Loading documents preview...
APPROVED APPROVED EXCEPT AS NOTED:RESUBMISSION REQUIRED NOT APPROVED, MODIFY AND RESUBMIT FOR INFORMATION ONLY. NOTE: THE APPROVAL SHALL NOT RELIEVE THE CONTRACTOR FROM HIS RESPONSIBILITY FOR COMPLIANCE TO CONTRACT REQUIREMENTS, DRAWING,SPECIFICATIONS & DATA SHEETS
EMPLOYER
CONTRACTORS
CONSULTANT
PROJECT
62
SIEMENS
KEPZ Extension (132/12 kV GIS Substation) RELAY SETTING CALCULATIONS
Date:
26.06.2018
Worked by:
Seema Naseer
Checked by:
Fatima Izhar
Approved by:
Yousuf Mubarak
Approved by:
C
*Remarks: LED configuration for all protection relays shall be made at site. SIEMENS Energy Sector Projects/Engineering
Page 2 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS A. A.1
40 MVA, POWER TRANSFORMERS PROTECTION Differential Protection(For E06 Bay)
7UT612
SIEMENS
Page 5
Transformer Differential Relay B.
RESTRICTED EARTH FAULT PROTEECTION
B.1
HV REF Relay
7SJ8012
SIEMENS
Page 17
B.2
LV REF Relay
7SJ8012
SIEMENS
Page 20
7SJ8031
SIEMENS
Page 25
OC relay using standard inverse characteristics
7SJ8031
SIEMENS
Page 26
Outgoing Cable Feeder 12kV Circuit (400/5A)
7SJ8031
SIEMENS
Page 27
7SJ8031
SIEMENS
Page 28
7SJ8031
SIEMENS
Page 29
7SJ8031
SIEMENS
Page 30
7SJ8031
SIEMENS
Page 31
7SJ8011
SIEMENS
Page 32
7SJ8011
SIEMENS
Page 33
7SJ8031
SIEMENS
Page 38
Outgoing Aux Trafo Feeder 12kV Circuit (with newly proposed CT) 7SJ8031
SIEMENS
Page 39
7SJ8031
SIEMENS
Page 40
7SJ8031
SIEMENS
Page 41
C.
OVER CURRENT PROTECTION
C.1
Outgoing Aux Trafo Feeder 12kV Circuit OC relay using standard inverse characteristics
C.1A C.2
Outgoing Aux Trafo Feeder 12kV Circuit (with newly proposed CT)
OC relay using standard inverse characteristics C.2A
Outgoing Cable Feeder 12kV Circuit (800/5A) OC relay using standard inverse characteristics
C.3
Outgoing Capacitor Feeder 12kV Circuit (400/5A) OC relay using standard inverse characteristics
C.4
Outgoing Capacitor Feeder 12kV Circuit (800/5A) OC relay using standard inverse characteristics
C.5
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV side) OC relay using standard inverse characteristics
C.6
40 MVA Transformer 132 kV Circuit (Trafo HV side) OC relay using standard inverse characteristics
C.7
13.3 MVA, Tertiary winding OC relay using standard inverse characteristics
D.
BACK UP EARTH FAULT PROTECTION
D.1
Outgoing Aux Trafo Feeder 12kV Circuit EF relay using standard inverse characteristics
D.1A
EF relay using standard inverse characteristics D.2
Outgoing Cable Feeder 12kV Circuit (400/5A) EF relay using standard inverse characteristics
D.2A
Outgoing Cable Feeder 12kV Circuit (800/5A) EF relay using standard inverse characteristics
*Remarks: LED configuration for all protection relays shall be made at site. SIEMENS Page 3 + Energy Sector Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.3
Outgoing Capacitor Feeder 12kV Circuit (400/5A)
7SJ8031
SIEMENS
Page 42
7SJ8031
SIEMENS
Page 43
7SJ8031
SIEMENS
Page 44
7SJ8031
SIEMENS
Page 45
7SJ8011
SIEMENS
Page 46
7SJ8011
SIEMENS
Page 47
7SJ8011
SIEMENS
Page 48
7SJ8011
SIEMENS
Page 49
7SJ8011
SIEMENS
Page 50
EF relay using standard inverse characteristics D.3A
Outgoing Capacitor Feeder 12kV Circuit (800/5A) EF relay using standard inverse characteristics
D.4
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV Side) with NGR EF relay using standard inverse characteristics
D.4A
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV Side) without NGR EF relay using standard inverse characteristics
D.5
40 MVA Transformer 12kV Circuit Neutral Protection (LV Side) with NGR EF protection using standard inverse characteristics
D.5A
40 MVA Transformer 12kV Circuit Neutral Protection (LV Side) without NGR EF protection using standard inverse characteristics
D.6
40 MVA Transformer 132 kV Circuit(Trafo HV Side) EF relay using standard inverse characteristics
D.7
13.3 MVA, Tertiary Winding TEF protection using standard inverse characteristics
D.8
40 MVA Transformer 132 kV Circuit Neutral Protection (HV Side) EF protection using standard inverse characteristics
D.9
40 MVA Transformer ,EF Relay for NGR
P14N
Shanghai Xinguang Page 51
EF protection using standard inverse characteristics E.
AVR RELAY
E.1
40MVA, PTR AVR RELAY
F.
CAPACITOR UNBALANCE PROTECTION
TAPCON
MR
Page 55
SIEMENS
Page 57
230 EXPERT
F.1 G.
Capacitor Bank Unbalance Protection Annexure
7SJ8031
Page 58
*Remarks: LED configuration for all protection relays shall be made at site. SIEMENS Page 4 + Energy Sector Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
Differential Protection
SIEMENS Energy Sector Projects/Engineering
Page 5 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
40 MVA Transformer Differential Protection Setting Calculation Data: I ). Relay type II ). Transformer Rating
=
7UT6121-5EB22-1AA0
=
40
MVA
III ). Voltage at maximum tap
Umax
=
151.80
kV
IV ). Voltage at minimum tap
Umin
=
112.20
kV
V ). Transformation Ratio
=
132 /12
VI ). Tap changing Range
=
+ 15 %
VII ).Vector Group
=
YNyn0(d11)
VIII) HV CT Ratio
=
200/1
A
=
2500/5
A
IX) LV CT Ratio
to
- 15 %
Calculations: A ). Rated Current B ). Differential Initial Setting
I - Diff >
C ). Differential Bias Slope Setting
SLOPE 1
D ). Differential Bias Slope Limit
SLOPE 2
E ). Differential Highest Setting
I - Diff >>
F ). Magnetising Inrush Restraint Level A
Load Current: As per 7UT612 manual , If a transformer winding is regulated, then the actual rated voltage of the winding is not used as UN for the stabilized side,but the voltage corresponding to the average current of the regulated range. The following applies: UN
=
2 x [(Umax x Umin) ÷ (Umax + Umin)]
(Refer 7UT manual page 21)
where Umax, Umin are the voltages at the limits of the regulated range. UHV
The voltage set on 132 kV side
= =
2 x [(151.8 x 112.2) 129.03
÷ (151.8
+112.2)]
kV
HV SIDE : Transformer Rated Current HV regulated side
=
40000
=
178.98172
=
0.895
÷
(√3 x 129.0)
=
178.9817
Corresponding rated current on secondary side of CT
SIEMENS Energy Sector Projects/Engineering
I N1
÷ 200/1
= 0.895
@ INObj
Page 6 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS LV SIDE : Transformer Rated Current LV unregulated side
=
40000
÷
(√3 × 12.0)
=
=
1924.5009
÷
2500 / 5 A
=
=
3.849
1924.501
Corresponding maximum full load current I N2
on secondary side of CT
B
Differential Initial Setting
3.849
@ INObj
I - DIFF >
Spill current calculation due to following Constant Errors: ●
Tap changer regulation
●
Magnetizing currents of CTs and Power transformer Transformer Rated Current at maximum tap position(1), +15%.
=
40000
÷
(√3 ×151.8 )
=
152.1
Corresponding maximum full load current at max. tap on secondary side of CT
= IN1(+15%)
→
÷ 200/1
=
0.761
@
IN1(+15%)
− INObj
Differential current in max. tap position
I Diff
=
Differential current in max. tap position
I Diff
=
Differential current at max. tap position
152.134
= 0.761 I NObj
0.85
(Refer 7UT manual page 34)
* I NObj - I NObj
0.85
=
I NObj
=
-0.150
I NObj
=
0.150
I NObj
=
40000
÷
=
205.829
0.850
-1
= 15.0%
Transformer Rated Current at minimum tap position(25) -15%.
(√3 ×112.2 )
=
205.829
Corresponding rated current at min tap on secondary side of CT IN1(-15%)
= I Diff
=
Differential current in min. tap position
I Diff
=
=
SIEMENS
IN1(-15%)
1.15
1.150 0.150
= 1.029 I NObj
− INObj =
1.15 *I NObj - I NObj
I NObj
=
Energy Sector Projects/Engineering
@
1.029
Differential current in min. tap position
÷ 200/1
1.15 *I NObj - I NObj (Refer 7UT manual page 34)
-1
I NObj
Page 7 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
→
Differential current at min. tap position
=
0.150
Thus tap changer regulation error is
=
15.0%
I NObj
CT magnetizing errors and mismatching of Cts has been considered as= 0.015 %
Maximum differential current
=
15.00%
+
0.02%
=
15.02%
=
20%
Considering safety margin based on variations of above factors due to variation in system condition and environment, the pick up value of differential current is to be selected as,
I - Diff >
(Available settings: 0.05 … 2.00 I/I no)
C
Differential Bias Slope Setting ○ Base Point 1 Considering the differential and restraining currents are equal at normal loading, therefore, by straight line equation; m = (y2 - y1) ÷ (x2 -x1) m= \
-1
tan = (m)
=
1
-
0
÷
1
-
0 =
1
45°
Since in the beginning, errors in Cts are unaccountable and differential / stabilizing currents are balance, therefore, base point of slope 1 is to be selected as, BASE POINT 1
=
0.00
(Available settings: 0.00 … 2.00 I/I no)
○ SLOPE 1 ●
As per manufacturer's guide line, the tripping characteristic is characterized by two slopes. Address 1241 A
SIEMENS Energy Sector Projects/Engineering
Slope 1 consider current proportional error which may result from
Page 8 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
e.g. ○
tap changer's regulation range of power transformer and
○
CT transformation manufacturing limitations.
