-6006

Sour Water Pump-C (Train B)

3

M

400

VAC

15.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9002A

Sulfur Transfer Pump A

3

M

400

VAC

2.20

212 P-290-P-9002 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9002B

Sulfur Transfer Pump B

3

M

400

VAC

2.20

213 P-290-CA-9001 A

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

290-CA-9001A

Claus Air Blower A Auxiliary Load

3

M

400

VAC

7.50

214 P-290-CA-9001 B

420-SWG/MCC-0004

Essential LV Switchgear/MCC Substation-1 (Power Generation)

290-CA-9001B

Claus Air Blower B Auxiliary Load

3

M

400

VAC

7.50

215 P-290-P-9001 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9001A

Sour Condensate Pump A

3

M

400

VAC

2.20

216 P-290-P-9001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9001B

Sour Condensate Pump B

3

M

400

VAC

2.20

217 P-290-P-9003 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9003A

Sulfur Handling Pump A

3

M

400

VAC

11.00

210 P-280B-P-6006

Volt

kW

Sulfur Recovery Unit 211 P-290-P-9002 A

260 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

218 P-290-P-9003 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9003B

Sulfur Handling Pump B

3

M

400

VAC

11.00

219 P-290-P-9011 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9011A

LP Condensate Pump A

3

M

400

VAC

11.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

290-P-9011B

LP Condensate Pump B

3

M

400

VAC

11.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9001A

Quench Water Pump-A

3

M

400

VAC

75.00

222 P-310-P-9001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9001B

Quench Water Pump-B

3

M

400

VAC

75.00

223 P-310-P-9002 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9002A

Wash Water Pump-A at TGU Absorber

3

M

400

VAC

11.00

224 P-310-P-9002 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9002B

Wash Water Pump-B at TGU Absorber

3

M

400

VAC

11.00

225 P-310-P-9003 A

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9003A

Rich Amine Pump-A at TGU Absorber

3

M

400

VAC

75.00

220 P-290-P-9011 B

Volt

kW

Tail Gas Unit (TGU) 221 P-310-P-9001 A

261 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

226 P-310-P-9003 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9003B

Rich Amine Pump-B at TGU Absorber

3

M

400

VAC

75.00

227 P-310-P-9004

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-P-9004

Sour Water Drain Return Pump

3

M

400

VAC

2.20

228 P-310-E-9002-1

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-E-9002-1

Quench Water Air Cooler #1

3

M

400

VAC

30.00

229 P-310-E-9002-2

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

310-E-9002-2

Quench Water Air Cooler #2

3

M

400

VAC

30.00

230 P-410-P-9001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9001A

BFW Transfer Pump-A

3

M

400

VAC

30.00

231 P-410-P-9001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9001B

BFW Transfer Pump-B

3

M

400

VAC

30.00

232 P-410-P-9003 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9003A

Steam Condensate Pump A

3

M

400

VAC

11.00

233 P-410-P-9003 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9003B

Steam Condensate Pump B

3

M

400

VAC

11.00

Volt

kW

Boiler Feed Water (BFW)

262 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

234 P-410-P-9004 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9004A

Blowdown Pump A

3

M

400

VAC

18.50

235 P-410-P-9004 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9004B

Blowdown Pump B

3

M

400

VAC

18.50

236 P-410-P-9005 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9005A

LP BFW Pump A

3

M

400

VAC

37.00

237 P-410-P-9005 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9005B

LP BFW Pump B

3

M

400

VAC

37.00

238 P-410-E-9001-1

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9001-1

Steam Condenser Fan-1

3

M

400

VAC

11.00

239 P-410-E-9001-2

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9001-2

Steam Condenser Fan-2

3

M

400

VAC

11.00

DELETEP-410-E-9001-3

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-3

Steam Condenser Fan-3

3

M

400

VAC

11.00

DELETEP-410-E-9001-4

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-4

Steam Condenser Fan-4

3

M

400

VAC

11.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-5

Steam Condenser Fan-5

3

M

0

VAC

0.00

DELETEP-410-E-9001-5

263 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

DELETEP-410-E-9001-6

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-6

Steam Condenser Fan-6

3

M

0

VAC

0.00

DELETEP-410-E-9001-7

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-7

Steam Condenser Fan-7

3

M

0

VAC

0.00

DELETEP-410-E-9001-8

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-8

Steam Condenser Fan-8

3

M

0

VAC

0.00

DELETEP-410-E-9001-9

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-9

Steam Condenser Fan-9

3

M

0

VAC

0.00

DELETEP-410-E-9001-10

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

410-E-9001-10

Steam Condenser Fan-10

3

M

0

VAC

0.00

240 P-410-TK-9002

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-TK-9002

Oxygen Scavenger Tank Mixer Motor

3

M

400

VAC

0.75

241 P-410-TK-9003

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-TK-9003

Neutralization Amine Tank Mixer Motor

3

M

400

VAC

0.75

242 P-410-TK-9004

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-TK-9004

Phosphate Solution Tank Mixer Motor

3

M

400

VAC

0.75

243 P-410-P-9008 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9008A

Oxygen Scavenger Pump Motor-A

3

M

400

VAC

0.75

264 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

244 P-410-P-9008 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9008B

Oxygen Scavenger Pump Motor-B

3

M

400

VAC

0.75

245 P-410-P-9009 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9009A

Neutralization Amine Pump Motor-A

3

M

400

VAC

1.10

246 P-410-P-9009 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9009B

Neutralization Amine Pump Motor-B

3

M

400

VAC

1.10

247 P-410-P-9010 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9010A

Phosphate Solution Pump Motor A

3

M

400

VAC

0.75

248 P-410-P-9010 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-P-9010B

Phosphate Solution Pump Motor B

3

M

400

VAC

0.75

249 P-410-E-9002-1

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9002-1

Deaerator Steam Condenser Motor 1

3

M

400

VAC

30.00

250 P-410-E-9001-2

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

410-E-9002-2

Deaerator Steam Condenser Motor 2

3

M

400

VAC

30.00

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

450-P-9004 A

Raw Water Feed Pump A

3

M

400

VAC

45.00

Volt

kW

Water Treating 251 P-450-P-9004 A

265 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

450-P-9004B

Raw Water Feed Pump B

3

M

400

VAC

45.00

253 P-460-P-9001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9001A

AGE Off-Gas K.O. Drum Pump-A

3

M

400

VAC

5.50

254 P-460-P-9001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9001B

AGE Off-Gas K.O. Drum Pump-B

3

M

400

VAC

5.50

255 P-460-P-9002 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9002A

TGU Off-Gas K.O. Drum Pump-A

3

M

400

VAC

5.50

256 P-460-P-9002 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-P-9002B

TGU Off-Gas K.O. Drum Pump-B

3

M

400

VAC

5.50

257 P-460-EA-9001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001A

Thermal Oxidizer Air Blower A Auxiliary Load

3

M

400

VAC

11.00

258 P-460-EA-9001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001B

Thermal Oxidizer Air Blower B Auxiliary Load

3

M

400

VAC

11.00

259 P-460-EA-9001 C

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001C

Thermal Oxidizer Air Blower C Auxiliary Load

3

M

400

VAC

11.00

252 P-450-P-9004 B

Volt

kW

Thermal Oxidizer Unit

266 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

260 P-460-EA-9001 D

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001D

Thermal Oxidizer Air Blower D Auxiliary Load

3

M

400

VAC

11.00

261 P-460-EA-9001 E

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

460-EA-9001E

Thermal Oxidizer Air Blower E Auxiliary Load

3

M

400

VAC

11.00

262 P-470-P-9013 A-01/02

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

470-P-9013 A

HP Flare Knockout Drum Condensate Pump A

3

M

400

VAC

90.00

263 P-470-P-9013 B-01/02

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

470-P-9013 B

HP Flare Knockout Drum Condensate Pump B

3

M

400

VAC

90.00

264 P-475-P-9014 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

475-P-9014 A

LP Flare Knockout Drum Condensate Pump A

3

M

400

VAC

75.00

265 P-475-P-9014 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

475-P-9014 B

LP Flare Knockout Drum Condensate Pump B

3

M

400

VAC

75.00

Volt

kW

HP Flare System

LP Flare System

Diesel Fuel

267 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

480-P-9015

Diesel Pump

3

M

400

VAC

5.50

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

490-P-9008

Firewater Jockey Pump

3

M

400

VAC

18.50

268 P-510-P-9001

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

510-P-9001

Close Drain Pump

3

M

400

VAC

37.00

269 P-520-P-9001

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

520-P-9001

Open Drain Pump

3

M

400

VAC

5.50

420-V-9001

Emergency Generator

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

3

F

400

VAC

320

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-BCH-5001

Battery Charger Emergency Diesel Generator

3

F

400

VAC

2.20

266 P-480-P-9015

Volt

kW

Fire Water System 267 P-490-P-9008

Open and Close Drain System

GENERATOR DEG - Emergency Generator 270 P-420-V-9001-01/02/03

271 P-420-BCH-5001

268 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

211-V-9007

Backup Generator Well Pad Central

211-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad Central

3

F

400

VAC

240.00

211-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad Central

211-BCH-5001

Battery Charger Backup Diesel Generator Well Pad Central

3

F

400

VAC

2.20

211-TRF-0001

11 / 0.4 kV Central Well Pad Transformer

211-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad Central

3

F

400

VAC

160

212-V-9006

Backup Generator Well Pad East

212-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad East

3

F

400

VAC

240.00

276 P-212-BCH-5001

212-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad East

212-BCH-5001

Battery Charger Backup Diesel Generator Well Pad East

3

F

400

VAC

2.20

277 P-212-TRF-0002

212-TRF-0001

11 /0.42 kV East Well Pad Transformer

212-SWG/MCC-0002

400 VAC Switchgear/MCC Well Pad East

3

F

400

VAC

160

Equipment Tag No.

Volt

kW

Backup Generator - Well Pad Central 272 P-211-V-9007-01/02

273 P-211-BCH-5001

274 P-211-TRF-0002-01/02

Backup Generator - Well Pad East 275 P-212-V-9006-01/02/03

Backup Generator - Infrastructure

269 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-GD-0001

Backup Generator Infrastructure

800-SWG/MCC-0001

400 VAC Switchgear/MCC Infrastructure

3

F

400

VAC

414

800-SWG/MCC-0002

400 VAC Switchgear/MCC Infrastructure

800-BCH-5001

Battery Charger Backup Diesel Generator Infrastructure

3

F

400

VAC

2.20

800-TRF-0001

11 / 0.4 kV Infrastructure Transformer

800-SWG/MCC-0002

400 VAC Switchgear/MCC Infrastructure

3

F

400

VAC

1,500

710-V-9003

Backup Generator Sales Gas Metering Station

710-SWG/MCC-0002

400 VAC Switchgear/MCC Sales Gas Metering Station

3

F

400

VAC

100.00

280 P-710-BCH-5001

710-SWG/MCC-0002

400 VAC Switchgear/MCC Sales Gas Metering Station

710-BCH-5001

Battery Charger Backup Diesel Generator Sales Gas Metering

3

F

400

VAC

2.20

281 P-710-TRF-0002

710-TRF-0001

11 / 0.42 kV Transformer Sales Gas Metering

410-SWG/MCC-0002

400 VAC Switchgear/MCC Sales Gas Metering Station

3

F

400

VAC

100.00

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1003

STG-A Lube Oil Clarifier Driver

3

M

400

VAC

1.50

DEL P-800-GD-0001-01/02/03/04

278 P-800-BCH-5001

DEL P-800-TRF-0001-01/02

Volt

kW

Backup Generator - Sales Gas Metering Station 279 P-710-V-9003

STG A - Main Generator A 282 P-420-P-1003

270 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

283 P-420-P-1001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1001A

STG-A Lube Oil Pump Driver-A

3

M

400

VAC

30.00

284 P-420-P-1001 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1001B

STG-A Lube Oil Pump Driver-B

3

M

400

VAC

30.00

285 P-420-P-1002 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1002A

STG-A Lube Oil Tank Mist SeparatorA

3

M

400

VAC

4.00

286 P-420-P-1002 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1002B

STG-A Lube Oil Tank Mist SeparatorB

3

M

400

VAC

4.00

287 P-420-P-1004

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1004

STG-A Jacking Oil Oump Driver

3

M

400

VAC

1.50

288 P-420-P-1005

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-1005

STG-A Bearing Gear Driver

3

M

400

VAC

4.00

289 P-420-P-2003

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2003

STG-B Lube Oil Clarifier Driver

3

M

400

VAC

1.50

290 P-420-P-2001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2001A

STG-B Lube Oil Pump Driver-A

3

M

400

VAC

30.00

Volt

kW

STG B - Main Generator B

271 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

291 P-420-P-2001 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2001B

STG-B Lube Oil Pump Driver-B

3

M

400

VAC

30.00

292 P-420-P-2002 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2002A

STG-B Lube Oil Mist Separator-A

3

M

400

VAC

4.00

293 P-420-P-2002 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2002B

STG-B Lube Oil Mist Separator-B

3

M

400

VAC

4.00

294 P-420-P-2004

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2004

STG-B Jacking Oil Oump Driver

3

M

400

VAC

1.50

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-P-2005

STG-B Bearing Gear Driver

3

M

400

VAC

4.00

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-E-4001

Radiator Fan Essential Generator

3

M

400

VAC

11.00

297 P-420-DPN-4001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DPN-4001

LCP Power Essential Generator

3

F

400

VAC

18.25

298 P-420-BCH-4001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-BCH-4001

Battery Charger Essential Generator

3

F

400

VAC

2.00

295 P-420-P-2005

Volt

kW

GEG+DEG - Essential Generator 296 P-420-E-4001

272 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Transformer Rectifier Unit (TRU) for Cathodic Protection 299 P-610-TRU-9001

420-SWG/MCC-0003

Main LV SWGR/MCC Substation-1 (Power Generation)

610-TRU-9001

Transformer Rectifier Unit (GPF Underground Pipeline)-1

3

F

400

VAC

3.50

300 P-620-TRU-9001

420-SWG/MCC-0003

Main LV SWGR/MCC Substation-1 (Power Generation)

620-TRU-9001

Transformer Rectifier Unit (GPF Underground Pipeline)-2

3

F

400

VAC

3.50

301 P-630-TRU-9001

420-SWG/MCC-0003

Main LV SWGR/MCC Substation-1 (Power Generation)

630-TRU-9001

Transformer Rectifier Unit (Sales Gas Metering Underground Pipeline)

3

F

400

VAC

3.50

420-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

64.00

SUBSTATION-1 (POWER GENERATION) 302 P-420-AC-UPS-0001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

303 P-420-AC-UPS-0001 B

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

420-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

64.00

304 P-420-AC-UPS-0001 C

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

64.00

305 P-420-DC-UPS-0001 A

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

13.78

273 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

306 P-420-DC-UPS-0001 B

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

13.78

307 P-420-HVAC-9001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-9001

HVAC Package for Substation-1

3

F

400

VAC

113.20

308 P-420-HVAC-9002

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-9002

HVAC Package for Substation-1

3

F

400

VAC

27.00

309 P-420-HVAC-9003

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-9003

HVAC Package for Substation-1

3

F

400

VAC

27.00

310 P-420-HVAC-9004

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-9004

HVAC Package for Substation-1

3

F

400

VAC

27.00

311 P-420-HVAC-9004

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-HVAC-6010

HVAC Auxiliary for Substation 1

3

F

400

VAC

32.20

312 P-900-LPN-4201

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

900-LPN-4201

Lighting DB (Outdoor) #1

3

F

400

VAC

46.30

313 P-420-LPN-4202

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-LPN-4202

Lighting (Indoor Substation-1) #1

3

F

400

VAC

13.80

274 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

314 P-420-DPE-0001

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation)

420-DPE-0001

Lighting (Outdoor Emergency) #1

3

F

400

VAC

7.20

315 P-900-WLO-001

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

900-WLO-001

Welding Receptacle #1

3

F

400

VAC

13.00

420-SWG/MCC-0003

Main LV Switchgear/MCC Substation-1 (Power Generation)

900-WLO-002

Welding Receptacle #2

3

F

400

VAC

13.00

316 P-900-WLO-002

Volt

kW

SUBSTATION-2 (TRAIN A AREA) 317 P-231-AC-UPS-0001 A

231-SWG/MCC-0003

Main LV Switchgear/MCC Substation-2 (Train-A)

231-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

40.00

318 P-231-AC-UPS-0001 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

40.00

319 P-231-AC-UPS-0001 C

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

40.00

320 P-231-DC-UPS-0001 A

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

10.92

275 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

321 P-231-DC-UPS-0001 B

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

10.92

322 P-231-HVAC-9001-01/02

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9001

HVAC package for Substation 2

3

F

400

VAC

146.70

323 P-231-HVAC-9002

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9002

HVAC package for Substation 2

3

F

400

VAC

34.00

324 P-231-HVAC-9003

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9003

HVAC package for Substation 2

3

F

400

VAC

34.00

325 P-231-HVAC-9004

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-9004

HVAC package for Substation 2

3

F

400

VAC

34.00

326 P-231-HVAC-6010

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-HVAC-6010

HVAC Auxiliary for Substation 2

3

F

400

VAC

45.00

327 P-900-LPN-2311

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

900-LPN-2311

Lighting DB (Outdoor) #2

3

F

400

VAC

93.30

328 P-231-LPN-2312

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

231-LPN-2312

Lighting (Indoor Substation-2) #2

3

F

400

VAC

11.90

276 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

329 P-232-DPE-0001

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

232-DPE-0001

Lighting (Outdoor Emergency) #2

3

F

400

VAC

12.50

330 P-900-WLO-003

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-003

Welding Receptacle #3

3

F

400

VAC

13.00

331 P-900-WLO-004

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-004

Welding Receptacle #4

3

F

400

VAC

13.00

332 P-900-WLO-007

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-007

Welding Receptacle #7

3

F

400

VAC

13.00

333 P-900-WLO-008

231-SWG/MCC-0002

Main LV Switchgear/MCC Substation-2 (Train-A)

900-WLO-008

Welding Receptacle #8

3

F

400

VAC

13.00

Volt

kW

334

HOLD (NOTE-5)

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

HOLD (NOTE-5)

Muster Point-1 GPF

3

F

400

VAC

2.00

335

HOLD (NOTE-5)

231-SWG/MCC-0003

Essential LV Switchgear/MCC Substation-2 (Train-A)

HOLD (NOTE-5)

Muster Point-2 GPF

3

F

400

VAC

2.00

SUBSTATION-3 (TRAIN-B AREA)

277 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

336 P-280-AC-UPS-0001 A

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

32.00

337 P-280-AC-UPS-0001 B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

32.00

338 P-280-AC-UPS-0001 C

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

32.00

339 P-280-DC-UPS-0001 A

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

8.06

340 P-280-DC-UPS-0001 B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

8.06

341 P-290-HVAC-9001A-01/02

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-9001A

HVAC package for Substation 3

3

F

400

VAC

224.20

342 P-290-HVAC-9001B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-9001B

HVAC package for Substation 3

3

F

400

VAC

71.00

343 P-290-HVAC-9001B

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-9001B

HVAC package for Substation 3

3

F

400

VAC

71.00

278 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

344 P-290-HVAC-6010

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

290-HVAC-6010

HVAC Auxiliary for Substation 3

3

F

400

VAC

83.00

344 P-900-LPN-2801

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

900-LPN-2801

Lighting DB (Outdoor Substation-3)

3

F

400

VAC

58.00

345 P-900-LPN-2802

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

900-LPN-2802

Lighting (Indoor Substation-3)

3

F

400

VAC

9.80

346 P-280-DPE-0001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280-DPE-0001

Lighting (Outdoor Emergency)

3

F

400

VAC

15.00

347 P-280A-LPN-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280A-LPN-9001

Lighting & Small Power DB (Indoor Instrument Building 280A)

3

F

400

VAC

2.10

348 P-900-WLO-005

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

900-WLO-005

Welding Receptacle #5

3

F

400

VAC

13.00

349 P-900-WLO-006

280-SWG/MCC-0003

Main LV Switchgear/MCC Substation-3 (Train-B)

900-WLO-006

Welding Receptacle #6

3

F

400

VAC

13.00

SUBSTATION-4 (UTILITY AREA)

279 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

350 P-480-AC-UPS-0001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

32.00

351 P-480-AC-UPS-0001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

32.00

352 P-480-AC-UPS-0001 C

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

32.00

353 P-480-DC-UPS-0001 A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DC-UPS-0001 A

110 VDC UPS System - Feeder A

3

F

400

VAC

5.46

354 P-480-DC-UPS-0001 B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DC-UPS-0001 B

110 VDC UPS System - Feeder B

3

F

400

VAC

5.46

355 P-480-HVAC-9001A

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-9001A

HVAC package for Substation 4

3

F

400

VAC

112.70

356 P-480-HVAC-9001B

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-9001B

HVAC package for Substation 4

3

F

400

VAC

34.00

357 P-480-HVAC-9001C

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-9001C

HVAC package for Substation 4

3

F

400

VAC

34.00

280 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

358 P-480-HVAC-9003

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-HVAC-6010

HVAC Auxiliary for Substation 4

3

F

400

VAC

45.00

358 P-900-LPN-4101

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

900-LPN-4101

Lighting DB (Outdoor Substation-4)

3

F

400

VAC

57.35

359 P-900-LPN-4102

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

900-LPN-4102

Lighting DB (Indoor Substation-4)

3

F

400

VAC

8.00

360 P-480-DPE-0001

480-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

480-DPE-0001

Lighting (Outdoor Emergency) #4

3

F

400

VAC

5.60

Volt

kW

INSTRUMENT BUILDING (280B-B-9001) 361 P-280A-HVAC-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-9001

HVAC package for Instrument Building Train-A

3

F

400

VAC

27.00

362 P-280A-HVAC-9002

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-9002

HVAC package for Instrument Building Train-A

3

F

400

VAC

27.00

363 P-280A-HVAC-9003

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-9003

HVAC package for Instrument Building Train-A

3

F

400

VAC

27.00

281 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

364 P-280A-HVAC-6010

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-HVAC-6010

HVAC Aux for Instrument Building Train-A

3

F

400

VAC

86.00

365 P-280B-HVAC-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-9001

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

366 P-280B-HVAC-9002

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-9002

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

367 P-280B-HVAC-9003

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-9003

HVAC package for Instrument Building Train-B

3

F

400

VAC

27.00

368 P-280B-HVAC-6010

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

280B-HVAC-6010

HVAC Aux for Instrument Building Train-B

3

F

400

VAC

86.00

369

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

HOLD (NOTE-5)

Instrument Panel (Train-A)

3

F

400

VAC

20.00

370

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

HOLD (NOTE-5)

Instrument Panel (Train-B)

3

F

400

VAC

20.00

282 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To 3 Ph / 1 Ph

F/M

Lighting (Indoor Substation-5) Train-A DP

3

F

400

VAC

7.52

280B-LPN-9001

Lighting (Indoor Substation-5) Train-B DP

3

F

400

VAC

7.52

Lighting (Outdoor Substation-5) Train-A DP

3

F

400

VAC

75.00

3

F

400

VAC

15.00

3

F

400

VAC

75.00

Equipment Tag No.

Description

Equipment Tag No.

371 P-280A-LPN-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-2 (Train-A)

280A-LPN-9001

372 P-280B-LPN-9001

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-B)

Description

Volt

kW

DEL

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-A)

HOLD (NOTE-5)

DEL

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-A)

HOLD (NOTE-5)

DEL

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-A)

HOLD (NOTE-5)

DEL

HOLD (NOTE-5)

280-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-3 (Train-A)

HOLD (NOTE-5)

Lighting (Emergency Outdoor Substation-5) Train-B DP

3

F

400

VAC

15.00

373 P-450-AC-UPS-0001 A

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-AC-UPS-0001 A

230 VAC UPS System - Feeder A Control Room

3

F

400

VAC

48.00

374 P-450-AC-UPS-0001 B

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-AC-UPS-0001 B

230 VAC UPS System - Feeder B Control Room

3

F

400

VAC

48.00

Lighting (Emergency Outdoor Substation-5) Train-A DP Lighting ( Outdoor Substation-5) Train-B DP

CONTROL BUILDING

283 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

375 P-450-AC-UPS-0001 C

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass Control Room

3

F

400

VAC

48.00

376 P-450-HVAC-9001

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-9001

AHU DX

3

F

400

VAC

11.00

377 P-450-HVAC-9002

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-9002

AHU DX

3

F

400

VAC

2.20

378 P-450-HVAC-6010

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-6010

Air Conditioner Cassette Type (Total = 14 unit)

3

F

400

VAC

29.35

379 P-450-HVAC-6020

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-6020

Electric Duct Heater

3

F

400

VAC

106.03

380 P-450-HVAC-6030

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

450-HVAC-6030

AC Auxiliary

3

F

400

VAC

6.30

420-SWG/MCC-0005

Emergency LV Switchgear/MCC Substation-1 (Power Generation)

900-LPN-4103

Lighting (Indoor Control Room)

3

F

400

VAC

30.20

381 P-900-LPN-4103

INFRASTRUCTURE SUBSTATION INFRASTRUCTURE 284 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

382 P-800-AC-UPS-0001 A

800-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

800-AC-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

40.00

383 P-800-AC-UPS-0001 B

800-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

800-AC-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

40.00

384 P-800-AC-UPS-0001 C

800-SWG/MCC-0002

Essential LV Switchgear/MCC Substation-4 (Utility)

800-AC-UPS-0001 (Pass)

230 VAC UPS System - Bypass

3

F

400

VAC

40.00

385 P-800-HVAC-1001

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Substation Infrastructure HVAC #1

3

F

400

VAC

71.50

386 P-800-HVAC-1002

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Substation Infrastructure HVAC #2

3

F

400

VAC

71.50

387 P-800-HVAC-1003

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Substation Infrastructure HVAC #3

3

F

400

VAC

71.50

388 P-900-DPN-9021-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9021-01

Distribution Panel Indoor Lighting & Small Power Infrastructure Substation

3

F

400

VAC

6.20

389 P-900-DPN-9021-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9021-02

Distribution Panel Outdoor Lighting Infrastructure Substation

3

F

400

VAC

41.25

285 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

390 P-900-DPN-9021-03

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

400VAC Switchgear/MCC Infrastructure

900-DPN-9021-03

Distribution Panel Emergency Lighting Infrastructure Substation

3

F

400

VAC

10.80

Equipment Tag No.

Description

800-SWG/MCC-0002

Volt

kW

Buildings Lighting and Socket Outlet Distribution Board 391 P-900-DPN-9004-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9004-01

Distribution Panel Indoor Lighting Administration Building

3

F

400

VAC

12.40

392 P-900-DPN-9004-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9004-02

Distribution Panel Small Power Administration Building

3

F

400

VAC

35.00

393 P-900-DPN-9012A-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9012A-01

Distribution Panel Indoor Lighting Dormitory Operator & Staff

3

F

400

VAC

22.40

394 P-900-DPN-9012A-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9012A-02

Distribution Panel Small Power Dormitory Operator & Staff

3

F

400

VAC

99.00

395 P-900-DPN-9012B-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9012B-01

Distribution Panel Indoor Lighting Dormitory Field Superintendent

3

F

400

VAC

12.82

396 P-900-DPN-9012B-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9012B-02

Distribution Panel Small Power Dormitory Field Superintendent

3

F

400

VAC

54.50

286 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9013-01

Distribution Panel Indoor Lighting Sport Hall & Multipurpose Building

3

F

400

VAC

20.00

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9013-02

Distribution Panel Small Power Sport Hall & Multipurpose Building

3

F

400

VAC

60.50

399 P-900-DPN-9007-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9007-01

Distribution Panel Lighting & Small Power Mosque

3

F

400

VAC

8.00

400 P-900-DPN-9009-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9009-01

Distribution Panel Indoor Lighting Kitchen & Dining Hall

3

F

400

VAC

6.20

401 P-900-DPN-9009-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9009-02

Distribution Panel Indoor Lighting Kitchen & Dining Hall

3

F

400

VAC

11.00

402 P-900-DPN-9011-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9011-01

Distribution Panel Lighting & Small Power Laundry Center Building

3

F

400

VAC

6.40

DEL 200-9006-LP-05

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

200-9006-LP-05

Training Building Lighting DB

3

F

400

VAC

9.00

403 P-900-DPN-9011-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9011-02

Distribution Panel Indoor Lighting Medical Center Building

3

F

400

VAC

8.00

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9011-03

Distribution Panel Small Power Medical Center Building

3

F

400

VAC

12.00

Equipment Tag No.

