Loading documents preview...
EEP 4113 Fault in Electric Power System
Dr. Mohd Taufiq Ishak
Module Outline
1. Introduction 2. Symmetrical/ Balanced Faults 3. Unsymmetrical/ Unbalanced Faults
EEP 4113 – Advanced Power Systems - Fault in Power System
2
Introduction • Analysis types: power flow - evaluate normal operating conditions fault analysis - evaluate abnormal operating conditions
• Fault analysis is also known as short circuit study. • In normal condition, a power system is operating at balanced 3-phase AC system. • Whenever a fault occurred, the bus voltages and flow of current in the network elements get affected. • Faults can cause over current at certain point of power system. EEP 4113 – Advanced Power Systems - Fault in Power System
3
Introduction • Faults occur in power system due to: insulation failure in the equipments flashover of lines initiated by lightning mechanical damage to conductors and towers accidental faulty operation
• Faults can be classified as Shunt faults and Series faults. Series faults are not so severe as compared to shunt faults.
EEP 4113 – Advanced Power Systems - Fault in Power System
4
Introduction • Fault types: Symmetrical/ balanced faults (3-phase) Unsymmetrical/ unbalanced faults single-line to ground and double-line to ground line-to-line faults
• The relative frequency of occurrence of various faults in the order of severity are as follows: balanced 3-phase fault double line to ground fault line to line fault single line to ground fault
5% 10% 15% 70%
EEP 4113 – Advanced Power Systems - Fault in Power System
5
Introduction • When a fault occurs in a power system, bus voltages reduces and large current flows in the lines. • This may cause damage to the equipments. • The magnitude of the fault currents depends on: the impedance of the network the internal impedances of the generators the resistance of the fault (arc resistance)
EEP 4113 – Advanced Power Systems - Fault in Power System
6
Introduction • Faulty section should be isolated from the rest of the network immediately. • This can be achieved by providing relays and circuit breakers. • The protective relays sense the occurrence of the fault and send signals to circuit breakers to open the circuit under faulty condition. • Proper relay setting and relay coordination are required for effective protection.
EEP 4113 – Advanced Power Systems - Fault in Power System
7
Introduction • The main purposes of fault analysis: specifying ratings for circuit breakers and fuses protective relay settings specifying the impedance of transformers and generators
• Network impedances are governed by generator impedances transformer connections and impedances transmission line impedances Load impedances grounding connections and resistances EEP 4113 – Advanced Power Systems - Fault in Power System
8
Subtransient and transient • Generator behavior is divided into three periods sub-transient period, lasting for the first few cycles transient period, covering a relatively longer time steady state period
• Sub-transient reactances, XG = Xd” determine the interrupting capacity of HV circuit breakers determine the operation timing of the protective relay system for high-voltage networks
• Transient reactances, XG = Xd’ determine the interrupting capacity of MV circuit breakers determine the operation timing of the protective relay system for medium-voltage networks EEP 4113 – Advanced Power Systems - Fault in Power System
9
Symmetrical Three-phase Fault • The balanced fault is a phenomenon where the three phases are short circuited simultaneously. • Since the network is balanced, it is solve on per phase basis. • A fault represents a structural network change equivalent to the addition of an impedance at the place of the fault if the fault impedance is zero, the fault is referred to as a bolted fault or solid fault
• For small networks, it can be solved by the Thévenin’s method, and for large networks, it is solved by the Bus Impedance Matrix method. EEP 4113 – Advanced Power Systems - Fault in Power System
10
Balanced Fault – Thévenin’s Method • Assumptions: generators are modeled as an emf behind the subtransient or transient reactance network resistances are neglected shunt capacitances are neglected system is considered as having no-load
• The fault is simulated by switching a fault impedance at the faulted bus. • The change in the network voltages is equivalent to adding the pre-fault bus voltage with all other sources short circuited. EEP 4113 – Advanced Power Systems - Fault in Power System
11
Balanced Fault – Thévenin’s Method • Example 1:
G1
G2
EEP 4113 – Advanced Power Systems - Fault in Power System
12
Balanced Fault – Thévenin’s Method • 3-phase fault with fault impedance, Zf = j0.16 on bus 3.
EEP 4113 – Advanced Power Systems - Fault in Power System
13
Balanced Fault – Thévenin’s Method • Convert the impedances of Z12, Z23, and Z31 from to Y.
