g Estimating Gas Turbine Performance The following is a method for estimating gas turbine performance using performance curves and site data (i.e., elevation, ambient temperature, inlet and exhaust pressure drops, and the type of fuel). Both full load and part load performance calculations are described and illustrated. Typical examples are provided for package power plants. Performance curves are based on the ISO standard (59°F, 60% relative humidity and 14.7 psia). Theses curves do not include the water or steam injection for NOx control due to the many different NOx levels offered. However, the effect of a known water or steam flow can be calculated separately per the dilutent effects curves. This procedure should be used only for the approximation of performance at site conditions and not for performance guarantees. Performance guarantees for this proposal are shown in the “Performance Specifications” section. The

performance curves included are to illustrate the calculation procedure and do not reflect current ratings. Performance curves applicable to the equipment offered in this proposal are listed under “Turbine and Generator Performance Curves” in the “Engineering Data” Section. Nomenclature D

=

differential; i.e. DP is pressure drop

fa

=

inlet DP factor for output

fb

=

exhaust DP factor for output

fc

=

compressor inlet temperature factor for output

fd

=

compressor inlet temperature factor for exhaust flow

fe

=

compressor inlet temperature factor for heat rate

ff

=

inlet DP factor for heat rate

fg

=

exhaust DP factor for heat rate

fh

=

humidity factor for output

fi

=

humidity factor for heat rate

HC

=

heat consumption (fuel consumption in Btu/h)

HR

=

heat rate (Btu/kWh)

KW

=

power output (kW)

P

=

barometric pressure (psia)

Pc

=

effective pressure (psia) at the inlet flange of a package power plant

Tx

=

exhaust gas temperature (°F)

Reference GTS–111D Estimating Gas Turbine Performance

page 1

Wx

=

exhaust flow (lb/h)

EFF

=

thermal efficiency (%)

(LHV) =

based on fuel lower heating value

Subscripts s, i, o s

denotes at site conditions

i

denotes at ISO conditions

o

denotes at site altitude, actual inlet and exhaust DP’s, and compressor inlet conditions of 59°F @ 60% RH.

I. Full Load Performance A. Method 1.

Output (KWs) = (KWi) x (Ps/14.7) x fa x fb x fc x fh

2.

Heat Rate (HRs) = (HRi) x fe x ff x fg x fi Note: Altitude has no effect on heat rate

3.

Heat Consumption (HCs) = (KWs) x (HRs)

4.

Exhaust Temperature (Tx) Read from appropriate curve. Add temperature increase for additional inlet and/or exhaust pressure drops.

5

Exhaust Flow (Wxs) = (Wxi) x (Pc/14.7) x fd Where Pc = Ps – (0.0361 x additional DP (inches of H2O) at inlet)

B. Notes 1.

Round off calculations as follows: Output – To nearest 10 kW or maximum of 4 significant figures Heat Rate – To nearest 10 Btu/kWh Heat Consumption – To nearest 0.1 x 106 Btu/h or maximum of 4 significant figures Exhaust Temperature – To nearest degree F Exhaust Flow – To four significant figures (lb/h)

2.

The ratio Ps/14.7 can be read directly from the altitude correction curve 416HA662

C. Sample Full Load Calculation Package Power Plant – MS7001(EA) Simple Cycle Model PG7111(EA) with an air–cooled generator.

Reference GTS–111D Estimating Gas Turbine Performance

page 2

Site Conditions:

1.

2.

Altitude

= 600 ft

Barometric Pressure Ps

= 14.39 psia (from Curve 416HA662)

Compressor Inlet Temperature

= 90°F

Inlet DP

= 2.5’ H2O (included in rating)

Exhaust DP

= 10” H2O (5.5” H2O is included in rating)

Fuel

= Distillate Oi1

Mode

= Base Load

Design Conditions (ISO) from Curve 499HA733 Output KWi

= 82100 kW

Heat Rate HRi

= 10560 Btu/kWh (LHV)

Exhaust Flow Wxi

= 2358 x 103 lb/h

Calculation of factors.

The ratings for the package power plant include a standard inlet and exhaust pressure drop as stated with the ratings. Therefore the pressure drops used to calculate fa, fb, ff, fg, Pc, and exhaust temperature increase are the pressure drops in excess of the standard pressure drops. The resulting performance decrease effect of additional pressure drop is subtracted from unity to obtain the output multiplication factor. The heat rate percentage effect is added to unity to obtain the heat rate multiplier for additional pressure drops. Output :

f a + 1.0 1 + 0.9953 f b + 1.0 * 0.42 x 4.5 100 4 (curve 499HA733 with additional 4.5” H2 O) f c + 0.890 (from Curve 499HA734) f h + 0.9982 (from Curve 498HA697)

Heat Rate :

f e + 1.025 (from Curve 499HA734) f f + 1.0 1 + 1.0047 f g + 1.0 ) 0.42 x 4.5 100 4 (curve 499HA733 with additional 4.5” H2 O) f i + 1.0048 (from Curve 498HA697)

ǒ

ǒ

Ǔ

Ǔ

Reference GTS–111D Estimating Gas Turbine Performance

page 3

Exhaust Flow :

3.