Description

397 P-900-DPN-9013-01

398 P-900-DPN-9013-02

404 P-900-DPN-9011-03

287 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9003-01

Distribution Panel Indoor Lighting & Small Power Security Gate House

3

F

400

VAC

3.20

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9016-01

Distribution Panel Indoor Lighting Operation Maintenance Building

3

F

400

VAC

38.00

407 P-900-DPN-9016-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9016-02

Distribution Panel Small Power Operation Maintenance Building

3

F

400

VAC

39.00

408 P-900-DPN-9017-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9017-01

Distribution Panel Indoor Lighting & Small Power Chemical Storage Building

3

F

400

VAC

20.00

409 P-900-DPN-9018-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9018-01

Distribution Panel Indoor Lighting Operation Warehouse Building

3

F

400

VAC

30.00

410 P-900-DPN-9018-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9018-02

Distribution Panel Small Power Operation Warehouse Building

3

F

400

VAC

31.50

411 P-900-DPN-9004-03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9004-03

Distribution Panel Indoor Lighting & Small Power Telcom Building

3

F

400

VAC

3.80

412 900-DPN-9001A-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9001A-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9001B-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

Equipment Tag No.

Description

405 P-900-DPN-9003-01

406 P-900-DPN-9016-01

413 900-DPN-9001B-01

288 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9001C-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9001D-01

Distribution Panel Indoor Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

416 900-DPN-9002-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9002-01

Distribution Panel Indoor Lighting & Small Power Guard House Building

3

F

400

VAC

3.60

417 P-900-DPN-9005-01

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-01

Distribution Panel Indoor Lighting Fire Emegency Station

3

F

400

VAC

2.80

418 P-900-DPN-9005-02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-02

Distribution Panel Small Power Fire Emegency Station

3

F

400

VAC

9.50

419 P-900-DPN-9005-03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-03

Distribution Panel Indoor Lighting Office Building

3

F

400

VAC

10.00

420 P-900-DPN-9005-04

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-04

Distribution Panel Small Power Office Building

3

F

400

VAC

44.50

421 P-900-DPN-9005-05

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-05

Distribution Panel Indoor Lighting Laboratory Building

3

F

400

VAC

7.35

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9005-06

Distribution Panel Small Power Laboratory Building

3

F

400

VAC

21.00

Equipment Tag No.

Description

414 900-DPN-9001C-01

415 900-DPN-9001D-01

422 P-900-DPN-9005-06

289 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9015-01

Distribution Panel Indoor Lighting & Small Power Vehicle Fuel Station Shelter

3

F

400

VAC

1.70

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

200-9014-LP-14

Diesel Station Genset Lighting DB

3

F

400

VAC

58.03

Equipment Tag No.

Description

423 P-900-DPN-9015-01

DEL P-200-9014-LP-14

Volt

kW

424

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Muster Point-1 Lighting DB Infrastructure Area

3

F

400

VAC

6.60

425

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Muster Point-2 Lighting DB Infrastructure Area

3

F

400

VAC

6.60

DEL

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Laboratory Building Sockets Outlet

3

F

400

VAC

163.20

DEL

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Dormitory Field Manager Sockets Outlet

3

F

400

VAC

43.52

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9020

Distribution Panel Air Conditioning Laboratory Building

3

F

400

VAC

40.08

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Dormitory Field Manager AC

3

F

400

VAC

6.40

Buildings Air Conditioned Distribution Board 426 P-900-HVAC-9020

DEL

HOLD (NOTE-5)

290 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9012A-03

Distribution Panel Air Conditioning Dormitory Operator & Staff

3

F

400

VAC

21.51

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-DPN-9012B-03

Distribution Panel Air Conditioning Dormitory Field Superintendent

3

F

400

VAC

11.52

429 P-900-HVAC-9009

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9009

Distribution Panel Air Conditioning Kitchen & Dinning Hall Building

3

F

400

VAC

34.85

430 P-900-HVAC-9003

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9003

Distribution Panel Air Conditioning Security Gate House

3

F

400

VAC

10.66

431 P-900-HVAC-9007

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9007

Distribution Panel Air Conditioning Mosque

3

F

400

VAC

58.00

432 P-900-HVAC-9013

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9013

Distribution Panel Air Conditioning Sport Hall & Multipurposed Building

3

F

400

VAC

50.63

433 P-900-HVAC-9008-01/02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9008

Distribution Panel Air Conditioning Administration Building

3

F

400

VAC

93.73

434 P-900-HVAC-9005-07

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9005-07

Distribution Panel Air Conditioning Fire Emergency Station

3

F

400

VAC

32.00

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9010

Distribution Panel Air Conditioning Medical Center Building

3

F

400

VAC

23.98

Equipment Tag No.

Description

427 P-900-DPN-9012A-03

428 P-900-DPN-9012B-03

435 P-900-HVAC-9010

291 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

436 P-900-HVAC-9011

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9011

Distribution Panel Air Conditioning Laundry Center Building

3

F

400

VAC

19.00

Equipment Tag No.

Description

Volt

kW

DEL

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Training Building AC

3

F

400

VAC

16.00

DEL

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Recreation Center AC

3

F

400

VAC

16.00

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9016

Distribution Panel Air Conditioning Operation Maintenance Building

3

F

400

VAC

42.27

438 P-900-HVAC-9017-01/02/03

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9017

Distribution Panel Air Conditioning Chemical Storage Building

3

F

400

VAC

53.65

439 P-900-HVAC-9018-01/02

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9018

Distribution Panel Air Conditioning Operation Warehouse Building

3

F

400

VAC

66.68

437 P-900-HVAC-9016-01/02

DEL

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Office AC

3

F

400

VAC

16.00

DEL

HOLD (NOTE-5)

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

HOLD (NOTE-5)

Diesel Station Genset

3

F

400

VAC

8.00

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9004

Distribution Panel Air Conditioning Telcom Building

3

F

400

VAC

28.90

440 P-900-HVAC-9004

292 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9005-08

Distribution Panel Air Conditioning Office Building

3

F

400

VAC

37.74

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9002A

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

443 P-900-HVAC-9002B

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9002B

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

444 P-900-HVAC-9002C

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9002C

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

445 P-900-HVAC-9002D

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9002D

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

446 P-900-HVAC-9001

800-SWG/MCC-0002

400VAC Switchgear/MCC Infrastructure

900-HVAC-9001

Distribution Panel Air Conditioning Guard House

3

F

400

VAC

3.54

447 P-211-P-9001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-P-9001

Potable Water Pump

3

M

400

VAC

0.37

DEL P-211-P-9002 A

211-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad Central

211-P-9002 A

Corrosion Inhibitor Injection Pump A

3

M

400

VAC

0.00

Equipment Tag No.

Description

441 900-HVAC-9005-08

442 P-900-HVAC-9002A

Volt

kW

CENTRAL WELL PAD

293 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

DEL P-211-P-9002 B

211-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad Central

211-P-9002 B

Corrosion Inhibitor Injection Pump B

3

M

400

VAC

0.00

DEL P-211-P-9003 A

211-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad Central

211-P-9003 A

Methanol Injection Pump A

3

M

400

VAC

0.00

DEL P-211-P-9003 B

211-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad Central

211-P-9003 B

Methanol Injection Pump B

3

M

400

VAC

0.00

448 P-211-P-9004

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-P-9004

Close Drain Pump

3

M

400

VAC

18.50

449 P-211-UPS-0001 A

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-UPS-0001 A

230 VAC UPS System - Feeder A

3

F

400

VAC

24.00

450 P-211-UPS-0001 B

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-UPS-0001 B

230 VAC UPS System - Feeder B

3

F

400

VAC

24.00

451 P-211-UPS-0001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-UPS-0001

230 VAC UPS System - Bypass

3

F

400

VAC

24.00

452 P-211-HVAC-9001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-9001

Central Well Pad Substation Building HVAC #1

3

F

400

VAC

71.50

294 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

453 P-211-HVAC-9002

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-9002

Central Well Pad Substation Building HVAC #2

3

F

400

VAC

71.50

454 P-211-HVAC-9003

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

211-HVAC-9003

Central Well Pad Substation Building HVAC #3

3

F

400

VAC

71.50

455 P-211-DPN-0001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPN-0001

Flare Package

3

F

400

VAC

3.00

456 P-211-DPN-0002

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPN-0002

Outdoor Lighting and Small Power

3

F

400

VAC

24.22

457 P-211-DPN-0003

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPN-0003

Indoor Lighting and Small Power

3

F

400

VAC

3.70

458 P-211-DPE-0001

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

211-DPE-0001

Emergency Lighting (Outdoor & Indoor)

3

F

400

VAC

7.27

211-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad Central

HOLD (NOTE-5)

Muster Point Lighting DB Central Wellpad

3

F

400

VAC

6.60

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-P-9001

Potable Water Pump

3

M

400

VAC

0.37

459

HOLD (NOTE-5)

Volt

kW

EAST WELL PAD 460 P-212-P-9001

295 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

DEL P-212-P-9002 A

212-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad East

212-P-9002 A

Corrosion Inhibitor Injection Pump A

3

M

400

VAC

0.00

DEL P-212-P-9002 B

212-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad East

212-P-9002 B

Corrosion Inhibitor Injection Pump B

3

M

400

VAC

0.00

DEL P-212-P-9003 A

212-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad East

212-P-9003 A

Methanol Injection Pump A

3

M

400

VAC

0.00

DEL P-212-P-9003 B

212-SWG/MCC-0001

400VAC Switchgear/MCC Well Pad East

212-P-9003 B

Methanol Injection Pump B

3

M

400

VAC

0.00

461 P-212-P-9004

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-P-9004

Close Drain Pump

3

M

400

VAC

45.00

462 P-212-UPS-1004 A

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-UPS-1004 A

230 VAC UPS System - Feeder A

3

F

400

VAC

24.00

463 P-212-UPS-1004 B

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-UPS-1004 B

230 VAC UPS System - Feeder B

3

F

400

VAC

24.00

464 P-212-UPS-1004

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-UPS-1004

230 VAC UPS System - Bypass

3

F

400

VAC

24.00

296 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

465 P-212-HVAC-9001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-9001

East Well Pad Substation Building HVAC #1

3

F

400

VAC

71.50

466 P-212-HVAC-9002

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-9002

East Well Pad Substation Building HVAC #2

3

F

400

VAC

71.50

467 P-212-HVAC-9003

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-HVAC-9003

East Well Pad Substation Building HVAC #3

3

F

400

VAC

71.50

468 P-212-DPN-1001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPN-1001

FLARE PANEL

3

F

400

VAC

3.00

469 P-212-DPN-1002

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPN-1002

Outdoor Lighting and Small Power

3

F

400

VAC

36.00

470 P-212-DPN-1003

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPN-1003

Indoor Lighting and Small Power

3

F

400

VAC

3.70

471 P-212-DPE-0001

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

212-DPE-0001

Emergency Lighting (Outdoor & Indoor)

3

F

400

VAC

9.60

212-SWG/MCC-0002

400VAC Switchgear/MCC Well Pad East

HOLD (NOTE-5)

Muster Point Lighting DB East Wellpad

3

F

400

VAC

6.60

472

HOLD (NOTE-5)

SALES GAS METERING STATION 297 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

DEL P-710-P-MOV-A

710-SWG/MCC-0001

400VAC Switchgear/MCC Sales Gas Metering Station

710-P-MOV-A

MOV Gas Metering Stream-A Inlet Line

3

M

400

VAC

1.50

DEL P-710-P-MOV-B

710-SWG/MCC-0001

400VAC Switchgear/MCC Sales Gas Metering Station

710-P-MOV-B

MOV Gas Metering Stream-B Inlet Line

3

M

400

VAC

1.50

DEL P-710-P-MOV-C

710-SWG/MCC-0001

400VAC Switchgear/MCC Sales Gas Metering Station

710-P-MOV-C

MOV Gas Cross-over Line

3

M

400

VAC

1.50

473 P-710-P-9001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-P-9001

Potable Water Pump

3

M

400

VAC

0.37

474 P-710-V-9004

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-V-9004

Instrument Air Compressor

3

M

400

VAC

11.00

475 P-710-AC-UPS-1001 A

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-AC-UPS-1001 A

Gas Metering 230VAC UPS System Feeder A

3

F

400

VAC

24.00

476 P-710-AC-UPS-1001 B

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-AC-UPS-1001 B

Gas Metering 230VAC UPS System Feeder B

3

F

400

VAC

24.00

477 P-710-AC-UPS-1001 C

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-AC-UPS-1001 C

Gas Metering 230VAC UPS System Bypass

3

F

400

VAC

24.00

298 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

478 P-710-HVAC-7101

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-HVAC-7101

Metering Station Building HVAC

3

F

400

VAC

5.20

479 P-710-LPN-1101

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-LPN-1101

Indoor Lighting Panel

3

F

400

VAC

16.43

480 P-710-DPN-2001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-SO-001

Metering Station Building Socket Outlet

3

F

400

VAC

5.00

481 P-710-LPN-1201

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-LPN-1201

Outdoor Lighting Panel

3

F

400

VAC

29.00

482 P-710-DPE-0001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-DPE-0001

Emergency Lighting Panel (Outdoor & Indoor)

3

F

400

VAC

7.00

483 P-710-LPR-1001

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

710-SO-002

Metering Station Welding Outlet

3

F

400

VAC

13.00

710-SWG/MCC-0002

400VAC Switchgear/MCC Sales Gas Metering Station

HOLD (NOTE-5)

Muster Point Sales Gas Metering Station

3

F

400

VAC

6.60

484

HOLD (NOTE-5)

299 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

D

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

(NOTE-4)

Motor Space Heater (Continuous) GPF (Qty=73 ea)

1

M

230

VAC

0.23

(NOTE-4)

Motor Space Heater (Intermittent) GPF (Qty=6 ea)

1

M

230

VAC

0.23

(NOTE-4)

Motor Space Heater (Stand-by) GPF (Qty=105 ea)

1

M

230

VAC

0.23

211-SH-1001

Space Heater for Close Drain Pump Central Wellpad

1

M

230

VAC

0.20

212-SH-1001

Space Heater for Close Drain Pump East Wellpad

1

M

230

VAC

0.20

420-SH-1011

STG-A Space Heater

1

M

230

VAC

2.25

420-SH-2011

STG-B Space Heater

1

M

230

VAC

2.25

Volt

kW

230 V POWER CABLES Space Heater

1

(NOTE-4)

420-SWG/MCC-0004

2

(NOTE-4)

420-SWG/MCC-0004

3

(NOTE-4)

420-SWG/MCC-0004

4

P-211-SH-1001

420-SWG/MCC-0004

5

P-212-SH-1001

420-SWG/MCC-0004

6

P-420-SH-1011

420-SWG/MCC-0004

7

P-420-SH-2011

420-SWG/MCC-0004

Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation) Essential LV SWGR/MCC Substation-1 (Power Generation)

230VAC UPS 300 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

SUBSTATION-1 (POWER GENERATION) 8

P-420-UCP-1001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-UCP-1001

UCP STG-A

1

F

210

VAC

1.00

9

P-420-BCH-1001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-BCH-1001

Battery Charger STG-A

1

F

210

VAC

1.00

10

P-420-UCP-4001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-UCP-4001

UCP Essential Generator

1

F

210

VAC

1.00

11

P-420-BCH-4001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-BCH-4001

Battery Charger Essential Generator

1

F

210

VAC

1.00

12

P-420-VCB-0001

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-VCB-0001

Motor Charging VCB for 420-SWG-0001

1

M

210

VAC

1.80

13

P-420-VCB-0002

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

420-VCB-0002

Motor Charging VCB for 420-SWG-0002

1

M

210

VAC

3.00

14

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O

1

F

210

VAC

0.50

15

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

1.00

301 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

16

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

ECMS NETWORK SERVER

1

F

210

VAC

1.00

17

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

ECMS PRINTER

1

F

210

VAC

0.50

18

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

LCP STG-A

1

F

210

VAC

1.00

19

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O

1

F

210

VAC

0.70

20

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O

1

F

210

VAC

0.20

21

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

LOAD SHEDDING PANEL-A

1

F

210

VAC

1.00

22

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

EMERGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

7.20

23

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

TELECOM CABINET

1

F

210

VAC

1.00

24

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

HP BOILER CABINET

1

F

210

VAC

1.00

302 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

25

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

LP BOILER CABINET

1

F

210

VAC

1.00

26

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

MAIN ECMS-A PANEL

1

F

210

VAC

1.50

27

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

28

HOLD (NOTE-5)

420-AC-UPS-0001A

230 VAC UPS System Power Generation Area (Bus-A)

HOLD (NOTE-5)

FACP CABINET

1

F

210

VAC

0.50

29

P-420-UCP-2001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-UCP-2001

UCP STG-B

1

F

210

VAC

1.00

30

P-420-BCH-2001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-BCH-2001

Battery Charger STG-B

1

F

210

VAC

1.00

31

P-420-UCP-5001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-UCP-5001

UCP Emergency Generator

1

F

210

VAC

1.00

32

P-420-BCH-5001

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-BCH-5001

Battery Charger Emergency Generator

1

F

210

VAC

0.50

303 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

33

P420-VCB-0003

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-VCB-0003

Motor Charging VCB for 420-SWG-0003

1

M

210

VAC

0.30

34

P420-VCB-0004

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-VCB-0004

Motor Charging VCB for 420-SWG-0004

1

M

210

VAC

0.50

35

P420-VCB-0005

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

420-VCB-0005

Motor Charging VCB for 420-SWG-0005

1

M

210

VAC

0.30

36

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O

1

F

210

VAC

0.50

37

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O

1

F

210

VAC

0.70

38

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O

1

F

210

VAC

0.20

39

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

ECMS OPC SERVER

1

F

210

VAC

1.00

40

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LCP STG-B

1

F

210

VAC

1.00

41

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LCP ESSENTIAL GEN

1

F

210

VAC

1.00

304 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

42

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

ECMS WORK STATION

1

F

210

VAC

1.00

43

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

ECMS NETWORK SWITCH

1

F

210

VAC

0.20

44

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LOAD SHEDDING PANEL-B

1

F

210

VAC

1.00

45

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

TELECOM CABINET

1

F

210

VAC

1.00

46

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

HP BOILER CABINET

1

F

210

VAC

1.00

47

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

LP BOILER CABINET

1

F

210

VAC

1.00

48

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

MAIN ECMS-B PANEL

1

F

210

VAC

1.50

49

HOLD (NOTE-5)

420-AC-UPS-0001 B

230 VAC UPS System Power Generation Area (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

SUBSTATION-2 (TRAIN A AREA) 305 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

50

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

Motor Charging VCB : 231-SWG-0001

1

M

210

VAC

2.20

51

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

Motor Charging ACB : 231-SWG-0002

1

M

210

VAC

0.30

52

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

53

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

0.40

54

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

55

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

56

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

57

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

58

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

306 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

59

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

VRU LCP

1

F

210

VAC

0.50

60

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

61

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

RECYLE GAS COMPRESSOR LCP

1

F

210

VAC

0.50

62

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

HP/LP A FLARE LCP

1

F

210

VAC

1.00

63

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

SALES GAS COMPRESSOR LCP

1

F

210

VAC

1.00

64

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

TEG LCP

1

F

210

VAC

0.50

65

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

SRU LCP

1

F

210

VAC

0.50

66

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

TGU LCP

1

F

210

VAC

0.50

67

HOLD (NOTE-5)

231-AC-UPS-0001A

230 VAC UPS System Train-A Area (Bus-A)

HOLD (NOTE-5)

UPS DB at Instrument Building 280A-B-9001

1

F

210

VAC

3.50

307 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

68

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

Motor Charging VCB : 231-SWG-0003

1

M

210

VAC

0.50

69

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

70

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

71

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

VRU LCP

1

F

210

VAC

0.50

72

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

ECMS WORKSTATION

1

F

210

VAC

0.50

73

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.20

74

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

EMERGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

8.80

75

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

308 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

76

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

Motor Charging VCB : 231-SWG-0004

1

M

210

VAC

0.30

77

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

78

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

79

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

80

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

81

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

RECYLE GAS COMPRESSOR LCP

1

F

210

VAC

0.50

82

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

SALES GAS COMPRESSOR LCP

1

F

210

VAC

1.00

83

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

TEG LCP

1

F

210

VAC

0.50

84

HOLD (NOTE-5)

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

SRU LCP

1

F

210

VAC

0.50

309 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

85

HOLD (NOTE-5)

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-AC-UPS-0001B

230 VAC UPS System Train-A Area (Bus-B)

HOLD (NOTE-5)

TGU LCP

1

F

210

VAC

0.50

Volt

kW

SUBSTATION-3 (TRAIN-B AREA) 86

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

Motor Charging VCB 280-SWG-0001

1

M

210

VAC

1.40

87

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

Motor Charging ACB : 280-SWG-0002

1

M

210

VAC

0.50

88

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

89

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

1.00

90

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

91

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

92

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL (280A-B9001)

1

F

210

VAC

0.50

310 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

93

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

94

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

95

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.20

96

HOLD (NOTE-5)

280-AC-UPS-0001A

230 VAC UPS System Train-B Area (Bus-A)

HOLD (NOTE-5)

UPS DB at Instrument Building 280B-B-9001

1

F

210

VAC

3.50

97

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

Motor Charging VCB : 280-SWG-0003

1

M

210

VAC

0.30

98

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL (280A-B9001)

1

F

210

VAC

0.50

99

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

100

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

311 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

101

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

ECMS WORKSTATION

1

F

210

VAC

0.50

102

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.80

103

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

EMERGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

10.40

104

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

105

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

106

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

107

HOLD (NOTE-5)

280-AC-UPS-0001B

230 VAC UPS System Train-B Area (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

Motor Charging VCB 480-SWG-0001

1

M

210

VAC

2.00

SUBSTATION-4 (UTILITY AREA) 108

HOLD (NOTE-5)

312 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

109

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

Motor Charging ACB : 480-SWG-0002

1

M

210

VAC

0.30

110

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

111

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

1.00

112

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

113

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

INSTRUMENT AIR COMPRESSORA LCP

1

F

210

VAC

1.00

114

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

INSTRUMENT AIR COMPRESSORB LCP

1

F

210

VAC

1.00

115

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

INSTRUMENT AIR COMPRESSORC LCP

1

F

210

VAC

1.00

116

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

117

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

313 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

118

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

EMERGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

4.00

119

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

REMOTE I/O ECMS-A PANEL

1

F

210

VAC

0.50

120

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

121

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

0.20

122

HOLD (NOTE-5)

480-AC-UPS-0001A

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

123

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

AIR MANAGER LCP

1

F

210

VAC

0.50

124

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

SIS REMOTE I/O PANEL

1

F

210

VAC

0.50

125

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

0.20

314 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

126

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

ECMS PANEL

1

F

210

VAC

0.50

127

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

ECMS WORKSTATION

1

F

210

VAC

0.50

128

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

1.00

129

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

INSTRUMENT AIR DRYER-A LCP

1

F

210

VAC

1.00

130

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

INSTRUMENT AIR DRYER-B LCP

1

F

210

VAC

1.00

131

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

INSTRUMENT AIR DRYER-C LCP

1

F

210

VAC

1.00

132

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

FIRE WATER PANEL BATTERY CHARGER-A

1

F

210

VAC

1.00

133

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

FIRE WATER PANEL BATTERY CHARGER-B

1

F

210

VAC

1.00

134

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

PCS REMOTE I/O PANEL

1

F

210

VAC

0.50

315 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

135

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

TELECOM CABINET

1

F

210

VAC

1.00

136

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-B)

HOLD (NOTE-5)

REMOTE I/O ECMS-B PANEL

1

F

210

VAC

0.50

137

HOLD (NOTE-5)

480-AC-UPS-0001B

230 VAC UPS System Utility Area (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

0.50

CONTROL BUILDING 138

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

PCS SYSTEM CABINET

1

F

210

VAC

1.00

139

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

SIS SYSTEM CABINET

1

F

210

VAC

0.50

140

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

F&G SYSTEM CABINET

1

F

210

VAC

0.20

141

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

142

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

LDS SYSTEM COMPUTER

1

F

210

VAC

0.65

316 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

143

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

OFFICE APPLICATION COMPUTER

1

F

210

VAC

0.65

144

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

MM SERVER

1

F

210

VAC

0.65

145

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

PROCESS MONITORING COMP

1

F

210

VAC

0.65

146

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

RTS SERVER

1

F

210

VAC

0.65

147

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

FO BACKBONE PATCH PANEL

1

F

210

VAC

2.00

148

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

MOM SYSTEM CABINET 2

1

F

210

VAC

0.65

149

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

SOE WORKSTATION

1

F

210

VAC

0.65

150

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

F&G MONITOR WORKSTATION

1

F

210

VAC

0.40

151

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

FIRE STATION MONITOR

1

F

210

VAC

0.40

317 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

152

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

HVAC CONTROL PANEL

1

F

210

VAC

0.60

153

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

ECMS-A PANEL

1

F

210

VAC

0.50

154

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

ECMS-A WORKSTATION

1

F

210

VAC

0.65

155

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

CWE SYSTEM CABINET

1

F

210

VAC

1.00

156

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

MOM SYSTEM CABINET 1

1

F

210

VAC

1.00

157

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

1.00

158

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Control Building (Bus-A)

HOLD (NOTE-5)

OPERATOR TRAINING SYSTEM CABINET

1

F

210

VAC

0.60

159

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PCS SYSTEM CABINET

1

F

210

VAC

1.00

318 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

160

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

SIS SYSTEM CABINET

1

F

210

VAC

0.50

161

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

F&G SYSTEM CABINET

1

F

210

VAC

0.20

162

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

FACP PANEL

1

F

210

VAC

0.50

163

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CCTV SERVER

1

F

210

VAC

0.65

164

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

EDMS SERVER

1

F

210

VAC

1.30

165

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

MIS BACK-UP SERVER

1

F

210

VAC

0.65

166

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

APMS SERVER

1

F

210

VAC

0.65

167

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

EPMS SERVER

1

F

210

VAC

0.65

168

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

HISTORIAN OPC SERVER

1

F

210

VAC

1.30

319 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

169

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PRINTER

1

F

210

VAC

0.69

170

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

FO BACKBONE PATCH PANEL

1

F

210

VAC

1.00

171

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CCTV SYSTEM

1

F

210

VAC

1.50

172

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CCTV MONITOR

1

F

210

VAC

0.80

173

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PAGA STATION

1

F

210

VAC

0.40

174

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PCS PLASMA TV

1

F

210

VAC

1.87

175

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

MOM SYSTEM CABINET 2

1

F

210

VAC

0.65

176

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

1.60

177

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

SIS CONSOLE

1

F

210

VAC

0.30

320 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

178

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

F&G CONSOLE

1

F

210

VAC

0.30

179

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

ECMS-B PANEL

1

F

210

VAC

0.50

180

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PCS EWS

1

F

210

VAC

0.40

181

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

ESD/F&G EWS

1

F

210

VAC

0.40

182

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

AMS EWS

1

F

210

VAC

0.40

183

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

CWE SYSTEM CABINET

1

F

210

VAC

1.00

184

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

MOM SYSTEM CABINET 1

1

F

210

VAC

1.00

185

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

OPERATOR TRAINING SYSTEM CABINET

1

F

210

VAC

0.60

186

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Control Building (Bus-B)

HOLD (NOTE-5)

PAGA CABINET

1

F

210

VAC

1.00

321 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

HOLD (NOTE-5)

EMERGENCY LIGHTING DB (outdoor & indoor) 211-DPE-0001

1

F

210

VAC

10.80

Volt

kW

INFRASTRUCTURE AREA SUBSTATION 187

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

188

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

800-SWG/MCC-0001 A

11 kV Switchgear Infrastructure Substation (BUS A)

1

F

210

VAC

0.50

189

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

800-BCH-5001

Back-Up Genset Charger

1

F

210

VAC

0.75

190

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

800-SWG/MCC-0002 A

400 VAC Switchgear/MCC Infrastructure Substation (BUS A)

1

F

210

VAC

1.00

191

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

192

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

ECMS Workstation

1

F

210

VAC

0.50

193

HOLD (NOTE-5)

800-AC-UPS-0001A

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

2.00

322 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

194

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

HOLD (NOTE-5)