These errors increases with increase in load, to find the suitable slope consider I diff = Therefore at full load, current I 1 = 1
and due to
20%
errors
20 % 0.8
I2=
Then according to stabilising current equation, I stab,
x
=
I1
I2
+
=
1
+
0.8
=
1.8 (Refer 7UT manual page 258)
If the slope selected is 0.1, then I diff,
y
= m.X+b =
I diff
( slope equation )
0.10 x 1.8
= 0.180
Though we have
20 %
differential current but relay shall give tripping at
18%
, therefore this value is not suitable. Now, the slope selected is 0.15 at full load \ I stab x, I diff,
y
=
+
I2
=
1
+
0.8
=
1.8
= m.X+b =
I diff
I1
( slope equation )
0.15 x 1.8
= 0.270
Therefore, from the above calculations we found that slope
0.150
is better
compensated for errors. But as per client's recommendation the slope setting is set 0.3 at full load. \ I stab x, I diff,
y
=
+
I2
=
1
+
0.8
= m.X+b =
I diff
I1
=
1.8 ( slope equation )
0.30 x 1.8
= 0.540
Thus Slope 1 setting
SLOPE 1
=
0.30
(Available settings: 0.10 … 0.50)
SIEMENS Energy Sector Projects/Engineering
Page 9 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
○ Base Point 2 This produces higher stabilization in the range of high currents which may lead to current transformer saturation. To consider base point for slope 2; For higher load currents 25% overloading is considered, therefore, Istab
=
I1
=
I2
+
1.25
+
1.25
=
(Refer 7UT manual page 258)
2.5
As the CT saturation criteria starts at this value, therefore, it is to be set at the value of
2.5 I/Ino
=
(Available settings: 0.00 … 10.00 I/I no)
○ SLOPE 2 ●
Address 1243 A
Slope 2 provides stabilization in differential scheme in case of higher
through fault currents resulted current transformer saturation. The stability of the protection can be influenced by these settings. To find the suitable slope consider the stabilization current, I stab
y
= m.X+b
For through fault current under heavy load, following satisfies Transformer 1:
Since
I1 =
If
÷
If
=
214247
÷
(√3×
112 )
=
1104.4 A
In
=
40000
÷
(√3×
132 )
=
175.0 A
1104.43
÷
175.0
In
=
=
6.313
Consider that degree of differential current at this point = 50% and fault is out side the zone, therefore, I diff(act),
y
=
I1
+
I2
I1
−
I2
I diff(act),
y
=
I1
+
I2
I1
−
I2
=
I diff(act),
y
=
-3.156
@
-3.2
Istab
=
I1
+
I2
=
6.31
=
9.469
+
3.16
(Refer 7UT manual page 258) 6.31
− 6.31 x 0.5
Now we set slope at 0.4 and check the suitability and veryfying the relation by; I diff(act) < I diff(set) I diff(set), I diff(set)
y
= m.X+b
=
0.40 x
9.469
at -
m
=
0.4
X
=
9.469
b
=
-1
1
= 2.788
SIEMENS Energy Sector Projects/Engineering
Page 10 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
But as per client's recommendation the slope setting is set at 0.7, I diff(set), y = m.X+b Now taken m = 0.7 = 0.70 x 9.469 -1.75 = 4.878 This I diff(set) value confirms the relation,
I diff(act) < I diff(set)
x
Differential Highest Setting
9.469
b=
-1.75
therefore the set value of SLOPE 2
(Available settings: 0.25 … 0.95)
D
=
=
0.70
I - DIFF >>
Rated current of transformer at normal tap.
=
178.98
=
18.67 %
A
Transformer Percentage impedance of transformer
= \ Fault MVA at this impedance
=
0.1867 40
÷
pu 0.187
= 214
MVA
Considering maximum fault MVA gives If
maximum through fault current
=
214
=
1102.46
A
Corresponding current at CT secondary
=
5.51
A
Through fault current with respect to I n
=
5.51
× 1000 ÷
÷
0.895
( √3 ×
=
112.2
6.160
)
I/In
It is set to be as I - Diff >> =
(Available settings: 0.5 … 35 I/I no)
SIEMENS Energy Sector Projects/Engineering
7.5
I/Ino
Page 11 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS ● ●
1226A
Trip time delay Idiff >
1236A
Trip time delay Idiff >>
In special cases it may be advantageous to delay the trip signal of the protection. But for this case we will not use this delay time, and relay will give tripping command as soon as it senses differential condition above threshold. Therefore Time delay is set zero.
E
Add-on stabilization
I - ADD ON STAB.
During an external fault which produces as high through flowing short circuit current causing current transformer saturation, a considerable differential current can be simulated, especially when the degree of saturation is different at the two measuring points. 7UT612 provides a saturation indicator which detects such phenomena and initiates add-on stabilization measures. The saturation indicator operates dynamically in the area which is designated with "add-on Stabilization". Current Transformer saturation during external faults is detected by a high initial stabilizing current which moves the operating point briefly into the "add-on stablization"area. In contrast, the operating point moves immediately along the fault characteristic when an internal fault occurs since the stabilization current will barely be higher than the differential current. The saturation indicator makes its decision within the first half period after fault inception. Transformer through fault current is calculated as; Transformer : since,
If
=
214247
÷
(√3×
112.2 )
=
1102.5 A
In
=
40000
÷
(√3×
132 )
=
174.95 A
(I f / I n) of I n
=
1102.4583
÷
174.954627 =
The Value is set as
6.3014 of I no
=
6.50
I/Ino
(Available settings: 2.00 … 15.00 I/I no)
SIEMENS Energy Sector Projects/Engineering
Page 12 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
F
2nd HARMONIC The Inrush current can amount to a multiple of the rated current and is characterized by a considerable 2nd harmonic content which is practically absent in the case of shortcircuit. Stabilization during inrush condition via 2nd harmonic content in differential current is also detected by relay which just initiates blocking of the tripping. \ Selected value =
15 %
( It is recommended by manufacturer which is sufficient in 90 % cases) (Available settings: 10 … 80%)
G
Cross blocking for 2nd Harmonic Since the inrush stabilization operates individually per phase, the protection is fully operative even when the transformer is switched on a single phase fault, whereby inrush currents may possibly be present in one of healthy phases. However, it is also possible to set the protection such that not only phase with inrush current exhibiting harmonic content in excess of the permissible value is stabilized but also the other phases of the differential stage I Diff> are blocked (so called "Cross block function). This cross-block can be limited to a selectable duration and can be set from 0 to 1000 AC period. Normally this function is set ineffective, however, in abnormal inrush condition this can be set to block in a defined ac period. According to the inrush current report of the transformer we suggest the setting of Cross block function Set at
=
25
Cycles
(Available settings: 2 … 1000Cycle; 0;
H
nth Harmonic Steady-state over excitation of transformer is characterized by odd harmonic content. The 3rd or 5th Harmonic is suitable to detect over excitation as the third harmonic is offered eleminated in the transformer windings (e.g. In a delta connected winding group), The fifth harmonic is usually used to avoid trip during over excitation, since the trafo is being used as distribution transformer, therefore, nth Harmonic function is set (Available settings: 10 … 80 %
SIEMENS Energy Sector Projects/Engineering
= 30%
Page 13 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS I.
Transformer parameter settings: ○ Rated primary voltage side 1 As per 7UT612 manual section 2.1.2, If a transformer winding is regulated, then the actual rated voltage of the winding is not used as UN for the stabilized side,but the voltage corresponding to the average current of the regulated range. The following applies: UN
=
2 x [(Umax x Umin) ÷ (Umax + Umin)]
(Refer 7UT manual page 21)
where Umax, Umin are the voltages at the limits of the regulated range. The voltage set on 132 kV side
UHV
=
2x
=
129.03
[(151.8
x 112.2) ÷
(151.8
+112.2)]
=
129.0 kV
kV
\ the rated primary voltage
○ Rated Secondary voltage side 2 The rated voltage of transformer side 2 in kV (phase to phase) is set under this address. =
\ the rated primary voltage
12.0 kV
○ Rated apparent power of the transformer(side 1 & 2) The primary rated apparent power of transformer is set under this address. The power must always be entered as a primary value, even if the device is generally configured in secondary values. 40.00 MVA
=
The apparent of transformer is (Available settings: 0.20 to 5000.00 MVA)
○ Starpoint of transformer the starpoint of side 1 is
=
Solid grounded
the starpoint of side 2 is
=
Resistor grounded
As the starpoint of transformer`s side 2 is earthed through NGR.
SIEMENS Energy Sector Projects/Engineering
Page 14 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
J.
CTs parameter settings:
○ CT starpoint in direction of object side 1 In order to ensure the correct polarity for the differential currents, the CT starpoint in direction of protected object is set under this address. = (Towards object)
Selected setting
(Furhter to be confirmed at site) ○ CT rated primary current side 1 This parameter is set to the rated primary current of the CT. Selected setting
=
200
=
1A
○ CT rated secondary current side 1 This parameter is set to the rated secondary current of the CT. Selected setting
○ CT starpoint in direction of object side 2 In order to ensure the correct polarity for the differential currents, the CT starpoint in direction of protected object is set under this address. = (Towards object)
Selected setting
(Furhter to be confirmed at site) ○ CT rated primary current side 2 This parameter is set to the rated primary current of the CT. Selected setting
=
2500
=
5A
○ CT rated secondary current side 2 This parameter is set to the rated secondary current of the CT. Selected setting
SIEMENS
Energy Sector Projects/Engineering
Page 15 +
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS Setting Parameters General Data: Address
Function
Value
0270
Rated Frequency
50 Hz
0271
Rated Sequence
L1,L2,L3
0312
Rated Apparent Power of Trafo side.1
40MVA
0322
Rated Apparent Power of Trafo side.2
40MVA
0311
Rated Primary Voltage side.1
129kV
0321
Rated Primary Voltage side.2
12kV
0313
Starpoint of side.1
Solid Grounded
0323
Starpoint of side.2
Resistor Grounded
0314
Trafo Winding Connection Side.1
Y(Wye)
0324
Trafo Winding Connection Side.2
Y(Wye)
0325
Vector Group Numeral of Side.2
0
0511
CT Starpoint in direction of object side.1
Towards Object (Further to be confirmed at site)
0512
CT rated Primary current Side.1
200A
0513
CT rated Seconadry current Side.1
1A
0521
CT Starpoint in direction of object side.2
Towards Object (Further to be confirmed at site)
0522
CT rated Primary current Side.2
2500A
0523
CT rated Seconadry current Side.2
5A
Differential Protection Address
Function
Value
Range
1201
Differential Protection
ON
On,OFF,BLK
1206
Inrush with 2. Harmonic Restraint
ON
On,OFF
1207
n-th Harmonic Restraint
5th Harm
3.Harm,5.Harm,OFF
1221
Pickup Value of Differential Curr.
0.2 I/Ino
0.05 to 2.00
1226A
T I-DIFF> Time Delay
0.00 s
0.00 to 60.00
1231
Pickup Value of High Set Trip I-DIFF>>
7.5 I/Ino
0.5 to 35.0
1236A
T I-DIFF>> Time Delay
0.00 s
0.00 to 60.0
1241A
Slope 1 of Tripping Characteristic
0.30
0.1 to 0.5
1242A
Base Point for Slope 1 of Charac.