EEP 4113 – Advanced Power Systems - Fault in Power System
14
Balanced Fault – Thévenin’s Method • Combine the parallel branches to get the Thévenin’s impedance at faulted bus, i.e. Z33.
EEP 4113 – Advanced Power Systems - Fault in Power System
15
Balanced Fault – Thévenin’s Method • Combine the parallel branches to get the Thévenin’s impedance at faulted bus, i.e. Z33. V3 (0) I3 (F ) Z 33 Z f V1 (0) V2 (0) V3 (0) 1.0 pu
V3 (0) 1.0 I3 (F ) j 2.0 Z 33 Z f j 0.34 j 0.16
EEP 4113 – Advanced Power Systems - Fault in Power System
16
Balanced Fault – Thévenin’s Method • The current flow for the two generators: j 0.6 I G1 I 3 ( F ) j1.2 pu j 0.4 j 0.6 IG2
j 0.4 I 3 ( F ) j 0.8 pu j 0.4 j 0.6
• Bus voltage changes, V1 0 ( j 0.2)( j1.2) 0.24 pu V2 0 ( j 0.4)( j 0.8) 0.32 pu V3 ( j 0.16)( j 2) 1.0 0.68 pu EEP 4113 – Advanced Power Systems - Fault in Power System
17
Balanced Fault – Thévenin’s Method • The fault voltages: V1 ( F ) V1 (0) V1 1.0 0.24 0.76 pu V2 ( F ) V2 (0) V2 1.0 0.32 0.68 pu V3 ( F ) V3 (0) V3 1.0 0.68 0.32 pu
• The short circuit currents in the lines: V1 ( F ) V2 ( F ) 0.76 0.68 I12 ( F ) j 0.1 pu z12 j 0.8 V1 ( F ) V3 ( F ) 0.76 0.32 I13 ( F ) j1.1 pu z13 j 0.4 V2 ( F ) V3 ( F ) 0.68 0.32 I 23 ( F ) j 0.9 pu z23 j 0.4 EEP 4113 – Advanced Power Systems - Fault in Power System
18
Balanced Fault – Thévenin’s Method • For more accurate solutions use the pre-fault bus voltages which can be obtained from the results of a power flow solution include loads - to preserve linearity, convert loads to constant impedance model Thévenin’s theorem allows the changes in the bus voltages to be obtained bus voltages are obtained by superposition of the prefault voltages and the changes in the bus voltages current in each branch can be solved
EEP 4113 – Advanced Power Systems - Fault in Power System
19
Balanced Fault – Short Circuit Capacity • Measures the electrical strength of the bus • Stated in MVA. • Determines the dimension of busbars and the interrupting capacity of circuit breakers • Definition: SCC 3VLL,k (0) I k ( F ) x 103
where VLL ,k (0) is the line-to-line voltage at bus k in kV I k (F ) is the faulted current in A EEP 4113 – Advanced Power Systems - Fault in Power System
20
Balanced Fault – Short Circuit Capacity • In per unit (pu), I k ( F ) pu
Vk (0) X kk
• The approximate formula for SCC or short-circuit MVA: SCC
SB MVA X kk
where SB is the base MVA and Xkk is the p.u. reactance to the point of fault. EEP 4113 – Advanced Power Systems - Fault in Power System
21
Balanced Fault – Short Circuit Capacity • Example 2 of SCC calculation: Z 33 j 0.34 S B 100MVA S B 100MVA SCC3 294MVA Z 33 0.34
EEP 4113 – Advanced Power Systems - Fault in Power System
22
Balanced Fault – Bus Impedance Matrix • Network reduction by Thévenin’s method is not efficient and not applicable to large networks. • Consider the following system: operating under balanced conditions each generator represented by a constant emf behind a proper reactance (Xd, Xd’, or Xd”) lines represented by their equivalent model EEP 4113 – Advanced Power Systems - Fault in Power System