Telecom UPS DB

1

F

210

VAC

13.40

195

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

800-BCH-5001

Back-Up Genset Charger

1

F

210

VAC

0.75

196

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

800-SWG/MCC-0002 B

400 VAC Switchgear/MCC Infrastructure Substation (BUS B)

1

F

210

VAC

1.00

197

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

198

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-B)

800-SWG/MCC-0001 B

11 kV Switchgear Infrastructure Substation (BUS B)

1

F

210

VAC

0.50

199

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

NETWORK SWITCH

1

F

210

VAC

2.00

200

HOLD (NOTE-5)

800-AC-UPS-0001B

230 VAC UPS System Infrastructure Area (Bus-A)

HOLD (NOTE-5)

F&G REMOTE I/O PANEL

1

F

210

VAC

2.00

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

0.50

CENTRAL WELLPAD SUBSTATION 201

HOLD (NOTE-5)

211-AC-UPS-0001A

323 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

202

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

203

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.50

204 P-211-SWG/MCC-0002

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-SWG-MCC-0002 A

400 VAC Switchgear/MCC Well Pad Central (BUS A)

1

F

210

VAC

1.00

205 P-211-ECMS-0001 A

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-ECMS-0001 A

ECMS Panel

1

F

210

VAC

0.50

206 P-211-ECMS-0002

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

P-211-ECMS-0002

ECMS PC

1

F

210

VAC

0.50

207 P-211-SWG/MCC-0001

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

211-SWG-MCC-0001 A

11 kV Switchgear Central Well Pad Substation (BUS A)

1

F

210

VAC

0.50

208

HOLD (NOTE-5)

211-AC-UPS-0001A

230 VAC UPS System Central Wellpad (Bus-A)

HOLD (NOTE-5)

Back-Up Genset Charger

1

F

210

VAC

0.75

209

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

324 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

210

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

211

HOLD (NOTE-5)

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.30

212 P-211-SWG-MCC-0002 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-SWG-MCC-0002 B

400 VAC Switchgear/MCC Well Pad Central (BUS B)

1

F

210

VAC

0.75

213 P-211-ECMS-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-ECMS-0001 B

ECMS Panel

1

F

210

VAC

0.50

214 P-211-SWG-MCC-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-SWG-MCC-0001 B

11 kV Switchgear Central Well Pad Substation (BUS B)

1

F

210

VAC

0.50

215 P-211-DPE-0001A

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-DPE-0001

Emergency Lighting (Outdoor & Indoor)

1

F

210

VAC

5.60

216 C-211-DPN-1001

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-DPN-1001

FLARE PANEL

1

F

210

VAC

0.50

217 C-211-HVAC-9004

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-HVAC-9004

HVAC CONTROL PANEL

1

F

210

VAC

0.50

EAST WELLPAD SUBSTATION 325 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

218

HOLD (NOTE-5)

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

219

HOLD (NOTE-5)

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

220

HOLD (NOTE-5)

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.30

221 P-212-SWG-MCC-0002 A

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-SWG-MCC-0002 A

400 VAC Switchgear/MCC East Well Pad Substation (BUS A)

1

F

210

VAC

0.75

222 P-212-ECMS-0001 A

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-ECMS-0001 A

ECMS Panel

1

F

210

VAC

0.50

223 P-212-ECMS-0002

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-ECMS-0002

ECMS PC

1

F

210

VAC

0.50

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

212-SWG-MCC-0001 A

11 kV Switchgear East Well Pad Substation (BUS A)

1

F

210

VAC

0.50

212-AC-UPS-0001A

230 VAC UPS System East Wellpad (Bus-A)

HOLD (NOTE-5)

Back-Up Genset Charger

1

F

210

VAC

0.75

224 P-212-SWG-MCC-0001 A

225

HOLD (NOTE-5)

326 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

226

HOLD (NOTE-5)

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

227

HOLD (NOTE-5)

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.50

228

HOLD (NOTE-5)

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

HOLD (NOTE-5)

Flow Comp Cabinet

1

F

210

VAC

0.30

229 P-212-SWG-MCC-0002 B

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

212-SWG-MCC-0002 B

400 VAC Switchgear/MCC East Well Pad Substation (BUS B)

1

F

210

VAC

0.75

230 P-212-ECMS-0001 B

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

212-ECMS-0001 B

ECMS Panel

1

F

210

VAC

0.50

231 P-212-SWG-MCC-0001 B

212-AC-UPS-0001B

230 VAC UPS System East Wellpad (Bus-B)

212-SWG-MCC-0001 B

11 kV Switchgear East Well Pad Substation (BUS B)

1

F

210

VAC

0.50

232 P-212-DPE-0001

212-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

212-DPE-0001

EMERGENCY LIGHTING DB (outdoor & indoor) 212-DPE-0001

1

F

210

VAC

9.60

233 C-212-DPN-1001

212-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

212-DPN-1001

FLARE PANEL

1

F

210

VAC

0.50

234 C-212-HVAC-9004

212-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

212-HVAC-9004

HVAC CONTROL PANEL

1

F

210

VAC

0.50

327 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

SALES GAS METERING SUBSTATION 235

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

236

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.40

237

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Flow Computer System

1

F

210

VAC

1.80

238

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Laser Jet Printer

1

F

210

VAC

0.50

239

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

Sales Gas Ccmputer

1

F

210

VAC

0.70

240

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

ECMS PC

1

F

210

VAC

0.50

241

HOLD (NOTE-5)

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

710-BCH-5001

Back-Up Genset Charger

1

F

210

VAC

0.75

242 C-710-BCH-5001

328 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

710-BCH-5001

400 VAC Switchgear/MCC Sales Gas Metering Substation (BUS A)

1

F

210

VAC

0.50

244 C-710-SWG-0001A

710-AC-UPS-0001A

230 VAC UPS System Sales Gas Metering (Bus-A)

710-SWG/MCC-0002

11 kV Switchgear Sales Gas Metering Substation (BUS A)

1

F

210

VAC

0.50

245

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

Telecom Cabinet

1

F

210

VAC

2.00

246

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

RTU/SCADA Cabinet

1

F

210

VAC

0.40

247

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

Dot Maztrix Printer

1

F

210

VAC

0.10

248

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

Flow Computer System

1

F

210

VAC

1.80

249

HOLD (NOTE-5)

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

HOLD (NOTE-5)

ECMS Panel

1

F

210

VAC

0.50

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-UCP-5001

Back-Up Genset UCP

1

F

210

VAC

0.75

Equipment Tag No.

Description

243 C-710-SWG/MCC-0002A

250 C-211-ECMS-0002

329 of 522

Volt

kW

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

251 C-710-DPE-0001

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-DPE-0001

EMERGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

4.00

252 C-710-HVAC-7101

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-HVAC-7101

HVAC CONTROL PANEL

1

F

210

VAC

0.50

253 C-710-SWG/MCC-0002A

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-BCH-5001

400 VAC Switchgear/MCC Sales Gas Metering Substation (BUS B)

1

F

210

VAC

0.50

254 C-710-SWG-0001A

710-AC-UPS-0001B

230 VAC UPS System Sales Gas Metering (Bus-B)

710-SWG/MCC-0002

11 kV Switchgear Sales Gas Metering Substation (BUS B)

1

F

210

VAC

0.50

Volt

kW

710-SWG-0001

E

DC POWER CABLES DC UPS SUBSTATION-1 (POWER GENERATION)

1

C-420-SWG/MCC-0001A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0001A

11 kV Switchgear: 420-SWG-0001A

1

F

108

VDC

1.00

2

C-420-SWG/MCC-0001B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0001B

11 kV Switchgear: 420-SWG-0001B

1

F

108

VDC

1.00

330 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

3

C-420-SWG/MCC-0003A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0003A

400 VAC MCC : 420-MCC-0003A

1

F

108

VDC

1.00

4

C-420-SWG/MCC-0003B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0003B

400 VAC MCC : 420-MCC-0003B

1

F

108

VDC

1.00

5

C-420-SWG/MCC-0005A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0005A

400 VAC MCC : 420-MCC-0005A

1

F

108

VDC

1.00

6

C-420-SWG/MCC-0004A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0004A

400 VAC MCC : 420-MCC-0004A

1

F

108

VDC

1.00

7

C-420-SWG/MCC-0004B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0004B

400 VAC MCC : 420-MCC-0004B

1

F

108

VDC

1.00

8

C-420-SWG/MCC-0005B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0005B

400 VAC MCC : 420-MCC-0005B

1

F

108

VDC

1.00

9

C-420-SWG/MCC-0002A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0002A

6,6 kV Switchgear: 420-SWG-0002A

1

F

108

VDC

1.00

10

C-420-SWG/MCC-0002B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-SWG/MCC-0002B

6,6 kV Switchgear: 420-SWG-0002B

1

F

108

VDC

1.00

11

C-420-TRF-0001A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0001A

TRAFO 420-TRF-0001A

1

F

108

VDC

0.10

331 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

12

C-420-TRF-0001B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0001B

TRAFO 420-TRF-0001B

1

F

108

VDC

0.10

13

C-420-TRF-0002A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0002A

TRAFO 420-TRF-0002A

1

F

108

VDC

0.10

14

C-420-TRF-0002B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0002B

TRAFO 420-TRF-0002B

1

F

108

VDC

0.10

15

C-420-TRF-0003A

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0003A

TRAFO 420-TRF-0003A

1

F

108

VDC

0.10

16

C-420-TRF-0003B

420-DC-UPS-0001

110 VDC UPS System Power Generation Substation

420-TRF-0003B

TRAFO 420-TRF-0003B

1

F

108

VDC

0.10

SUBSTATION-2 (TRAIN-A AREA) 17

C-231-SWG/MCC-0001A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0001 (BUS A)

6.6 kV Switchgear / MCC MV 1A Substation-2 (Train-A)

1

F

108

VDC

1.00

18

C-231-SWG/MCC-0001B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0001 (BUS B)

6.6 kV Switchgear / MCC MV 1B Substation-2 (Train-A)

1

F

108

VDC

1.00

332 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

19

C-231-SWG/MCC-0002A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0002 (BUS A)

400 VAC Switchgear / MCC LV 2A Substation-2 (Train-A)

1

F

108

VDC

1.00

20

C-231-SWG/MCC-0002B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0002 (BUS B)

400 VAC Switchgear / MCC LV 2B Substation-2 (Train-A)

1

F

108

VDC

1.00

21

C-231-SWG/MCC-0003A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0003 (BUS A)

400 VAC Switchgear / MCC LV 3A Substation-2 (Train-A)

1

F

108

VDC

1.00

22

C-231-SWG/MCC-0003B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0003 (BUS B)

400 VAC Switchgear / MCC LV 3B Substation-2 (Train-A)

1

F

108

VDC

1.00

23

C-231-SWG/MCC-0004A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0004 (BUS A)

400 VAC Switchgear / MCC LV 4A Substation-2 (Train-A)

1

F

108

VDC

1.00

24

C-231-SWG/MCC-0004B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-SWG/MCC-0004 (BUS B)

400 VAC Switchgear / MCC LV 4B Substation-2 (Train-A)

1

F

108

VDC

1.00

25

C-231-TRF-0001A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0001A

TRAFO 231-TRF-0001A

1

F

108

VDC

0.10

26

C-231-TRF-0001B

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0001B

TRAFO 231-TRF-0001B

1

F

108

VDC

0.10

27

C-231-TRF-0002A

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0002A

TRAFO 231-TRF-0002A

1

F

108

VDC

0.10

333 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

28

C-231-TRF-0002B

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

231-DC-UPS-0001

110 VDC UPS System Train-A Substation

231-TRF-0002B

TRAFO 231-TRF-0002B

1

F

108

VDC

0.10

Volt

kW

SUBSTATION-3 (TRAIN-B AREA) 29

C-280-SWG/MCC-0001A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0001A

6,6 kV Switchgear: 280-SWG-0001A

1

F

108

VDC

1.00

30

C-280-SWG/MCC-0001B

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0001B

6,6 kV Switchgear: 280-SWG-0001B

1

F

108

VDC

1.00

31

C-280-SWG/MCC-0002A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0002A

400 VAC MCC : 280-MCC-0002A

1

F

108

VDC

1.00

32

C-280-SWG/MCC-0002B

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0002B

400 VAC MCC : 280-MCC-0002B

1

F

108

VDC

1.00

33

C-280-SWG/MCC-0003A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0003A

400 VAC MCC : 280-MCC-0003A

1

F

108

VDC

1.00

34

C-280-SWG/MCC-00013

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-SWG/MCC-0003B

400 VAC MCC : 280-MCC-0003B

1

F

108

VDC

1.00

35

C-280-TRF-0001A

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-TRF-0001A

TRAFO 280-TRF-0001A

1

F

108

VDC

0.10

334 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

36

C-280-TRF-0001B

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

280-DC-UPS-0001

110 VDC UPS System Train-B Substation

280-TRF-0001B

TRAFO 280-TRF-0001B

1

F

108

VDC

0.10

Volt

kW

SUBSTATION-4 (UTILITY AREA) 37

C-480-SWG/MCC-0001A

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0001A

6,6 kV Switchgear: 480-SWG-0001A

1

F

108

VDC

1.00

38

C-480-SWG/MCC-0001B

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0001B

6,6 kV Switchgear: 480-SWG-0001B

1

F

108

VDC

1.00

39

C-480-SWG/MCC-0002A

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0002A

400 VAC MCC : 480-MCC-0002A

1

F

108

VDC

1.00

40

C-480-SWG/MCC-0002B

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-SWG/MCC-0002B

400 VAC MCC : 480-MCC-0002B

1

F

108

VDC

1.00

41

C-480-TRF-0001A

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-TRF-0001A

TRAFO 480-TRF-0001A

1

F

108

VDC

0.10

42

C-480-TRF-0001B

480-DC-UPS-0001

110 VDC UPS System Utility Substation

480-TRF-0001B

TRAFO 480-TRF-0001B

1

F

108

VDC

0.10

BATTERY RACK FOR UPS GPF 230 VAC UPS 335 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

43

P-420-BAT-0001 A-01/02

420-AC-UPS-0001 A

Substation-1 230 VAC UPS System Feeder A

420-BAT-0001 A

Battery Rack for Substation-1 230 VAC UPS System - Feeder A

1

F

220

VDC

61.04

44

P-420-BAT-0001 B-01/02

420-AC-UPS-0001 B

Substation-1 230 VAC UPS System Feeder B

420-BAT-0001 B

Battery Rack for Substation-1 230VAC UPS System - Feeder B

1

F

220

VDC

61.04

45

P-231-BAT-0001 A

231-AC-UPS-0001 A

Substation-2 230 VAC UPS System Feeder A

231-BAT-0001 A

Battery Rack for Substation-2 230 VAC UPS System - Feeder A

1

F

220

VDC

25.43

46

P-231-BAT-0001 B

231-AC-UPS-0001 B

Substation-2 230VAC UPS System Feeder B

231-BAT-0001 B

Battery Rack for Substation-2 230VAC UPS System - Feeder B

1

F

220

VDC

25.43

47

P-280-BAT-0001 A

280-AC-UPS-0001 A

Substation-3 230VAC UPS System Feeder A

280-BAT-0001 A

Battery Rack for Substation-3 230 VAC UPS System - Feeder A

1

F

220

VDC

27.88

48

P-280-BAT-0001 B

280-AC-UPS-0001 B

Substation-3 230VAC UPS System Feeder B

280-BAT-0001 B

Battery Rack for Substation-3 230VAC UPS System - Feeder B

1

F

220

VDC

27.88

49

P-480-BAT-0001 A

480-AC-UPS-0001 A

Substation-4 230 VAC UPS System Feeder A

480-BAT-0001 A

Battery Rack for Substation-4 230 VAC UPS System - Feeder A

1

F

220

VDC

27.88

50

P-480-BAT-0001 B

480-AC-UPS-0001 B

Substation-4 230 VAC UPS System Feeder B

480-BAT-0001 B

Battery Rack for Substation-4 230VAC UPS System - Feeder B

1

F

220

VDC

27.88

51

P-410-BAT-0001 A-01/02

410-AC-UPS-0001 A

Control Building 230 VAC UPS System - Feeder A

410-BAT-0001 A

Battery Rack for Control Building 230 VAC UPS System - Feeder A

1

F

220

VDC

53.10

336 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

52

P-410-BAT-0001 B-01/02

410-AC-UPS-0001 B

Control Building 230 VAC UPS System - Feeder B

410-BAT-0001 B

Battery Rack for Control Building 230VAC UPS System - Feeder B

1

F

220

VDC

53.10

53

P-800-BAT-0001 A-01/02

800-AC-UPS-0001 A

Infrastructure 230 VAC UPS System Feeder A

800-BAT-0001 A

Battery Rack for Infrastructure 230 VAC UPS System - Feeder A

1

F

220

VDC

53.10

54

P-800-BAT-0001 B-01/02

800-AC-UPS-0001 B

Infrastructure 230 VAC UPS System Feeder B

800-BAT-0001 B

Battery Rack for Infrastructure 230VAC UPS System - Feeder B

1

F

220

VDC

53.10

55

P-211-BAT-0001 A

211-AC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 A

Battery Rack for Central Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

56

P-211-BAT-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 B

Battery Rack for Central Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

230 VAC UPS System Central Wellpad (Bus-B) 57

P-212-BAT-0001 A

212-UPS-1004 A

230 VAC UPS System Central Wellpad (Bus-B)

212-BAT-0001 A

Battery Rack for East Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

58

P-212-BAT-0001 B

212-UPS-1004 B

230 VAC UPS System Central Wellpad (Bus-B)

212-BAT-0001 B

Battery Rack for East Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

230 VAC UPS System Central Wellpad (Bus-B) 337 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

59 P-710-BAT-1001 A

710-AC-UPS-1001 A

230 VAC UPS System Central Wellpad (Bus-B)

710-BAT-1001 A

Battery Rack for Gas Metering 230 VAC UPS System - Feeder A

1

F

220

VDC

20.44

60 P-710-BAT-1001 B

710-AC-UPS-1001 B

230 VAC UPS System Central Wellpad (Bus-B)

710-BAT-1001 B

Battery Rack for Gas Metering 230VAC UPS System - Feeder B

1

F

220

VDC

20.44

Volt

kW

230 VAC UPS System Central Wellpad (Bus-B) 230 VAC UPS System Central Wellpad (Bus-B)

GPF 110 VDC UPS 61

P-420-BAT-0002A

420-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

420-BAT-0002 A

Battery Rack for Substation-1 110 VDC UPS System - Feeder A

1

F

110

VDC

20.35

62

P-420-BAT-0002 B

420-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

420-BAT-0002 B

Battery Rack for Substation-1 110VDC UPS System - Feeder B

1

F

110

VDC

20.35

63

P-231-BAT-0002 A

231-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

231-BAT-0002 A

Battery Rack for Substation-2 110 VDC UPS System - Feeder A

1

F

110

VDC

16.48

64

P-231-BAT-0002 B

231-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

231-BAT-0002 B

Battery Rack for Substation-2 110VDC UPS System - Feeder B

1

F

110

VDC

16.48

65

P-280-BAT-0002 A

280-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

280-BAT-0002 A

Battery Rack for Substation-3 110 VDC UPS System - Feeder A

1

F

110

VDC

12.72

66

P-280-BAT-0002 B

280-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

280-BAT-0002 B

Battery Rack for Substation-3 110VDC UPS System - Feeder B

1

F

110

VDC

12.72

338 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

67

P-480-BAT-0002 A

480-DC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

480-BAT-0002 A

Battery Rack for Substation-4 110 VDC UPS System - Feeder A

1

F

110

VDC

8.85

68

P-480-BAT-0002 B

480-DC-UPS-0001 B

230 VAC UPS System Central Wellpad (Bus-B)

480-BAT-0002 B

Battery Rack for Substation-4 110VDC UPS System - Feeder B

1

F

110

VDC

8.85

230 VAC UPS System Central Wellpad (Bus-B) 230 VAC UPS System Central Wellpad (Bus-B)

WELLPAD 230 VAC UPS 69

P-211-BAT-0001 A

211-AC-UPS-0001 A

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 A

Battery Rack for Central Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

70

P-211-BAT-0001 B

211-AC-UPS-0001B

230 VAC UPS System Central Wellpad (Bus-B)

211-BAT-0001 B

Battery Rack for Central Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

71

P-212-BAT-0001 A

212-UPS-1004 A

230 VAC UPS System Central Wellpad (Bus-B)

212-BAT-0001 A

Battery Rack for East Wellpad 230 VAC UPS System - Feeder A

1

F

220

VDC

17.71

72

P-212-BAT-0001 B

212-UPS-1004 B

230 VAC UPS System Central Wellpad (Bus-B)

212-BAT-0001 B

Battery Rack for East Wellpad 230VAC UPS System - Feeder B

1

F

220

VDC

17.71

339 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

F

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

TYPICAL LIGHTING & SMALL POWER CABLES TYPICAL OUTDOOR LIGHTINGS

1

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Lighting DB (Outdoor) #1

(NOTE-6)

400W Normal HPS Floodlight

3

F

400

VAC

25.60

2

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

230V AC UPS DB

(NOTE-6)

400W Emergency HPS Floodlight

3

F

400

VAC

0.40

3

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Lighting DB (Outdoor) #1

(NOTE-6)

150W Normal HPS Wellglass

3

F

400

VAC

0.15

4

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Lighting DB (Outdoor) #1

(NOTE-6)

250W HPS Streetlight

3

F

400

VAC

0.25

TYPICAL INDOOR LIGHTING 5

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Lighting (Indoor Substation-1) #1

(NOTE-6)

2x36 W Normal Fluorescent Light

1

F

230

VAC

0.07

6

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

230V AC UPS DB

(NOTE-6)

2x36 W Emergency Fluorescent Light

1

F

230

VAC

0.07

340 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

OUTER PERIMETER LIGHTING (For One (1) Loop Perimeter Lighting Cable) 7

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (16 ea)

1

F

400

VAC

2.40

8

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (14 ea)

1

F

393

VAC

2.10

9

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (12 ea)

1

F

392

VAC

1.80

10

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (10 ea)

1

F

391

VAC

1.50

11

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (8 ea)

1

F

390

VAC

1.20

12

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (6 ea)

1

F

387

VAC

0.90

13

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (4 ea)

1

F

385

VAC

0.60

14

HOLD (NOTE-5, NOTE-6)

(NOTE-6)

Outer Perimeter Lighting DB

(NOTE-6)

150W Normal HPS Floodlight (2 ea)

1

F

383

VAC

0.30

341 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

G

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

TIE-IN BANYU URIP

1

P-620-LPN-0001

HOLD (NOTE-5)

Distribution Board Helipad

HOLD (NOTE-5)

Distribution Board Guard House

3

F

400

VAC

4.40

2

HOLD (NOTE-5)

HOLD (NOTE-5)

Distribution Board Guard House

HOLD (NOTE-5)

Indoor Lighting Fluoroscent 2x36 W

1

F

230

VAC

0.07

3

HOLD (NOTE-5)

HOLD (NOTE-5)

Distribution Board Guard House

HOLD (NOTE-5)

Air Conditioning

1

F

230

VAC

1.50

4

HOLD (NOTE-5)

HOLD (NOTE-5)

Distribution Board Guard House

HOLD (NOTE-5)

Outdoor Lighting Floodlight 2x400 W

1

F

230

VAC

1.60

5

HOLD (NOTE-5)

HOLD (NOTE-5)

Distribution Board Guard House

HOLD (NOTE-5)

Socket Outlet

1

F

230

VAC

1.20

342 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From

Power

To

Equipment Tag No.

Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

6

HOLD (NOTE-5)

HOLD (NOTE-5)

UPS Distribution Board PB-24 of Banyu Urip

HOLD (NOTE-5)

SCADA-RTU Panel in PB-24

1

F

230

VAC

5.00

7

HOLD (NOTE-5)

UPDP826551

UPS 230V AC Distribution Board A/B

HOLD (NOTE-5)

CWS Workstation

1

F

230

VAC

0.657

8

HOLD (NOTE-5)

UPDP826551

UPS 230V AC Distribution Board A/B

HOLD (NOTE-5)

PCS System

1

F

230

VAC

0.95

9

HOLD (NOTE-5)

UPDP826551

UPS 230V AC Distribution Board A/B

HOLD (NOTE-5)

Flow Comp System

1

F

230

VAC

0.51

Notes : 1. Short Circuit Values (kA) in Column AI are based on ETAP simulated short circuit at each of load end (user) 2. CSA of cable (Smin) are based on the following : 343 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

ISC x √t

a.) For MV Feeder, Smin of cable determined by formulas : Smin =

k

b.) For 6600 V Motor, Smin determined by Let-through Energy of Protection Device as per Appendix-E c.) For 400 V Motor, Smin determined by Let-through Energy of Protection Device as per Appendix-F d.) For 400 V Feeder, Smin determined by Let-through Energy of Protection Device as per Appendix-G e.) For 230V Cable, Smin determined by Let-through Energy of Protection Device as per Appendix-H (Merlin Gerin C60N for Feeder and C60H for Motor) 3. Sizing cable of switchgear is based on maximum load of switchgear plus 15% contingency and 20% growth allowance of load 4. This is only general calculation of Cable for Space Heater (for motor rated > 5.5 kW). For the complete list of Space Heater cable can be seen in the Doc. No. JTB-SF-E-LST-900-00013~00018, Electrical Cable 5. The Cable Tag Number shall be verifired in the detail engineering phase. 6. The calculation of typical lighting & small power cable in this document are used as an general sizing only. The total number of lighting fixtures will sum in the Electrical MTO.

Legends:

344 of 522

GAS DEVELOPMEN

Cable Route No.

Voltage No. Equip System, Phase Type Vin

Cable Tag.No. From Equipment Tag No.

Vin (Voltage Source) Vd% (Voltage dropn in %) Vd max %(Voltage drop max in %)

IFL (Full Load current (Amp)) R (Cable resistance (ohm/1000 meter at 90 ºC)) X (Cable reactance (ohm/1000 meter at 50 Hz))

Power

To Description

Equipment Tag No.