0.0 I/Ino
0.0 to 2.0
1243A
Slope 2 of Tripping Characteristic
0.70
0.25 to 0.95
1244A
Base Point for Slope 2 of Charac.
2.5 I/Ino
0.0 to 10.0
1256A
Pickup for Add-on Stabilization
6.5 I/Ino
2.00 to 15.0
1257A
Duration of Add-on Stabilization
15 cycles
2 to 250
1261
2nd Harmonic Content in I-DIFF
15 %
10 to 80
1262A
Time for Cross-blocking 2nd Harm.
25 cycles
2 to 1000
1271
n.HARMONIC
30 %
10 to 80
1272A
Time for Cross-blocking n. Harm.
0 cycles
2 to 1000
SIEMENS Energy Sector Projects/Engineering
Page 16 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
HV Restricted Earth Fault Protection
SIEMENS Energy Sector Projects/Engineering
Page 17 +
### EM-TS PROJECTS /A5175/Relay Settings
SIEMENS Transformer HV Restricted Earth Fault Protection Relay Type: 7SJ8012-5EB20-1FA0 HV Bushing CT 200/1A
CT Ratio: Class of Accuracy:
5P20
Burden:
30
VA
CT Resistance:
Rct = 0.7
Knee Point Voltage:
VK = 540
CT primary current:
200
Ω V
A
Power Transformer Data: Power Rating =
40
MVA
Percentage Impedance =
18.67
%
Rated HV Voltage = U N =
112.2
kV
Trafo. Rated Current
(at Maximum tap:112.2kV)
I TFL = Power Rating /(3 x Voltage) 6 = 40 x 10 / (3 x 112000)
=
3-phase primary fault current
205.83 A
I F = Power Rating /(3 x Voltage x Percentage impedance) 6 = 40 x 10 / (3 x 112200 x 18.67/100)
(Calculated at the highest tap:
112.2 kV)
= 1102.46 A
Maximum primary through fault current of trafo
IF =
1500 A
(20 times the rated current) 7SJ8012 HV RESTRICTED EARTH FAULT SETTINGS 1 Maximum value of primary fault current for Internal Fault
IF
=
1500.00
A
2 Maximum value of primary through fault current for which prot must remain stable
I FM
=
1102.46
A
3 Trafo full load current
I TFL
=
205.83
A
4 Turns ratio of CT core
N
=
200
5 CT Secondary current
I sn
=
1
6 Rated symmetrical short-circuit current factor
Kssc
=
20
7 Rated CT Burden
Rb
=
30
Ω
8 CT knee point voltage
VK
=
540.00
V
9 CT Secondary Winding Resistance
RCT
=
0.70
Ohms
10 Lead resistance between furthest current transformer and relay
RL
=
0.40
Ohms
=
6
Ohms
0.02
A
0.090
A
A
terminals VA/I R2
11 Relay Impedance
RR
12 CT core magnetizing current (secondary) at relay setting voltage (Calculated)
IE
=
13 Relay Operating Current
IR
=
(Relay setting current range)
SIEMENS Energy Sector Projects/Engineering
(0.001….1.4)
Page 18 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
14 Number of CT cores in circulating current differential circuit
n
15 Minimum Setting Voltage (Calculated)
Vs
I FM x (RCT + 2 x RL) / N
=
4
=
8.27
V
=
50
V
=
34.0
A
(Refer Siemens Reyroll manual page 9) 16 Relay setting voltage
VR
17 Primary current required for pick-up of protection (sensitivity)
IP
N x (I R + n x I E + I m)
(Refer Siemens Reyroll manual page 9) Primary current required for pick-up of protection as percentage
=
16.52%
=
9227
V
6126.08
V
of I TFL
of trafo full load current VF
18 The theoretical voltage which would be produced across the
I FM x (RL + RCT + Rs+ RR) / N
(Refer Siemens 7SJ8 High imp test page:15) relay circuit under internal fault condition. 19 Peak voltage across relay circuit under maximum internal fault
2√(2VK (VF - VK)
VRMAX
=
(Refer Siemens 7VH6 manual page:A-5)
conditions.
VRMAX > 2KV
20 External Metrosil required
=
Yes
=
0.0000
(Refer 7VH60 manual page A-5) Im
21 Metrosil Current (calculated)
0.52 x(Vs xѴ2 / C)^1/β
A
(Refer Metrosil manual page 1) 22 Constant(given value)
C
=
405
23 Constant(given value)
β
=
0.250
VR / IR
=
555.55 Ohms
RS
24 Value of stabilizing resistor(calculated)
(Vk>2VS and Vk<4VS) (Refer Siemens 7SJ8 High imp test page:11) 25 Knee point Voltage must be greater than twice
VK > 2VR
=
Yes
(Refer Siemens 7SJ8 High imp test page:11) the relay setting voltage 26 Continuos Power rating of Stabilizing Resistor
(I R2 X Rs)
=
14
Watt
( Vk3 x Rs x I fm )1/4 x 1.3
=
1426
Watt
1220
Watt
Pstab,cont
27 RMS Voltage Developed across stabilizing resistor
Vrms
Vrms
(Refer Siemens 7SJ8 High imp test page:14) Pstab,0.5s
28 Short time Power rating of Stabilizing Resistor
(Vrms2/Rs)
=
(Refer Siemens 7SJ8 High imp test page:14)
Setting Parameters General Data Adress
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
200A
0205
CT Rated Secondary Current
1A
0217
IE-CT Rated Primary Current
200A
0218
IE-CT Rated Secondary Current
1A
HV REF Protection Adress
Function
Value
Range
3117
50 1 Ph-1 Pickup
0.090
0.001 to 1.600 A: infinity
Stabilising Resistor (Variable)
Rs
= 555. 55
Primary Operating Current,
IP
= 34.0
Metrosil Require
SIEMENS Energy Sector Projects/Engineering
W (0 - 2000 W Variable
= Yes
Page 19 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
LV Restricted Earth Fault Protection
SIEMENS Energy Sector Projects/Engineering
Page 20 + ### EM-TS PROJECTS /A5175/Relay Settings
SIEMENS Transformer LV Restricted Earth Fault Protection Relay Type: 7SJ8012-5EB20-1FA0 LV Bushing CT 2500/5A
CT Ratio: Class of Accuracy:
5P20
Burden:
30
VA
CT Resistance:
Rct = 0.9
Knee Point Voltage:
VK = 120
CT primary current:
2500
Ω V
A
Power Transformer Data: Power Rating = Percentage Impedance =
40
MVA
18.67
%
Rated LV Voltage = UN =
12
kV
(at Maximum tap:112.2kV)
Trafo. Rated Current
I TFL = Power Rating /(3 x Voltage) 6 = 40 x 10 / (3 x 12000)
=
3-phase primary fault current
1924.50 A
I FM = Power Rating /(3 x Voltage x Percentage impedance) 6 = 40 x 10 / (3 x 12000 x 18.67/100)
Maximum primary fault current
=
10309.28 A
IF =
1500 A
(Calculated at LV Voltage:
12 kV)
(equal to NGR ratings) 7SJ8012 LV RESTRICTED EARTH FAULT SETTINGS 1 Maximum value of primary fault current for Internal Fault
IF
=
1500
A
2 Maximum value of primary through fault current for which prot must remain stable
I FM
=
10307.99
A
3 Trafo full load current
I TFL
=
1924.50
A
4 Turns ratio of CT core
N
=
500
5 CT Secondary current
I sn
=
5
6 Rated symmetrical short-circuit current factor
Kssc
=
20
7 Rated CT Burden
Rb
=
1.2
Ω
8 CT knee point voltage
VK
=
120.00
V
9 CT Secondary Winding Resistance
RCT
=
0.90
Ohms
10 Lead resistance between furthest current transformer and relay
RL
=
0.40
Ohms
=
0.83
Ohms
0.021
A
0.600
A
2500/5
A
terminals VA/I R2
11 Relay Impedance
RR
12 CT core magnetizing current (secondary) at relay setting voltage (Calculated)
IE
=
13 Relay Operating Current
IR
=
(Relay setting current range)
SIEMENS Energy Sector Projects/Engineering
(0.001….1.4)
Page 21 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
14 Number of CT cores in circulating current differential circuit
n
15 Minimum Setting Voltage (Calculated)
Vs
I FM x (RCT + 2 x RL) / N
=
4
=
35.05
V
=
50
V
=
342.0
A
(Refer Siemens 7VH6 manual page:A-4) VR
16 Relay setting voltage
IP
17 Primary current required for pick-up of protection (sensitivity)
N x (I R + n x I E + I m)
(Refer Siemens 7SJ8 High imp test page:12) Primary current required for pick-up of protection as percentage
=
17.77%
=
1762
V
1255.51
V
of I TFL
of trafo full load current VF
18 The theoretical voltage which would be produced across the
I FM x (RL + RCT + Rs+ RR) / N
(Refer Siemens 7SJ8 High imp test page:15) relay circuit under internal fault condition. 19 Peak voltage across relay circuit under maximum internal fault
2√(2VK (VF - VK)
VRMAX
=
(Refer Siemens 7VH6 manual page:A-5)
conditions.
VRMAX > 2KV
20 External Metrosil required
=
NO
(Refer Siemens 7VH6 manual page:A-5) Im
21 Metrosil Current (calculated)
0.52 x(Vs xѴ2 / C)^1/β
=
0.00004
A
(Refer Metrosil manual page 1) 22 Constant(given value)
C
=
540
23 Constant(given value)
β
=
0.250
VR / IR
=
83
RS
24 Value of stabilizing resistor(calculated)
Ohms
(Vk>2VS and Vk<4VS) (Refer Siemens 7SJ8 High imp test page:11) 25 Knee point Voltage must be greater than twice
VK > 2VR
=
Yes
(Refer Siemens 7SJ8 High imp test page:11) the relay setting voltage 26 Continuos Power rating of Stabilizing Resistor
(I R2 X Rs)
=
30
Watt
( Vk3 x Rs x I fm )1/4 x 1.3
=
303
Watt
1105
Watt
Pstab,cont
27 RMS Voltage Developed across stabilizing resistor
Vrms
Vrms
(Refer Siemens 7SJ8 High imp test page:14) Pstab,0.5s
28 Short time Power rating of Stabilizing Resistor
(Vrms2/Rs)
=
(Refer Siemens 7SJ8 High imp test page:14)
Setting Parameters General Data Adress
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
2500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Primary Current
2500A
0218
IE-CT Rated Secondary Current
5A
LV REF Protection Adress
Function
Value
Range
3117
50 1 Ph-1 Pickup
0.600
0.005 to 8.000 A: infinity
Stabilising Resistor (Variable)
Rs
= 83
Primary Operating Current,
IP
= 342
Metrosil Require
SIEMENS Energy Sector Projects/Engineering
W (0 - 150 W Variable
= NO
Page 22 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
BACKUP OVER CURRENT PROTECTION
SIEMENS Energy Sector Projects/Engineering
Page 23 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.