P c + 14.39 psia * 0 + 14.39 psia f d + 0.930 (from Curve 499HA734)

Calculation of Full Load Conditions at Site: Output KW s + 82100 x 14.39 x 1.0 x 0.9953 x 0.890 x 0.9982 14.7 + 71063 or 71060kW Heat Rate HR s + 10560 x 1.025 x 1.0 x 1.0047 x 1.0048 + 10927 or 10930 BtuńkWh (LHV) Heat Consumption HC s + 71060 x 10930 + 776.7 x 10 6 Btuńh (LHV)

Exhaust temperature is calculated by adding the temperature increase due to pressure drops to the value read from Curve 499HA734: T x + 1006 ) 1.9 (0 ) 4.5) F 4 T x + 1008.1 or 1008 F Exhaust Flow + 2358 x 10 3 x 14.39 x .930 14.7 + 2146.7 x 10 3 or 2147 x 10 3 Ibńh

II. Part Load Performance Part load output, heat rate and heat consumption are calculated in a similar manner as base load using the part load heat consumption curve. Before using the output % off the heat consumption curve, all part load performance must be referenced to 59°F site performance kWo. A. Method 1.

At site barometric pressure with site inlet and exhaust pressure drops and at 59°F compressor inlet temperature, calculate the following base load performance parameters: Output, kWo Heat rate, HRo Heat consumption, HCo This data then becomes the corrected values on which to base the part load calculations.

2.

Reference GTS–111D Estimating Gas Turbine Performance

Calculate percentage of load:

page 4

% load = required load/kWo 3.

From the applicable performance curve, at the percent of load calculated from (2) above and at the compressor inlet temperature, read the percent of design heat consumption. HCs = HCo x % design heat consumption.

4.

Heat rate at required load: HRs = HCs ÷ kWs

5.

Exhaust flow and temperature are calculated in an analogous manner as base load using corrected design outputs as shown above, and the Effects of Modulated Inlet Guide Vanes Curve at the appropriate ambient. The extreme right hand point of each ambient curve on the Modulated Inlet Guide Vane Curve represents the full open IGV position, the knee point in each curve represents the closed IGV position, Note that this curve is for combined cycle machines only. Simple cycle machines, which are not normally concerned with part load Exhaust conditions, operated on a different schedule and can not be calculated using this curve.

B. Sample Part Load Calculation The following sample part load calculations are for the MS7001(EA) simple cycle package power plant used previously. Site conditions: Altitude Barometric pressure Compressor inlet temperature Relative Humidity Inlet DP Exhaust DP Fuel Load required 1.

= 600 ft = 14.39 psia = 90°F = 60%RH = 2.5” H2O (included in rating) = 10” H2O (5.5” H2O is included in rating) = Distillate Oil = 75 percent base load

Calculation of site performance at full load and 59°F at 60%RH: KWo = KWi x (14.39/14.7) x fa x fb KWo = 821000 x 0.9789 x 1.0 x 0.9953 = 79990 kW HRo = HRi x ff x fg HRo = 10560 x 1.0 x 1.0047 = 10610 Btu/kWh (LHV) HCo = KWo x HRo Reference GTS–111D Estimating Gas Turbine Performance

page 5

HCo = 79990 x 10610 = 848.7 x 106 Btu/h (LHV) 2.

Calculation of site performance for 90°F @ 60%RH: Site output (base load) = KWo x fc x fh = 79990 x 0.891 x 0.9983 = 71150 kW At 75% base load, required load = 71150 x 0.75 = 53360 kW % load = 53360/79990 = 66.7%

3.

From Curve 499HA733 at 66.7% design load and 90°F, % design heat consumption = 71% Part load, site heat consumption, HCs = HCo x % design heat rate HCs = 848.7 x .71 = 602.6 x 106 Btu/h (LHV)

4.

Site heat rate HRs = HCs ÷ kWs HRs = 602.6 x 106 ÷ 53360 = 11290 x Btu/kWh (LHV)

5.

