CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-ARRANQUE DE LA UNIDAD

Date

CENTRO DE ENTRENAMEINTO PARA LAT

1

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA INSTALLATION CHECKLIST FOR CVGF GEAR-DRIVE CENTRIFUGAL WATER CHILLER

HOJA DE REVISION

Job Name

Location

Model #

Serial #

Revise la cargaStartde nitrógeno Sales Order # Up Date de embarque. No PRE-START UP OPERATIONS

1 1.

z

Siga la secuencia del número de la esquina superior izquierda.

2.

T1 To Earth __________

T4 To Earth __________

T1 To T2 _________

T1 ToT4 ________

T2 To Earth _________

T5 To Earth __________

T1 To T3 _________

T2 To T5 ________

T3 To Earth _________

T6 To Earth __________

T2 To T3 _________

T3 To T6 ________

3.

Relieve the nitrogen holding charge from the unit.

4.

Evacuate the chiller See evacuation procedures At Rear of manual.

# 5.

6.

7.

8.

9

Check the nitrogen holding charge on the chiller. The normal holding charge of a CVGF chiller is 34 kPa (5 psig) at 23.8 °C (75 °F). If it is not a leak test must be carried out. Pressure ___________kPa. Pressure ___________PSIG Disconnect the power leads from the motor Meg-test each phase to ground, and phase to phase. DO NOT MEGA TEST MOTOR WHILE UNDER A VACUUM

PRE- START OPERATION - EVAPORATOR



Check that isolation and flow balancing valves are installed and that the thermometers and pressure gauges are installed in/out of evaporator on machine side of any valve or elbow If evaporator pump is controlled by the UCP2, check that the field wiring is correct and complete. Check that the evaporator pump(s) have been run for 24 hrs and that the system and strainers have been properly cleaned and/or flushed. The evaporator water strainer should ideally be in close proximity to the entering water connection of the evaporator Check that provisions have been installed to properly maintain water treatment additives and that the initial water treatment has been added to the system

2 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

2

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

1

REVISE LA UNIDAD EN BUSCA DE DAÑOS

9

3 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

3

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

2

REVISE TODAS LAS PARTES QUE HAYAN SIDO EMBARCADAS CON LA UNIDAD

9

4 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

4

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

3

VERIFIQUE LA CANTIDAD DE REFRIGERANTE EMBARCADO

9

5 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

5

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

4

VERIFIQUE LA NIVELACION APROPIADA DE LA UNIDAD ELEVE LA UNIDAD EN UN EXTREMO PARA ALINEAR LOS PUNTOS DE REFERENCIA CON EL NIVEL DE AGUA

9

MIDA Y MARQUE UNA MISMA DISTANCIA HACIA ARRIBA A PARTIR DE CADA PIE DE LA MAQUINA

TUBO DE PLASTICO TRANSPARENTE (LLENE CON AGUA HASTA LA MARCA PERFORADA)

6 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

6

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

5

ASEGURE QUE EN EL LUGAR DE LA OBRA SE ENCUENTREN LOS DIAGRAMAS CORRECTOS DE CABLEADO, CONTROLES Y TUBERIA

9

7 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

7

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

6

REVISE Y VERIFIQUE LA DISPOSICION DE LA TUBERIA PARA ASEGURAR QUE CONCUERDA CON LAS CARACTERISTICAS DE DISEÑO.

9

8 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

8

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

7

VERIFIQUE QUE EL CONDENSADOR ESTA ENTUBADO CON EL FLUJO DE AGUA ENTRANDO POR LA PARTE INFERIOR Y SALIENDO POR LA PARTE SUPERIOR

Entrada Agua

9

Salida Agua

9 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

9

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

8

VERIFIQUE QUE LAS BOMBAS DE AGUA DEL SISTEMA NO ESTAN CLASIFICADAS A 3600 RPM @ 60HZ O A 3000 RPM @ 50HZ

9

10 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

10

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

9

VERIFIQUE QUE TODOS LOS COMPONENTES DEL LADO DE AGUA ESTEN INSTALADOS

9

1. VALVULAS DE AISLAMIENTO 2. VALVULAS DE BALANCEO 3. INTERRUPTOR DE PRESION DIFERENCIAL O DE FLUJO 4. TAPAS DE PRESION 5. POZOS DE TERMOMETRO 6. COLADORES 7. VALVULAS DE DRENADO 8. VALVULAS DE VENTILADO

11 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

11

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

10

VERIFIQUE QUE SE HA CONSIDERADO EL TRATAMIENTO APROPIADO DEL AGUA

9

12 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

12

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

11

VERIFIQUE QUE LAS BOMBAS DEL AGUA HELADA Y DEL CONDENSADOR OPERAN DEBIDAMENTE

9

13 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

13

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

12

REVISE LA VALVULA DE ALIVIO DE PRESION (DISCO DE RUPTURA)

9

ESPACIADOR TUERCA PERNO

ENSAMBLE DE TUBERIA EXTERIOR

CONEXION DE SUCCION DISCO DE RUPTURA

TAPA PARED EXTERIOR LINEA DE DESFOGUE DE DESCARGA DE LA PURGA

ESTE TUBO DEBE SER SOPORTADO

ENSAMBLE DEL DISCO DE RUPTURA

CONEXION DE ACERO FLEXIBLE

LINEA DE GOTEO

14 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

VALVULA DE DRENE NPT

14

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA VERIFIQUE QUE TODO CABLEADO INCLUYENDO LAS

13

INTERCONEXIONES ESTEN COMPLETAS HACIA LA UNIDAD Y EN CONFORMIDAD CON LOS CODIGOS LOCALES Panel UCP2

9

(Nuevo) Panel CH530

CH530 podría incluir más opciones !

15 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

15

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

14

VERIFIQUE LA DISPONIBILIDAD DEL SUMINISTRO DE ENERGIA ELECTRICA

N IO C RA CO E E OP N S E

115 VAC

9

HERRAMIENTA DE POTENCIA

EV

AC

UA

CIO

N

16 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

16

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA

15

REVISE LOS VENTILADORES DE LA TORRE DE ENFRIAMIENTO Y LOS CONTROLES

9

17 Insert Footer

CENTRO DE ENTRENAMEINTO PARA LAT

17

CENTRAVAC: FUNDAMENTOS DE LA UNIDAD

CVHE/F/G GUIAS PARA PRE-PUESTA EN MARCHA VERIFIQUE CON EL INGENIERO DE VENTAS, EL INSTALADOR

16

Y EL CLIENTE, QUE TODO ESTA LISTO Y DISPONIBLE PARA EL ARRANQUE