OVER CURRENT PROTECTION
C.1
Outgoing Aux Trafo Feeder 12kV Circuit OC relay using standard inverse characteristics
C.1A
Siemens
7SJ8031
Siemens
7SJ8031
Siemens
7SJ8031
Siemens
Outgoing Capacitor Feeder 12kV Circuit(800/5A) OC relay using standard inverse characteristics
C.5
7SJ8031
Outgoing Capacitor Feeder 12kV Circuit(400/5A) OC relay using standard inverse characteristics
C.4
Siemens
Outgoing Cable Feeder 12kV Circuit (800/5A) OC relay using standard inverse characteristics
C.3
7SJ8031
Outgoing Cable Feeder 12kV Circuit (400/5A) OC relay using standard inverse characteristics
C.2A
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV side) 7SJ8031 OC relay using standard inverse characteristics
C.6
Siemens
40 MVA Transformer 132 kV Circuit (Trafo HV side) OC relay using standard inverse characteristics
C.7
Siemens
Outgoing Aux Trafo Feeder 12kV Circuit (with newly proposed CT) OC relay using standard inverse characteristics
C.2
7SJ8031
7SJ8011
Siemens
7SJ8011
Siemens
13.3 MVA Tertiary winding OC relay using standard inverse characteristics
SIEMENS Energy Sector Projects/Engineering
Page 24 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.1
500 KVA Aux Transformer 12kV side Overcurrent Protection
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
400 /
5A
Plug Setting: Considering 1.2 times overloading, the overcurrent plug setting of protected object should be
120 % of rated current. = 500kVA x 1.2 ÷
(√3
x 12 kV)
= 28.87 A = 28.87 A
Corresponding secondary current
÷ 400
÷5
= 0.36 A
≈ 7.2% x In
= 0.36 A
pickup setting
= 0.5 to 20 A (steps 0.01) Recommneded Relay settings
= 8.0% x In
pickup setting
≈ 0.40 A ≈ 0.50 A
Hence selected pickup setting
(Note:Due to limitation of relay range ,we propose to select Pick up value 0.5 instead of 0.4) B.
Time Multiplier Setting: Fault Current contributed by
= 500kVA x 1 ÷
(√3 x 12 kV
transformer
= 522.96 A
Multiples of Fault Current
=
523.0
x 0.046)
÷( 400
/5
x 0.50)
= 13.07 A = 0.14
As per IEC Normal Inverse characteristic
÷ [(13.1)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.654 sec.
Operating time
= 2.65 sec.
at TMS = 1
Operating time for Auxiliary Trafo 12kV side
= 0.200
Since, 2.65 x TMS
= 0.200 sec. TMS = 0.075
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time C.
= 2.650
x 0.080
0.080 0.212 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
1207
51 Pickup
1.25A
0.50 to 20A
1208
51 Time Dial
0.080
0.05 to 3.2 sec
1211
51 IEC Curve SI** 1202 50-2 Pickup 15A** 1203 0 sec 50-2 Delay ** Note: Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Energy Sector Projects/Engineering
Range
Norm,Very,Ext,long 5.0A to 75A 0 to 60 sec
Page 25 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.1A
500 KVA Aux Transformer 12kV side Overcurrent Protection Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
100 /
50 /
5A
(Note:Due to limitation of relay range ,we propose 100/5A ratio. Currently both settings have been (provided. However, 800/400/5A CT settings will be removed after confirmation) A.
Plug Setting: Considering 1.2 times overloading, the overcurrent plug setting of protected object should be
120 % of rated current. = 500kVA x 1.2 ÷
(√3
x 12 kV)
= 28.87 A = 28.87 A
Corresponding secondary current
÷ 100
÷5
= 1.44 A
≈ 28.9% x In
= 1.44 A
pickup setting
= 0.5 to 20 A (steps 0.01) Recommneded Relay settings
= 29.0% x In
pickup setting
≈ 1.45 A ≈ 1.45 A
Hence selected pickup setting B.
Time Multiplier Setting: Fault Current contributed by
= 500kVA x 1 ÷
(√3 x 12 kV
transformer
= 522.96 A
Multiples of Fault Current
=
523.0
x 0.046)
÷( 100
/5
x 1.45)
= 18.03 A = 0.14
As per IEC Normal Inverse characteristic
÷ [(18.0)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.351 sec.
Operating time
= 2.35 sec.
at TMS = 1
Operating time for Auxiliary Trafo 12kV side
= 0.200
Since, 2.35 x TMS
= 0.200 sec. TMS = 0.085
Available setting
= 0.05 to 3.2s (steps 0.01s)
≈ ≈
Hence the selected TMS Operating time C.
= 2.350
x 0.090
0.090 0.212 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
100A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
100A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
1207
51 Pickup
1.45A
0.50 to 20A
1208
51 Time Dial
0.090
0.05 to 3.2 sec
NI
Norm,Very,Ext,long
28.7A** 0 sec
5.0A to 75A 0 to 60 sec
1211
51 IEC Curve 1217 50-3 Pickup 1218 50-3 Delay **1.1 x (Fault current/ CT ratio) = (522.9/100/5)*1.1=28.7 SIEMENS Energy Sector Projects/Engineering
Range
Page 26 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.2
12 kV Outgoing Feeder Overcurrent Protection (Settings at CT ratio 400/5 A)
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
400 /
Plug Setting: Considering max. current through the circuit
= 400 A
Feeder overloading considered as
= 400 A
Corresponding secondary current
= 400.0 A
5A
x 1.0
= 400 A ÷ 400
÷5
= 5.00 A
≈ 100.0% x In
= 5.00 A
Hence selected pickup setting
= 0.5 to 20 A (steps 0.01)
B.
Recommneded Relay settings
= 100.0% x In
Hence selected pickup setting
= 5.00 A
Time Multiplier Setting: Fault Current contributed by
=
40 MVA x 1 ÷
(√3 x 12 kV
transformer
= 10307.99 A
Multiples of Fault Current (I/I P)
= 10308
x 0.187)
÷( 400
/5
x 5.00)
= 25.77 A As per trip time characteristics according to IEC, tripping times do not decrease above I/I P > 20. = 0.14
\ As per IEC Normal Inverse characteristic
÷ [(20.00)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
= 0.200
Operating time for Out Going Feeder 12kV side For selectivity the tripping time choosen Since, 2.27 x TMS
= 0.200 sec. TMS = 0.088
Available setting
= 0.05 to 3.2s (steps 0.01s)
≈ ≈
Hence the selected TMS Operating time
C.
= 2.270
x 0.090
0.090 0.204 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
Range
1207
51 Pickup
5.00A
0.50 to 20A
1208
51 Time Dial
0.090
0.05 to 3.2 sec
1211
51 IEC Curve
NI
Norm,Very,Ext,long
1217
50-3 Pickup 50-3 Delay
30A** 0 sec
5.0A to 75A
1218
0 to 60 sec
**Note: As per KE Practice, since fault current is 2400A at primary side, therefore high set will be considered (fault current/CT ratio)=(2400/400/5)=30A at secondary side. SIEMENS Energy Sector Projects/Engineering
Page 27 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.2A
12 kV Outgoing Feeder Overcurrent Protection (Settings at CT ratio 800/5 A)
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
400 /
5A
Plug Setting: Considering max. current through the circuit
= 800 A
Feeder overloading considered as
= 800 A
Corresponding secondary current
= 800.0 A
x 1.0
= 800 A ÷ 800
÷5
= 5.00 A
≈ 100.0% x In
= 5.00 A
Hence selected pickup setting
= 0.5 to 20 A (steps 0.01)
B.
Recommneded Relay settings
= 100.0% x In
Hence selected pickup setting
= 5.00 A
Time Multiplier Setting: Fault Current contributed by
=
40 MVA x 1 ÷
(√3 x 12 kV x 0.187)
transformer
= 10307.99 A
Multiples of Fault Current (I/I P)
= 10308
÷( 800
/5
x 5.00)
= 12.88 A = 0.14
\ As per IEC Normal Inverse characteristic
÷ [(12.88)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.669 sec.
Operating time
= 2.67 sec.
at TMS = 1
= 0.200
Operating time for Out Going Feeder 12kV side For selectivity the tripping time choosen Since, 2.67 x TMS
= 0.200 sec. TMS = 0.075
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time C.
= 2.670
x 0.080
0.080 0.214 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
800A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
800A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
1207
51 Pickup
5.00A
0.50 to 20A
1208
51 Time Dial
0.080
0.05 to 3.2 sec
1211
51 IEC Curve
SI**
Norm,Very,Ext,long
15A** 0.1 sec
5.0A to 75A 0 to 60 sec
1202 1218 ** Note:
50-2 Pickup 50-2 Delay
Range
Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Energy Sector Projects/Engineering
Page 28 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.3
4 MVA, 12 kV Capacitor Feeder Overcurrent Protection
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
400 /
5A
=
4MVA
x 1.0 ÷
=
192.45 A
=
192.45 A
=
2.41 A
=
2.41 A
=
0.5 to 20 A(steps 0.01)
Recommneded Relay settings
=
49.0% x In
Hence selected pickup setting
=
2.45 A
Plug Setting: Feeder overloading considered as Corresponding secondary current Hence selected pickup setting
B.
Time Multiplier Setting: Fault Current contributed by
=
40 MVA
x1 ÷
÷ 400
÷5
≈ 48.1% x In
(√3 x 12 kV
x 0.187)
10307.99 A
transformer
=
Multiples of Fault Current
=
10308.0
=
52.59 A
=
0.14
As per IEC Normal Inverse characteristic
(√3 x 12 kV)
÷( 400 ÷ [(20.0)
/5 0.02
x 2.45)
-1]
(Refer 7SJ80 manual page 384) =
2.267 sec.
=
2.27 sec.
Operating time for Capacitor Feeder 12kV side
=
0.200
Since, 2.27 x TMS
=
0.200 sec.
=
0.088
Available setting
=
0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
0.090
Operating time
TMS
Operating time C.
= 2.270
x 0.090
at TMS = 1
0.204 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
1207
51 Pickup
2.5A**
0.50 to 20A
1208
51 Time Dial
0.080**
0.05 to 3.2 sec
1211
51 IEC Curve
SI**
Norm,Very,Ext,long
1202
50-2 Pickup 50-2 Delay
15A** 0 sec
5.0A to 75A 0 to 60 sec
1203
Value
Range
** Note: Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Page 29 + Energy Sector Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.4
4 MVA, 12 kV Capacitor Feeder Overcurrent Protection
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
Plug Setting: Feeder overloading considered as
=
5A
4MVA x 1.0 ÷
(√3 x 12 kV)
=
192.45 A
=
192.45 A
=
1.20 A
=
1.20 A
=
0.5 to 20 A(steps 0.01)
Recommneded Relay settings
=
25.0% x In
Hence selected pickup setting
=
1.25 A
Corresponding secondary current Hence selected pickup setting
B.