Description

3 Ph / 1 Ph

F/M

Volt

kW

Cos  (Load steady state power factor )

Sin φ

Cos β (Load starting power factor)

Lmax (Maximum Cable Length (m))

L (Cable Length (m))

Ist (Motor Starting Current (Amp))

345 of 522

=Sqrt (1-Cos² φ))

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

11 kV Switchgear ation-1 (Power Generation)

3

F

11,000

11 kV Switchgear ation-1 (Power Generation)

3

F

11 kV Switchgear ation-1 (Power Generation)

3

/ 6.6 kV Transformer A ation-1 (Power Generation)

/ 6.6 kV Transformer B ation-1 (Power Generation)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

6,500

7,471

1.00

0.87

0.49

N/A

392.14

N/A

0

14

2

3/C -

185

mm²

0.1281

0.095

748

0.56

418.8

11,000

VAC

6,500

7,471

1.00

0.87

0.49

N/A

392.14

N/A

0

14

2

3/C -

185

mm²

0.1281

0.095

748

0.56

418.8

F

11,000

VAC

3,000

3,448

1.00

0.87

0.49

N/A

180.99

N/A

5

13

1

3/C -

150

mm²

0.16

0.098

332

0.56

185.9

3

F

11,000

VAC

11,520

14,400

1.00

0.80

0.60

N/A

755.80

N/A

0

16

3

3/C -

300

mm²

0.0799

0.089

1446

0.56

809.7

3

F

11,000

VAC

11,520

14,400

1.00

0.80

0.60

N/A

755.80

N/A

0

16

3

3/C -

300

mm²

0.0799

0.089

1446

0.56

809.7

11 kV Switchgear Infrastructure

3

F

11,000

VAC

2,223

2,779

1.00

0.80

0.60

N/A

145.86

N/A

4

11

1

3/C -

95

mm²

0.247

0.105

263

0.56

147.2

1 / 0.42 kV Transformer Infrastructure

3

F

11,000

VAC

2,400

3,000

1.00

0.80

0.60

N/A

157.46

N/A

4

12

1

3/C -

120

mm²

0.197

0.102

298

0.56

166.8

346 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

11 kV Switchgear ntral Well Pad Substation

3

F

11,000

0.42 kV Central Wellpad Transformer

3

F

11 kV Switchgear ast Well Pad Substation

3

11 kV Switchgear ast Well Pad Substation / 0.42 kV East Wellpad Transformer

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

389

486

1.00

0.80

0.60

N/A

25.53

N/A

3

10

1

3/C -

70

mm²

0.343

0.111

220

0.56

123.2

11,000

VAC

384

480

1.00

0.80

0.60

N/A

25.19

N/A

1

8

1

3/C -

35

mm²

0.669

0.123

154

0.56

86.24

F

11,000

VAC

384

480

1.00

0.80

0.60

N/A

25.19

N/A

3

10

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

3

F

11,000

VAC

389

486

1.00

0.80

0.60

N/A

25.53

N/A

3

10

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

3

F

11,000

VAC

384

480

1.00

0.80

0.60

N/A

25.19

N/A

1

8

1

3/C -

35

mm²

0.669

0.115

154

0.56

86.24

11 kV Switchgear s Gas Metering Substation

3

F

11,000

VAC

166

207

1.00

0.80

0.60

N/A

12.60

N/A

0

7

1

3/C -

25

mm²

0.927

0.13

129

0.56

72.24

1 / 0.42 kV Transformer Sales Gas Metering

3

F

11,000

VAC

120

150

1.00

0.80

0.60

N/A

12.60

N/A

0

7

1

3/C -

25

mm²

0.927

0.13

129

0.56

72.24

347 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

0.4 kV Main Transformer

3

F

6,600

0.4 kV Main Transformer

3

F

4 kV Essential Transformer

3

4 kV Essential Transformer

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1,200

1,500

1.00

0.80

0.60

N/A

131.22

N/A

4

11

1

3/C -

95

mm²

0.247

0.099

263

0.56

147.2

6,600

VAC

1,200

1,500

1.00

0.80

0.60

N/A

131.22

N/A

4

11

1

3/C -

95

mm²

0.247

0.099

263

0.56

147.2

F

6,600

VAC

1,536

1,920

1.00

0.80

0.60

N/A

167.96

N/A

5

13

1

3/C -

150

mm²

0.16

0.093

332

0.56

185.9

3

F

6,600

VAC

1,536

1,920

1.00

0.80

0.60

N/A

167.96

N/A

5

13

1

3/C -

150

mm²

0.16

0.093

332

0.56

185.9

V Switchgear / MCC MV 1A Substation-2 (Train-A)

3

F

6,600

VAC

4,840

6,050

1.00

0.80

0.60

N/A

529.20

N/A

0

16

2

3/C -

300

mm²

0.0799

0.084

964

0.56

539.8

V Switchgear / MCC MV 1B Substation-2 (Train-A)

3

F

6,600

VAC

4,840

6,050

1.00

0.80

0.60

N/A

529.20

N/A

0

16

2

3/C -

300

mm²

0.0799

0.084

964

0.56

539.8

/0.4 kV Transformer 1A Substation-2 (Train-A)

3

F

6,600

VAC

960

1,200

1.00

0.80

0.60

N/A

104.97

N/A

3

10

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

/0.4 kV Transformer 1B Substation-2 (Train-A)

3

F

6,600

VAC

960

1,200

1.00

0.80

0.60

N/A

104.97

N/A

3

10

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

348 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

/0.4 kV Transformer 2A Substation-2 (Train-A)

3

F

6,600

/0.4 kV Transformer 2B Substation-2 (Train-A)

3

F

6 kV Switchgear/MCC Substation-3 (Train-B)

3

6 kV Switchgear/MCC Substation-3 (Train-B)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3,840

4,800

1.00

0.80

0.60

N/A

419.89

N/A

1

15

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

6,600

VAC

3,840

4,800

1.00

0.80

0.60

N/A

419.89

N/A

1

15

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

F

6,600

VAC

3,842

4,802

1.00

0.80

0.60

N/A

420.10

N/A

1

15

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

3

F

6,600

VAC

3,842

4,802

1.00

0.80

0.60

N/A

420.10

N/A

1

15

2

3/C -

240

mm²

0.0984

0.087

862

0.56

482.7

kV Transformer A Substation3 (Train-B)

3

F

6,600

VAC

3,456

4,320

1.00

0.80

0.60

N/A

377.90

N/A

0

14

2

3/C -

185

mm²

0.1281

0.09

748

0.56

418.8

kV Transformer B Substation3 (Train-B)

3

F

6,600

VAC

3,456

4,320

1.00

0.80

0.60

N/A

377.90

N/A

0

14

2

3/C -

185

mm²

0.1281

0.09

748

0.56

418.8

V Switchgear / MCC MV 2A Substation-4 (Utility)

3

F

6,600

VAC

1,798

2,248

1.00

0.80

0.60

N/A

196.62

N/A

5

14

1

3/C -

185

mm²

0.1281

0.09

374

0.56

209.4

349 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

F

6,600

kV Transformer Substation-4 (Utility)

3

F

kV Transformer Substation-4 (Utility)

3

mpressor (3rd Stage) MotorA

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1,798

2,248

1.00

0.80

0.60

N/A

196.62

N/A

5

14

1

3/C -

185

mm²

0.1281

0.09

374

0.56

209.4

6,600

VAC

768

960

1.00

0.80

0.60

N/A

83.98

N/A

3

10

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

F

6,600

VAC

768

960

1.00

0.80

0.60

N/A

83.98

N/A

3

10

1

3/C -

70

mm²

0.343

0.104

220

0.56

123.2

3

M

6,600

VAC

300.00

340.91

0.952

0.88

0.47

0.50

31.33

203.62

0

0

1

3/C -

#N/A mm²

#N/A

#N/A

#N/A

0.56

#N/A

mpressor (3rd Stage) MotorB

3

M

6,600

VAC

300.00

340.91

0.952

0.88

0.47

0.50

31.33

203.62

0

0

1

3/C -

#N/A mm²

#N/A

#N/A

#N/A

0.56

mpressor (4th Stage) MotorA

3

M

6,600

VAC

750.00

842.70

0.965

0.89

0.46

0.50

76.39

496.54

0

0

1

3/C -

#N/A mm²

#N/A

#N/A

#N/A

0.56

mpressor (4th Stage) MotorB

3

M

6,600

VAC

750.00

842.70

0.965

0.89

0.46

0.50

76.39

496.54

0

0

1

3/C -

#N/A mm²

#N/A

#N/A

#N/A

0.56

V Switchgear / MCC MV 2B Substation-4 (Utility)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

350 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

n Amine Pump-A (Train A)

3

M

6,600

n Amine Pump-B (Train A)

3

M

n Amine Pump-A (Train B)

3

n Amine Pump-B (Train B)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

6,600

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

M

6,600

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

3

M

6,600

VAC

200.00

229.89

0.947

0.87

0.49

0.50

21.24

138.03

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

P BWF Start-Up Pump

3

M

6,600

VAC

300.00

340.91

0.952

0.88

0.47

0.50

31.33

203.62

0

7

1

3/C -

25

mm²

0.927

0.13

129

0.56

72.24

ent Air Compressor Package Motor A

3

M

6,600

VAC

355.00

403.41

0.957

0.88

0.47

0.50

36.87

239.69

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

351 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ent Air Compressor Package Motor B

3

M

6,600

ent Air Compressor Package Motor C

3

M

ewater Pump - Electric

3

Inlet Cooler Fan 1

Inlet Cooler Fan 2

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

355.00

403.41

0.957

0.88

0.47

0.50

36.87

239.69

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

6,600

VAC

355.00

403.41

0.957

0.88

0.47

0.50

36.87

239.69

0

7

1

3/C -

25

mm²

0.927

0.122

129

0.56

72.24

M

6,600

VAC

300.00

340.91

0.952

0.88

0.47

0.50

31.33

203.62

2

9

1

3/C -

50

mm²

0.494

0.11

181

0.56

101.3

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

352 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Inlet Cooler Fan 3

3

M

400

Inlet Cooler Fan 4

3

M

Inlet Cooler Fan 5

3

Inlet Cooler Fan 6

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Inlet Cooler Fan 7

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Inlet Cooler Fan 8

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

ced Water Transfer Pump A

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

ced Water Transfer Pump B

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

353 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

e Produced Water Transfer Pump A

3

M

400

e Produced Water Transfer Pump B

3

M

3

Condensate Transfer Pump A

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

5

13

1

3/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

5

13

1

3/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

Condensate Transfer Pump B

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ompressor (1st Stage) MotorA

3

M

0

VAC

132.00

150.00

0.954

0.88

0.47

0.50

#DIV/0!

#DIV/0!

0

###

2

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

ompressor (1st Stage) MotorB

3

M

0

VAC

132.00

150.00

0.954

0.88

0.47

0.50

#DIV/0!

#DIV/0!

0

###

2

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

Skim Oil Pump

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

354 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ercooler-A (1st Stage) Fan-1

3

M

400

ercooler-A (1st Stage) Fan-2

3

M

ercooler-B (1st Stage) Fan-1

3

ercooler-B (1st Stage) Fan-2

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

mpressor (2nd Stage) MotorA

3

M

0

VAC

75.00

85.23

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

0

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

mpressor (2nd Stage) MotorB

3

M

0

VAC

75.00

85.23

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

0

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

ercooler-A (2nd Stage) Fan-1

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

0

2

1

3/C -

9.4500

0.60

ercooler-A (2nd Stage) Fan-2

3

M

0

VAC

1.10

1.29

0.802

0.85

0.53

0.50

#DIV/0!

#DIV/0!

1

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

ercooler-B (2nd Stage) Fan-1

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

0

2

1

3/C -

9.4500

0.60

355 of 522

2.5

2.5

mm²

mm²

0.0961

0.0961

29

29

Amp

17.40

#DIV/

17.40

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ercooler-B (2nd Stage) Fan-2

3

M

0

ercooler-A (3rd Stage) Fan-1

3

M

ercooler-A (3rd Stage) Fan-2

3

ercooler-B (3rd Stage) Fan-1

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.10

1.29

0.802

0.85

0.53

0.50

#DIV/0!

#DIV/0!

1

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

5.8800

0.60

M

0

VAC

2.20

2.62

0.842

0.84

0.54

0.50

#DIV/0!

#DIV/0!

1

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

5.8800

0.60

ercooler-B (3rd Stage) Fan-2

3

M

0

VAC

2.20

2.62

0.842

0.84

0.54

0.50

#DIV/0!

#DIV/0!

1

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

RU Knockout Pump A

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RU Knockout Pump B

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Motor for VRU Compressor

3

M

400

VAC

160.00

179.78

0.961

0.89

0.46

0.50

270.01

1755.09

0

12

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

356 of 522

4

4

mm²

mm²

0.0899

0.0899

37

37

Amp

#DIV/

22.20

#DIV/

22.20

#DIV/

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ethanol Injection Pump

3

M

400

ndensate Reflux Pump A

3

M

ndensate Reflux Pump B

3

ndensate Cooler Fan-1

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.00

3.49

0.851

0.86

0.51

0.50

5.92

38.46

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

ndensate Cooler Fan-2

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

sate Stabilizer Recycle Liquid Pump

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

le Gas Compressor Cooler Fan-1

3

M

400

VAC

3.00

3.49

0.851

0.86

0.51

0.50

5.92

38.46

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

le Gas Compressor Cooler Fan-2

3

M

400

VAC

3.00

3.49

0.851

0.86

0.51

0.50

5.92

38.46

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

357 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

EG Circulator Pump A

3

M

400

EG Circulator Pump B

3

M

EG Reflux Pump A

3

EG Reflux Pump B

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ced Water Booster Pump A

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ced Water Booster Pump B

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

3

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

7

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

EG Makeup Pump

egeneration Overhead Gas Compressor A

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

358 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

egeneration Overhead Gas Compressor B

3

M

400

eneration Tower Cooler Fan-1

3

M

eneration Tower Cooler Fan-2

3

ycol Drain Return Pump

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

pylene Condenser Fan 1

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

pylene Condenser Fan 2

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

pylene Condenser Fan 3

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

pylene Condenser Fan 4

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

359 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

pylene Condenser Fan 5

3

M

400

pylene Condenser Fan 6

3

M

pylene Condenser Fan 7

3

pylene Condenser Fan 8

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

ne Compressor A (1st Stage) Auxiliary Load

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ne Compressor A (2nd Stage) Auxiliary Load

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ne Compressor B (1st Stage) Auxiliary Load

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ne Compressor B (2nd Stage) Auxiliary Load

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

360 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

olvent Air Cooler-A (AGRU A) #1

3

M

400

olvent Air Cooler-A (AGRU A) #2

3

M

olvent Air Cooler-A (AGRU A) #3

3

olvent Air Cooler-A (AGRU A) #4

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-A (AGRU A) #5

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-A (AGRU A) #6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-A (AGRU A) #7

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-A (AGRU A) #8

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-B (AGRU A) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

361 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

olvent Air Cooler-B (AGRU A) #2

3

M

400

olvent Air Cooler-B (AGRU A) #3

3

M

olvent Air Cooler-B (AGRU A) #4

3

olvent Air Cooler-B (AGRU A) #5

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-B (AGRU A) #6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-B (AGRU A) #7

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

olvent Air Cooler-B (AGRU A) #8

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

6

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

for HP Lean Solvent Pump 1 (Train A)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

6

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

for HP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

6

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

362 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

for HP Lean Solvent Pump 3 (Train A)

3

M

400

flux Pump-1 A (Train A)

3

M

flux Pump-1 B (Train A)

3

flux Pump-2 A (Train A)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

6

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

flux Pump-2 B (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

d Solvent Pump (Stand-By) Train A

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Hydrocarbon Pump (StandBy) Train A

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

for LP Lean Solvent Pump 1 (Train A)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

for LP Lean Solvent Pump 2 (Train A)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

363 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

M

400

iary for Regenerator Lean olvent Pump 1 (Train A)

3

M

iary for Regenerator Lean olvent Pump 2 (Train A)

3

iary for Regenerator Lean olvent Pump 3 (Train A)

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

Condensate Pump-1A (Train A)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

Condensate Pump-1B (Train A)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

Condensate Pump-2A (Train A)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

Condensate Pump-2B (Train A)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

ad Condenser-A (AGRU A) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

for LP Lean Solvent Pump 3 (Train A)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

364 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ad Condenser-A (AGRU A) #2

3

M

400

ad Condenser-A (AGRU A) #3

3

M

ad Condenser-A (AGRU A) #4

3

ad Condenser-B (AGRU A) #1

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU A) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU A) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU A) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

RU Fresh Solvent Pump A

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

RU Fresh Solvent Pump B

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

365 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

olvent Air Cooler-A (AGRU B) #1

3

M

400

olvent Air Cooler-A (AGRU B) #2

3

M

olvent Air Cooler-A (AGRU B) #3

3

olvent Air Cooler-A (AGRU B) #4

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-A (AGRU B) #5

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-A (AGRU B) #6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-A (AGRU B) #7

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-A (AGRU B) #8

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

366 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

olvent Air Cooler-B (AGRU B) #1

3

M

400

olvent Air Cooler-B (AGRU B) #2

3

M

olvent Air Cooler-B (AGRU B) #3

3

olvent Air Cooler-B (AGRU B) #4

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-B (AGRU B) #5

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-B (AGRU B) #6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-B (AGRU B) #7

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

olvent Air Cooler-B (AGRU B) #8

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

for HP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

5

8

1

3/C -

35

mm²

0.6690

0.0753

122

0.60

73.20

367 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

for HP Lean Solvent Pump 2 (Train B)

3

M

400

for HP Lean Solvent Pump 3 (Train B)

3

M

flux Pump-1 A (Train B)

3

flux Pump-1 B (Train B)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

5

8

1

3/C -

35

mm²

0.6690

0.0753

122

0.60

73.20

400

VAC

22.00

24.72

0.928

0.89

0.46

0.50

38.45

249.91

5

8

1

3/C -

35

mm²

0.6690

0.0753

122

0.60

73.20

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

flux Pump-2 A (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

flux Pump-2 B (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

d Solvent Pump (Stand-By) Train B

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Hydrocarbon Pump (StandBy) Train B

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

for LP Lean Solvent Pump 1 (Train B)

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

368 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

for LP Lean Solvent Pump 2 (Train B)

3

M

400

for LP Lean Solvent Pump 3 (Train B)

3

M

iary for Regenerator Lean olvent Pump 1 (Train B)

3

iary for Regenerator Lean olvent Pump 2 (Train B)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

iary for Regenerator Lean olvent Pump 3 (Train B)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

iler Condensate Pump-1 A (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

ler Condensate Pump-1 B (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

iler Condensate Pump-2 A (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

ler Condensate Pump-2 B (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

369 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ad Condenser-A (AGRU B) #1

3

M

400

ad Condenser-A (AGRU B) #2

3

M

ad Condenser-A (AGRU B) #3

3

ad Condenser-A (AGRU B) #4

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU B) #1

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU B) #2

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU B) #3

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ad Condenser-B (AGRU B) #4

3

M

400

VAC

55.00

61.80

0.944

0.89

0.46

0.50

94.49

614.18

5

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

370 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Gas Dehy TEG Circulation Pump A

3

M

400

Gas Dehy TEG Circulation Pump B

3

M

Gas Dehy TEG Lean Cooler Fan-1

3

Gas Dehy TEG Lean Cooler Fan-2

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

132.00

150.00

0.954

0.88

0.47

0.50

226.95

1475.15

5

16

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

400

VAC

132.00

150.00

0.954

0.88

0.47

0.50

226.95

1475.15

5

16

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

Gas Dehy TEG Lean Cooler Fan-3

3

M

0

VAC

15.00

16.67

0.913

0.90

0.44

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

Gas Dehy TEG Lean Cooler Fan-4

3

M

0

VAC

15.00

16.67

0.913

0.90

0.44

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

Gas Dehy TEG Supply Pump

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

EG Drain Vessel Pump

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

371 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Gas Compressor Discharge Cooler Fan 1

3

M

400

Gas Compressor Discharge Cooler Fan 2

3

M

Gas Compressor Discharge Cooler Fan 3

3

Gas Compressor Discharge Cooler Fan 4

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

M

0

VAC

30.00

34.09

0.932

0.88

0.47

0.50

#DIV/0!

#DIV/0!

3

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

3

M

0

VAC

30.00

34.09

0.932

0.88

0.47

0.50

#DIV/0!

#DIV/0!

3

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

Gas Compressor A Auxiliary Load

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

4

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

Gas Compressor B Auxiliary Load

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

4

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

sh Water Pump-1 at AGE Absorber (Train A)

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

sh Water Pump-2 at AGE Absorber (Train A)

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

372 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

sh Water Pump-3 at AGE Absorber (Train A)

3

M

400

rator Reflux Pump-1 (Train A)

3

M

rator Reflux Pump-2 (Train A)

3

rator Reflux Pump-3 (Train A)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

Solvent Sump Pump-A (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

Solvent Sump Pump-B (Train A)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

rator Overhead Condenser 1 (Train A)

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

4

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

rator Overhead Condenser 2 (Train A)

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

4

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

rator Bottoms Pump 1 (Train A)

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

4

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

373 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

rator Bottoms Pump 2 (Train A)

3

M

400

rator Bottoms Pump 3 (Train A)

3

M

n Amine Cooler (Train A) #1

3

n Amine Cooler (Train A) #2

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

4

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

4

12

1

3/C -

120

mm²

0.1970

0.0708

240

0.60

144.0

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

n Amine Cooler (Train A) #3

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

n Amine Cooler (Train A) #4

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

n Amine Cooler (Train A) #5

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

n Amine Cooler (Train A) #6

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

n Amine Cooler (Train A) #7

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

374 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

n Amine Cooler (Train A) #8

3

M

400

ine Pump-1 at AGE Absorber (Train A)

3

M

ine Pump-2 at AGE Absorber (Train A)

3

ine Pump-3 at AGE Absorber (Train A)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

5

15

1

3/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

5

15

1

3/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

5

15

1

3/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

h Solvent Pump A (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

Solvent Pump B (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

r Water Pump-1 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

r Water Pump-2 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

r Water Pump-3 (Train A)

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

375 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

sh Water Pump-1 at AGE Absorber (Train B)

3

M

400

sh Water Pump-2 at AGE Absorber (Train B)

3

M

sh Water Pump-3 at AGE Absorber (Train B)

3

generator Reflux Pump-1 (Train B)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

generator Reflux Pump-2 (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

generator Reflux Pump-3 (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

nt Sump Pump-A (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

nt Sump Pump-B (Train B)

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

376 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

rator Overhead Condenser 1 (Train B)

3

M

400

rator Overhead Condenser 2 (Train B)

3

M

rator Bottoms Pump-1 (Train B)

3

rator Bottoms Pump-2 (Train B)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

rator Bottoms Pump-3 (Train B)

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

n Amine Cooler (Train B) #1

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

n Amine Cooler (Train B) #2

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

n Amine Cooler (Train B) #3

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

n Amine Cooler (Train B) #4

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

377 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

n Amine Cooler (Train B) #5

3

M

400

n Amine Cooler (Train B) #6

3

M

n Amine Cooler (Train B) #7

3

n Amine Cooler (Train B) #8

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

ine Pump-A at AGE Absorber (Train B)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

2

12

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

ine Pump-B at AGE Absorber (Train B)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

2

12

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

ine Pump-C at AGE Absorber (Train B)

3

M

400

VAC

110.00

127.91

0.951

0.86

0.51

0.50

194.13

1261.85

2

12

2

3/C -

120

mm²

0.1970

0.0708

480

0.60

288.0

r Water Pump-A (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

r Water Pump-B (Train B)

3

M

400

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

378 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

M

400

ulfur Transfer Pump A

3

M

ulfur Transfer Pump B

3

Air Blower A Auxiliary Load

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

15.00

16.67

0.913

0.90

0.44

0.50

26.35

171.27

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Air Blower B Auxiliary Load

3

M

400

VAC

7.50

8.43

0.899

0.89

0.46

0.50

13.53

87.94

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

ur Condensate Pump A

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

ur Condensate Pump B

3

M

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

ulfur Handling Pump A

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

Water Pump-C (Train B)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

379 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ulfur Handling Pump B

3

M

400

P Condensate Pump A

3

M

P Condensate Pump B

3

Quench Water Pump-A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

Quench Water Pump-B

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

sh Water Pump-A at TGU Absorber

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

h Water Pump-B at TGU Absorber

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

5

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

ine Pump-A at TGU Absorber

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

380 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ine Pump-B at TGU Absorber

3

M

400

Water Drain Return Pump

3

M

ench Water Air Cooler #1

3

ench Water Air Cooler #2

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

6

14

1

3/C -

185

mm²

0.1281

0.0720

304

0.60

182.4

400

VAC

2.20

2.62

0.842

0.84

0.54

0.50

4.49

29.18

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

5

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

5

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

BFW Transfer Pump-A

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

BFW Transfer Pump-B

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

am Condensate Pump A

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

am Condensate Pump B

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

381 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Blowdown Pump A

3

M

400

Blowdown Pump B

3

M

LP BFW Pump A

3

LP BFW Pump B

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

4

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

3

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

4

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

eam Condenser Fan-1

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

eam Condenser Fan-2

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

eam Condenser Fan-3

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.56

44.24

eam Condenser Fan-4

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.56

44.24

eam Condenser Fan-5

3

M

0

VAC

0.00

0.00

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

382 of 522

#DIV/0! #DIV/0! #DIV/0!

0.56

Amp

#DIV/

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

eam Condenser Fan-6

3

M

0

eam Condenser Fan-7

3

M

eam Condenser Fan-8

3

eam Condenser Fan-9

eam Condenser Fan-10

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.00

0.00

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

0

VAC

0.00

0.00

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

M

0

VAC

0.00

0.00

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

3

M

0

VAC

0.00

0.00

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

3

M

0

VAC

0.00

0.00

0.948

0.88

0.47

0.50

#DIV/0!

#DIV/0!

4

###

1

3/C - #DIV/0! mm²

#DIV/0! #DIV/0! #DIV/0!

0.56

#DIV/

Scavenger Tank Mixer Motor

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

alization Amine Tank Mixer Motor

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ate Solution Tank Mixer Motor

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

n Scavenger Pump Motor-A

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

383 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

n Scavenger Pump Motor-B

3

M

400

zation Amine Pump Motor-A

3

M

zation Amine Pump Motor-B

3

hate Solution Pump Motor A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

400

VAC

1.10

1.29

0.802

0.85

0.53

0.50

2.33

15.14

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

M

400

VAC

1.10

1.29

0.802

0.85

0.53

0.50

2.33

15.14

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

hate Solution Pump Motor B

3

M

400

VAC

0.75

0.87

0.772

0.86

0.51

0.50

1.63

10.60

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

or Steam Condenser Motor 1

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

or Steam Condenser Motor 2

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

aw Water Feed Pump A

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

4

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

384 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

aw Water Feed Pump B

3

M

400

Off-Gas K.O. Drum Pump-A

3

M

Off-Gas K.O. Drum Pump-B

3

Off-Gas K.O. Drum Pump-A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

4

9

1

3/C -

50

mm²

0.4940

0.0748

144

0.60

86.40

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Off-Gas K.O. Drum Pump-B

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

mal Oxidizer Air Blower A Auxiliary Load

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

mal Oxidizer Air Blower B Auxiliary Load

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

mal Oxidizer Air Blower C Auxiliary Load

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

385 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

mal Oxidizer Air Blower D Auxiliary Load

3

M

400

mal Oxidizer Air Blower E Auxiliary Load

3

M

Knockout Drum Condensate Pump A

3

Knockout Drum Condensate Pump B

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

M

400

VAC

90.00

100.00

0.951

0.90

0.44

0.50

151.77

986.53

2

11

2

3/C -

95

mm²

0.2470

0.0711

422

0.60

253.2

3

M

400

VAC

90.00

100.00

0.951

0.90

0.44

0.50

151.77

986.53

2

11

2

3/C -

95

mm²

0.2470

0.0711

422

0.60

253.2

Knockout Drum Condensate Pump A

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

8

16

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

Knockout Drum Condensate Pump B

3

M

400

VAC

75.00

85.23

0.948

0.88

0.47

0.50

129.76

843.46

8

16

1

3/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

386 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Diesel Pump

3

M

400

3

M

Close Drain Pump

3

Open Drain Pump

irewater Jockey Pump

gency LV Switchgear/MCC ation-1 (Power Generation) Charger Emergency Diesel Generator

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

M

400

VAC

37.00

41.57

0.936

0.89

0.46

0.50

64.11

416.70

6

11

1

3/C -

95

mm²

0.2470

0.0711

211

0.60

126.6

3

M

400

VAC

5.50

6.25

0.886

0.88

0.47

0.50

10.18

66.18

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

3

F

400

VAC

320

400.00

1.00

0.80

0.60

N/A

577.35

N/A

0

16

3

4/C -

300

mm²

0.0799

0.0835

1188

0.60

712.8

3

F

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

387 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

0 VAC Switchgear/MCC Well Pad Central

3

F

400

ry Charger Backup Diesel nerator Well Pad Central

3

F

0 VAC Switchgear/MCC Well Pad Central

3

0 VAC Switchgear/MCC Well Pad East

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

240.00

300.00

1.00

0.80

0.60

N/A

433.01

N/A

0

16

2

4/C -

300

mm²

0.0799

0.0835

792

0.60

475.2

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

F

400

VAC

160

200

1.00

0.80

0.60

N/A

288.68

N/A

3

13

2

4/C -

150

mm²

0.16

0.0843

542

0.60

325.2

3

F

400

VAC

240.00

300.00

1.00

0.80

0.60

N/A

433.01

N/A

0

16

3

4/C -

300

mm²

0.0799

0.0835

1188

0.60

712.8

ry Charger Backup Diesel enerator Well Pad East

3

F

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

0 VAC Switchgear/MCC Well Pad East

3

F

400

VAC

160

200

1.00

0.80

0.60

N/A

288.68

N/A

5

15

1

4/C -

240

mm²

0.0984

0.0842

538

0.60

322.8

388 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

0 VAC Switchgear/MCC Infrastructure

3

F

400

ry Charger Backup Diesel enerator Infrastructure

3

F

0 VAC Switchgear/MCC Infrastructure

3

0 VAC Switchgear/MCC es Gas Metering Station

Description



Power

Volt

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

414

518

1.00

0.80

0.60

N/A

747.67

N/A

0

16

4

4/C -

300

mm²

0.0799

0.0835

1584

0.56

887.0

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

F

400

VAC

1,500

1

1.00

0.80

0.60

N/A

2706.33

N/A

-1

15

3

4/C -

240

mm²

0.0984

0.0842

1053

0.56

589.6

3

F

400

VAC

100.00

125.00

1.00

0.80

0.60

N/A

180.42

N/A

4

14

1

4/C -

185

mm²

0.1281

0.0851

304

0.60

182.4

ry Charger Backup Diesel erator Sales Gas Metering

3

F

400

VAC

2.20

2.62

0.842

0.84

0.54

N/A

4.49

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

0 VAC Switchgear/MCC es Gas Metering Station

3

F

400

VAC

100.00

200.00

1.00

0.80

0.60

N/A

180.42

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

346

0.60

207.6

A Lube Oil Clarifier Driver

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

389 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

A Lube Oil Pump Driver-A

3

M

400

A Lube Oil Pump Driver-B

3

M

Lube Oil Tank Mist SeparatorA

3

Lube Oil Tank Mist SeparatorB

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

A Jacking Oil Oump Driver

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

G-A Bearing Gear Driver

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

B Lube Oil Clarifier Driver

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

B Lube Oil Pump Driver-A

3

M

400

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

390 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

B Lube Oil Pump Driver-B

3

M

400

B Lube Oil Mist Separator-A

3

M

B Lube Oil Mist Separator-B

3

B Jacking Oil Oump Driver

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

30.00

34.09

0.932

0.88

0.47

0.50

52.80

343.17

3

7

1

3/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

3

M

400

VAC

1.50

1.76

0.816

0.85

0.53

0.50

3.12

20.29

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

G-B Bearing Gear Driver

3

M

400

VAC

4.00

4.49

0.860

0.89

0.46

0.50

7.54

49.03

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

or Fan Essential Generator

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Power Essential Generator

3

F

400

VAC

18.25

20.28

0.913

0.90

0.44

N/A

32.06

N/A

6

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

Charger Essential Generator

3

F

400

VAC

2.00

2.11

1.000

0.95

0.31

N/A

3.04

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

391 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

former Rectifier Unit (GPF nderground Pipeline)-1

3

F

400

former Rectifier Unit (GPF nderground Pipeline)-2

3

F

ansformer Rectifier Unit Gas Metering Underground Pipeline)