23
Balanced Fault – Bus Impedance Matrix • Place the pre-fault voltages into a vector: V1 (0) Vbus (0) Vk (0) Vn (0)
• Replace the loads by a constant impedance model using the pre-fault bus voltages: Z iL
Vi (0)
2
S L*
EEP 4113 – Advanced Power Systems - Fault in Power System
24
Balanced Fault – Bus Impedance Matrix • The change in the network voltage caused by the fault is equivalent to placing a fault voltage at the faulted bus with all the other sources short-circuited:
EEP 4113 – Advanced Power Systems - Fault in Power System
25
Balanced Fault – Bus Impedance Matrix • Using superposition, the fault voltages are calculated from the pre-fault voltages by adding the change in bus voltages due to the fault: Vbus ( F ) Vbus (0) Vbus
where
V1 Vbus Vk Vn EEP 4113 – Advanced Power Systems - Fault in Power System
26
Balanced Fault – Bus Impedance Matrix • The injected bus currents: I bus YbusVbus
• Current entering every bus is zero except at the faulted bus. Since the current is leaving the bus k, it is taken as negative current. 0 Y11 I k ( F ) Yk1 0 Yn1
Y1k
Ykk
Ynk
Y1n V1 Ykn Vk Ynn Vn
=
EEP 4113 – Advanced Power Systems - Fault in Power System
I bus ( F ) YbusVbus
27
Balanced Fault – Bus Impedance Matrix • Solving for Vbus, Vbus ZbusI bus (F )
where Zbus = Y-1bus is the bus impedance matrix. Vbus ( F ) Vbus (0) ZbusI bus ( F )
V1 ( F ) V1 (0) Z11 Vk ( F ) Vk (0) Z k1 Vn ( F ) Vn (0) Z n1
Z1k
Z kk
Z nk
Z1n 0 Z kn I k ( F ) Z nn 0
EEP 4113 – Advanced Power Systems - Fault in Power System
28
Balanced Fault – Bus Impedance Matrix • Since there is only one nonzero element in the current vector, Vk ( F ) Vk (0) Z kk I k ( F )
• From the Thévenin’s circuit, Vk ( F ) Z f I k ( F )
• Combining the both equations, the fault current becomes, Vk (0) Ik (F ) Z kk Z f
EEP 4113 – Advanced Power Systems - Fault in Power System
29
Balanced Fault – Bus Impedance Matrix • For ith equation, Vi ( F ) Vi (0) Zik I k ( F )
• Substituting Ik(F), Z ik Vi ( F ) Vi (0) Vk (0) Z kk Z f
• For fault current in the line, I ij ( F )
Vi ( F ) V j ( F ) zij
Small letter of z, it is taken from the original network and not from the Zbus!
EEP 4113 – Advanced Power Systems - Fault in Power System
30
Balanced Fault – Bus Impedance Matrix • Example 3: Using the previous example, Zf = j0.16 pu. The bus admittance matrix, j 2.5 j8.75 j1.25 Ybus j1.25 j 6.25 j 2.5 j 2.5 j 2.5 j5.0
The impedance matrix, j 0.16 1 Z bus Ybus j 0.08 j 0.12
j 0.08 j 0.24 j 0.16
j 0.12 j 0.16 j 0.34
EEP 4113 – Advanced Power Systems - Fault in Power System
31
Balanced Fault – Bus Impedance Matrix • The fault current, V3 (0) 1.0 I3 (F ) j 2.0 pu Z 33 Z f j 0.34 j 0.16
• The bus voltages during fault, V1 ( F ) V1 (0) Z13I 3 ( F ) 1.0 ( j 0.12)( j 2.0) 0.76 pu V2 ( F ) V2 (0) Z 23I 3 ( F ) 1.0 ( j 0.16)( j 2.0) 0.68 pu V3 ( F ) V3 (0) Z 33I 3 ( F ) 1.0 ( j 0.34)( j 2.0) 0.32 pu
EEP 4113 – Advanced Power Systems - Fault in Power System
32
Balanced Fault – Bus Impedance Matrix • The fault currents in the lines, V1 ( F ) V2 ( F ) 0.76 0.68 I12 ( F ) j 0.1 pu z12 j 0.8 V1 ( F ) V3 ( F ) 0.76 0.32 I13 ( F ) j1.1 pu z13 j 0.4 I 23 ( F )