400 /
Time Multiplier Setting: Fault Current contributed by
=
40 MVA
x1 ÷
÷5
≈ 24.1% x In
(√3 x 12 kV
x 0.187)
10307.99 A
transformer
=
Multiples of Fault Current
=
10308.0
=
51.54 A
=
0.14
As per IEC Normal Inverse characteristic
÷ 800
÷( 800 ÷ [(20.0)
/5 0.02
x 1.25)
-1]
(Refer 7SJ80 manual page 384) =
2.267 sec.
=
2.27 sec.
Operating time for Capacitor Feeder 12kV side
=
0.200
Since, 2.27 x TMS
=
0.200 sec.
=
0.088
Available setting
=
0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
0.090
Operating time
TMS
Operating time
= 2.270
x 0.090
at TMS = 1
0.204 sec.
C. Settings recommended : General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
800A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
800A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
1207
51 Pickup
1.25A
0.50 to 20A
1208
51 Time Dial
0.090
0.05 to 3.2 sec
1211
51 IEC Curve
NI
Norm,Very,Ext,long
1217
50-3 Pickup 50-3 Delay
20.0A 0 sec
5.0A to 75A 0 to 60 sec
1218
**1.1 x (Fault current/ CT ratio) = 1.1 x (10459.24/800/5) = SIEMENS Energy Sector Projects/Engineering
Range
71.9A
Page 30 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.5
40 MVA Transformer, 12 kV Incomer Overcurrent Protection
A.
Relay Type:
= 7SJ8031-5EB00-1FB0
CT Ratio
=
2500 /
5A
Plug Setting: Considering 1.2 times overloading, the overcurrent plug setting of protected object should be
120
% of rated current.
Transformer LV winding rated current
40 MVA x 1.2 ÷
=
(√3 x 12 kV)
= 2309.40 A = 2309.4 A
Corresponding secondary current
÷ 2500
÷5
= 4.62 A
≈ 92.4% x In
= 4.62 A
Hence selected pickup setting
= 0.5 to 20 A(steps 0.01)
B.
Recommneded Relay settings
= 93.0% x In
Hence selected pickup setting
= 4.65 A
Time Multiplier Setting: Fault Current contributed by
=
40 MVA x 1 ÷
(√3 x 12 kV
transformer
= 10307.99 A
Multiples of Fault Current
=
x 0.187)
10308.0 ÷( 2500
/5
x 4.65)
= 4.43354 As per IEC Normal Inverse characteristic
0.14
=
÷ [(4.43)
0.02
-1]
(Refer 7SJ80 manual page 384) = 4.631 sec.
Operating time
= 4.63 sec. = 0.900
Operating time for transformer 12kV side
at TMS = 1 (as per Client)
= 0.900 Since, 4.63 x TMS
= 0.900 sec. TMS = 0.194
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 4.630
x 0.200
0.200 0.926 sec.
C. Settings recommended : General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
2500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
2500A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
Range
1207
51 Pickup
4.23A**
0.50 to 20A
1208
51 Time Dial
0.2
0.05 to 3.2 sec
1211
51 IEC Curve
SI**
Norm,Very,Ext,long
20.62A** 0.4 sec
5.0A to 75A 0 to 60 sec
1202 1203 ** Note:
50-2 Pickup 50-2 Delay
Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Page 31 + Energy Sector Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.6
40 MVA Transformer, 132 kV Trafo (HV side)Overcurrent Protection
A.
Relay Type:
= 7SJ8031-5EB00-1FB0
CT Ratio
=
200 /
1A
Plug Setting: Considering 1.2 times overloading, the overcurrent plug setting of protected object should be
120 % of rated current.
Transformer HV winding rated current
40 MVA
=
x 1.2 ÷
(√3 x 112 kV)
= 247.44 A Corresponding secondary current
= 247.44 A
÷ 200
÷1
Hence selected pickup setting
= 1.24 A
≈ 123.7% x In
= 0.1 to 4 A(steps 0.01)
B.
Recommneded Relay settings
= 124.0% x In
Hence selected pickup setting
≈ 1.24 A
Time Multiplier Setting: Fault Current contributed by
=
40 MVA x 1 ÷
(√3
a transformer at 132kV side
= 1104.43 A
Multiples of Fault Current
=
1104.43
=
4.45 A
=
0.14
As per IEC Normal Inverse characteristic
x 112 kV
x 0.187)
÷( 200
/1
÷ [(4.45)
0.02
x 1.24)
-1]
(Refer 7SJ80 manual page 384) = 4.617 sec.
Operating time
= 4.62 sec. = 1.200
Operating time for transformer 132kV side Since, 4.62 x TMS
at TMS = 1 (as per Client)
= 1.200 sec. TMS = 0.2597
Available settings
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time C.
= 4.620
x 0.260
0.260 1.201 sec.
Settings recommended :
General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
200A
0205
CT Rated Secondary Current
1A
0217
IE-CT Rated Secondary Current
200A
0218
IE-CT Rated Secondary Current
1A
OverCurrent Protection Address
Function
Value
Range
1207
51 Pickup
1.24A
0.10 to 4A
1208
51 Time Dial
0.260
0.05 to 3.2 sec
1211
51 IEC Curve
NI
Norm,Very,Ext,long
1217 1218
50-3 Pickup 50-3 Delay
6.16A** 0 sec
5.0A to 75A 0 to 60 sec
**1.1 x (Fault current/ CT ratio) = 1.1 x (1120/200/1) =6.16 SIEMENS Page 32 + Energy Sector Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS C.7
13.3 MVA Tertiary Winding Overcurrent Protection
A.
Relay Type:
= 7SJ8011-5EB20-1FA0
CT Ratio
=
Plug Setting: Transformer tertiary winding rated current
=
500 /
5A
13 MVA x 1.0 ÷
(√3 x 12 kV)
= 639.90 A = 640 / 1.732
=
Corresponding secondary current
= 370
÷ 500
Hence selected pickup setting
= 3.70 A
≈
1.00 A
370 X
÷5
74.0% x In
= 0.5 to 20 A(steps 0.01)
B.
Recommneded Relay settings
= 74.0% x In
Hence selected pickup setting
≈ 3.70 A
Time Multiplier Setting: Fault Current
= 5.1KA (Given as per manufacturer)
Multiples of Fault Current
=
5100.00
=
13.78 A
=
0.14
As per IEC Normal Inverse characteristic
÷( 500 ÷ [(13.78)
/5 0.02
x 3.70)
-1]
(Refer 7SJ80 manual page 384) = 2.599 sec.
Operating time
= 2.60 sec.
at TMS = 1
= 0.500
for selectivity the tripping time chosen Since, 2.60 x TMS
= 0.500 sec. TMS = 0.1923
Available settings
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time C.
= 2.600
x 0.200
0.200 0.520 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
500A
0218
IE-CT Rated Secondary Current
5A
OverCurrent Protection Address
Function
Value
1207
51 Pickup
3.7A
0.50 to 20A
1208
51 Time Dial
0.2
0.05 to 3.2 sec
1211
51 IEC Curve
NI
Norm,Very,Ext,long
56.1A** 0 sec**
5.0A to 75A 0 to 60 sec
1217 1218 ** Note:
50-3 Pickup 50-3 Delay
Range
1.1 x (Fault current/ CT ratio) = 1.1 x (5100/500/5) = 56.1A Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Page 33 + Energy Sector Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS Results Summary
Operating Time
PMS
TMS
0.2 sec.
2.5A**
0.080
C.1A 500 KVA Aux Transformer 12kV Circuit(with newly proposed CT) 0.2 sec. OC relay using standard inverse characteristics
1.45 A
0.090
0.2 sec.
5.00A
0.090
0.2 sec.
5.00A
0.080
0.2 sec.
4.85A
0.090
0.2sec.
2.45A
0.090
0.9 sec.
4.23A**
0.2
1.2 sec.
1.24A
0.270
0.5 sec.
3.7A
0.2
C.1
500 KVA Aux Transformer 12kV Circuit OC relay using standard inverse characteristics
C.2
Outgoing Cable Feeder 12kV Circuit (400/5A) OC relay using standard inverse characteristics
C.2A Outgoing Cable Feeder 12kV Circuit (800/5A) OC relay using standard inverse characteristics C.3
Outgoing Capacitor Feeder 12kV Circuit(400/5A) OC relay using standard inverse characteristics
C.4
Outgoing Capacitor Feeder 12kV Circuit(800/5A) OC relay using standard inverse characteristics
C.5
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV side) OC relay using standard inverse characteristics
C.6
40 MVA Transformer 132 kV Circuit (Trafo HV side) OC relay using standard inverse characteristics
C.7
13.3 MVA Tertiary Winding Overcurrent Protection OC relay using standard inverse characteristics
SIEMENS Energy Sector Projects/Engineering
Page 34 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
EARTH FAULT PROTECTION
SIEMENS Energy Sector Projects/Engineering
Page 35 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.
BACK UP EARTH FAULT PROTECTION
D.1
Outgoing Aux Trafo Feeder 12kV Circuit EF relay using standard inverse characteristics
D.1A
7SJ8031
Siemens
7SJ8031
Siemens
7SJ8031
Siemens
7SJ8011
Siemens
7SJ8011
Siemens
7SJ8011
Siemens
7SJ8011
Siemens
40 MVA Transformer 132 kV Circuit(Trafo HV Side) EF relay using standard inverse characteristics
D.7
Siemens
40 MVA Transformer 12kV Circuit Neutral Protection Witout NGR (LV Side) EF protection using standard inverse characteristics
D.6
7SJ8031
40 MVA Transformer 12kV Circuit Neutral Protection with NGR (LV Side) EF protection using standard inverse characteristics
D.5A
Siemens
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV Side) without NGR EF relay using standard inverse characteristics
D.5
7SJ8031
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV Side) with NGR EF relay using standard inverse characteristics
D.4A
Siemens
Outgoing Capacitor Feeder 12kV Circuit(800/5A) EF relay using standard inverse characteristics
D.4
7SJ8031
Outgoing Capacitor Feeder 12kV Circuit (400/5A) EF relay using standard inverse characteristics
D.3A
Siemens
Outgoing Cable Feeder 12kV Circuit (800/5A) EF relay using standard Definite characteristics
D.3
7SJ8031
Outgoing Cable Feeder 12kV Circuit (400/5A) EF relay using standard Definite characteristics
D.2A
Siemens
Outgoing Aux Trafo Feeder 12kV Circuit(with newly proposed CT) EF relay using standard inverse characteristics
D.2
7SJ8031
13.3 MVA, Tertiary Windig TEF protection using standard inverse characteristics
SIEMENS Energy Sector T&D Projects/Engineering
Page 36 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
D.8
40 MVA Transformer 132 kV Circuit Neutral Protection (HV Side) EF protection using standard inverse characteristics
D.9
7SJ8011
Siemens
40 MVA Transformer EF for NGR EF protection using standard inverse characteristics
P14NB16A7C0500A
Shanghai xinguang
SIEMENS Energy Sector T&D Projects/Engineering
Page 37 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.1
500 KVA Aux Transformer 12kV side Earth Fault Protection
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
Plug Setting: Min. fault as percentage of rated current
=
Aux Trafo. rated current
=
800 /
400 /
5A
20% 500kVA x 0.2 ÷
(√3
x 12 kV)
4.81 A = 4.8 A
Corresponding secondary current
÷ 400
÷5
= 0.06 A
≈
= 0.06 A
pickup setting
1.2% x In
= 0.25 to 20 A (steps 0.01) = 0.25 A
Hence Pickup setting
(Note:Due to limitation of Relay range ,we propose to select Pick up value 0.25 instead of 0.06) B.