3

AC UPS System - Feeder A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.50

4.38

0.950

0.80

0.60

N/A

6.65

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

400

VAC

3.50

4.38

0.950

0.80

0.60

N/A

6.65

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

F

400

VAC

3.50

4.38

0.950

0.80

0.60

N/A

6.65

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

64.00

80.00

0.900

0.80

0.60

N/A

128.30

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

AC UPS System - Feeder B

3

F

400

VAC

64.00

80.00

0.900

0.80

0.60

N/A

128.30

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

VAC UPS System - Bypass

3

F

400

VAC

64.00

80.00

0.900

0.80

0.60

N/A

128.30

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

DC UPS System - Feeder A

3

F

400

VAC

13.78

17.23

0.900

0.80

0.60

N/A

27.62

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

392 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

DC UPS System - Feeder B

3

F

400

C Package for Substation-1

3

F

C Package for Substation-1

3

C Package for Substation-1

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

13.78

17.23

0.900

0.80

0.60

N/A

27.62

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

400

VAC

113.20

141.50

1.000

0.80

0.60

N/A

204.24

N/A

5

15

1

4/C -

240

mm²

0.0984

0.0842

351

0.60

210.6

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

C Package for Substation-1

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

C Auxiliary for Substation 1

3

F

400

VAC

32.20

40.25

1.000

0.80

0.60

N/A

58.10

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

ghting DB (Outdoor) #1

3

F

400

VAC

46.30

54.47

0.950

0.85

0.53

N/A

82.76

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

ng (Indoor Substation-1) #1

3

F

400

VAC

13.80

16.24

0.950

0.85

0.53

N/A

24.67

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

393 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

F

400

Welding Receptacle #1

3

F

Welding Receptacle #2

3

AC UPS System - Feeder A

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.20

8.47

0.950

0.85

0.53

N/A

12.87

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

3

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

AC UPS System - Feeder B

3

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

VAC UPS System - Bypass

3

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

DC UPS System - Feeder A

3

F

400

VAC

10.92

13.65

0.900

0.80

0.60

N/A

21.89

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

g (Outdoor Emergency) #1

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

394 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

DC UPS System - Feeder B

3

F

400

C package for Substation 2

3

F

C package for Substation 2

3

C package for Substation 2

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

10.92

13.65

0.900

0.80

0.60

N/A

21.89

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

400

VAC

146.70

183.38

1.000

0.80

0.60

N/A

264.68

N/A

0

12

2

4/C -

120

mm²

0.197

0.0839

480

0.60

288.0

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

C package for Substation 2

3

F

400

VAC

34.00

42.50

1.000

0.80

0.60

N/A

61.34

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

C Auxiliary for Substation 2

3

F

400

VAC

45.00

56.25

1.000

0.80

0.60

N/A

81.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

ghting DB (Outdoor) #2

3

F

400

VAC

93.30

109.76

1.000

0.85

0.53

N/A

158.43

N/A

4

13

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

ng (Indoor Substation-2) #2

3

F

400

VAC

11.90

14.00

1.000

0.85

0.53

N/A

20.21

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

395 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

F

400

Welding Receptacle #3

3

F

Welding Receptacle #4

3

Welding Receptacle #7

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

12.50

14.71

1.000

0.85

0.53

N/A

21.23

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Welding Receptacle #8

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Muster Point-1 GPF

3

F

400

VAC

2.00

2.35

0.950

0.85

0.53

N/A

3.57

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

Muster Point-2 GPF

3

F

400

VAC

2.00

2.35

0.950

0.85

0.53

N/A

3.57

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

g (Outdoor Emergency) #2

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

396 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

AC UPS System - Feeder A

3

F

400

AC UPS System - Feeder B

3

F

VAC UPS System - Bypass

3

DC UPS System - Feeder A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

3

F

400

VAC

8.06

10.08

0.900

0.80

0.60

N/A

16.16

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

DC UPS System - Feeder B

3

F

400

VAC

8.06

10.08

0.900

0.80

0.60

N/A

16.16

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

C package for Substation 3

3

F

400

VAC

224.20

280.25

1.000

0.80

0.60

N/A

404.51

N/A

-1

15

2

4/C -

240

mm²

0.0984

0.0842

702

0.60

421.2

C package for Substation 3

3

F

400

VAC

71.00

88.75

1.000

0.80

0.60

N/A

128.10

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

C package for Substation 3

3

F

400

VAC

71.00

88.75

1.000

0.80

0.60

N/A

128.10

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

397 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

C Auxiliary for Substation 3

3

F

400

g DB (Outdoor Substation-3)

3

F

ting (Indoor Substation-3)

3

ing (Outdoor Emergency)

& Small Power DB (Indoor trument Building 280A)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

83.00

103.75

1.000

0.80

0.60

N/A

149.75

N/A

4

13

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

400

VAC

58.00

68.24

0.950

0.85

0.53

N/A

103.67

N/A

4

11

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

F

400

VAC

9.80

11.53

1.000

0.85

0.53

N/A

16.64

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

15.00

17.65

1.000

0.85

0.53

N/A

25.47

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

2.10

2.47

1.000

0.85

0.53

N/A

3.57

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

elding Receptacle #5

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

elding Receptacle #6

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.4

398 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

AC UPS System - Feeder A

3

F

400

AC UPS System - Feeder B

3

F

VAC UPS System - Bypass

3

DC UPS System - Feeder A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

F

400

VAC

32.00

40.00

0.900

0.80

0.60

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

3

F

400

VAC

5.46

6.83

0.900

0.80

0.60

N/A

10.95

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

DC UPS System - Feeder B

3

F

400

VAC

5.46

6.83

0.900

0.80

0.60

N/A

10.95

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

C package for Substation 4

3

F

400

VAC

112.70

132.59

0.900

0.85

0.53

N/A

212.64

N/A

5

16

1

4/C -

300

mm²

0.0799

0.0835

396

0.60

237.6

C package for Substation 4

3

F

400

VAC

34.00

40.00

0.900

0.85

0.53

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

C package for Substation 4

3

F

400

VAC

34.00

40.00

0.900

0.85

0.53

N/A

64.15

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

399 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

C Auxiliary for Substation 4

3

F

400

g DB (Outdoor Substation-4)

3

F

g DB (Indoor Substation-4)

3

g (Outdoor Emergency) #4

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

45.00

52.94

0.900

0.85

0.53

N/A

84.90

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

400

VAC

57.35

67.47

1.000

0.85

0.53

N/A

97.39

N/A

4

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

F

400

VAC

8.00

9.41

1.000

0.85

0.53

N/A

13.58

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

5.60

6.59

1.000

0.85

0.53

N/A

9.51

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

C package for Instrument Building Train-A

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

C package for Instrument Building Train-A

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

C package for Instrument Building Train-A

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

400 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Aux for Instrument Building Train-A

3

F

400

C package for Instrument Building Train-B

3

F

C package for Instrument Building Train-B

3

C package for Instrument Building Train-B

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

86.00

107.50

1.000

0.80

0.60

N/A

155.16

N/A

4

13

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

27.00

33.75

1.000

0.80

0.60

N/A

48.71

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Aux for Instrument Building Train-B

3

F

400

VAC

86.00

107.50

1.000

0.80

0.60

N/A

155.16

N/A

4

13

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

trument Panel (Train-A)

3

F

400

VAC

20.00

23.53

0.900

0.85

0.53

N/A

37.74

N/A

4

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

trument Panel (Train-B)

3

F

400

VAC

20.00

23.53

0.90

0.85

0.53

N/A

37.74

N/A

4

7

1

4/C -

25

mm²

0.9270

0.0908

101

0.60

60.60

401 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

(Indoor Substation-5) Train-A DP

3

F

400

(Indoor Substation-5) Train-B DP

3

F

(Outdoor Substation-5) Train-A DP

3

ting (Emergency Outdoor ubstation-5) Train-A DP

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

7.52

8.85

0.90

0.85

0.53

N/A

14.19

N/A

3

5

1

4/C -

10

mm²

2.3400

0.0930

61

0.60

36.60

400

VAC

7.52

8.85

0.90

0.85

0.53

N/A

14.19

N/A

3

5

1

4/C -

10

mm²

2.3400

0.0930

61

0.60

36.60

F

400

VAC

75.00

88.24

0.90

0.85

0.53

N/A

141.51

N/A

4

12

1

4/C -

120

mm²

0.1970

0.0839

240

0.56

134.4

3

F

400

VAC

15.00

17.65

0.90

0.85

0.53

N/A

28.30

N/A

5

7

1

4/C -

25

mm²

0.9270

0.0908

101

0.56

56.56

( Outdoor Substation-5) Train-B DP

3

F

400

VAC

75.00

88.24

0.90

0.85

0.53

N/A

141.51

N/A

4

12

1

4/C -

120

mm²

0.1970

0.0839

240

0.56

134.4

ting (Emergency Outdoor bstation-5) Train-B DP

3

F

400

VAC

15.00

17.65

0.90

0.85

0.53

N/A

28.30

N/A

5

7

1

4/C -

25

mm²

0.9270

0.0908

101

0.56

56.56

AC UPS System - Feeder A Control Room

3

F

400

VAC

48.00

60.00

0.900

0.80

0.60

N/A

96.23

N/A

4

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

AC UPS System - Feeder B Control Room

3

F

400

VAC

48.00

60.00

0.900

0.80

0.60

N/A

96.23

N/A

4

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

402 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

F

400

AHU DX

3

F

AHU DX

3

itioner Cassette Type (Total = 14 unit)

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

48.00

60.00

0.900

0.80

0.60

N/A

96.23

N/A

4

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

400

VAC

11.00

12.94

0.900

0.85

0.53

N/A

20.75

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

F

400

VAC

2.20

2.59

0.900

0.85

0.53

N/A

4.15

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

29.35

34.53

0.900

0.85

0.53

N/A

55.38

N/A

4

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

Electric Duct Heater

3

F

400

VAC

106.03

124.74

0.900

0.85

0.53

N/A

200.05

N/A

0

10

2

4/C -

70

mm²

0.343

0.0864

356

0.60

213.6

AC Auxiliary

3

F

400

VAC

6.30

7.41

0.900

0.85

0.53

N/A

11.89

N/A

2

4

2

4/C -

6

mm²

3.93

0.098

92

0.60

55.20

3

F

400

VAC

30.20

35.53

0.950

0.85

0.53

N/A

53.98

N/A

4

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

VAC UPS System - Bypass Control Room

ng (Indoor Control Room)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

403 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

AC UPS System - Feeder A

3

F

400

AC UPS System - Feeder B

3

F

VAC UPS System - Bypass

3

tion Infrastructure HVAC #1

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

F

400

VAC

40.00

50.00

0.900

0.80

0.60

N/A

80.19

N/A

3

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

3

F

400

VAC

71.50

84.12

1.000

0.85

0.53

N/A

121.41

N/A

4

11

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

tion Infrastructure HVAC #2

3

F

400

VAC

71.50

84.12

1.000

0.85

0.53

N/A

121.41

N/A

4

11

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

tion Infrastructure HVAC #3

3

F

400

VAC

71.50

84.12

1.000

0.85

0.53

N/A

121.41

N/A

4

11

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

Distribution Panel or Lighting & Small Power frastructure Substation

3

F

400

VAC

6.20

6.53

1.000

0.95

0.31

N/A

9.42

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

Distribution Panel Outdoor Lighting frastructure Substation

3

F

400

VAC

41.25

43.42

1.000

0.95

0.31

N/A

62.67

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

404 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Distribution Panel Emergency Lighting frastructure Substation

3

F

400

Distribution Panel Indoor Lighting dministration Building

3

F

Distribution Panel Small Power dministration Building

3

Distribution Panel Indoor Lighting rmitory Operator & Staff

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

10.80

11.37

1.000

0.95

0.31

N/A

16.41

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

400

VAC

12.40

13.05

1.000

0.95

0.31

N/A

18.84

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

F

400

VAC

35.00

36.84

1.000

0.95

0.31

N/A

53.18

N/A

6

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

3

F

400

VAC

22.40

23.58

1.000

0.95

0.31

N/A

34.03

N/A

8

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

Distribution Panel Small Power rmitory Operator & Staff

3

F

400

VAC

99.00

104.21

1.000

0.95

0.31

N/A

150.41

N/A

7

16

1

4/C -

300

mm²

0.0799

0.0835

396

0.60

237.6

Distribution Panel Indoor Lighting itory Field Superintendent

3

F

400

VAC

12.82

13.49

1.000

0.95

0.31

N/A

19.48

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Distribution Panel Small Power itory Field Superintendent

3

F

400

VAC

54.50

57.37

1.000

0.95

0.31

N/A

82.80

N/A

6

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

405 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Distribution Panel Indoor Lighting Hall & Multipurpose Building

3

F

400

Distribution Panel Small Power Hall & Multipurpose Building

3

F

Distribution Panel ighting & Small Power Mosque

3

Distribution Panel Indoor Lighting Kitchen & Dining Hall

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

20.00

21.05

1.000

0.95

0.31

N/A

30.39

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

400

VAC

60.50

63.68

1.000

0.95

0.31

N/A

91.92

N/A

4

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

F

400

VAC

8.00

8.42

1.000

0.95

0.31

N/A

12.15

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

6.20

6.53

1.000

0.95

0.31

N/A

9.42

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Distribution Panel Indoor Lighting Kitchen & Dining Hall

3

F

400

VAC

11.00

11.58

1.000

0.95

0.31

N/A

16.71

N/A

6

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

Distribution Panel ighting & Small Power aundry Center Building

3

F

400

VAC

6.40

6.74

1.000

0.95

0.31

N/A

9.72

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Training Building Lighting DB

3

F

400

VAC

9.00

9.47

1.000

0.95

0.31

N/A

13.67

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.56

44.24

Distribution Panel Indoor Lighting edical Center Building

3

F

400

VAC

8.00

8.42

1.000

0.95

0.31

N/A

12.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Distribution Panel Small Power edical Center Building

3

F

400

VAC

12.00

12.63

1.000

0.95

0.31

N/A

18.23

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

406 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Distribution Panel or Lighting & Small Power Security Gate House

3

F

400

Distribution Panel Indoor Lighting ation Maintenance Building

3

F

Distribution Panel Small Power ation Maintenance Building

3

Distribution Panel or Lighting & Small Power emical Storage Building

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.20

3.37

1.000

0.95

0.31

N/A

4.86

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

400

VAC

38.00

40.00

1.000

0.95

0.31

N/A

57.74

N/A

6

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

F

400

VAC

39.00

41.05

1.000

0.95

0.31

N/A

59.25

N/A

6

10

1

4/C -

70

mm²

0.343

0.0864

178

0.60

106.8

3

F

400

VAC

20.00

21.05

1.000

0.95

0.31

N/A

30.39

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Distribution Panel Indoor Lighting ation Warehouse Building

3

F

400

VAC

30.00

31.58

1.000

0.95

0.31

N/A

45.58

N/A

3

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Distribution Panel Small Power ation Warehouse Building

3

F

400

VAC

31.50

33.16

1.000

0.95

0.31

N/A

47.86

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Distribution Panel or Lighting & Small Power Telcom Building

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

Distribution Panel or Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

Distribution Panel or Lighting & Small Power Gate House Building

3

F

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

407 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Distribution Panel or Lighting & Small Power Gate House Building

3

F

400

Distribution Panel or Lighting & Small Power Gate House Building

3

F

Distribution Panel or Lighting & Small Power Guard House Building

3

Distribution Panel Indoor Lighting ire Emegency Station

Distribution Panel Small Power ire Emegency Station

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

400

VAC

3.80

4.00

1.000

0.95

0.31

N/A

5.77

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

F

400

VAC

3.60

3.79

1.000

0.95

0.31

N/A

5.47

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

3

F

400

VAC

2.80

2.95

1.000

0.95

0.31

N/A

4.25

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

9.50

10.00

1.000

0.95

0.31

N/A

14.43

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Distribution Panel Indoor Lighting Office Building

3

F

400

VAC

10.00

10.53

1.000

0.95

0.31

N/A

15.19

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Distribution Panel Small Power Office Building

3

F

400

VAC

44.50

46.84

1.000

0.95

0.31

N/A

67.61

N/A

7

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

Distribution Panel Indoor Lighting Laboratory Building

3

F

400

VAC

7.35

7.74

1.000

0.95

0.31

N/A

11.17

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Distribution Panel Small Power Laboratory Building

3

F

400

VAC

21.00

22.11

1.000

0.95

0.31

N/A

31.91

N/A

7

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

408 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

F

400

Station Genset Lighting DB

3

F

ster Point-1 Lighting DB Infrastructure Area

3

ster Point-2 Lighting DB Infrastructure Area

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.70

1.79

1.000

0.95

0.31

N/A

2.58

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

400

VAC

58.03

68.27

1.000

0.85

0.53

N/A

98.54

N/A

4

10

1

4/C -

70

mm²

0.343

0.0864

178

0.56

99.68

F

400

VAC

6.60

7.76

0.950

0.85

0.53

N/A

11.80

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

6.60

7.76

0.950

0.85

0.53

N/A

11.80

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

tory Building Sockets Outlet

3

F

400

VAC

163.20

192.00

1.000

0.85

0.53

N/A

277.13

N/A

-1

12

2

4/C -

120

mm²

0.197

0.0839

480

0.51

244.8

ory Field Manager Sockets Outlet

3

F

400

VAC

43.52

51.20

1.000

0.85

0.53

N/A

73.90

N/A

4

9

1

4/C -

50

mm²

0.494

0.0877

144

0.51

73.44

Distribution Panel Air Conditioning Laboratory Building

3

F

400

VAC

40.08

42.19

1.000

0.95

0.31

N/A

60.90

N/A

8

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

3

F

400

VAC

6.40

7.53

1.000

0.85

0.53

N/A

10.87

N/A

1

3

1

2/C -

4

mm²

5.88

0.1025

37

0.51

18.87

Distribution Panel or Lighting & Small Power hicle Fuel Station Shelter

mitory Field Manager AC

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

409 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Distribution Panel Air Conditioning rmitory Operator & Staff

3

F

400

Distribution Panel Air Conditioning itory Field Superintendent

3

F

Distribution Panel Air Conditioning en & Dinning Hall Building

3

Distribution Panel Air Conditioning Security Gate House Distribution Panel Air Conditioning Mosque

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

21.51

25.31

1.000

0.85

0.53

N/A

36.53

N/A

7

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

400

VAC

11.52

13.55

1.000

0.85

0.53

N/A

19.56

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

F

400

VAC

34.85

41.00

1.000

0.85

0.53

N/A

59.18

N/A

9

13

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

3

F

400

VAC

10.66

12.54

1.000

0.85

0.53

N/A

18.10

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

58.00

61.05

1.000

0.95

0.31

N/A

88.12

N/A

9

15

1

4/C -

240

mm²

0.0984

0.0842

351

0.60

210.6

Distribution Panel Air Conditioning all & Multipurposed Building

3

F

400

VAC

50.63

59.56

1.000

0.85

0.53

N/A

85.97

N/A

7

13

1

4/C -

150

mm²

0.16

0.0843

271

0.60

162.6

Distribution Panel Air Conditioning dministration Building

3

F

400

VAC

93.73

110.27

1.000

0.85

0.53

N/A

159.16

N/A

5

14

2

4/C -

185

mm²

0.1281

0.0851

608

0.60

364.8

Distribution Panel Air Conditioning ire Emergency Station

3

F

400

VAC

32.00

37.65

1.000

0.85

0.53

N/A

54.34

N/A

5

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

Distribution Panel Air Conditioning edical Center Building

3

F

400

VAC

23.98

28.21

1.000

0.85

0.53

N/A

40.72

N/A

4

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

410 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Distribution Panel Air Conditioning aundry Center Building

3

F

400

Training Building AC

3

F

Recreation Center AC

3

Distribution Panel Air Conditioning ation Maintenance Building

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

19.00

22.35

1.000

0.85

0.53

N/A

32.26

N/A

7

9

1

4/C -

50

mm²

0.494

0.0877

144

0.60

86.40

400

VAC

16.00

18.82

1.000

0.85

0.53

N/A

27.17

N/A

3

5

1

2/C -

10

mm²

2.34

0.093

61

0.51

31.11

F

400

VAC

16.00

18.82

1.000

0.85

0.53

N/A

27.17

N/A

3

5

1

2/C -

10

mm²

2.34

0.093

61

0.51

31.11

3

F

400

VAC

42.27

49.73

1.000

0.85

0.53

N/A

71.78

N/A

9

14

2

4/C -

185

mm²

0.1281

0.0851

608

0.60

364.8

Distribution Panel Air Conditioning emical Storage Building

3

F

400

VAC

53.65

63.12

1.000

0.85

0.53

N/A

91.10

N/A

7

13

3

4/C -

150

mm²

0.16

0.0843

813

0.60

487.8

Distribution Panel Air Conditioning ation Warehouse Building

3

F

400

VAC

66.68

78.45

1.000

0.85

0.53

N/A

113.23

N/A

8

15

2

4/C -

240

mm²

0.0984

0.0842

702

0.60

421.2

Office AC

3

F

400

VAC

16.00

18.82

1.000

0.85

0.53

N/A

27.17

N/A

3

5

1

2/C -

10

mm²

2.34

0.093

61

0.51

31.11

Diesel Station Genset

3

F

400

VAC

8.00

9.41

1.000

0.85

0.53

N/A

13.58

N/A

0

2

1

2/C -

2.5

mm²

9.45

0.1086

29

0.51

14.79

Distribution Panel Air Conditioning Telcom Building

3

F

400

VAC

28.90

34.00

1.000

0.85

0.53

N/A

49.07

N/A

7

11

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

411 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Distribution Panel Air Conditioning Office Building

3

F

400

Distribution Panel Air Conditioning Gate House

3

F

Distribution Panel Air Conditioning Gate House

3

Distribution Panel Air Conditioning Gate House

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

37.74

39.73

1.000

0.95

0.31

N/A

57.34

N/A

7

11

1

4/C -

95

mm²

0.247

0.0842

211

0.60

126.6

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

Distribution Panel Air Conditioning Gate House

3

F

400

VAC

7.06

7.43

1.000

0.95

0.31

N/A

10.73

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Distribution Panel Air Conditioning Guard House

3

F

400

VAC

3.54

3.73

1.000

0.95

0.31

N/A

5.38

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

Potable Water Pump

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

on Inhibitor Injection Pump A

3

M

400

VAC

0.00

0.00

0.772

0.86

0.51

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.56

25.76

412 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

on Inhibitor Injection Pump B

3

M

400

thanol Injection Pump A

3

M

thanol Injection Pump B

3

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.00

0.00

0.772

0.86

0.51

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

400

VAC

0.00

0.00

0.802

0.85

0.53

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

M

400

VAC

0.00

0.00

0.802

0.85

0.53

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

3

M

400

VAC

18.50

20.33

0.924

0.91

0.41

0.50

31.76

206.42

3

5

1

3/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC UPS System - Feeder A

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

AC UPS System - Feeder B

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

VAC UPS System - Bypass

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

71.50

84.12

0.900

0.85

0.53

N/A

134.90

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

Close Drain Pump

Well Pad Substation Building HVAC #1

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

413 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Well Pad Substation Building HVAC #2

3

F

400

Well Pad Substation Building HVAC #3

3

F

3

or Lighting and Small Power

r Lighting and Small Power

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

71.50

84.12

0.900

0.85

0.53

N/A

134.90

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

400

VAC

71.50

84.12

0.900

0.85

0.53

N/A

134.90

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

F

400

VAC

3.00

3.49

1.000

0.86

0.51

N/A

5.04

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

24.22

30.28

1.000

0.80

0.60

N/A

43.70

N/A

3

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

3

F

400

VAC

3.70

4.63

1.000

0.80

0.60

N/A

6.68

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

Emergency Lighting (Outdoor & Indoor)

3

F

400

VAC

7.27

9.08

1.000

0.80

0.60

N/A

13.11

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

uster Point Lighting DB Central Wellpad

3

F

400

VAC

6.60

7.76

0.950

0.85

0.53

N/A

11.80

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Potable Water Pump

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Flare Package

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

414 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

on Inhibitor Injection Pump A

3

M

400

on Inhibitor Injection Pump B

3

M

thanol Injection Pump A

3

thanol Injection Pump B

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.00

0.00

0.772

0.86

0.51

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.56

25.76

400

VAC

0.00

0.00

0.772

0.86

0.51

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.56

25.76

M

400

VAC

0.00

0.00

0.802

0.85

0.53

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.56

25.76

3

M

400

VAC

0.00

0.00

0.802

0.85

0.53

0.50

0.00

0.00

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.56

25.76

3

M

400

VAC

45.00

51.14

0.939

0.88

0.47

0.50

78.60

510.92

5

10

1

3/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

AC UPS System - Feeder A

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

AC UPS System - Feeder B

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

VAC UPS System - Bypass

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

Close Drain Pump

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

415 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Well Pad Substation Building HVAC #1

3

F

400

Well Pad Substation Building HVAC #2

3

F

Well Pad Substation Building HVAC #3

3

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

71.50

84.12

0.900

0.85

0.53

N/A

134.90

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

400

VAC

71.50

84.12

0.900

0.85

0.53

N/A

134.90

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

F

400

VAC

71.50

84.12

0.900

0.85

0.53

N/A

134.90

N/A

4

12

1

4/C -

120

mm²

0.197

0.0839

240

0.60

144.0

3

F

400

VAC

3.00

3.49

1.000

0.86

0.51

N/A

5.04

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

or Lighting and Small Power

3

F

400

VAC

36.00

45.00

1.000

0.80

0.60

N/A

64.95

N/A

3

8

1

4/C -

35

mm²

0.669

0.0883

122

0.60

73.20

r Lighting and Small Power

3

F

400

VAC

3.70

4.63

1.000

0.80

0.60

N/A

6.68

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

Emergency Lighting (Outdoor & Indoor)

3

F

400

VAC

9.60

12.00

1.000

0.80

0.60

N/A

17.32

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

uster Point Lighting DB East Wellpad

3

F

400

VAC

6.60

7.76

0.950

0.85

0.53

N/A

11.80

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

FLARE PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

416 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Gas Metering Stream-A Inlet Line