V2 ( F ) V3 ( F ) 0.68 0.32 j 0.9 pu z23 j 0.4
EEP 4113 – Advanced Power Systems - Fault in Power System
33
Unsymmetrical Fault • Unsymmetrical faults are analyzed using symmetrical components. • The symmetrical components method allows unbalanced three-phase phasor quantities to be replaced by the sum of three separate but balanced symmetrical components. • The balanced 3-phase phasors consists of: positive sequence negative sequence zero sequence EEP 4113 – Advanced Power Systems - Fault in Power System
34
Unsymmetrical Fault – Sym. Components • Representation of symmetrical components: I c1
I b2 120°
120° 120°
I a0 0 I bI 0
120°
I a1
I b1
120° 120°
I a2
c
I c2
+ve Sequence A balanced 3-phase system in the normal a-b-c sequence
-ve Sequence A balanced 3-phase system of reversed sequence a-c-b sequence
Zero Sequence Three phasors equal in magnitude and phase revolving in the +ve phase rotation
EEP 4113 – Advanced Power Systems - Fault in Power System
35
Unsymmetrical Fault – Sym. Components • Positive sequence phasors: I a1 I a1 0 I a1 I b1 I a1 240 a 2 I a1 I c1 I a1 120 aI a1
• Operator a identities a 1120 0.5 j 0.866 a 2 1240 0.5 j 0.866 a 3 1360 1 j 0 1 a a2 0 EEP 4113 – Advanced Power Systems - Fault in Power System
36
Unsymmetrical Fault – Sym. Components • Negative sequence phasors: I a2 I a2 0 I a2 I b2 I a2 120 aI a2 I c2 I a2 240 a 2 I a2
• Zero sequence phasors I a0 I a0 0 I a0 I b0 I a0 0 I a0 I c0 I a0 0 I a0
EEP 4113 – Advanced Power Systems - Fault in Power System
37
Unsymmetrical Fault – Sym. Components • Relating unbalanced phasors to symmetrical components: I a I a0 I a1 I a2 I a0 I a1 I a2 I b I b0 I b1 I b2 I a0 a 2 I a1 aI a2 I c I c0 I c1 I c2 I a0 aI a1 a 2 I a2
• In matrix notation I a 1 1 I 1 a 2 b I c 1 a
1 I a0 1 a Ia a 2 I a2
EEP 4113 – Advanced Power Systems - Fault in Power System
38
Unsymmetrical Fault – Sym. Components • [A] is known as the symmetrical components transformation matrix: 1 1 A 1 a 2 1 a
I abc AI a012
1 a a 2
• Solving for the symmetrical components leads to: I a012 A1I abc
1 1 1 1 A 1 a 3 1 a 2
1 1 * 2 a A 3 a
EEP 4113 – Advanced Power Systems - Fault in Power System
39
Unsymmetrical Fault – Sym. Components • In component form, the calculation for symmetrical components are: 1 I a I b I c 3 1 I a1 I a aI b a 2 I c 3 1 2 I a I a a 2 I b aI c 3
I a0
• Similar expressions exist for voltages: V abc AVa012 Va012 A1V abc EEP 4113 – Advanced Power Systems - Fault in Power System
40
Unsymmetrical Fault – Sym. Components • The apparent power (S) may also be expressed in terms of symmetrical components: S (3 ) V S (3 )
abcT
I
abc*
012 T AVa
012 * AI a
012T Va
T
A
* 012* A Ia
Since AT A, then AT A* 3
S (3 ) 3 V
012T
I
012*
0 0* 3Va I a
1 1* 3Va I a
2 2* 3Va I a
EEP 4113 – Advanced Power Systems - Fault in Power System
41
Unsymmetrical Fault – Sym. Components • Example 4: Obtain the symmetrical components of a set of unbalanced currents: I a 1.625, I b 1.0180, I c 0.9132
Solution: 1.625 1.0180 0.9132 0.4596.5 3 2 1 . 6 25 a ( 1 . 0 180 ) a (0.9132) 1 Ia 0.94 0.1 3 2 1 . 6 25 a (1.0180) a(0.9132) 2 Ia 0.6022.3 3