Time Multiplier Setting: Fault current of a transformer at 12kV side
= 1500A
(equal to NGR Rating) = 1500A
Multiples of Fault Current
÷( 400
/5
x 0.25)
= 75.00 A \ As per IEC Normal Inverse characteristic
0.14
=
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
= 0.200
For Selectivity Operating time considered Since, 2.27 x TMS
= 0.200 sec. TMS = 0.088
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
x 0.090
0.090 0.204 sec.
C. Settings recommended : General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Function
Value
1307
51N Pickup
0.25A
0.250 to 20A
1308
51N Time Dial
0.09A
0.05 to 3.2 sec
1311
51N IEC Curve
SI**
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
15.0 A 0 sec
0.25 to 175A
Address
50N-2 Delay
Range
0 to 60 sec
** Note: Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Energy Sector T&D Projects/Engineering
Page 38 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.1A
500 KVA Aux Transformer 12kV side Earth Fault Protection Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
100 /
50 /
5A
(Note:Due to limitation of relay range ,we propose 100/5A ratio. Currently both settings have been (provided. However, 800/400/5A CT settings will be removed after confirmation)
A.
Plug Setting: Min. fault as percentage of rated current
=
Aux Trafo. rated current
=
20% 500kVA
x 0.2 ÷
(√3
x 12 kV)
4.81 A = 4.8 A
Corresponding secondary current
÷ 100
÷5
= 0.24 A = 0.24 A
pickup setting
≈
4.8% x In
= 0.25 to 20 A (steps 0.01)
B.
Hence Pickup setting
= 0.25 A
Time Multiplier Setting: Fault current of a transformer at 12kV side
= 1500A
(equal to NGR Rating) = 1500A
Multiples of Fault Current
÷( 100
/5
x 0.25)
= 240.00 A \ As per IEC Normal Inverse characteristic
0.14
=
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec. For Selectivity Operating time considered
= 0.200
Since, 2.27 x TMS
= 0.200 sec.
at TMS = 1
TMS = 0.088 Available setting
= 0.05 to 3.2s (steps 0.01s)
≈ ≈
Hence the selected TMS Operating time
= 2.270
x 0.090
0.090 0.204 sec.
C. Settings recommended : General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
100A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
100A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
Range
1307
51N Pickup
0.25A
0.250 to 20A
1308
51N Time Dial
0.090
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
66A** 0 sec
0.25 to 175A
50N-2 Delay
0 to 60 sec
**1.1 x (Fault current/ CT ratio) = 1.1 x (1200/100/5) =66A Note:As per client's comment,Definite time curve can also be consider.The operating time t=0.2 sec will be considered for Definite time. SIEMENS Energy Sector T&D Projects/Engineering
Page 39 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.2
12 kV Outgoing Cable Feeder Earth Fault Protection (Settings at CT ratio 400/5 A)
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
Plug Setting: Min. fault as percentage of rated current
=
20%
Feeder rated current
= 400 A
Corresponding secondary current
= 80.0 A
400 /
x 0.2
5A
= 80 A ÷ 400
÷5
= 1.00 A
≈
= 1.00 A
Hence selected pickup setting
20.0% x In
= 0.25 to 20 A (steps 0.01)
B.
Recommneded Relay settings
= 20.0% x In
Hence selected pickup setting
= 1.00 A
Time Multiplier Setting: Fault current contributed
=
40 MVA
x1 ÷
(√3
by transformer
= 10307.99 A
Multiples of Fault Current
= 10307.99
x 12 kV
x 0.187)
÷( 400
/5
x 1.00)
= 128.85 A \ As per IEC Normal Inverse characteristic
0.14
=
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
= 0.200
For Selectivity Operating time considered Since, 2.27 x TMS
= 0.200 sec. TMS = 0.088
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
x 0.090
0.090 0.204 sec.
C. Settings recommended : General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
1307
51N Pickup
1.00 A
0.250 to 20A
1308
51N Time Dial
0.090
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
30A** 0 sec
0.25 to 175A
50N-2 Delay
Range
0 to 60 sec
**Note: As per KE Practice, since fault current is 2400A at primary side, therefore high set will be considered (fault current/CT ratio)=(2400/400/5)=30A at secondary side. SIEMENS Page 40 + Energy Sector T&D Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.2A
12 kV Outgoing Cable Feeder Earth Fault Protection (Settings at CT ratio 800/5 A)
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
Plug Setting: Min. fault as percentage of rated current
=
20%
Feeder rated current
= 800 A
Corresponding secondary current
= 160.0 A
400 /
5A
x 0.2
160 A
= ÷ 800
÷5
= 1.00 A
≈
= 1.00 A
Hence selected pickup setting
20.0% x In
= 0.25 to 20 A (steps 0.01)
B.
Recommneded Relay settings
= 20.0% x In
Hence selected pickup setting
= 1.00 A
Time Multiplier Setting: Fault Current contributed by
=
40 MVA
x1 ÷
(√3
transformer
= 10307.99 A
Multiples of Fault Current
= 10308.0
x 12 kV
x 0.187)
÷( 800
/5
x 1.00)
= 64.42 A \ As per IEC Normal Inverse characteristic
=
0.14
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
= 0.200
For Selectivity Operating time considered Since, 2.27 x TMS
= 0.200 sec. TMS = 0.088
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
x 0.090
0.090 0.204 sec.
C. Settings recommended : General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
800A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
800A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
Range
1307
51N Pickup
0.5A**
0.250 to 20A
1308
51N Time Dial
0.080**
0.05 to 3.2 sec
1311
51N IEC Curve
SI**
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
2.77A** 0.1 sec**
0.25 to 175A
50N-2 Delay
0 to 60 sec
** Note: Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Page 41 + Energy Sector T&D Projects/Engineering
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.3
4 MVA, 12 kV Capacitor Feeder Earth Fault Protection
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
Min. fault as percentage of rated current
=
20%
Feeder rated current
=
4MVA
400 /
5A
Plug Setting: x 0.2 ÷
(√3
x 12 kV)
= 38.49 A = 38.49 A
Corresponding secondary current
÷ 400
÷5
= 0.48 A
≈ 9.6% x In
= 0.48 A
Hence selected pickup setting
= 0.25 to 20 A(steps 0.01)
B.
Recommneded Relay settings
= 10.0% x In
Hence selected pickup setting
= 0.50 A
Time Multiplier Setting: Fault Current contributed by
=
transformer
= 10307.99 A
Multiples of Fault Current
= 10307.99
40 MVA
x1 ÷
(√3 x 12 kV
÷( 400
/5
x 0.187)
x 0.50)
= 257.70 A \ As per IEC Normal Inverse characteristic
0.14
=
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
= 0.200
Operating time for 12kV Capacitor Feeder Since, 2.27 x TMS
= 0.200 sec. TMS = 0.088
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
x 0.090
0.090 0.204 sec.
C. Settings recommended : General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
1307
51N Pickup
0.25A
0.250 to 20A
1308
51N Time Dial
0.09A
0.05 to 3.2 sec
1311
51N IEC Curve
1317 1318
50N-2 Pickup 50N-2 Delay
Range
SI
Norm,Very,Ext,long
2.77A 0 sec
0.25 to 175A 0 to 60 sec
** Note: Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Energy Sector T&D Projects/Engineering
Page 42 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.3A
4 MVA, 12 kV Capacitor Feeder Earth Fault Protection
A.
Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
=
800 /
Min. fault as percentage of rated current
=
20%
Feeder rated current
=
4MVA
400 /
5A
Plug Setting: x 0.2 ÷
(√3
x 12 kV)
= 38.49 A = 38.49 A
Corresponding secondary current
÷ 800
÷5
= 0.24 A
≈ 4.8% x In
= 0.24 A
Hence selected pickup setting
= 0.25 to 20 A(steps 0.01)
B.
Recommneded Relay settings
= 5.0% x In
Hence selected pickup setting
= 0.25 A
Time Multiplier Setting: Fault Current contributed by
=
transformer
= 10307.99 A
Multiples of Fault Current
= 10307.99
40 MVA
x1 ÷
(√3 x 12 kV
÷( 800
/5
x 0.187)
x 0.25)
= 257.70 A \ As per IEC Normal Inverse characteristic
0.14
=
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
= 0.200
Operating time for 12kV Capacitor Feeder Since, 2.27 x TMS
= 0.200 sec. = 0.088
TMS Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
x 0.090
0.090 0.204 sec.
C. Settings recommended : General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
400A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
400A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
1307
51N Pickup
0.25 A
0.250 to 20A
1308
51N Time Dial
0.09
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
2.77 A 0 sec
0.25 to 175A
50N-2 Delay
**1.1 x (Fault current/ CT ratio) = 1.1 x (10459.24/800/5) = SIEMENS Energy Sector T&D Projects/Engineering
Range
0 to 60 sec
72A
Page 43 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.4
40 MVA Transformer, 12 kV Incomer Earth Fault Protection(Trafo. LV side) With NGR
A.
Relay Type:
=
CT Ratio
=
Plug Setting: Min. fault as percentage of rated current
2500 /
5A
20%
= =
40 MVA x 0.2 ÷
=
384.90 A
=
384.9 A
=
0.77 A
=
0.77 A
=
0.25 to 20 A (steps 0.01)
Recommneded Relay settings
=
16.0% x In
Hence selected pickup setting
≈
0.80 A
Time Multiplier Setting: Fault current of a transformer at 12kV side
=
1.5 kA
=
1500
=
3.75 A
=
0.14
Transformer LV winding rated current Corresponding secondary current Hence selected pickup setting
B.
7SJ8031-5EB00-1FB0
(√3
x 12 kV)
÷ 2500
≈
÷5
15.4% x In
(As per client comment)
(equal to NGR Rating) Multiples of Fault Current As per IEC Normal Inverse characteristic
÷( 2500 ÷ [(3.75)
/5 0.02
x 0.80)
-1]
(Refer 7SJ80 manual page 384) Operating time Operating time for transformer 12 kV side Since, 5.23 x TMS
=
5.226 sec.