3

M

400

Gas Metering Stream-B Inlet Line

3

M

OV Gas Cross-over Line

3

Potable Water Pump

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.50

1.88

0.900

0.80

0.60

0.50

3.01

19.55

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.56

20.72

400

VAC

1.50

1.88

0.900

0.80

0.60

0.50

3.01

19.55

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.56

20.72

M

400

VAC

1.50

1.88

0.900

0.80

0.60

0.50

3.01

19.55

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.56

20.72

3

M

400

VAC

0.37

0.46

0.710

0.80

0.60

0.50

0.94

6.11

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

trument Air Compressor

3

M

400

VAC

11.00

12.50

0.912

0.88

0.47

0.50

19.78

128.59

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

ering 230VAC UPS System Feeder A

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

ering 230VAC UPS System Feeder B

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

ering 230VAC UPS System Bypass

3

F

400

VAC

24.00

30.00

0.900

0.80

0.60

N/A

48.11

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

417 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ing Station Building HVAC

3

F

400

ndoor Lighting Panel

3

F

ng Station Building Socket Outlet

3

Outdoor Lighting Panel

mergency Lighting Panel (Outdoor & Indoor)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.20

6.50

1.000

0.80

0.60

N/A

9.38

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

400

VAC

16.43

19.33

1.000

0.85

0.53

N/A

27.90

N/A

3

5

1

4/C -

10

mm²

2.34

0.093

61

0.60

36.60

F

400

VAC

5.00

6.25

1.000

0.80

0.60

N/A

9.02

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

3

F

400

VAC

29.00

36.25

1.000

0.80

0.60

N/A

52.32

N/A

3

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

3

F

400

VAC

7.00

8.24

1.000

0.85

0.53

N/A

11.89

N/A

2

4

1

4/C -

6

mm²

3.93

0.098

46

0.60

27.60

ing Station Welding Outlet

3

F

400

VAC

13.00

13.27

0.950

0.98

0.20

N/A

20.15

N/A

4

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

Muster Point es Gas Metering Station

3

F

400

VAC

6.60

7.76

0.950

0.85

0.53

N/A

11.80

N/A

5

7

1

4/C -

25

mm²

0.927

0.0908

101

0.60

60.60

418 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

Space Heater (Continuous) GPF (Qty=73 ea)

1

M

230

Space Heater (Intermittent) GPF (Qty=6 ea)

1

M

r Space Heater (Stand-by) GPF (Qty=105 ea)

1

Heater for Close Drain Pump Central Wellpad

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.23

0.23

0.95

0.98

0.20

0.50

1.07

6.98

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

230

VAC

0.23

0.23

0.95

0.98

0.20

0.50

1.07

6.98

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

M

230

VAC

0.23

0.23

0.95

0.98

0.20

0.50

1.07

6.98

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

M

230

VAC

0.20

0.20

0.95

1.00

0.00

0.50

0.92

5.95

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Heater for Close Drain Pump East Wellpad

1

M

230

VAC

0.20

0.21

1.00

0.95

0.31

0.50

0.92

5.95

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

STG-A Space Heater

1

M

230

VAC

2.25

2.25

0.900

1.00

0.00

0.50

10.87

70.65

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

STG-B Space Heater

1

M

230

VAC

2.25

2.25

0.900

1.00

0.00

0.50

10.87

70.65

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

419 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

UCP STG-A

1

F

210

attery Charger STG-A

1

F

CP Essential Generator

1

Charger Essential Generator

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.05

1.000

0.95

0.31

N/A

5.01

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Motor Charging VCB for 420-SWG-0001

1

M

210

VAC

1.80

1.80

0.900

1.00

0.00

0.50

9.52

61.90

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

Motor Charging VCB for 420-SWG-0002

1

M

210

VAC

3.00

3.00

0.900

1.00

0.00

0.50

15.87

103.17

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

PCS REMOTE I/O

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

VAC CONTROL PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

420 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

1

F

210

ECMS PRINTER

1

F

LCP STG-A

1

SIS REMOTE I/O

F&G REMOTE I/O

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

0.70

0.70

0.900

1.00

0.00

N/A

3.70

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

AD SHEDDING PANEL-A

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

RGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

7.20

7.20

0.900

1.00

0.00

N/A

38.10

N/A

5

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

TELECOM CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

HP BOILER CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

MS NETWORK SERVER

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

421 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

LP BOILER CABINET

1

F

210

MAIN ECMS-A PANEL

1

F

PAGA CABINET

1

FACP CABINET

UCP STG-B

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

1.50

1.50

0.900

1.00

0.00

N/A

7.94

N/A

3

4

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

attery Charger STG-B

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

P Emergency Generator

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

tery Charger Emergency Generator

1

F

210

VAC

0.50

0.60

0.842

0.84

0.00

N/A

3.37

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

422 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Motor Charging VCB for 420-SWG-0003

1

M

210

Motor Charging VCB for 420-SWG-0004

1

M

Motor Charging VCB for 420-SWG-0005

1

PCS REMOTE I/O

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

0.50

2.65

17.20

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

SIS REMOTE I/O

1

F

210

VAC

0.70

0.70

0.900

1.00

0.00

N/A

3.70

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F&G REMOTE I/O

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS OPC SERVER

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

LCP STG-B

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

CP ESSENTIAL GEN

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

423 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

CMS WORK STATION

1

F

210

MS NETWORK SWITCH

1

F

AD SHEDDING PANEL-B

1

TELECOM CABINET

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

HP BOILER CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

LP BOILER CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

MAIN ECMS-B PANEL

1

F

210

VAC

1.50

1.50

0.900

1.00

0.00

N/A

7.94

N/A

3

4

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

424 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Motor Charging VCB : 231-SWG-0001

1

M

210

Motor Charging ACB : 231-SWG-0002

1

M

S REMOTE I/O PANEL

1

VAC CONTROL PANEL

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.20

2.20

0.900

1.00

0.00

0.50

11.64

75.66

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

S REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

S REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

G REMOTE I/O PANEL

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS PANEL

PAGA CABINET

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

425 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

VRU LCP

1

F

210

OTE I/O ECMS-A PANEL

1

F

E GAS COMPRESSOR LCP

1

HP/LP A FLARE LCP

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

TEG LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

SRU LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

TGU LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

210

VAC

3.50

3.50

0.900

1.00

0.00

N/A

18.52

N/A

9

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

GAS COMPRESSOR LCP

DB at Instrument Building 280A-B-9001

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

426 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Motor Charging VCB : 231-SWG-0003

1

M

210

1

F

ECMS PANEL

1

VRU LCP

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

0.50

2.65

17.20

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

CMS WORKSTATION

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

NETWORK SWITCH

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RGENCY LIGHTING DB (outdoor & indoor)

1

F

210

VAC

8.80

8.80

0.900

1.00

0.00

N/A

46.56

N/A

6

8

1

2/C -

35

mm²

0.6690

0.0753

122

0.60

73.20

S REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

S REMOTE I/O PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

427 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Motor Charging VCB : 231-SWG-0004

1

M

210

1

F

1

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

E GAS COMPRESSOR LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

GAS COMPRESSOR LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

TEG LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

SRU LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

G REMOTE I/O PANEL

PAGA CABINET

OTE I/O ECMS-B PANEL

FACP PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

428 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

TGU LCP

1

F

210

Motor Charging VCB 280-SWG-0001

1

M

Motor Charging ACB : 280-SWG-0002

1

S REMOTE I/O PANEL

VAC CONTROL PANEL

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

210

VAC

1.40

1.40

0.900

1.00

0.00

0.50

7.41

48.15

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

M

210

VAC

0.50

0.50

0.900

1.00

0.00

0.50

2.65

17.20

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

ECMS PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

PAGA CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

MOTE I/O PANEL (280A-B9001)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

429 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

G REMOTE I/O PANEL

1

F

210

OTE I/O ECMS-A PANEL

1

F

NETWORK SWITCH

1

DB at Instrument Building 280B-B-9001

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

3.50

3.50

0.900

1.00

0.00

N/A

18.52

N/A

9

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

1

M

210

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

MOTE I/O PANEL (280A-B9001)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

G REMOTE I/O PANEL

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Motor Charging VCB : 280-SWG-0003

ECMS PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

430 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

CMS WORKSTATION

1

F

210

NETWORK SWITCH

1

F

RGENCY LIGHTING DB (outdoor & indoor)

1

S REMOTE I/O PANEL

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.80

0.80

0.900

1.00

0.00

N/A

4.23

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

F

210

VAC

10.40

10.40

0.900

1.00

0.00

N/A

55.03

N/A

5

8

1

2/C -

35

mm²

0.6690

0.0753

122

0.60

73.20

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

FACP PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Motor Charging VCB 480-SWG-0001

1

M

210

VAC

2.00

2.00

0.900

1.00

0.00

0.50

10.58

68.78

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

PAGA CABINET

OTE I/O ECMS-B PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

431 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Motor Charging ACB : 480-SWG-0002

1

M

210

S REMOTE I/O PANEL

1

F

VAC CONTROL PANEL

1

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.30

0.30

0.900

1.00

0.00

0.50

1.59

10.32

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

UMENT AIR COMPRESSORA LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

UMENT AIR COMPRESSORB LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

UMENT AIR COMPRESSORC LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

S REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

G REMOTE I/O PANEL

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

432 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

RGENCY LIGHTING DB (outdoor & indoor)

1

F

210

OTE I/O ECMS-A PANEL

1

F

PAGA CABINET

1

NETWORK SWITCH

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.00

4.00

0.900

1.00

0.00

N/A

21.16

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

FACP PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

AIR MANAGER LCP

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

S REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

G REMOTE I/O PANEL

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

433 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

ECMS PANEL

1

F

210

1

F

1

UMENT AIR DRYER-A LCP

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

UMENT AIR DRYER-B LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

UMENT AIR DRYER-C LCP

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

WATER PANEL BATTERY CHARGER-A

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

WATER PANEL BATTERY CHARGER-B

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

S REMOTE I/O PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

CMS WORKSTATION

FACP PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

434 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

TELECOM CABINET

1

F

210

OTE I/O ECMS-B PANEL

1

F

1

CS SYSTEM CABINET

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

IS SYSTEM CABINET

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

&G SYSTEM CABINET

1

F

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

PAGA CABINET

FACP PANEL

S SYSTEM COMPUTER

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

435 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

1

F

210

1

F

1

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ACKBONE PATCH PANEL

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

3

4

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

M SYSTEM CABINET 2

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

SOE WORKSTATION

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

MONITOR WORKSTATION

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RE STATION MONITOR

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

APPLICATION COMPUTER

MM SERVER

ESS MONITORING COMP

RTS SERVER

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

436 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

1

F

210

1

F

CMS-A WORKSTATION

1

WE SYSTEM CABINET

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.60

0.60

0.900

1.00

0.00

N/A

3.17

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

ATOR TRAINING SYSTEM CABINET

1

F

210

VAC

0.60

0.60

0.900

1.00

0.00

N/A

3.17

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

CS SYSTEM CABINET

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

VAC CONTROL PANEL

ECMS-A PANEL

M SYSTEM CABINET 1

PAGA CABINET

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

437 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

IS SYSTEM CABINET

1

F

210

&G SYSTEM CABINET

1

F

FACP PANEL

1

CCTV SERVER

EDMS SERVER

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.20

0.20

0.900

1.00

0.00

N/A

1.06

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.30

1.30

0.900

1.00

0.00

N/A

6.88

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

APMS SERVER

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

EPMS SERVER

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.30

1.30

0.900

1.00

0.00

N/A

6.88

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

IS BACK-UP SERVER

TORIAN OPC SERVER

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

438 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

PRINTER

1

F

210

1

F

CCTV SYSTEM

1

CCTV MONITOR

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.69

0.69

0.900

1.00

0.00

N/A

3.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.50

1.50

0.900

1.00

0.00

N/A

7.94

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

0.80

0.80

0.900

1.00

0.00

N/A

4.23

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

PAGA STATION

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

PCS PLASMA TV

1

F

210

VAC

1.87

1.87

0.900

1.00

0.00

N/A

9.87

N/A

3

4

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

M SYSTEM CABINET 2

1

F

210

VAC

0.65

0.65

0.900

1.00

0.00

N/A

3.44

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

NETWORK SWITCH

1

F

210

VAC

1.60

1.60

0.900

1.00

0.00

N/A

8.47

N/A

3

4

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

SIS CONSOLE

1

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ACKBONE PATCH PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

439 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

F&G CONSOLE

1

F

210

ECMS-B PANEL

1

F

PCS EWS

1

ESD/F&G EWS

AMS EWS

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

M SYSTEM CABINET 1

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

ATOR TRAINING SYSTEM CABINET

1

F

210

VAC

0.60

0.60

0.900

1.00

0.00

N/A

3.17

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

WE SYSTEM CABINET

PAGA CABINET

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

440 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

RGENCY LIGHTING DB (outdoor & indoor) 211-DPE-0001

1

F

210

11 kV Switchgear frastructure Substation (BUS A)

1

F

ack-Up Genset Charger

1

0 VAC Switchgear/MCC frastructure Substation (BUS A)

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

10.80

10.80

0.900

1.00

0.00

N/A

57.14

N/A

4

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS Workstation

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

G REMOTE I/O PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

441 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Telecom UPS DB

1

F

210

ack-Up Genset Charger

1

F

0 VAC Switchgear/MCC frastructure Substation (BUS B)

1

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

13.40

13.40

0.900

1.00

0.00

N/A

70.90

N/A

4

8

1

2/C -

35

mm²

0.6690

0.0753

122

0.60

73.20

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

11 kV Switchgear frastructure Substation (BUS B)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

NETWORK SWITCH

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

G REMOTE I/O PANEL

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS Panel

Telecom Cabinet

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

442 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

RTU/SCADA Cabinet

1

F

210

Flow Comp Cabinet

1

F

1

ECMS Panel

ECMS PC

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.00

1.00

0.900

1.00

0.00

N/A

5.29

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

11 kV Switchgear ntral Well Pad Substation (BUS A)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ack-Up Genset Charger

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

0 VAC Switchgear/MCC Well Pad Central (BUS A)

Telecom Cabinet

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

443 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

RTU/SCADA Cabinet

1

F

210

Flow Comp Cabinet

1

F

1

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Emergency Lighting (Outdoor & Indoor)

1

F

210

VAC

5.60

5.60

0.900

1.00

0.00

N/A

29.63

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

FLARE PANEL

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

0 VAC Switchgear/MCC Well Pad Central (BUS B) ECMS Panel

11 kV Switchgear ntral Well Pad Substation (BUS B)

VAC CONTROL PANEL

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

444 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Telecom Cabinet

1

F

210

RTU/SCADA Cabinet

1

F

Flow Comp Cabinet

1

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS PC

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

11 kV Switchgear ast Well Pad Substation (BUS A)

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ack-Up Genset Charger

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

0 VAC Switchgear/MCC ast Well Pad Substation (BUS A)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

445 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Telecom Cabinet

1

F

210

RTU/SCADA Cabinet

1

F

Flow Comp Cabinet

1

0 VAC Switchgear/MCC ast Well Pad Substation (BUS B) ECMS Panel

11 kV Switchgear ast Well Pad Substation (BUS B)

RGENCY LIGHTING DB (outdoor & indoor) 212-DPE-0001 FLARE PANEL

VAC CONTROL PANEL

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.30

0.30

0.900

1.00

0.00

N/A

1.59

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

9.60

9.60

0.900

1.00

0.00

N/A

50.79

N/A

4

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

446 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Telecom Cabinet

1

F

210

RTU/SCADA Cabinet

1

F

low Computer System

1

Laser Jet Printer

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

1.80

1.80

0.900

1.00

0.00

N/A

9.52

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Sales Gas Ccmputer

1

F

210

VAC

0.70

0.70

0.900

1.00

0.00

N/A

3.70

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS PC

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

ack-Up Genset Charger

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

447 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

0 VAC Switchgear/MCC s Gas Metering Substation (BUS A)

1

F

210

11 kV Switchgear s Gas Metering Substation (BUS A)

1

F

Telecom Cabinet

1

RTU/SCADA Cabinet

Dot Maztrix Printer

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

2.00

2.00

0.900

1.00

0.00

N/A

10.58

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

210

VAC

0.40

0.40

0.900

1.00

0.00

N/A

2.12

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.10

0.10

0.900

1.00

0.00

N/A

0.53

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

low Computer System

1

F

210

VAC

1.80

1.80

0.900

1.00

0.00

N/A

9.52

N/A

3

4

1

2/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

ECMS Panel

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

Back-Up Genset UCP

1

F

210

VAC

0.75

0.75

0.900

1.00

0.00

N/A

3.97

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

448 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

1

F

210

VAC CONTROL PANEL

1

F

0 VAC Switchgear/MCC s Gas Metering Substation (BUS B)

1

11 kV Switchgear s Gas Metering Substation (BUS B)

Description

Power

Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.00

4.00

0.900

1.00

0.00

N/A

21.16

N/A

5

6

1

2/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

210

VAC

0.50

0.50

0.900

1.00

0.00

N/A

2.65

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

witchgear: 420-SWG-0001A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

witchgear: 420-SWG-0001B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

RGENCY LIGHTING DB (outdoor & indoor)

Volt



Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

449 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

AC MCC : 420-MCC-0003A

1

F

108

AC MCC : 420-MCC-0003B

1

F

AC MCC : 420-MCC-0005A

1

AC MCC : 420-MCC-0004A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC MCC : 420-MCC-0004B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC MCC : 420-MCC-0005B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Switchgear: 420-SWG-0002A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

Switchgear: 420-SWG-0002B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

RAFO 420-TRF-0001A

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

450 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

RAFO 420-TRF-0001B

1

F

108

RAFO 420-TRF-0002A

1

F

RAFO 420-TRF-0002B

1

RAFO 420-TRF-0003A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RAFO 420-TRF-0003B

1

F

108

VDC

0.10

1.00

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

V Switchgear / MCC MV 1A Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

V Switchgear / MCC MV 1B Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

451 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

AC Switchgear / MCC LV 2A Substation-2 (Train-A)

1

F

108

AC Switchgear / MCC LV 2B Substation-2 (Train-A)

1

F

AC Switchgear / MCC LV 3A Substation-2 (Train-A)

1

AC Switchgear / MCC LV 3B Substation-2 (Train-A)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC Switchgear / MCC LV 4A Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC Switchgear / MCC LV 4B Substation-2 (Train-A)

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

RAFO 231-TRF-0001A

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RAFO 231-TRF-0001B

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RAFO 231-TRF-0002A

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

452 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

RAFO 231-TRF-0002B

1

F

108

Switchgear: 280-SWG-0001A

1

F

Switchgear: 280-SWG-0001B

1

AC MCC : 280-MCC-0002A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC MCC : 280-MCC-0002B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC MCC : 280-MCC-0003A

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC MCC : 280-MCC-0003B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

RAFO 280-TRF-0001A

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

453 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

RAFO 280-TRF-0001B

1

F

108

Switchgear: 480-SWG-0001A

1

F

Switchgear: 480-SWG-0001B

1

AC MCC : 480-MCC-0002A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

AC MCC : 480-MCC-0002B

1

F

108

VDC

1.00

1.00

0.900

1.00

0.00

N/A

10.29

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

RAFO 480-TRF-0001A

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

RAFO 480-TRF-0001B

1

F

108

VDC

0.10

0.10

0.900

1.00

0.00

N/A

1.03

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

454 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ery Rack for Substation-1 AC UPS System - Feeder A

1

F

220

ery Rack for Substation-1 AC UPS System - Feeder B

1

F

ery Rack for Substation-2 AC UPS System - Feeder A

1

ery Rack for Substation-2 AC UPS System - Feeder B

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

61.04

61.04

0.800

1.00

0.00

N/A

346.80

N/A

4

14

2

2/C -

185

mm²

0.1281

0.0720

608

0.60

364.8

220

VDC

61.04

61.04

0.800

1.00

0.00

N/A

346.80

N/A

4

14

2

2/C -

185

mm²

0.1281

0.0720

608

0.60

364.8

F

220

VDC

25.43

25.43

0.800

1.00

0.00

N/A

144.50

N/A

7

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

1

F

220

VDC

25.43

25.43

0.800

1.00

0.00

N/A

144.50

N/A

7

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

ery Rack for Substation-3 AC UPS System - Feeder A

1

F

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

6

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

ery Rack for Substation-3 AC UPS System - Feeder B

1

F

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

6

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

ery Rack for Substation-4 AC UPS System - Feeder A

1

F

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

6

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

ery Rack for Substation-4 AC UPS System - Feeder B

1

F

220

VDC

27.88

27.88

0.800

1.00

0.00

N/A

158.40

N/A

6

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

y Rack for Control Building AC UPS System - Feeder A

1

F

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

3

13

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

455 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

y Rack for Control Building AC UPS System - Feeder B

1

F

220

ery Rack for Infrastructure AC UPS System - Feeder A

1

F

ery Rack for Infrastructure AC UPS System - Feeder B

1

y Rack for Central Wellpad AC UPS System - Feeder A

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

3

13

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

3

13

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

F

220

VDC

53.10

53.10

0.800

1.00

0.00

N/A

301.70

N/A

3

13

2

2/C -

150

mm²

0.1600

0.0712

542

0.60

325.2

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

y Rack for Central Wellpad AC UPS System - Feeder B

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ery Rack for East Wellpad AC UPS System - Feeder A

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ery Rack for East Wellpad AC UPS System - Feeder B

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

456 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

y Rack for Gas Metering C UPS System - Feeder A

1

F

220

y Rack for Gas Metering C UPS System - Feeder B

1

F

ery Rack for Substation-1 DC UPS System - Feeder A

1

ery Rack for Substation-1 DC UPS System - Feeder B

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

20.44

20.44

0.800

1.00

0.00

N/A

116.11

N/A

5

11

1

2/C -

95

mm² 0.2470 0.0711

211

0.60

126.6

220

VDC

20.44

20.44

0.800

1.00

0.00

N/A

116.11

N/A

5

11

1

2/C -

95

mm² 0.2470 0.0711

211

0.60

126.6

F

110

VDC

20.35

20.35

0.800

1.00

0.00

N/A

231.20

N/A

7

16

1

2/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

1

F

110

VDC

20.35

20.35

0.800

1.00

0.00

N/A

231.20

N/A

7

16

1

2/C -

300

mm²

0.0799

0.0704

396

0.60

237.6

ery Rack for Substation-2 DC UPS System - Feeder A

1

F

110

VDC

16.48

16.48

0.800

1.00

0.00

N/A

187.30

N/A

7

15

1

2/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

ery Rack for Substation-2 DC UPS System - Feeder B

1

F

110

VDC

16.48

16.48

0.800

1.00

0.00

N/A

187.30

N/A

7

15

1

2/C -

240

mm²

0.0984

0.0711

351

0.60

210.6

ery Rack for Substation-3 DC UPS System - Feeder A

1

F

110

VDC

12.72

12.72

0.800

1.00

0.00

N/A

144.50

N/A

7

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

ery Rack for Substation-3 DC UPS System - Feeder B

1

F

110

VDC

12.72

12.72

0.800

1.00

0.00

N/A

144.50

N/A

7

13

1

2/C -

150

mm²

0.1600

0.0712

271

0.60

162.6

457 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

ery Rack for Substation-4 DC UPS System - Feeder A

1

F

110

ery Rack for Substation-4 DC UPS System - Feeder B

1

F

y Rack for Central Wellpad AC UPS System - Feeder A

1

y Rack for Central Wellpad AC UPS System - Feeder B

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VDC

8.85

8.85

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

110

VDC

8.85

8.85

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ery Rack for East Wellpad AC UPS System - Feeder A

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

ery Rack for East Wellpad AC UPS System - Feeder B

1

F

220

VDC

17.71

17.71

0.800

1.00

0.00

N/A

100.60

N/A

5

10

1

2/C -

70

mm²

0.3430

0.0734

178

0.60

106.8

458 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

3

F

400

3

F

W Normal HPS Wellglass

3

250W HPS Streetlight

W Normal Fluorescent Light

Description

W Normal HPS Floodlight

Emergency HPS Floodlight

Emergency Fluorescent Light

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

25.60

26.12

0.950

0.98

0.20

N/A

39.69

N/A

3

6

1

4/C -

16

mm²

1.47

0.091

79

0.60

47.40

400

VAC

0.40

0.41

0.950

0.98

0.20

N/A

0.62

N/A

0

2

1

4/C -

2.5

mm²

9.45

0.1086

29

0.60

17.40

F

400

VAC

0.15

0.15

0.950

0.98

0.20

N/A

0.23

N/A

0

2

1

4/C -

2.5

mm²

9.45

0.1086

29

0.60

17.40

3

F

400

VAC

0.25

0.26

0.950

0.98

0.20

N/A

0.39

N/A

0

2

1

4/C -

2.5

mm²

9.45

0.1086

29

0.60

17.40

1

F

230

VAC

0.07

0.07

0.900

1.00

0.00

N/A

0.35

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

1

F

230

VAC

0.07

0.07

0.900

1.00

0.00

N/A

0.35

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

459 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

W Normal HPS Floodlight (16 ea)

1

F

400

W Normal HPS Floodlight (14 ea)

1

F

W Normal HPS Floodlight (12 ea)

1

W Normal HPS Floodlight (10 ea)

Description

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

2.40

2.40

0.900

1.00

0.00

N/A

6.67

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

393

VAC

2.10

2.10

0.900

1.00

0.00

N/A

5.94

N/A

6

7

1

2/C -

25

mm²

0.9270

0.0779

101

0.60

60.60

F

392

VAC

1.80

1.80

0.900

1.00

0.00

N/A

5.10

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

1

F

391

VAC

1.50

1.50

0.900

1.00

0.00

N/A

4.26

N/A

4

5

1

2/C -

10

mm²

2.3400

0.0802

61

0.60

36.60

W Normal HPS Floodlight (8 ea)

1

F

390

VAC

1.20

1.20

0.900

1.00

0.00

N/A

3.42

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

W Normal HPS Floodlight (6 ea)

1

F

387

VAC

0.90

0.90

0.900

1.00

0.00

N/A

2.58

N/A

2

3

1

2/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

W Normal HPS Floodlight (4 ea)

1

F

385

VAC

0.60

0.60

0.900

1.00

0.00

N/A

1.73

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

W Normal HPS Floodlight (2 ea)

1

F

383

VAC

0.30

0.30

0.900

1.00

0.00

N/A

0.87

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

460 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

bution Board Guard House

3

F

400

oor Lighting Fluoroscent 2x36 W

1

F

1

Description

Air Conditioning

tdoor Lighting Floodlight 2x400 W Socket Outlet

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

4.40

5.00

0.912

0.88

0.47

N/A

7.91

N/A

4

6

1

3/C -

16

mm²

1.4700

0.0781

79

0.60

47.40

230

VAC

0.07

0.09

0.900

0.80

0.60

N/A

0.43

N/A

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

230

VAC

1.50

1.88

0.900

0.80

0.60

N/A

9.06

N/A

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

230

VAC

1.60

2.00

0.710

0.80

0.60

N/A

12.25

N/A

1

3

1

3/C -

4

mm²

5.8800

0.0899

37

0.60

22.20

1

F

230

VAC

1.20

1.50

0.710

0.80

0.60

N/A

9.19

N/A

0

2

1

3/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

461 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

3 Ph / 1 Ph

F/M

1

F

230

CWS Workstation

1

F

PCS System

1

Flow Comp System

1

Description

ADA-RTU Panel in PB-24

Power

Volt



Cos φ

Sin φ

Cos β (Start)

IFL

Ist

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

Impedace

No.of Run

Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

kW

kVA

p.u

p.u

p.u

p.u

Amp

Amp

VAC

5.00

5.68

0.912

0.88

0.47

N/A

27.09

N/A

2

4

1

3/C -

6

mm²

3.9300

0.0853

46

0.60

27.60

230

VAC

0.657

0.657

0.900

1.00

0.00

N/A

3.17

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

230

VAC

0.95

0.95

0.900

1.00

0.00

N/A

4.59

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

F

230

VAC

0.51

0.51

0.900

1.00

0.00

N/A

2.46

N/A

1

2

1

2/C -

2.5

mm²

9.4500

0.0961

29

0.60

17.40

462 of 522

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Volt

Power

kW

kVA



p.u

Cos φ

p.u

Sin φ

p.u

Cos β (Start)

p.u

ISC x √t k

er and C60H for Motor)

can be seen in the Doc. No. JTB-SF-E-LST-900-00013~00018, Electrical Cable Schedule.

ting fixtures will sum in the Electrical MTO.