I a0
EEP 4113 – Advanced Power Systems - Fault in Power System
42
Unsymmetrical Fault – Sym. Components • Solution: Ic
I a0 I b0 I c0
Ia
1320
96.50
250
Ib
a-b-c set
Zero-sequence set
I c1
I b2
-0.1
22.30
I a1 0
I b1 Positive-sequence set
I a2
I c2 Negative-sequence set
EEP 4113 – Advanced Power Systems - Fault in Power System
43
Unsymmetrical Fault – Sym. Components • Example 5: The symmetrical components of a set of unbalanced voltages are Va0 0.690, Va1 1.030, Va2 0.8 30
Obtain the original unbalanced voltages. Solution:
Va 0.690 1.030 0.8 30 1.708824.2 Vb 0.690 a 2 1.030 a0.8 30 0.490
Vc 0.690 a1.030 a 2 0.8 30 1.7088155.8
EEP 4113 – Advanced Power Systems - Fault in Power System
44
Unsymmetrical Fault – Sym. Components • Solution: Vc
Vb
Va0 Vb0 Vc0
Va 900 24.20
a-b-c set
Vc1
Zero-sequence set
Vb2
Va1
Vb1
Positive-sequence set
Vc2
Va2 Negative-sequence set
EEP 4113 – Advanced Power Systems - Fault in Power System
45
Unsymm. Fault – Sequence Impedances • The impedance offered to the flow of a sequence current creating sequence voltages: positive sequence impedance, Z1 negative sequence impedance, Z2 zero sequence impedance, Z0
• Augmented network models: wye-connected balanced loads transmission line 3-phase transformers generators
EEP 4113 – Advanced Power Systems - Fault in Power System
46
Unsymm. Fault – Sequence Impedances • Balanced Y-connected load
Line-to-ground voltages Va Z s I a Z m I b Z m I c Z n I n Vb Z m I a Z s I b Z m I c Z n I n Vc Z m I a Z m I b Z s I c Z n I n
Neutral current I n I a Ib Ic
EEP 4113 – Advanced Power Systems - Fault in Power System
47
Unsymm. Fault – Sequence Impedances • Balanced Y-connected load Rewriting in matrix form, Va Z s Z n V Z Z n b m Vc Z m Z n
Zm Zn Zs Zn Zm Zn
Zm Zn I a Z m Z n I b Z s Z n I c
V abc Z abcI abc
Writing Vabc and Iabc in symmetrical components, AVa012 Z abc AI a012
Multiplying by A-1, Va012 A1Z abc AI a012 Z 012I a012 where Z 012 A1Z abc A EEP 4113 – Advanced Power Systems - Fault in Power System
48
Unsymm. Fault – Sequence Impedances • Balanced Y-connected load 1 1 1 012 Z 1 a 3 1 a 2
1 Zs Zn a 2 Z m Z n a Z m Z n
Zm Zn Zs Zn Zm Zn
Z m Z n 1 1 Z m Z n 1 a 2 Z s Z n 1 a
1 a a 2
0 0 Z s 3Z n 2Z m 0 Zs Zm 0 0 0 Z s Z m Z s 3Z n 0 0 0 Z s 0 when Z m 0 0 0 Z s EEP 4113 – Advanced Power Systems - Fault in Power System
49
Unsymm. Fault – Sequence Impedances • Transmission Lines
A
B
Positive B Sequence
C
C
A
EEP 4113 – Advanced Power Systems - Fault in Power System
Negative Sequence
50
Unsymm. Fault – Sequence Impedances • Transmission Lines Va1
Va1 Z s I a Z n I n Va2
Va2
Vb1
Vb1 Z s I b Z n I n Vb2
Vb2
Vc1
Vc2
Vn 0 Z n I n I n I a Ib Ic 0
Vn Va1 Z s Z n 1 Vb Z n Vc1 Z n
Vc1 Z s I c Z n I n Vc2
Zn Zs Zn Zn
2 I a Va 2 Z n I b Vb Z s Z n I c Vc2
Zn
EEP 4113 – Advanced Power Systems - Fault in Power System
51
Unsymm. Fault – Sequence Impedances • Transmission Lines 1 2 Vabc Z abcI abc Z abc 1 2 AV012 Z abc AI 012 AV012
Z 012 A1Z abc A 1 1 1 1 a 3 1 a 2 Z s 3Z n 0 0
1 Z s Z n a 2 Z n a Z n 0 Zs 0
Zn Zs Zn Zn
Z n 1 1 Z n 1 a 2 Z s Z n 1 a