=
5.23 sec.
=
1.500
=
1.500 sec.
at TMS = 1
=
0.287
Available settings
=
0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
0.290
TMS
Operating time
= 5.230
x 0.290
1.517 sec.
Settings recommended : General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
2500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
2500A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Value
Function
1307
51N Pickup
1308
51N Time Dial
1311
51N IEC Curve
1317 1318
50N-2 Pickup 50N-2 Delay
Range
0.55A**
0.250 to 20A
0.09**
0.05 to 3.2 sec
SI**
Norm,Very,Ext,long
2.77A** 0.4 sec
0.25 to 175A 0 to 60 sec
** Note: Values has been modified as per site (GSM/GSP) recommendation. SIEMENS Energy Sector T&D Projects/Engineering
Page 44 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.4A
A.
40 MVA Transformer, 12 kV Incomer Earth Fault Protection(Trafo. LV side) Without NGR Relay Type:
=
CT Ratio
=
2500 /
=
40 MVA
=
384.90 A
=
384.9 A
=
0.77 A
=
0.77 A
=
0.25 to 20 A (steps 0.01)
Recommneded Relay settings
=
16.0% x In
Hence selected pickup setting
≈ 0.80 A
Time Multiplier Setting: Fault current of a transformer at 12kV side
=
40 MVA
=
10307.99 A
=
10308.0
=
25.77 A
=
0.14
Plug Setting: Min. fault as percentage of rated current
5A
20%
=
Transformer LV winding rated current Corresponding secondary current Hence selected pickup setting
B.
7SJ8031-5EB00-1FB0
Multiples of Fault Current As per IEC Normal Inverse characteristic
x 0.2 ÷
(√3
x 12 kV)
÷ 2500
≈
÷5
15.4% x In
x1 ÷
(√3
÷( 2500
x 12 kV
/5
÷ [(20.00)
0.02
x 0.187)
x 0.80)
-1]
(Refer 7SJ80 manual page 384) =
2.267 sec.
=
2.27 sec.
=
0.900
=
0.900 sec.
=
0.396
Available settings
=
0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
0.400
Operating time
Operating time for transformer 12 kV side Since, 2.27 x TMS TMS
Operating time
= 2.270
x 0.400
at TMS = 1
0.908 sec.
Settings recommended : General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
2500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
2500A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Value
Function
Range
1307
51N Pickup
0.8A
0.250 to 20A
1308
51N Time Dial
0.4
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
23.0A** 0.4 sec
0.25 to 175A
50N-2 Delay
**1.1 x (Fault current/ CT ratio) = 1.1 x (10459.24/2500/5) = SIEMENS Energy Sector T&D Projects/Engineering
0 to 60 sec
23A
Page 45 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.5
40 MVA Transformer, 12 kV Circuit Neutral Protection(LV Side) with NGR = 7SJ8031-5EB00-1FB0 Relay Type: =
CT Ratio : A.
2500 /
5A
Plug Setting : Min. fault as percentage of rated current
20%
=
Transformer LV winding rated current
40 MVA x 0.2 ÷
=
(√3
x 12 kV)
= 384.90 A Corresponding secondary current
= 384.90 A
Hence selected pickup setting
≈ 0.77 ≈ 0.77 A
÷ 2500
÷5
≈ 15.4% x In
= 0.25 to 20 A (steps 0.01)
B.
Recommneded Relay settings
= 16.0% x In
Hence selected pickup setting
≈ 0.80 A
Time Multiplier Setting: Fault current of a transformer at 12kV side
=
1500.0 A (As per client comment)
(equal to NGR Rating) = 1500.0
Multiples of Fault Current
÷( 2500
/5
x 0.80)
= 3.75 A As per IEC Normal Inverse characteristic
0.14
=
÷ [(3.8)
0.02
-1]
(Refer 7SJ80 manual page 384) = 5.226 sec.
Operating time
= 5.23 sec. Operating time of the Incomer Relay 12 kV side
= 1.517
Operating time for Trafo 12kV EF Since, 5.23 x TMS
= 1.517
at TMS = 1
= 1.517 sec. TMS = 0.290
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 5.230
x 0.290
0.290 1.517 sec.
C.
Settings recommended General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
2500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
2500A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
Range 0.250 to 20A
1307
51N Pickup
0.8A
1308
51N Time Dial
0.29
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
2.64A** 0.4 sec
0.25 to 175A
50N-2 Delay
**1.1 x (Fault current/ CT ratio) = 1.1 x (1200/2500/5) = SIEMENS Energy Sector T&D Projects/Engineering
0 to 60 sec
2.64A
Page 46 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.5A
A.
40 MVA Transformer, 12 kV Circuit Neutral Protection(LV Side) Without NGR Relay Type:
= 7SJ8031-5EB00-1FB0
CT Ratio :
=
2500 /
5A
Plug Setting : Min. fault as percentage of rated current
20%
=
Transformer LV winding rated current
40 MVA
=
x 0.2 ÷
(√3
x 12 kV)
= 384.90 A = 384.90 A
Corresponding secondary current
÷ 2500
÷5
≈ 0.77 ≈ 0.77 A
Hence selected pickup setting
≈
15.4% x In
= 0.25 to 20 A (steps 0.01)
B.
Recommneded Relay settings
= 16.0% x In
Hence selected pickup setting
≈ 0.80 A
Time Multiplier Setting: Fault current of a transformer
=
40 MVA
x1 ÷
(√3
at 12kV side
= 10291.45 A
Multiples of Fault Current
= 10291.4
x 12 kV
x 0.187)
÷( 2500
/5
x 0.80)
= 25.73 A As per IEC Normal Inverse characteristic
0.14
=
÷ [(20.0)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec. Operating time of the Incomer Relay 12 kV side
= 1.000
Operating time for Trafo 12kV EF Since, 2.27 x TMS
= 1.000
at TMS = 1
= 1.000 sec. TMS = 0.441
Available setting
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
x 0.450
0.450 1.022 sec.
C.
Settings recommended General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
2500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
2500A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
Range 0.250 to 20A
1307
51N Pickup
0.8A
1308
51N Time Dial
0.45
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
23A** 0.4 sec
0.25 to 175A
50N-2 Delay
**1.1 x (Fault current/ CT ratio) = 1.1 x (10459.24/2500/5) = SIEMENS Energy Sector T&D Projects/Engineering
0 to 60 sec
23A
Page 47 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.6
40 MVA Transformer, 132 kV Trafo(HV Side) Earth Fault Protection
A.
B.
Relay Type:
= 7SJ8011-5EB20-1FA0
CT Ratio
=
200 /
Plug Setting: Min. fault as percentage of rated current
=
20%
Transformer HV winding rated current
=
40 MVA
1A
x 0.2 ÷
(√3
=
41.17 A
Corresponding secondary current
=
41.17 A 0.21 A
Hence selected pickup setting
≈ ≈ =
0.05 to 4 A (steps 0.01)
x112 kV)
÷ 200
÷1
≈ 20.6% x In
0.21 A
Recommneded Relay settings
= 20.6% x In
Hence selected pickup setting
≈ 0.21 A
Time Multiplier Setting: = 40 MVA x 1 ÷
Fault Current contributed by
(√3
x 112 kV
x 0.187)
÷( 200
/1
= 1102.46 A
a transformer at 132kV side
= 1102.5 As per IEC Normal Inverse characteristic
=
26.78 A
=
0.14
÷ [(20.00)
0.02
x 0.21)
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at TMS = 1
For selectivity to earth fault protection, tripping time is choosen Since, 2.27 x TMS
= 1.00
Available settings
= 0.05 to 3.2s (steps 0.01s)
Hence the selected TMS
≈ ≈
Operating time
= 2.270
= 1.00 sec.
x 0.450
0.441
≈
0.450
1.022 sec.
C. Settings recommended : General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
200A
0205
CT Rated Secondary Current
1A
0217
IE-CT Rated Secondary Current
200A
0218
IE-CT Rated Secondary Current
1A
Earthfault Protection Address
Function
Value
1307
51N Pickup
0.21A
0.05 to 4A
1308
51N Time Dial
0.45
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
35 A Blocked,infinity
0.05 to 35A
50N-2 Delay
**1.1 x (Fault current/ CT ratio) = 1.1 x (1102.5/200/1) = SIEMENS Page 48 + Energy Sector T&D Projects/Engineering
Range
0 to 60 sec
6.1A EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.7
13.3 MVA Tertiary Winding Earth Fault Protection
A.
Relay Type:
= 7SJ8011-5EB20-1FA0
CT Ratio :
=
500 /
5A
Plug Setting : Min. fault as percentage of rated current
= 20%
Transformer tertiary winding rated current
= 13 MVA
÷
(√3 x 12 kV)
= 639.90 A = 640 / 1.732
0.20 A
= 370 X
= 74.00 A Corresponding secondary current
= 74.00 A
÷ 500
Hence selected pickup setting
= 0.74 A
≈ 14.8% x In
÷5
= 0.25 to 20 A(steps 0.01)
B.
Recommneded Relay settings
= 15.0% x In
Hence selected pickup setting
≈ 0.75 A
Time Multiplier Setting: Fault current
= 5.1KA
Multiples of Fault Current
= 5100.0
÷( 500
/5
x 0.75)
= 68.00 A = 0.14
As per IEC Normal Inverse characteristic
÷ [(20)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec. Tripping time choosen
= 0.500
Since, 2.27 x TMS
= 0.500 sec.
at TMS = 1
TMS = 0.220 Available setting
= 0.05 to 3.2s (steps 0.01s)
≈ ≈
Hence the selected TMS Operating time C.
= 2.270
x 0.230
0.230 0.522 sec.
Settings recommended :
General Data Function
Value
0214
Address
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
500A
0205
CT Rated Secondary Current
5A
0217
IE-CT Rated Secondary Current
500A
0218
IE-CT Rated Secondary Current
5A
Earthfault Protection Address
Function
Value
1307
51N Pickup
0.75A
0.250 to 20A
1308
51N Time Dial
0.23
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
56.1A** 0
0.25 to 175A
50N-2 Delay 56.1A **1.1 x (Fault current/ CT ratio) = 1.1 x (5100/500/5) = SIEMENS Page 49 + Energy Sector T&D Projects/Engineering
Range
0 to 60 sec
EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.8
40 MVA Transformer 132kV Circuit Neutral Protection(HV Side)
A.
Relay Type:
= 7SJ8011-5EB20-1FA0
CT Ratio :
=
200 /
1A
Plug Setting : Min. fault as percentage of rated current
= 20%
Transformer HV winding rated current
= 40 MVA
x 0.2 ÷ (√3
x112 kV)
= 41.17 A
B.