463 of 522

IFL

Amp

Ist

Amp

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

No.of Run

Impedace Type

Current Carrying Capacit CCC

R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

Corretion Factor

Derate

Amp

APPENDIX-A

GAS DEVELOPMENT PROJECT FOR THE JAMBARAN-TIUNG BIRU FIELD CABLE SELECTION SUMMARY

Description

3 Ph / 1 Ph

F/M

Sin φ

Volt

Power

kW

=Sqrt (1-Cos² φ))

Lmax (Maximum Cable Length (m)) Ist (Motor Starting Current (Amp))

kVA



p.u

Cos φ

p.u

Sin φ

Cos β (Start)

p.u

p.u

IFL

Amp

Ist

Amp

Index

Voltage No. Equip System, Phase Type Vin

Selected Cable Correction

Load Data

No.of Run

Impedace Type R at 90°C

X at 50 Hz

Rated

Ω/km

Ω/km

Amp

n (Quantity of cables in parallel per phase)

AG (Above Ground Installation)

 (Efficiency)

UG (Under Ground Installation)

Isc (Short circuit current )

464 of 522

Current Carrying Capacit CCC

Corretion Factor

Derate

Amp

APPENDIX-B Resistance and Reactance Cable For Calculation Reference Used for UPS load, Lighting, Space heater APPENDIX-C Resistance, Reactance and Current Carrying Capacity of Cable (Copper Conductor, XLPE insulated, Steel Wire Armor, PVC Sheathed, Comply to IEC standard 60502-1)

N2XRY 2x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal)

No

Current Carrying Capacities AC Resistance DC Resistance Cross Sectional Reactance at at 90 °C at 90 °C area (mm²) 50 Hz (Ω/km) in air Underground (Ω/km) (Ω/km) (Amp) (Amp)

Conductor S.C Current @ 1 second (Amp)

AdJust Table (In Air)

1

1.5

15.4300

0.0999

12.1000

26

26

212

26

1

2

2.5

9.4500

0.0961

7.4100

36

34

353

36

2

3

4

5.8800

0.0899

4.6100

49

44

564

49

3

4

6

3.9300

0.0853

3.0800

63

56

846

63

4

5

10

2.3400

0.0802

1.8300

86

73

1410

86

5

6

16

1.4700

0.0781

1.1500

115

95

2256

115

6

7

25

0.9270

0.0779

0.7270

149

121

3525

149

7

8

35

0.6690

0.0753

0.5240

185

146

4935

185

8

9

50

0.4940

0.0748

0.3870

225

173

7050

225

9

10

70

0.3430

0.0734

0.2680

289

213

9870

289

10

11

95

0.2470

0.0711

0.1930

352

252

13395

352

11

12

120

0.1970

0.0708

0.1530

410

287

16920

410

12

13

150

0.1600

0.0712

0.1240

473

324

21150

473

13

14

185

0.1281

0.0720

0.0991

542

363

26085

542

14

15

240

0.0984

0.0711

0.0754

641

419

33840

641

15

16

300

0.0799

0.0704

0.0601

741

474

42300

741

16

erence

AdJust Table (Underground)

26

1

34

2

44

3

56

4

73

5

95

6

121

7

146

8

173

9

213

10

252

11

287

12

324

13

363

14

419

15

474

16

Resistance and Reactance Cable For Calculation Reference Used For Motor 3 Phase APPENDIX-C

Resistance, Reactance and Current Carrying Capacity of Cable

(Copper Conductor, XLPE insulated, Steel Wire Armor, PVC Sheathed, Comply to IEC standard 60502-1)

N2XRY 3x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities AC Resistance Reactance at DC Resistance Conductor S.C at 90 °C 50 Hz at 90 °C Current @ 1 in air Underground (Ω/km) (Ω/km) (Ω/km) second (Amp) (Amp) (Amp)

No

Cross Sectional area (mm²)

1

1.5

15.4300

0.0999

12.1000

23

22

212

23

1

2

2.5

9.4500

0.0961

7.4100

32

29

353

32

2

3

4

5.8800

0.0899

4.6100

42

37

564

42

3

4

6

3.9300

0.0853

3.0800

54

46

846

54

4

5

10

2.3400

0.0802

1.8300

75

61

1410

75

5

6

16

1.4700

0.0781

1.1500

100

79

2256

100

6

7

25

0.9270

0.0779

0.7270

127

101

3525

127

7

8

35

0.6690

0.0753

0.5240

158

122

4935

158

8

9

50

0.4940

0.0748

0.3870

192

144

7050

192

9

10

70

0.3430

0.0734

0.2680

246

178

9870

246

10

11

95

0.2470

0.0711

0.1930

298

211

13395

298

11

12

120

0.1970

0.0708

0.1530

346

240

16920

346

12

13

150

0.1600

0.0712

0.1240

399

271

21150

399

13

AdJust Table (In Air)

14

185

0.1281

0.0720

0.0991

456

304

26085

456

14

15

240

0.0984

0.0711

0.0754

538

351

33840

538

15

16

300

0.0799

0.0704

0.0601

621

396

42300

621

16

Notes

ence

AdJust Table (Underground)

22

1

29

2

37

3

46

4

61

5

79

6

101

7

122

8

144

9

178

10

211

11

240

12

271

13

304

14

351

15

396

16

APPENDIX-B Resistance and Reactance Cable For Calculation Reference APPENDIX-B.1 Resistance, Reactance and Current Carrying Capacity of 11 kV 3 Core Cable

APPENDIX-B.2

(Copper Conductor, XLPE insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured, Galvanized Steel Tape Binding, PVC Sheathed, Comply to IEC standard 60502-1)

(Copper Conductor, XLPE insulated, Copper Tape Shielded Steel Tape Binding, PVC Sheathed, Comply to IEC standar

XLPE/FSWA/PVC 3x(25-300) mm² 8.7/15 (17.5) kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal)

XLPE/FSWA/PVC 3x(25-300) mm² 6/10 (12) kV, Taken from Appr

Current Carrying Capacities No

No. Core and Cross Sectional area

AC Resistance at 90 °C (Ω/km)

Reactance at 50 Hz (Ω/km)

DC Resistance at 90 °C (Ω/km)

In air (Amp)

Underground (Amp)

Resistance, Reactance and Curre

Conductor S.C Current @ 1 second (Amp)

AdJust Table (In Air)

AdJust Table (Undergroun d)

No

No. Core and Cross AC Resistance Sectional area at 90 °C (Ω/km)

1

3C x 1.5 mm²

-

-

-

-

-

-

-

1

-

1

1

3C x 1.5 mm²

-

2

3C x 2.5 mm²

-

-

-

-

-

-

-

2

-

2

2

3C x 2.5 mm²

-

3

3C x 4 mm²

-

-

-

-

-

-

-

3

-

3

3

3C x 4 mm²

-

-

-

-

-

-

4

-

4

4

3C x 6 mm²

-

4

3C x 6 mm²

-

-

5

3C x 10 mm²

-

-

-

-

-

-

-

5

-

5

5

3C x 10 mm²

-

6

3C x 16 mm²

-

-

-

-

-

-

-

6

-

6

6

3C x 16 mm²

-

7

3C x 25 mm²

0.9270

0.1300

0.7270

143

129

4

143

7

129

7

7

3C x 25 mm²

0.9270

8

3C x 35 mm²

0.6690

0.1230

0.5240

172

154

5

172

8

154

8

8

3C x 35 mm²

0.6690

9

3C x 50 mm²

0.4940

0.1180

0.3870

205

181

7

205

9

181

9

9

3C x 50 mm²

0.4940

10

3C x 70 mm²

0.3430

0.1110

0.2680

253

220

10

253

10

220

10

10

3C x 70 mm²

0.3430

11

3C x 95 mm²

0.2470

0.1050

0.1930

307

263

13

307

11

263

11

11

3C x 95 mm²

0.2470

12

3C x 120 mm²

0.1970

0.1020

0.1530

352

298

17

352

12

298

12

12

3C x 120 mm²

0.1970

13

3C x 150 mm²

0.1600

0.0980

0.1240

397

332

21

397

13

332

13

13

3C x 150 mm²

0.1600

14

3C x 185 mm²

0.1281

0.0950

0.0991

453

374

26

453

14

374

14

14

3C x 185 mm²

0.1281

15

3C x 240 mm²

0.0984

0.0920

0.0754

529

431

34

529

15

431

15

15

3C x 240 mm²

0.0984

16

3C x 300 mm²

0.0799

0.0890

0.0601

599

482

42

599

16

482

16

16

3C x 300 mm²

0.0799

APPENDIX-B.3 Resistance, Reactance and Current Carrying Capacity of 0.6/1 kV 4 Core Cable

APPENDIX-B.4

(Copper Conductor, XLPE insulated, Steel Wire Armor, PVC Sheathed, Comply to IEC standard 60502-1)

(Copper Conductor, XLPE insulated, Steel Wire Armor, PV

4x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal)

3x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture L

Current Carrying Capacities No

1

No. Core and Cross Sectional area

4C x 1.5

AC Resistance at 90 °C (Ω/km)

Reactance at 50 Hz (Ω/km)

DC Resistance at 90 °C (Ω/km)

15.4300

0.1125

12.1000

In air (Amp) 23

Resistance, Reactance and Curre

Underground (Amp) 22

Conductor S.C Current @ 1 second (Amp)

212

AdJust Table (In Air) 23

1

AdJust Table (Undergroun d)

22

1

No

1

No. Core and Cross AC Resistance Sectional area at 90 °C (Ω/km)

3C x 1.5 mm²

15.4300

APPENDIX-B Resistance and Reactance Cable For Calculation Reference 2

4C x 2.5

9.4500

0.1086

7.4100

32

29

353

32

2

29

2

2

3C x 2.5 mm²

9.4500

3

4C x 4

5.8800

0.1025

4.6100

42

37

564

42

3

37

3

3

3C x 4 mm²

5.8800

4

4C x 6

3.9300

0.0980

3.0800

54

46

846

54

4

46

4

4

3C x 6 mm²

3.9300

5

4C x 10

2.3400

0.0930

1.8300

75

61

1410

75

5

61

5

5

3C x 10 mm²

2.3400

6

4C x 16

1.4700

0.0910

1.1500

100

79

2256

100

6

79

6

6

3C x 16 mm²

1.4700

7

4C x 25

0.9270

0.0908

0.7270

127

101

3525

127

7

101

7

7

3C x 25 mm²

0.9270

8

4C x 35

0.6690

0.0883

0.5240

158

122

4935

158

8

122

8

8

3C x 35 mm²

0.6690

9

4C x 50

0.4940

0.0877

0.3870

192

144

7050

192

9

144

9

9

3C x 50 mm²

0.4940

10

4C x 70

0.3430

0.0864

0.2680

246

178

9870

246

10

178

10

10

3C x 70 mm²

0.3430

11

4C x 95

0.2470

0.0842

0.1930

298

211

13395

298

11

211

11

11

3C x 95 mm²

0.2470

12

4C x 120

0.1970

0.0839

0.1530

346

240

16920

346

12

240

12

12

3C x 120 mm

0.1970

0.1240

399

271

21150

399

13

271

13

13

3C x 150 mm

0.1600

13

4C x 150

0.1600

0.0843

14

4C x 185

0.1281

0.0851

0.0991

456

304

26085

456

14

304

14

14

3C x 185 mm

0.1281

15

4C x 240

0.0984

0.0842

0.0754

538

351

33840

538

15

351

15

15

3C x 240 mm

0.0984

16

4C x 300

0.0799

0.0835

0.0601

621

396

42300

621

16

396

16

16

3C x 300 mm

0.0799

Note

APPENDIX-C Resistance, Reactance and Current Carrying Capacity of Cable (Copper Conductor, XLPE insulated, Steel Wire Armor, PVC Sheathed, Comply to IEC standard 60502-1) 2x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities AC Resistance at 90 °C (Ω/km)

Reactance at 50 Hz (Ω/km)

DC Resistance at 90 °C (Ω/km)

1

2C x 1.5

15.4300

0.0999

12.1000

26

26

212

26

1

26

1

2

2C x 2.5

9.4500

0.0961

7.4100

36

34

353

36

2

34

2

3

2C x 4

5.8800

0.0899

4.6100

49

44

564

49

3

44

3

4

2C x 6

3.9300

0.0853

3.0800

63

56

846

63

4

56

4

5

2C x 10

2.3400

0.0802

1.8300

86

73

1410

86

5

73

5

6

2C x 16

1.4700

0.0781

1.1500

115

95

2256

115

6

95

6

7

2C x 25

0.9270

0.0779

0.7270

149

121

3525

149

7

121

7

8

2C x 35

0.6690

0.0753

0.5240

185

146

4935

185

8

146

8

9

2C x 50

0.4940

0.0748

0.3870

225

173

7050

225

9

173

9

10

2C x 70

0.3430

0.0734

0.2680

289

213

9870

289

10

213

10

No

in air (Amp)

Underground (Amp)

Conductor S.C Current @ 1 second (Amp)

AdJust Table (In Air)

No. Core and Cross Sectional area

AdJust Table (Undergroun d)

APPENDIX-B Resistance and Reactance Cable For Calculation Reference 11

2C x 95

0.2470

0.0711

0.1930

352

252

13395

352

11

252

11

12

2C x 120

0.1970

0.0708

0.1530

410

287

16920

410

12

287

12

13

2C x 150

0.1600

0.0712

0.1240

473

324

21150

473

13

324

13

14

2C x 185

0.1281

0.0720

0.0991

542

363

26085

542

14

363

14

15

2C x 240

0.0984

0.0711

0.0754

641

419

33840

641

15

419

15

16

2C x 300

0.0799

0.0704

0.0601

741

474

42300

741

16

474

16

APPENDIX-B ce and Reactance Cable For Calculation Reference APPENDIX-B.2

Resistance, Reactance and Current Carrying Capacity of 6.6 kV 3 Core Cable

(Copper Conductor, XLPE insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured, Galvanized Steel Tape Binding, PVC Sheathed, Comply to IEC standard 60502-1) XLPE/FSWA/PVC 3x(25-300) mm² 6/10 (12) kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities Reactance at DC Resistance 50 Hz (Ω/km) at 90 °C (Ω/km)

APPENDIX-B.4

in air (Amp)

Underground (Amp)

Conductor S.C Current @ 1 second (Amp)

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0.1220

0.7270

143

129

4

0.1150

0.5240

172

154

5

0.1100

0.3870

205

181

7

0.1040

0.2680

253

220

10

0.0990

0.1930

307

263

13

0.0960

0.1530

352

298

17

0.0930

0.1240

397

332

21

0.0900

0.0991

453

374

26

0.0870

0.0754

529

431

34

0.0840

0.0601

599

482

42

Resistance, Reactance and Current Carrying Capacity of 0.6/1 kV 3 Core Cable

(Copper Conductor, XLPE insulated, Steel Wire Armor, PVC Sheathed, Comply to IEC standard 60502-1) 3x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities Reactance at DC Resistance 50 Hz (Ω/km) at 90 °C (Ω/km)

0.0999

12.1000

in air (Amp) 23

Underground (Amp) 22

Conductor S.C Current @ 1 second (Amp)

212

APPENDIX-B ce and Reactance Cable For Calculation Reference 0.0961

7.4100

32

29

353

0.0899

4.6100

42

37

564

0.0853

3.0800

54

46

846

0.0802

1.8300

75

61

1410

0.0781

1.1500

100

79

2256

0.0779

0.7270

127

101

3525

0.0753

0.5240

158

122

4935

0.0748

0.3870

192

144

7050

0.0734

0.2680

246

178

9870

0.0711

0.1930

298

211

13395

0.0708

0.1530

346

240

16920

0.0712

0.1240

399

271

21150

0.0720

0.0991

456

304

26085

0.0711

0.0754

538

351

33840

0.0704

0.0601

621

396

42300

Notes

APPENDIX-B ce and Reactance Cable For Calculation Reference

Resistance and Reactance Cable For Calculation Reference Used For Generator, Incoming Distribution board APPENDIX-C

Resistance, Reactance and Current Carrying Capacity of Cable

(Copper Conductor, XLPE insulated, Steel Wire Armor, PVC Sheathed, Comply to IEC standard 60502-1)

N2XRY 4x(1,5-300) mm² 0,6/1 kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities AC Resistance DC Resistance Reactance at at 90 °C at 90 °C 50 Hz (Ω/km) In air Underground (Ω/km) (Ω/km) (Amp) (Amp)

Conductor S.C Current @ 1 second (Amp)

AdJust Table (In Air)

No

No. Core and Cross Sectional area

1

1.5

15.4300

0.1125

12.1000

23

22

212

23

1

2

2.5

9.4500

0.1086

7.4100

32

29

353

32

2

3

4

5.8800

0.1025

4.6100

42

37

564

42

3

4

6

3.9300

0.0980

3.0800

54

46

846

54

4

5

10

2.3400

0.0930

1.8300

75

61

1410

75

5

6

16

1.4700

0.0910

1.1500

100

79

2256

100

6

7

25

0.9270

0.0908

0.7270

127

101

3525

127

7

8

35

0.6690

0.0883

0.5240

158

122

4935

158

8

9

50

0.4940

0.0877

0.3870

192

144

7050

192

9

10

70

0.3430

0.0864

0.2680

246

178

9870

246

10

11

95

0.2470

0.0842

0.1930

298

211

13395

298

11

12

120

0.1970

0.0839

0.1530

346

240

16920

346

12

13

150

0.1600

0.0843

0.1240

399

271

21150

399

13

14

185

0.1281

0.0851

0.0991

456

304

26085

456

14

15

240

0.0984

0.0842

0.0754

538

351

33840

538

15

16

300

0.0799

0.0835

0.0601

621

396

42300

621

16

erence

AdJust Table (Underground)

22

1

29

2

37

3

46

4

61

5

79

6

101

7

122

8

144

9

178

10

211

11

240

12

271

13

304

14

351

15

396

16

Resistance and Reactance Cable For Calculation Reference Used For Generator, Incoming Distribution board APPENDIX-C

Resistance, Reactance and Current Carrying Capacity of Cable

(Copper Conductor, XLPE insulated, Copper Tape Shielded, Rounded Aluminium Wire Armoured, PVC Sheathed, Comply to IEC standard 60502-1) XLPE/AWA/PVC 1x(25-630) mm² 6/10 (12) kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities AC Resistance DC Resistance Reactance at at 90 °C at 20 °C 50 Hz (Ω/km) In air at 30 oC Underground (Ω/km) (Ω/km) (Amp) at 20 oC(Amp)

Conductor S.C Current @ 1 second (kA)

AdJust Table (In Air)

No

No. Core and Cross Sectional area

1

1.5

-

-

-

-

-

-

-

1

2

2.5

-

-

-

-

-

-

-

2

3

4

-

-

-

-

-

-

-

3

4

6

-

-

-

-

-

-

-

4

5

10

-

-

-

-

-

-

-

5

6

16

-

-

-

-

-

-

-

6

7

25

0.9270

0.1510

0.7270

163

140

3.5

163

7

8

35

0.6690

0.1420

0.5240

198

166

4.5

198

8

9

50

0.4940

0.1360

0.3870

238

196

7.0

238

9

10

70

0.3430

0.1290

0.2680

296

239

9.8

296

10

11

95

0.2470

0.1210

0.1930

361

285

13.3

361

11

12

120

0.1960

0.1190

0.1530

417

323

16.9

417

12

13

150

0.1590

0.1150

0.1240

473

361

21.1

473

13

14

185

0.1272

0.1120

0.0991

543

406

26.0

543

14

15

240

0.0972

0.1080

0.0754

641

469

33.8

641

15

16

300

0.0779

0.1040

0.0601

735

526

42.3

735

16

17

400

0.0614

0.1010

0.0470

845

590

56.4

845

17

18

50

0.0482

0.0980

0.0366

940

655

70.5

940

18

19

630

0.0376

0.0940

0.0283

1080

740

88.8

1080

19

Resistance and Reactance Cable For Calculation Reference Used For Generator, Incoming Distribution board APPENDIX-C

Resistance, Reactance and Current Carrying Capacity of Cable

(Copper Conductor, XLPE insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured, Galvanized Steel Tape Binding, PVC Sheathed, Comply to IEC standard 60502-1) XLPE/FSWA/PVC 3x(25-630) mm² 6/10 (12) kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal)

No

No. Core and Cross Sectional area

AC Resistance DC Resistance Reactance at at 90 °C at 20 °C 50 Hz (Ω/km) (Ω/km) (Ω/km)

Current Carrying Capacities

Conductor S.C Current @ 1 second (kA)

AdJust Table (In Air)

AC Resistance DC Resistance Reactance at at 90 °C at 20 °C 50 Hz (Ω/km) In air at 30 oC Underground (Ω/km) (Ω/km) (Amp) at 20 oC(Amp)

Conductor S.C Current @ 1 second (kA)

AdJust Table (In Air)

No

No. Core and Cross Sectional area

1

1.5

-

-

-

-

-

-

-

1

2

2.5

-

-

-

-

-

-

-

2

3

4

-

-

-

-

-

-

-

3

4

6

-

-

-

-

-

-

-

4

5

10

-

-

-

-

-

-

-

5

6

16

-

-

-

-

-

-

-

6

7

25

0.9270

0.1220

0.7270

143

129

3.5

143

7

8

35

0.6690

0.1150

0.5240

172

154

4.5

172

8

9

50

0.4940

0.1100

0.3870

205

181

7.0

205

9

10

70

0.3430

0.1040

0.2680

253

220

9.8

253

10

11

95

0.2470

0.0990

0.1930

307

263

13.3

307

11

12

120

0.1970

0.0960

0.1530

352

298

16.9

352

12

13

150

0.1600

0.0930

0.1240

397

332

21.1

397

13

14

185

0.1281

0.0900

0.0991

453

374

26.0

453

14

15

240

0.0984

0.0870

0.0754

529

431

33.8

529

15

16

300

0.0799

0.0840

0.0601

599

482

42.3

599

16

erence

AdJust Table (Underground)

-

1

-

2

-

3

-

4

-

5

-

6

140

7

166

8

196

9

239

10

285

11

323

12

361

13

406

14

469

15

526

16

590

17

655

18

740

19

erence

AdJust Table (Underground)

AdJust Table (Underground)

-

1

-

2

-

3

-

4

-

5

-

6

129

7

154

8

181

9

220

10

263

11

298

12

332

13

374

14

431

15

482

16

Resistance and Reactance Cable For Calculation Reference Used For Generator, Incoming Distribution board APPENDIX-C

Resistance, Reactance and Current Carrying Capacity of Cable

(Copper Conductor, XLPE insulated, Copper Tape Shielded, Rounded Aluminium Wire Armoured, PVC Sheathed, Comply to IEC standard 60502-1) XLPE/AWA/PVC 1x(25-630) mm² 8.7/15 (17.5) kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal) Current Carrying Capacities AC Resistance DC Resistance Reactance at at 90 °C at 20 °C 50 Hz (Ω/km) In air at 30 oC Underground (Ω/km) (Ω/km) (Amp) at 20 oC(Amp)

Conductor S.C Current @ 1 second (kA)

AdJust Table (In Air)

No

No. Core and Cross Sectional area

1

1.5

-

-

-

-

-

-

-

1

2

2.5

-

-

-

-

-

-

-

2

3

4

-

-

-

-

-

-

-

3

4

6

-

-

-

-

-

-

-

4

5

10

-

-

-

-

-

-

-

5

6

16

-

-

-

-

-

-

-

6

7

25

0.9270

0.1560

0.7270

163

140

3.5

163

7

8

35

0.6690

0.1480

0.5240

198

166

4.5

198

8

9

50

0.4940

0.1420

0.3870

238

196

7.0

238

9

10

70

0.3430

0.1330

0.2680

296

239

9.8

296

10

11

95

0.2470

0.1280

0.1930

361

285

13.3

361

11

12

120

0.1960

0.1240

0.1530

417

323

16.9

417

12

13

150

0.1590

0.1200

0.1240

473

361

21.1

473

13

14

185

0.1272

0.1150

0.0991

543

406

26.0

543

14

15

240

0.0972

0.1110

0.0754

641

469

33.8

641

15

16

300

0.0779

0.1070

0.0601

735

526

42.3

735

16

17

400

0.0614

0.1040

0.0470

845

590

56.4

845

17

18

50

0.0482

0.1010

0.0366

940

655

70.5

940

18

19

630

0.0376

0.0970

0.0283

1080

740

88.8

1080

19

Resistance and Reactance Cable For Calculation Reference Used For Generator, Incoming Distribution board APPENDIX-C

Resistance, Reactance and Current Carrying Capacity of Cable

(Copper Conductor, XLPE insulated, Copper Tape Shielded, Galvanized Flat Steel Wire Armoured, Galvanized Steel Tape Binding, PVC Sheathed, Comply to IEC standard 60502-1) XLPE/FSWA/PVC 3x(25-630) mm² 8.7/15 (17.5) kV, Taken from Approved Manufacture List (Sumi Indo Kabel or equal)

No

No. Core and Cross Sectional area

AC Resistance DC Resistance Reactance at at 90 °C at 20 °C 50 Hz (Ω/km) (Ω/km) (Ω/km)

Current Carrying Capacities

Conductor S.C Current @ 1 second (kA)

AdJust Table (In Air)

AC Resistance DC Resistance Reactance at at 90 °C at 20 °C 50 Hz (Ω/km) In air at 30 oC Underground (Ω/km) (Ω/km) (Amp) at 20 oC(Amp)

Conductor S.C Current @ 1 second (kA)

AdJust Table (In Air)

No

No. Core and Cross Sectional area

1

1.5

-

-

-

-

-

-

-

1

2

2.5

-

-

-

-

-

-

-

2

3

4

-

-

-

-

-

-

-

3

4

6

-

-

-

-

-

-

-

4

5

10

-

-

-

-

-

-

-

5

6

16

-

-

-

-

-

-

-

6

7

25

0.9270

0.1300

0.7270

143

129

3.5

143

7

8

35

0.6690

0.1230

0.5240

172

154

4.5

172

8

9

50

0.4940

0.1180

0.3870

205

181

7.0

205

9

10

70

0.3430

0.1110

0.2680

253

220

9.8

253

10

11

95

0.2470

0.1050

0.1930

307

263

13.3

307

11

12

120

0.1970

0.1020

0.1530

352

298

16.9

352

12

13

150

0.1600

0.0980

0.1240

397

332

21.1

397

13

14

185

0.1281

0.0950

0.0991

453

374

26.0

453

14

15

240

0.0984

0.0920

0.0754

529

431

33.8

529

15

16

300

0.0799

0.0890

0.0601

599

482

42.3

599

16

erence

AdJust Table (Underground)

-

1

-

2

-

3

-

4

-

5

-

6

140

7

166

8

196

9

239

10

285

11

323

12

361

13

406

14

469

15

526

16

590

17

655

18

740

19

erence

AdJust Table (Underground)

AdJust Table (Underground)

-

1

-

2

-

3

-

4

-

5

-

6

129

7

154

8

181

9

220

10

263

11

298

12

332

13

374

14

431

15

482

16

PT. TRIPATRA ENGINEERS & CONSTRUCTORS

: : :

Project Client Job No

PASE B FIELD DEVELOPMENT PROJECT Mobil Pase INC 9350

CABLE SIZING CALCULATION NO.