1 a a 2
0 0 Z s
EEP 4113 – Advanced Power Systems - Fault in Power System
52
Unsymm. Fault – Sequence Impedances • Synchronous Generators Similar modeling of impedances to sequence impedances Typical values for common generators remember that the transient fault impedance is a function of time positive sequence values are the same as Xd, Xd’, and Xd” negative sequence values are affected by the rotation of the rotor X2 Xd” zero sequence values are isolated from the airgap of the machine. the zero sequence reactance is approximated to the leakage reactance X0 XL
EEP 4113 – Advanced Power Systems - Fault in Power System
53
Unsymm. Fault – Sequence Impedances • Synchronous Generators Zero Sequence
Positive Sequence
Negative Sequence
X0
X1
X2
VT0
VT1
VT2
EEP 4113 – Advanced Power Systems - Fault in Power System
54
Unsymm. Fault – Sequence Impedances • Loaded Synchronous Generators
EEP 4113 – Advanced Power Systems - Fault in Power System
55
Unsymm. Fault – Sequence Impedances • Loaded Synchronous Generators Z s 3Z n Z 012 0 0 Va0 1 Va Va2
0 Z 0 0 0 Z s 0
0 Zs 0
0 Z Ea 0 0 0
0
0 Z1 0
0 Z1 0
0 0 Z 2
0 I a0 1 0 Ia Z 2 I a2
EEP 4113 – Advanced Power Systems - Fault in Power System
Z0
Z1
Z2
Va0
Va1
Va2 56
Unsymm. Fault – Sequence Impedances • Transformers • Series Leakage Impedance the magnetization current and core losses represented by the shunt branch are neglected (they represent only 1% of the total load current) the transformer is modeled with the equivalent series leakage impedance
• Three single-phase units & five-legged core three-phase units the series leakage impedance is the same for all the sequences
Z 0 Z1 Z 2 ZL • Three-legged core three-phase units the series leakage impedance is the same for the positive and negative sequence only
Z1 Z 2 ZL EEP 4113 – Advanced Power Systems - Fault in Power System
57
Unsymm. Fault – Sequence Impedances • Transformers • the positive sequence line voltage on the HV side leads the corresponding line voltage on the LV side by 30° • consequently, for the negative sequence voltages the corresponding phase shift is -30° • Zero-sequence network connections of the transformer depends on the winding connection
EEP 4113 – Advanced Power Systems - Fault in Power System
58
Unsymm. Fault – Sequence Impedances • Transformers • Representation circuits for Zero-sequence:
EEP 4113 – Advanced Power Systems - Fault in Power System
59
Unsymm. Fault – Sequence Impedances • Transformers • Representation circuits for Zero-sequence:
EEP 4113 – Advanced Power Systems - Fault in Power System
60
Unsymm. Fault – Single Line-to-ground Fault
Va Z f I a Ib Ic 0 I a0 1 1 1 1 I a 3 1 a I a2 1 a 2 I a0
I a1
EEP 4113 – Advanced Power Systems - Fault in Power System
I a2
1 I a a 2 0 a 0
Ia 3
61
Unsymm. Fault – Single Line-to-ground Fault
Since,
Va0 0 Z 0 1 Va Ea 0 Va2 0 0
Va0 0 Z 0 I a0 Va1 Ea Z 1I a1 Va2 0 Z 2 I a2
0 Z1 0
0 I a0 1 0 Ia Z 2 I a2
Va Va V Va Ea (Z 1 Z 2 Z 0 ) I a0 0
1 a
2
The fault current, 3Z f I a0 Ea ( Z 1 Z 2 Z 0 ) I a0 I f Ia
3I a0
3 Ea 1 Z Z 2 Z 0 3Z f
EEP 4113 – Advanced Power Systems - Fault in Power System
62