Entering the Modulated Inlet Guide Vane Effects Curve (516HA129) at the 66.7% output calculated in Step 2 and, for the 90°F ambient curve; Exh Temp. = 990°F Wexh % design = 75.5% Wexh = Wi x % design Wexh = 2358 x .755 = 1780 x 103 lb/h

Performance With Water or Steam Injection The amount of steam or water injection required to meet a given NOx emission level is not available from a curve because of the many variables impacting this value. In fact, the exact flow is typically not finalized until the field Emissions Compliance Testing. However, given a specific flow value, the resulting effect on output and Heat Rate can be determined using the Injection Effects Curves. For example, taking the “dry” Output and Heat Rate Performance calculated from Example I and, assuming GE has reported (for the specific conditons given) an estimated steam flow to meet 65 ppmvd @ 15% O2 NOx of 42590 lb/h (11.83 pps); The resulting output and Heat Rate would be:

Reference GTS–111D Estimating Gas Turbine Performance

page 6

KW = 71060 x (1 + 0.059) (from curve 499HA899A) = 75250 KW HR = 10930 x (1 – .0275) (from curve 499HA900A) = 10630 Btu/Kw–h (LHV)

Reference GTS–111D Estimating Gas Turbine Performance

page 7

SI and Metric Units Conversion The following is a list of conversion factors most commonly used for gas turbine performance calculations.

Conversion Factors To Convert atm atm bars bars Btu/h Btu/h Btu/hph Btu/lb °F °C °C ft3/min ft3/min gal/mln in. of mercury in. of water (at 4°C) in. of water (at 4°C) J kg kg/cm2 kg/m3 kW lb/in2 l/min l/min scf W

Reference GTS–111D Estimating Gas Turbine Performance

page 8

To kg/cm2 lb/in2 atm lb/in2 kcal/h kJ/h kJ/kWh kJ/kg °R °F °K l/s m3/min l/s kg/cm2

Multiply By 1.0333 14.7 0.9869 14.5 0.2520 1.0548 1.4148 2.326 °F + 459.7 (°C x 9/5) + 32 °C + 273.2 0.4720 0.02832 0.06308 0.03453

kg/cm2

0.00254

lb/in2 Btu lb lb/in2 lb/ft3 hp Pa ft3/s gal/s Nm3 Btu/h

0.03613 9.478 x 10–4 2.205 14.22 0.06243 1.341 6894.8 5.886 x 10–4 0.004403 0.0268 3.4129

GENERAL ELECTRIC MODEL PG7111(EA) GAS TURBINE ESTIMATED PERFORMANCE – CONFIGURATION: NATURAL GAS & DISTILLATE Compressor Inlet Conditions 59 F (15.0 C), 60% Rel. Humidity Atmospheric Pressure 14.7 psia (1.013 bar) FUEL DESIGN OUTPUT DESIGN HEAT RATE (LHV) DESIGN HEAT CONS (LHV) X10–6 DESIGN EXHAUST FLOW X10–3 MODE: BASE LOAD

kW Btu (kJ)/kWh Btu (kJ)/h lb/h (kg)/h

NATURAL GAS 83500 10480 (11060) 875.1 (923.5) 2351 (1066)

DISTILLATE 82100 10560 (11140) 867.0 (914.6) 2358 (1070) PPB 061088

NOTES: 1. Altitude correction on curve 416HA662 REV A 2. Ambient temperature correction on curve 499HA734 REV A 3. Effect of modulated IGV’s on exhaust flow and temp. on curve 516HA129 4. Air cooled generator 7A6 5. Humidity correction on curve 498HA697 REV B – all performance calculated with specific humidity of .0064 or less so as not to exceed 100% relative humidity. 6. Plant performance is measured at the generator terminals and includes allowances for excitation power, shaft driven auxiliaries, and 2.5 in. H2O (6.2 mbar) inlet and 5.5 in. H2O (13.7 mbar) exhaust pressure drops. 7. Additional pressure drop effects: %Effect on Output Heat Rate 4 in. H2O (10.0 mbar) inlet –1.42 0.45 4 in. H2O (10.0 mbar) exhaust –0.42 0.42

Effect on Exhaust Temp. 1.9 F (1.1 C) 1.9 F (1.1 C)

HEAT CONSUMPTION – PERCENT DESIGN

130 0F

120 59 F

110 100 120 F 90 80 70 60 50 40 30 20 10 0

10

DATE: 10/17/89 DA JAQUEWAY

20

30 40 50 60 70 80 90 100 110 120 130 GENERATOR OUTPUT – PERCENT DESIGN

499HA733 REV A

Reference GTS–111D Estimating Gas Turbine Performance

page 9

GENERAL ELECTRIC MODEL PG7111(EA) GAS TURBINE

EXHAUST TEMPERATURE (DEG. F)

Effect of Compressor Inlet Temperature on Output, Heat Rate, Heat Consumption, Exhaust Flow And Exhaust Temperature at 100% Speed FUEL: NATURAL GAS & DISTILLATE OIL DESIGN VALUES ON CURVE 499HA733 REV A DESIGN MODE: BASE LOAD 1040 1030 1020 1010 1000 990 980 970 960 950 940 130 125 120 PERCENT DESIGN

115 110 HEAT RATE

105 100 95 90

EXHAUST FLOW

85

HEAT CONS.