CABLE ROUTE

CABLE NO. FROM

ESTIMATE LENGTH LENGTH

CAPACITY TO

(Kw)

(KVA)

(m)

(feet)

VOLTAGE

PF

(V)

DESIGN CURRENT

CABLE SIZE

(A)

Sq.mm

CABLE GLAN SOURCE END

PASE B 1 LBS - 10 - 13 001A - P1 11 KV SWGR. PSG-10-13-001

LBS - 10 - 13 001A

400

500

5875

19274.94

11000

0.8

26.24 Err:504

TMC 7247 (2 1/2") or Equal

2 LBS - 10 - 13 001B - P1 11 KV SWGR. PSG-10-13-001

LBS - 10 - 13 001B

400

500

5875

19274.94

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

3 PXF-10-13-001A - P1

11 KV LBS - 10 - 13 001A at Pase B

PXF-10-13-001A

400

500

10

32.81

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

4 PXF-10-13-001B - P

11 KV LBS - 10 - 13 001B at Pase B

PXF-10-13-001B

400

500

10

32.81

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

5 CP-10-13-002A - P

400V MCC PMC-10-13-001A

Cathodic protetion

11

14

100

328.08

400

0.8

20.19

TMC 285 (3/4) or Equal

6 CP-10-13-002A - P

400V MCC PMC-10-13-001B

Cathodic protetion

11

14

100

328.08

400

0.8

20.19

TMC 285 (3/4) or Equal

V - 1303A Air Dryer Package

3.2

4

80

262.47

400

0.8

5.77

TMC 285 (3/4) or Equal

7 V - 1303A - P

400V MCC PMC-10-13-001A

8 V - 1303B - P

400V MCC PMC-10-13-001B

V - 1303B Air Dryer Package

3.2

4

85

278.87

400

0.8

5.77

TMC 285 (3/4) or Equal

9 V - 1301A - P

400V MCC PMC-10-13-001A

V - 1301A Motor Air Compressor

15

17

86

282.15

400

0.8

24.88

TMC 285 (3/4) or Equal

10 V - 1301B - P

400V MCC PMC-10-13-001B

V - 1101B Motor Air Compressor

15

17

185

606.96

400

0.8

24.88

TMC 285 (3/4) or Equal

TR - 10 - 13 - 002 Lighting Trafo 400/240V

20

25

10

32.81

400

0.8

36.08

TMC 4140 (1 1/4") or Equal

11 TR - 10 - 13 - 002 - P

400V MCC PMC-11805C

12 LDP - 10 - 13 - 002 - P

Transformer 400/240V

LDP - 10 - 13 - 002 Linghting Panel

20

25

10

32.81

400

0.8

36.08

TMC 4140 (1 1/4") or Equal

13 TP - 10 - 13 - 002 - P1

400V MCC PMC-11805C

TP - 10 - 13 - 002 Transfer Panel

10

13

15

49.21

400

0.8

18.04

TMC 285 (3/4) or Equal

14 TP - 10 - 13 - 002 - P2

400V MCC PMC-11805D

TP - 10 - 13 - 002 Transfer Panel

10

13

15

49.21

400

0.8

18.04

TMC 285 (3/4) or Equal

400V MCC PMC-11805D

W/O - 10 - 13 - 002 - Welding Outlet

30

38

85

278.87

400

0.8

54.13

TMC 4140 (1 1/4") or Equal

1 LBS - 11805A - P

11 KV SWGR. PSG-10-13-001

LBS - 11805A at SLS D

400

500

55

168

11000

0.8

26.24 Err:504

TMC 7247 (2 1/2") or Equal

2 LBS - 11805B- P

11 KV SWGR. PSG-10-13-001

LBS - 11805B at SLS D

400

500

50

152

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

3 LBS - 11805C - P1

11 KV SWGR. PSG-10-13-001

LBS - 11805C at SLS D

400

500

40

122

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

4 LBS - 11805D - P1

11 KV SWGR. PSG-10-13-001

LBS - 11805D at SLS D

400

500

43

131

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

5 PXF-11805C - P1

11 KV LBS - 10 - 13 001A at Pase B

PXF-11805C

400

500

10

30

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

6 PXF-11805D - P1

11 KV LBS - 10 - 13 001B at Pase B

PXF-11805D

400

500

10

30

11000

0.8

26.24

TMC 7247 (2 1/2") or Equal

15 W/O - 10 - 13 - 002 - P

SLS D

7 V - 1103A - P

400V MCC PMC-11805C

V - 1103A Air Dryer Package

3.2

4

195

594

400

0.8

5.77

TMC 285 (3/4) or Equal

8 V - 1103B - P

400V MCC PMC-11805D

V - 1103B Air Dryer Package

3.2

4

190

579

400

0.8

5.77

TMC 285 (3/4) or Equal

9 V - 1101A - P

400V MCC PMC-11805C

V - 1101A Motor Air Compressor

15

17

190

579

400

0.8

24.88

TMC 285 (3/4) or Equal

V - 1101B Motor Air Compressor

15

17

185

564

400

0.8

24.88

TMC 285 (3/4) or Equal

10 V - 1101B - P

400V MCC PMC-11805D

11 V - 1113A - P

400V MCC PMC-11805C

V - 1113A Motor KO Drum

11

14

210

640

400

0.8

20.19

TMC 3112 (1") or Equal

12 V - 1113B - P

400V MCC PMC-11805D

V - 1113B Motor KO Drum

11

14

212

646

400

0.8

20.19

TMC 3112 (1") or Equal

13 TR - 10 - 13 - 001 - P

400V MCC PMC-11805C

TR - 10 - 13 - 001 Lighting Trafo 400/240V

20

25

12

37

400

0.8

36.08

TMC 4140 (1 1/4") or Equal

LDP - 10 - 13 - 001 Linghting Panel

20

25

10

30

400

0.8

36.08

TMC 4140 (1 1/4") or Equal

TP - 10 - 13 - 001 Transfer Panel

10

13

22

67

400

0.8

18.04

TMC 285 (3/4) or Equal

14 LDP - 10 - 13 - 001 - P 15 TP - 10 - 13 - 001 - P1

Electrical Cable Sizing

Transformer 400/240V 400V MCC PMC-11805C

Pase B Field Development Project

Page 499 of 522

Project Client Job No

: : :

PASE B FIELD DEVELOPMENT PROJECT Mobil Pase INC 9350

CABLE SIZING CALCULATION NO.

CABLE ROUTE

CABLE NO. FROM

16 TP - 10 - 13 - 001 - P2 17 W/O - 10 - 13 - 001 - P

Electrical Cable Sizing

400V MCC PMC-11805D 400V MCC PMC-11805D

ESTIMATE LENGTH LENGTH

CAPACITY TO

VOLTAGE

PF

DESIGN CURRENT

CABLE SIZE

(A)

Sq.mm

CABLE GLAN SOURCE END

(Kw)

(KVA)

(m)

(feet)

(V)

TP - 10 - 13 - 001 Transfer Panel

10

13

21

64

400

0.8

18.04

TMC 285 (3/4) or Equal

W/O - 10 - 13 - 001 - Welding Outlet

30

38

190

579

400

0.8

54.13

TMC 4140 (1 1/4") or Equal

Pase B Field Development Project

Page 500 of 522

Err:504

SIZING CALCULATION CABLE GLAND

CABLE LUG LOAD END

Err:504

Err:504

Electrical Cable Sizing

Qty

Err:504

Size

Err:504

LOCK NUT Qty

Err:504

CABLE AMPACITY

TABEL

Size

Err:504

INC

Err:504

(0.8*A)

###

Err:504

(A)

Err:504

R

X

ohm per

ohm per

VOLTAGE DROP (%)

1000 ft

1000 ft

#REF!

Err:504

Err:504

Err:504

8

2

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

8

2

2

###

#VALUE!

#VALUE!

8

2

2

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

8

2

2

###

#VALUE!

#VALUE!

8

2

3

###

#VALUE!

#VALUE!

8

2

1

###

#VALUE!

#VALUE!

2

1

###

#VALUE!

#VALUE!

2

###

#VALUE!

#VALUE!

2

###

#VALUE!

#VALUE!

2

###

#VALUE!

#VALUE!

1

###

Err:504

1

###

#VALUE!

2

1

###

#VALUE!

#VALUE!

2

1

###

#VALUE!

#VALUE!

2

1

###

#VALUE!

#VALUE!

8

2

1

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

8

2

3

###

#VALUE!

#VALUE!

8

2

3

###

#VALUE!

#VALUE!

8

2

3

###

#VALUE!

#VALUE!

8

2

3

###

#VALUE!

#VALUE!

8

2

1

###

#VALUE!

#VALUE!

8

2

1

###

#VALUE!

#VALUE!

8

2

###

#VALUE!

#VALUE!

Err:504

Err:504

Err:504

Err:504

Err:504

Pase B Field Development Project

Err:504

Err:504

Err:504

Err:504

Page 501 of 522

Err:504

SIZING CALCULATION CABLE GLAND

CABLE LUG LOAD END

Electrical Cable Sizing

Qty

Size

LOCK NUT Qty

8

2

8

2

CABLE AMPACITY

TABEL

Size

INC 2

Pase B Field Development Project

(0.8*A)

(A)

R

X

ohm per

ohm per

VOLTAGE DROP (%)

1000 ft

1000 ft

#REF!

###

#VALUE!

#VALUE!

###

#VALUE!

#VALUE!

Page 502 of 522

APPENDIX-C Derating Factors (Ambient temperature factor, grouping factors) 1). Underground Installation (MV Cable)

2). Above ground Installation (in

a.) Table A.52-15 (52-D2) of IEC 364-5-52

b.) Sumi Indo Kabel MV Product Catalogue

a.) Table A.52-14 (52-D1) of IEC 364-5-52

Correction factors (kg1) for ambient ground temperatures other than 20 °C, to be applied to the current-carrying capacities for cables in the ground

Correction factors for depth of laying for Direct buried Three-core cables

b.) Table Installation Method in Table 52-B2

Correction factors (kg1) for ambient air temperatures other than 30 °C, to be applied to the current-carrying capacities for cables in the air

Depth of Laying (m) Insulation Ground temperature (oC)

Derating Factor

0.5

0.6

0.8

1

1.25

1

1.04

1.03

1

0.98

0.96

0.95

Insulation

Air temperature (oC)

PVC

XLPE and EPR

10

1.22

1.15

15

1.17

1.12

20

1.12

1.08

PVC

XLPE and EPR

10

1.1

1.07

15

1.05

1.04

25

0.95

0.96

30

0.89

0.93

c.) Table A.52-16 (52-D3) of IEC 364-5-52

25

1.06

1.04

35

0.84

0.89

Correction factors for soil thermal resistivities for Direct buried Three-core cables

35

0.94

0.96

40

0.77

0.85

40

0.87

0.91

45

0.71

0.8

45

0.79

0.87

50

0.63

0.76

50

0.71

0.82

55

0.55

0.71

55

0.61

0.76

60

0.45

0.65

60

0.5

0.71

65

-

0.6

65

-

0.65

70

-

0.53

70

-

0.58

75

-

0.46

75

-

0.5

80

-

0.38

80

-

0.41

85

-

90

-

95

-

Correction factors, Kg4 (750mm depth of trench cable) =

1.01

Values of soila thermal resistivity (K.m/W)

Derating Factor

1

1.5

2

2..5

3

1.18

1.1

1.05

1

0.96

Correction factors, Kg3 (1.2 K.W/m soil thermal resistivity) =

1.14

d.) Table A.52-18 (52-E2) of IEC 364-5-52 Correction factors (kg2) for more than one circuit, cables laid directly in the ground Installation Method D in Tables 52-C1 to 52-C4 (Single or multicore cables)

Number of circuits

Cable to cable clearance (a)* Nil One cable (cables 0.125 m diameter touching)

0.25 m

0.5 m

Perforated trays

31

(note 3)

Vertical perforated

31

trays (note 4)

Ladder, supports,

32

cleats, etc.

33

(note 4)

34

Correction factor, Ka2 (worst case, nine or more Notes:

1.

Correction factors , Kg1 ( 20 °C ground temperature assumed) =

0.89

2

0.75

0.8

0.85

0.9

0.9

3

0.65

0.7

0.75

0.8

0.85

4

0.60

0.60

0.70

0.75

0.80

5

0.55

0.55

0.65

0.70

0.80

6

0.50

0.55

0.60

0.70

0.80

Correction factors , Ka1 ( 40 °C air temperature) =

3. 4.

Above ground total correction Factor, Kat = Ka1 x Ka2 =

Total Correction factors, Kg2 (10 circuits laid directly in the ground) =

Underground cable total Correction Factor, Kgt = Kg1 x Kg2 x Kg3 x Kg4 =

0.56

2.

0.91

0.55

0.60

APPENDIX-C

Ambient temperature factor, grouping factors) 2). Above ground Installation (in free air) b.) Table A.52-20 (52-E4) of IEC 364-5-52 Number of Cables Installation Method in Table 52-B2

Number of Trays

1

2

3

4

6

9

1

1.00

0.88

0.82

0.79

0.76

0.73

2

1.00

0.87

0.80

0.77

0.73

0.68

3

1.00

0.86

0.79

0.76

0.71

0.66

1

1.00

1.00

0.98

0.95

0.91

-

2

1.00

0.99

0.96

0.92

0.87

-

3

1.00

0.98

0.95

0.91

0.85

-

1

1.00

0.80

0.82

0.78

0.73

0.72

2

1.00

0.88

0.81

0.76

0.71

0.70

1

1.00

0.91

0.89

0.88

0.87

-

2

1.00

0.91

0.88

0.87

0.85

-

1

1.00

0.87

0.82

0.80

0.79

0.78

2

1.00

0.86

0.80

0.78

0.76

0.73

3

1.00

0.85

0.79

0.76

0.73

0.70

1

1.00

1.00

1.00

1.00

1.00

-

2

1.00

0.99

0.98

0.97

0.96

-

3

1.00

0.98

0.97

0.96

0.93

-

Correction factor, Ka2 (worst case, nine or more cable on tray with up to three level superimposed trays) =

Ka2-1

Ka2-2

0.66

Value given are averages for the cable types and range of conductor sizes considered in Tables 52-B7 to 52-B12. The spread in values is generally less than ± 7.5%.

Factors apply to single layer groups of cables as shown above and do NOT apply when cables are installed in more than one layer touching each other. Values for such lower and must ve determined by appropriate method.installation may be significantly Values are given for a vertical spacing between trays of 300 mm. For closer vertical spacing the factors should be reduced. Values are given for a horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing the factors should be reduced.

APPENDIX-C Derating Factors (Ambient temperature factor, grouping fcators) 1). Underground Installation

2). Above ground Installation (in free air)

Table 52-D2 of IEC 364-5-523

Table 52-D1 of IEC 364-5-523

Correction factors (kg1) for ambient ground temperatures other than 20 °C, to be applied to the current-carrying capacities for cables in the ground

PVC

10 15

Installation Method in Table 52-B2

Correction factors (kg1) for ambient air temperatures other than 30 °C, to be applied to the current-carrying capacities for cables in the air

Insulation

Ground temperature (oC)

TABLE A.52-20 (52-E4) of IEC 364-5-523

Insulation

Unperforated

Number of Cables Number of Trays

1

2

3

4

1

0.95

0.85

0.80

0.75

2

0.95

0.85

0.75

0.75

3

0.95

0.85

0.75

0.70

1 2

1.00 0.95

0.95 0.95

0.95 0.90

0.95 0.90

XLPE and EPR

Ground temperature (oC)

PVC

XLPE and EPR

Trays

1.1 1.05

1.07 1.04

10 15

1.22 1.17

1.15 1.12

(Note 3)

25

0.95

0.96

20

1.12

1.08

3

0.95

0.95

0.90

0.90

30

0.89

0.93

25

1.06

1.04

1

1.00

0.90

0.80

0.80

35

0.84

0.89

35

0.94

0.96

Perforated

2

1.00

0.85

0.80

0.75

40

0.77

0.85

40

0.87

0.91

Trays

3

1.00

0.85

0.80

0.75

45

0.71

0.8

45

0.79

0.87

(Note 3)

1

1.00

1.00

1.00

0.95

50

0.63

0.76

50

0.71

0.82

2

1.00

1.00

0.95

0.90

55

0.55

0.71

55

0.61

0.76

3

1.00

1.00

0.95

0.90

60

0.45

0.65

60

0.5

0.71

Vertical

1

1.00

0.90

0.80

0.75

65

-

0.6

65

-

0.65

Perforated

2

1.00

0.90

0.80

0.75

70

-

0.53

70

-

0.58

75

-

0.46

75

-

0.5

1

1.00

0.90

0.90

0.90

80

-

0.38

80

-

0.41

2

1.00

0.90

0.90

0.85

85

-

(Note 4)

90

-

Ladder

1

1.00

0.85

0.80

0.80

95

-

Support,

0.85

0.80

0.80

0.85 1.00 1.00 1.00

0.80 1.00 1.00 0.95

0.75 1.00 0.95 0.95

Correction factors , Kg1 ( 20 °C ground temperature assumed) =

Correction factors , Ka1 ( 40 °C ground temperature) =

1

H

J

K

Trays

Cleats, Etc. (Note 3)

0.91

2 L

3 1 2 3

1.00 1.00 1.00 1.00

TABLE 52-E2 of IEC 364-5-523 Correction factors (kg2) for more than one circuit, cables laid directly in the ground Installation Method D in Tables 52-C1 to 52-C4 (Single or multicore cables)

Correction factor, Ka2-3 = Ka2-1 x ka2-2= Notes:

0,75 x 0,8 =

0.6

1.

Value given are averages for the cable types and range of conductor sizes considered in Tables 52-B7 to 52-B12. The spre generally less than ± 7.5%.

2

Factors apply to single layer groups of cables as shown above and do NOT apply when cables are installed in more than on touching each other. Values for such lower and must ve determined by appropriate method.installation may be significantly

Cable to cable clearance (a)* Number of circuits

Nil (cables touching)

One cable diameter

0.125 m

0.25 m

0.5 m

2

0.75

0.8

0.85

0.9

0.9

3

Values are given for a vertical spacing between trays of 300 mm. For closer vertical spacing the factors should be reduced.

3

0.65

0.7

0.75

0.8

0.85

4

4

0.60

0.60

0.70

0.75

0.80

Values are given for a horizontal spacing between trays of 225 mm with trays mounted back to back. For closer spacing the be reduced.

5

0.55

0.55

0.65

0.70

0.80

6

0.50

0.55

0.60

0.70

0.80

Total Correction factors, Kgt =

0.60

( Assumptions 4 number of circuits, and one cable diameter cable to cable clearance)

Underground cable total Correction Factor, Kgt = Kg1 x Kg2 =

0.6

Above ground total correction Factor, Kat = Ka1 x Ka2-3 =

0.55

ables 6

9

0.70

0.70

0.70

0.65

0.65

0.60

0.90 0.85

-

0.85

-

0.75

0.75

0.75

0.70

0.70

0.65

0.90

-

0.85

-

0.85

-

0.75

0.70

0.70

0.70

Ka2-2

0.85 0.85

-

0.80

0.80

0.75

0.75

0.75 1.00 0.95 0.95

0.70 -

Ka2-1

les 52-B7 to 52-B12. The spread in values is

es are installed in more than one layer stallation may be significantly

he factors should be reduced.

o back. For closer spacing the factors should

APPENDIX-D K Constanta for XLPE Cable Table 43A of IEC 60364-4-43 - Values of k fo Phase Conductor

PVC

PVC

≤ 300 mm2

> 300 mm2

EPR / XLPE

Rubber

Mineral

60 oC With PVC

Initial Temperature oC

70

Final Temperature oC

160

70

90

60

70

140

250

200

160

Material of Conductor : Copper

115

103

143

141

115 *

Aluminium

76

68

94

93

-

115

-

-

-

-

Tin-soldered joints in copper conductors

* This value shall be used for bare cables exposed to touch

APPENDIX-D nstanta for XLPE Cable

C 60364-4-43 - Values of k fo Phase Conductor

Mineral

Bare 105 250

135 -

APPENDIX-E MINIMUM CABLE SIZE CHART BASED ON VACUUM CONTACTOR AND HRC FUSE SELECTION (For 6600 (a) Cable Data

(b) Minimum cable allowed based on Fuse Let-Through Energy (I2t) Value Cable LetThrough Energy

Cable Size (mm2)

Motor Full Load Current Motor Power Motor Rating in Amp @ Factor at (kW) Voltage (V) = Steady State 6600 V

Cable Constanta (k)

(S2k2)

Motor Efficiency

143

A2S

25

143

1.28E+07

160

17.54

0.84

0.95

35

143

2.51E+07

200

21.92

0.84

0.95

50

143

5.11E+07

250

27.74

0.83

0.95

70

143

1.00E+08

280

30.69

0.84

0.95

90

143

1.85E+08

315

34.17

0.84

0.96

120

143

2.94E+08

400

41.42

0.88

0.96

150

143

4.60E+08

500

51.24

0.88

0.97

185

143

7.00E+08

800

81.98

0.88

0.97

240

143

1.18E+09

1120

115.97

0.88

0.96

300

143

1.84E+09

1250

127.98

0.89

0.96

400

143

3.27E+09

1800

184.29

0.89

0.96

500

143

5.11E+09

3150

319.19

0.89

0.97

630

143

8.12E+09

3350

335.68

0.90

0.97

2 x 120

143

5.89E+09

4000

396.41

0.91

0.97

2 x 150

143

9.20E+09

2 x 185

143

1.40E+09

Notes :

1) Fuse characteristic is based on K81 type used for up to 45 kA Isc at 6.6 kV applications. 2) Fuse Let-through Energy shall be less than Cable Let-through Energy. 3) To obtain minimum cable cross-section area for 3150 kW motor and larger, if the fuse rating is not available, the short circuit wi shall be determined based motor protection tripping time or respective Switchgear short circuit withstand capability. 4) Fuse sizes are shown indicative only, and are to be determined by Switchgear Manufacturer for suitability with the related equip For this calculation purpose, the cut-off level is determined using data for GEC Alstom General / Motor HV HRC Type K81 fuse assuming a maximum run-up time of 15 seconds and up to 4 starts per hour.

APPENDIX-E UUM CONTACTOR AND HRC FUSE SELECTION (For 6600 V Motor Feeders)

nimum cable allowed based on Fuse Let-Through Energy (I2t) Value

Fuse Rating

Fuse LetThrough (I2t)

Min. Cable Size Allowed (mm2)

50

2.10E+05

25

50

2.10E+05

25

63

2.40E+05

25

63

2.40E+05

25

80

4.15E+05

25

80

4.15E+05

25

100

5.15E+05

25

200

9.20E+05

25

250

1.77E+06

25

250

1.77E+06

25

315

2.23E+06

25

N/A

N/A

(Note-3)

N/A

N/A

(Note-3)

N/A

N/A

(Note-3)

50 kW motor and larger, if the fuse rating is not available, the short circuit withstand capability of cable g time or respective Switchgear short circuit withstand capability. e determined by Switchgear Manufacturer for suitability with the related equipment. ermined using data for GEC Alstom General / Motor HV HRC Type K81 fuse links,

APPENDIX-F MINIMUM CABLE SIZE CHART BASED ON MOTOR PROTECTION AND MCCB SELECTION (For 400 V (a) Cable Data

(b) Minimum cable allowed based on Motor Feeder Breaking Device Let-Throu Cable LetThrough Energy

Cable Size (mm2)

Motor Full Load Current Motor Power Motor Rating in Amp @ Factor at (kW) Voltage (V) = Steady State 400 V

Cable Constanta (k)

(S2k2)

Motor Efficiency

143

A2S

2.5

143

1.28E+05

0.37

1.13

0.74

0.64

4

143

3.27E+05

0.55

1.42

0.79

0.71

6

143

7.36E+05

0.75

1.85

0.77

0.76

10

143

2.04E+06

1.1

2.61

0.77

0.79

16

143

5.23E+06

1.5

3.43

0.78

0.81

25

143

1.28E+07

2.2

4.55

0.84

0.83

35

143

2.51E+07

3

6.06

0.84

0.85

50

143

5.11E+07

4

7.99

0.84

0.86

70

143

1.00E+08

5.5

10.86

0.84

0.87

90

143

1.85E+08

7.5

14.14

0.86

0.89

120

143

2.94E+08

11

21.78

0.81

0.90

150

143

4.60E+08

15

28.32

0.84

0.91

185

143

7.00E+08

18.5

34.55

0.84

0.92

240

143

1.18E+09

22

41.09

0.84

0.92

300

143

1.84E+09

30

56.10

0.83

0.93

37

67.64

0.84

0.94

45

80.28

0.87

0.93

55

97.17

0.86

0.95

75

132.50

0.86

0.95

90

157.17

0.87

0.95

110

190.10

0.87

0.96

132

228.12

0.87

0.96

150

259.23

0.87

0.96

Notes :

1) MCCB characteristic is based on Merlin Gerin - NS-L type used for up to 100 kA Isc at 400 V applications. 2) MCCB Let-through Energy shall be less than Cable Let-through Energy. 3) Motor ratings up to 5.5 kW will use GV2-L type of MCP. 4) Motor ratings from 5.5 kW p to 200 kW will use MCCB NS-L type. 5) MCP and MCCB sizes are shown indicatively only, and are to be determined by the switchgear manufacturer for suitability with

during detailed design.

APPENDIX-F MOTOR PROTECTION AND MCCB SELECTION (For 400 V Motor Feeders)

nimum cable allowed based on Motor Feeder Breaking Device Let-Through Energy

MCP / MCCB Type

MCP / MCCB Let-Through (I2t)

Min. Cable Size Allowed (mm2)

GV2-L

7.00E+03

2.5

GV2-L

7.00E+03

2.5

GV2-L

7.00E+03

2.5

GV2-L

1.70E+04

2.5

GV2-L

3.00E+04

2.5

GV2-L

5.00E+04

2.5

GV2-L

7.50E+04

2.5

GV2-L

7.50E+04

2.5

NS100

5.00E+05

6

NS100

5.00E+05

6

NS100

5.00E+05

6

NS100

5.00E+05

6

NS100

5.00E+05

6

NS100

5.00E+05

6

NS100

5.00E+05

6

NS100

5.00E+05

6

NS160

6.00E+05

6

NS160

6.00E+05

6

NS250

8.00E+05

10

NS250

8.00E+05

10

NS250

8.00E+05

10

NS400

1.80E+06

10

NS630

3.50E+06

16

and are to be determined by the switchgear manufacturer for suitability with the related equipment

APPENDIX-G MINIMUM CABLE SIZE CHART BASED ON MCCB SELECTION (For 400 V Power Distribution F (a) Cable Data

(b) Min. cable allowed based on 400V Power Distribution Breaking Device LetCable LetThrough Energy

Cable Size (mm2)

Load Rating (kW)

Full Load Current in Amp @ Voltage (V) = 400 V

Load Power Factor at Steady State

Load Efficiency

Cable Constanta (k)

(S2k2)

143

A2S

2.5

143

1.28E+05

1.2

2.26

0.85

0.90

4

143

3.27E+05

1.5

2.83

0.85

0.90

6

143

7.36E+05

2.1

3.96

0.85

0.90

10

143

2.04E+06

2.8

5.28

0.85

0.90

16

143

5.23E+06

3.7

6.98

0.85

0.90

25

143

1.28E+07

4.8

9.06

0.85

0.90

35

143

2.51E+07

6.5

12.26

0.85

0.90

50

143

5.11E+07

9.3

17.55

0.85

0.90

70

143

1.00E+08

12.2

23.02

0.85

0.90

90

143

1.85E+08

15.4

29.06

0.85

0.90

120

143

2.94E+08

18

33.96

0.85

0.90

150

143

4.60E+08

23.8

44.91

0.85

0.90

185

143

7.00E+08

29.7

56.04

0.85

0.90

240

143

1.18E+09

35.5

66.98

0.85

0.90

300

143

1.84E+09

47.7

90.00

0.85

0.90

58.3

110.00

0.85

0.90

70

132.07

0.85

0.90

83.7

157.92

0.85

0.90

101.8

192.07

0.85

0.90

121.9

230.00

0.85

0.90

147.9

279.05

0.85

0.90

177.5

334.90

0.85

0.90

Notes :

1) MCCB characteristic is based on Merlin Gerin - NS-L type used for up to 100 kA Isc at 400 V applications. 2) MCCB Let-through Energy shall be less than Cable Let-through Energy. 3) Air Circuit Breaker will be utilized for 800 Amp load rating and larger. 4) MCCB sizes are shown indicatively only, and are to be determined by the switchgear manufacturer for suitability with the relate

APPENDIX-G ED ON MCCB SELECTION (For 400 V Power Distribution Feeders)

n. cable allowed based on 400V Power Distribution Breaking Device Let-Through Energy

MCB / MCCB Type

MCB / MCCB Let-Through (I2t)

Min. Cable Size Allowed (mm2)

C60N

0.00E+00

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

C60N

5.00E+05

6

NS160

6.00E+05

6

NS160

6.00E+05

6

NS160

6.00E+05

6

NS250

8.00E+05

6

NS250

8.00E+05

6

NS400

1.80E+06

10

NS400

1.80E+06

10

NS400

1.80E+06

10

NS400

1.80E+06

10

o be determined by the switchgear manufacturer for suitability with the related equipment during detailed design.

Related Documents