Corresponding secondary current
= 41.17 A
÷ 200
Hence selected pickup setting
≈ 0.21 A ≈ 0.21 A
≈ 20.6% x In
Recommneded Relay settings
= 20.6% x In
Hence selected pickup setting
≈ 0.21 A
TMS Setting : Fault Current contributed by
40 MVA x 1 ÷
=
÷1
(√3 x 112 kV x 0.187)
a transformer at 132kV side
= 1102.46 A
Multiples of fault current
= 1102.5
÷( 200
/1
x 0.21)
= 26.78 As per IEC Normal Inverse characteristic
0.14 ÷
=
[(20.00)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.27 sec. = 2.27 sec.
Operating time Hence operating time for EF Since, 2.27 x TMS TMS
at TMS = 1
=
1.100
=
1.100
=
1.100 sec.
=
0.485
sec.
Available settings
= 0.05 to 3.2s (steps 0.01s)
Selected TMS setting
≈ ≈
Revised operating time
= 2.267
x 0.490
0.490 1.111 sec.
C. Settings recommended : General Data Address
Function
Value
0214
Rated Frequency
50HZ
0209
Phase Sequence
L1,L2,L3
0204
CT Rated Primary Current
200A
0205
CT Rated Secondary Current
1A
0217
IE-CT Rated Secondary Current
200A
0218
IE-CT Rated Secondary Current
1A
Earthfault Protection Address
Function
Value
Range
1307
51N Pickup
0.21A
0.05 to 4A
1308
51N Time Dial
0.49
0.05 to 3.2 sec
1311
51N IEC Curve
NI
Norm,Very,Ext,long
1317 1318
50N-2 Pickup
35.0 A Blocked,Infinity
0.05 to 35A
50N-2 Delay
**1.1 x (Fault current/ CT ratio) = 1.1 x (1118.64/200/1) = SIEMENS Energy Sector T&D Projects/Engineering
0 to 60 sec
6.1A
Page 50 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS D.9
A.
40 MVA Transformer, EF Relay for NGR Relay Type:
= P14NB16A7C0500A
CT Ratio :
=
100 /
5A
Plug Setting : Min. fault as percentage of rated current Considering max. current through the circuit
20%
=
= 50 A
x 0.2
= 10 A Corresponding secondary current
= 10 A
÷ 100
Hence selected pickup setting
≈ 0.50 ≈ 0.10 A
≈
÷5
= 0.05 to 4 x In (steps 0.01x In ) = 0.10 x In B.
Time Multiplier Setting:
Fault current of NGR
= 1500.0 A
Multiples of Fault Current
= 1500.0
÷( 100
/5
x 0.10)
= 750.00 A As per IEC Normal Inverse characteristic
0.14
=
÷ [(20.0)
0.02
-1]
(Refer 7SJ80 manual page 384) = 2.267 sec.
Operating time
= 2.27 sec.
at T = 1
Operating time of the Incomer Relay 12 kV side
= 1.500
+ 0.25
Operating time for NGR EF
= 1.750
Since, 2.27 x T
= 1.750 sec. T = 0.771
Available setting
= 0.025 to 1.2s (steps 0.005)
Hence the selected T
≈ ≈
Operating time C.
= 2.270
x 0.780
0.780 1.771 sec.
Settings recommended Function IN1>1 Current IN1>1 Time IN1>1 Function
SIEMENS Energy Sector T&D Projects/Engineering
Value
Range
0.10 x In
0.05 to 4 x In
0.78
0.025 to 1.2 sec
NI Page 51 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
Operating Time
PMS
TMS
0.2 sec.
0.5A**
0.080**
0.2 sec.
0.25 A
0.090
0.2 sec.
1.0A
0.090
0.2 sec.
1.0A
0.090
0.2 sec.
0.5A**
0.08**
0.2 sec.
0.25 A
0.090
1.5 sec.
0.55A**
0.09**
0.9 sec.
0.8A
0.4
0.8A
0.24
1.0 sec.
0.8A
0.45
1.0 sec.
0.21A
0.45
TEF protection using standard inverse characteristics
0.5 sec.
0.75A
0.23
40 MVA Transformer 132 kV Circuit Neutral Protection (HV Side)
1.1 sec.
0.21A
0.49
1.8 sec.
0.10 A
0.780
Results Summary
D.1
Outgoing Aux Trafo Feeder 12kV Circuit EF relay using standard inverse characteristics
D.1A
Outgoing Aux Trafo Feeder 12kV Circuit(with newly proposed CT) EF relay using standard inverse characteristics
D.2
Outgoing Cable Feeder 12kV Circuit (400/5A) EF relay using standard Definite characteristics
D.2A
Outgoing Cable Feeder 12kV Circuit (800/5A) EF relay using standard Definite characteristics
D.3
Outgoing Capacitor Feeder 12kV Circuit (400/5A) EF relay using standard inverse characteristics
D.3A
Outgoing Capacitor Feeder 12kV Circuit(800/5A) EF relay using standard inverse characteristics
D.4
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV Side) with NGR EF relay using standard inverse characteristics
D.4A
40 MVA Transformer 12kV Incomer Circuit(Trafo. LV Side) without NGR EF relay using standard inverse characteristics
D.5
40 MVA Transformer 12kV Circuit Neutral Protection with NGR (LV Side) EF protection using standard inverse characteristics
D.5A
40 MVA Transformer 12kV Circuit Neutral Protection Witout NGR (LV Side) EF protection using standard inverse characteristics
D.6
40 MVA Transformer 132 kV Circuit(Trafo HV Side) EF relay using standard inverse characteristics
D.7
D.8
1.5 sec.
13.3 MVA, Tertiary Windig
EF protection using standard inverse characteristics D.9
40 MVA Transformer EF for NGR EF protection using standard inverse characteristics
SIEMENS Energy Sector T&D Projects/Engineering
Page 52 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
AVR Relay
SIEMENS Energy Sector Projects/Engineering
Page 53 + EM-TS PROJECTS/A5175/Relay settings
SIEMENS
E.
E.1
AVR Relay
AVR Relay
SIEMENS Energy Sector Projects/Engineering
Tapcon 230 Expert
MR
Page 54 + EM-TS PROJECTS/A5175/Relay settings
SIEMENS
AVR Setting Calculation Data: I ). Relay type
= Tapcon 230 Expert
II ). Transformer Rating
= 40
MVA
III ). Voltage at maximum tap
Umax
= 151.80
kV
IV ). Voltage at minimum tap
Umin
= 112.20
kV
V ). Transformation Ratio
= 132 /12
VI ). Tap changing Range
= + 15 %
VII ).Vector Group
= YNyn0(d11)
to
- 15 %
Setting Parameters
Function
Value
Range
Desired Voltage
100V
Bandwith
5%
0.5 to 9 %
Delay time T1
40 sec
0 to 60 sec
Control Reponse Time
Linear
Linear / Integral
Under Voltage
90%
60 to 100 %
Under Voltage Delay time U <
10 sec
0 to 20 sec
Over Voltage
110%
100 to 140 %
EM-TS PROJEC
SIEMENS Energy Sector Projects/Engineering
Page 55 + EM-TS PROJECTS/A5175/Relay settings
SIEMENS
Capacitor Feeder Un Balance Protection
SIEMENS Energy Sector Projects/Engineering
Page 56 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
F.1
2x4 MVA, 12 kV Capacitor Bank Unbalance Protection Relay Type
= 7SJ8031-5EB00-1FB0
CT Ratio
= 20 / 5A
, 20 VA, Cl : 10P10
Capacitor Data: ▪
Rated Power
= 8
MVAr
▪
Rated Voltage
= 12.00
kV
▪
Rated Current
= 384.90
A
▪
Frequency
= 50
Hz
f
General:
As per existing KE practice the unbalance setting considered For Alarm and Trip
C.
Neutral unbalance current setting considered for Alarm
=
2A
A
(Secondary Current)
Unbalance time delay setting considered for alarm
=
5.000
sec
Neutral unbalance current setting considered for Trip
=
3.7A
A
Unbalance time delay setting considered for Trip
=
0.300
sec
(Secondary Current)
Settings recommended :
Address
Function
Value
Range
1204
51 Pickup
2A
0.10 to 4A
1205
51 Time Dial
5 sec
0 to 60 sec
1202
50-2 Pickup
3.7A
0.10 to 35A
50-2 Delay
0.3 sec
0 to 60 sec
1203
SIEMENS Energy Sector Projects/Engineering
Page 57 + EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
Annexure
SIEMENS Energy Sector Projects/Engineering
Page 58 + EM-TS PROJECTS /A5175/Relay Settings
132/12kV KEPZ AIS S/S
IDMT Overcurrent Curves (HV & LV Overcurrent with outgoing feeders(Aux Trafo,Capacitor,Cable) 1000
100
10
Incomer (Trafo LV)
t[s]
Outgoing(Aux Trafo) HV side
1
Outgoing(Capacitor) Outgoing(Cable 400/5 Tap)
1
Outgoing(Cable 800/5 Tap) Transformer Dmage Curve
0.1
0.01 10
100
1000
10000 I[A]
100000
1000000
10000000
132/12kV KEPZ AIS S/S
IDMT Earth Fault Curves (HV & LV Earthfault with outgoing feeders(Aux trafo,Capacitor,Cable ) 1000
100
10 t[s]
Incomer With NGR Outgoing(Aux Trafo) HV Side
1
Outgoing(Capacitor) Incomer Without NGR Outgoing(Cable 400/5 Tap)
Cable 400/5
Outgoing(Cable 800/5 Tap)
Cable 800/5
0.1
0.01 10
100
1000
10000 I[A]
100000
1000000
10000000
132/12kV KEPZ AISS/S
IDMT Earth Fault Curves (HV & LV Neutral with outgoing feeders(Aux trafo,Capacitor,Cable) 1000
100
10 t[s]
Outgoing(Aux Trafo) Outgoing(Cable 400/5 Tap) Outgoing (Cable 800/5 Tap)
1
Outgoing(Capacitor) LV Neutral with NGR LV Neutral Without NGR
Cable 800/5
Cable 400/5
HV Neutral
0.1
0.01 10
100
1000
10000 I[A]
100000
1000000
10000000
⇓
⁄
⁄
#22418∋& #22418∋& ∋:%∋26 #5 016∋& 4∋57∃/+55+10 4∋37+4∋& 016 #22418∋& /1&+(; #0& 4∋57∃/+6 (14 +0(14/#6+10 10.; 016∋ 6∗∋ #22418#. 5∗#.. 016 4∋.+∋8∋ 6∗∋ %1064#%614 (41/ ∗+5 4∋52105+∃+.+6; (14 %1/2.+#0%∋ 61 %1064#%6 4∋37+4∋/∋065 &4#9+0) 52∋%+(+%#6+105 # 5∗∋∋65
⇓
⇓