80 OUTPUT

75 70 0

10

20

30

40

50

60

70

80

90

100

110

120

COMPRESSOR INLET TEMPERATURE (DEG. F) DATE 10/17/89 DA JAQUEWAY

Reference GTS–111D Estimating Gas Turbine Performance

499HA734 REV A

page 10

GENERAL ELECTRIC MODEL PG7111(EA) GAS TURBINE Effect of Modulated Inlet Guide Vanes on Exhaust Flow and Temperature As a Function of Output and Compressor Inlet Temperature.

EXHAUST FLOW – PERCENT DESIGN

EXHAUST TEMPERATURE (DEG. F)

FUEL: NATURAL GAS & DISTILLATE OIL DESIGN VALUES ON CURVE 499HA733 REV A DESIGN MODE: BASE LOAD 1100 1050 1000 950 900

0F

850 800 750

30 F 59 F 90 F

700 650

120 F

600 550 500 115 110 105 100 95 90 0F

85 30 F

80 59 F

75 90 F

70 120 F

65 0

10

20

30 40 50 60 70 80 90 100 110 120 130 GENERATOR OUTPUT – PERCENT

DATE 10/17/89 DA JAQUEWAY

516HA129

Reference GTS–111D Estimating Gas Turbine Performance

page 11

GENERAL ELECTRIC GAS TURBINE ALTITUDE CORRECTION FACTOR ALTITUDE VS ATMOSPHERIC PRESSURE AND ALTITUDE VS CORRECTION FACTOR FOR GAS TURBINE OUTPUT AND FUEL CONSUMPTION NOTES: 1. Heat Rate and Thermal Efficiency are not affected by altitude. 2. Correction Factor = P(atm)/14.7 15.5

1

15

0.95 CORRECTION FACTOR

14.5

0.9

14

0.85

13.5

0.8

13

0.75

12.5

0.7

ATMOSPHERIC PRESSURE

12

0.65

11.5

0.6

11

0.55

10.5

0.5 0

1

2

3

4

5

6

7

8

9

ALTITUDE – THOUSAND FEET 416HA662 REV A

4/24/90 F.J. BROOKS

Reference GTS–111D Estimating Gas Turbine Performance

page 12

GENERAL ELECTRIC MS6001, MS7001 AND MS9001 GAS TURBINES CORRECTIONS TO OUTPUT AND HEAT RATE FOR NON–ISO SPECIFIC HUMIDITY CONDITIONS For operation at base load on exhaust temperature control curve 1.01 1.009 ISO SPECIFIC HUMIDITY 0.0064 lb. water vapor/lb. dry air

1.008 1.007 1.006

HEAT RATE

1.005

CORRECTION FACTOR

1.004 1.003 1.002 1.001 1 0.999 POWER OUTPUT

0.998 0.997 0.996 0.995 0.994 0.000

0.005 0.010 0.015 0.020 0.025 0.030 SPECIFIC HUMIDITY (lb. water vapor/lb. dry air)

10/10/89 DA JAQUEWAY

0.03 5

498HA697 REV B

Reference GTS–111D Estimating Gas Turbine Performance

page 13

GE MODEL PG7001(EA) GAS TURBINE EFFECT OF STEAM INJECTION ON OUTPUT BASE LOAD – NATURAL GAS / DISTILLATE

12 11 100F

PERCENT INCREASE IN OUTPUT

10 9 59F

8 45F

7 0F

6 5 4 3 2 CURVE 499HA899A KH CONWAY 4/14/89

1 0 0

2

4

6

8

10

12

14

STEAM INJECTION – LB/S

Reference GTS–111D Estimating Gas Turbine Performance

page 14

16

18

20

GE MODEL PG7001(EA) GAS TURBINE EFFECT OF STEAM INJECTION ON HEAT RATE BASE LOAD – NATURAL GAS / DISTILLATE

6.0 5.5 5.0 100F

PERCENT DECREASE IN HEAT RATE

4.5 4.0 59F

3.5

45F

3.0

0F

2.5 2.0 1.5 1.0 CURVE 499HA900A KH CONWAY 4/14/89

0.5 0. 0

2

4

6

8

10

12

14

16

18

20

STEAM INJECTION – LB/S

Reference GTS–111D Estimating Gas Turbine Performance

page 15