Unsymm. Fault – Line-to-line Fault
Vb Vc Z f I b Ib Ic 0 Ia 0 I a0 1 1 1 1 I a 3 1 a I a2 1 a 2
EEP 4113 – Advanced Power Systems - Fault in Power System
1 0 a 2 I b a I b
63
Unsymm. Fault – Line-to-line Fault I a1 I a2 Vb Va0 a 2Va1 aVa2
I a 1 1 I 1 a 2 b I c 1 a
Vc Va0 aVa1 a 2Va2
The fault current,
Vb Vc (a
Ib I c (a 2 a) I a1 j 3I a1
Va Va0 Va1 Va2
2
a)(Va1
Va2 )
1 0 a I a1 a 2 I a1
Z f Ib
I a1
Ea 1 Z Z2 Zf
EEP 4113 – Advanced Power Systems - Fault in Power System
64
Unsymm. Fault – Double Line-to-ground Fault Vb Vc Z f ( I b I c )
I a I a0 I a1 I a2 0 From previous section, Vb Va0 a 2Va1 aVa2 Vc Va0 aVa1 a 2Va2
Since Vb Vc
Va1 Va2 Vb Z f ( I a0 a 2 I a1 aI a2 I a0 aI a1 a 2 I a2 ) Z f (2 I a0 I a1 I a2 ) 3Z f I a0 EEP 4113 – Advanced Power Systems - Fault in Power System
65
Unsymm. Fault – Double Line-to-ground Fault
I a0
Va0 Va1 Ea Z 1I a1 0 3Z f Z 3Z f
Va0 0 Z 0 I a0
Since Va1 Ea Z 1I a1 Va2 0 Z 2 I a2
1 1 E Z Ia 2 a Ia Z2
I a1
Z 1
Ea Z 2 ( Z 0 3Z f ) Z 2 Z 0 3Z f
I f I b I c 3I a0
By using I a0 I a1 I a2 0
Fault current
EEP 4113 – Advanced Power Systems - Fault in Power System
66
Conclusion Sequence Impedance Circuit:
EEP 4113 – Advanced Power Systems - Fault in Power System
67
Example
• The neutral of each generator is grounded through a current limiting resistor of 25/3 % on a 100 MVA base • All network data is expressed on a 100 MVA base • Find the fault current for 3-phs, 1-phs, L-L, L-L-G bolted faults at bus 3 through a fault impedance Zf = j0.1 pu. EEP 4113 – Advanced Power Systems - Fault in Power System
68
Example
• Positive sequence impedance network:
Y
EEP 4113 – Advanced Power Systems - Fault in Power System
69
Example
• Negative sequence impedance network:
Y
EEP 4113 – Advanced Power Systems - Fault in Power System
70
Example
• Zero sequence impedance network:
Open circuited
Open circuited
Y
EEP 4113 – Advanced Power Systems - Fault in Power System
71
Example • 3-phase fault V3a( 0)
1.0 I (F ) 1 j3.125 pu 902.11 90 Z 33 Z f j 0.22 j 0.1 a 3
• Single Line-to-ground fault a V 0 1 2 3 (0) I3 I3 I3 1 j 0.9174 pu 2 0 Z 33 Z 33 Z 33 3Z f
Fault current
I 3a 1 1 b 2 I 1 a 3 I 3c 1 a
1 I 30 3I 30 j 2.7523 0 pu a I3 0 0 a 2 I 30 0 0
EEP 4113 – Advanced Power Systems - Fault in Power System
72
Example
• Line-to-line fault I 30 0 I 31 I 32
V3a( 0) 1 Z 33
2 Z 33
Zf
j1.8519 pu
Fault current I 3a 1 1 1 0 0 b j1.8519 3.2075 pu 2 I 1 a a 3 I 3c 1 a a 2 j1.8519 3.2075
EEP 4113 – Advanced Power Systems - Fault in Power System
73
Example
• Double Line-to-ground fault Positive sequence component
V3a( 0)
I 31 1 Z 33
2 0 Z 33 ( Z 33 3Z f ) 2 0 Z 33 Z 33 3Z f
j 2.6017 pu
Negative sequence component
I 32
1 1 V3a(0) Z 33 I3 2 Z 33
1 ( j 0.22)( j 2.6017) j1.9438 pu j 0.22
EEP 4113 – Advanced Power Systems - Fault in Power System
74
Example
• Double Line-to-ground fault Zero sequence component I 30
1 1 V3a( 0) Z 33 I3 0 Z 33
3Z f
j 0.6579 pu
Phase currents I 3a 1 1 1 j 0.6579 0 b j 2.6017 4.058165.93 pu 2 I 1 a a 3 I 3c 1 a a 2 j1.9438 4.05814.07 Fault current I3 ( F ) I3b I3c 1.973290 EEP 4113 – Advanced Power Systems - Fault in Power System
75