Final Causes Of Failure Of Distribution Transformers In India 1 [searchtoll]

  • Uploaded by: Mariut Elena Larisa
  • 0
  • 0
  • January 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Final Causes Of Failure Of Distribution Transformers In India 1 [searchtoll] as PDF for free.

More details

  • Words: 1,238
  • Pages: 14
Loading documents preview...
Ranjana Singh Jabalpur Engineering College Jabalpur , M.P. , India [email protected] Amarjit Singh Gyan Ganga Institute of Technology and Science Jabalpur , M.P. , India [email protected]

1

`

`

`

Failure of distribution transformer affects the economy of nation in the form of loss of revenue, materials, repairing charges etc. , besides the inconvenience caused by interruption of power supply to consumers. Along with other causes, the main cause of failure of distribution transformers is prolonged overloading. In this paper three distribution transformers are analyzed and results are verified by dissolved gas analysis.

Keywords- causes of failure; cold load pickup current; distribution transformer; harmonics; overloading

2

`

`

`

Unfortunately the failure rate of these transformers is very high in India, around 25% per annum, which is not favorably comparable to international norms of 1-2%. Transformer insulation deteriorates as a function of time and temperature. The winding I²R losses, the core losses, and the stray losses in the tank and metal support structures are the principle sources of heat that cause the oil and winding temperature rise . This leads to ageing and decomposition of both oil and cellulose which liberate gases within the transformer. The amount and type of gases formed and dissolved into the oil can be determined with the help of Dissolved Gas Analysis (DGA). 3

All three transformers under consideration were supplied by different manufacturers and have the same specifications as follows - 200 kVA, 11/0.433 kV, Dy 11, 50 Hz, 3-phase, high voltage winding current - 10.5 A, low voltage winding current - 266.67 A, Aluminium wound. Figures are of Case B in which all three phases of HV and LV windings were severely burnt.

4

Transformer installed in rural area which failed after 23 months i. e. within warranty period of 3 years (Manufacturer – X) : Diagnosis Results: Failure of one phase of HV windings is caused by overloading. Overloading/unbalanced loading due to power theft by hooking the mains is one of the major causes of transformer failure [5]. It may be assumed that stealing of power by some of the consumers would have been done by hooking the approachable bottom most conductor i.e. B phase of the system.

5

Fig. 1. Burnt HV windings

Fig. 2. Charred paper insulation

Fig.3. B phase of LV winding

It was found by inspection that one phase of HV windings was damaged severely as shown in Fig. 1. Fig. 2 gives the view of charred paper insulation. Fig. 3 shows the burnt condition of LV winding of same phase.

6

Transformer installed in urban area which failed after only 11 months i.e. within warranty period of 3 years (Manufacturer – Y) : Diagnosis results : This transformer was supplying residential and some commercial buildings. The large number of personal computers and adjustable speed drives/air conditioners in commercial buildings generate very high levels of harmonics and can result in effective overloading of the distribution transformer supplying the buildings. Cold load pickup (CLP) current may also be considered as one of the reasons of its failure. In India load shedding of 1 to 6 hours is a routine of daily life. CLP current is many times greater than pre outage current which causes heavy overloading of the distribution transformer. 7

Fig. 5. Oil Samples Fig. 4. ig. 4 shows one phase of burnt LV windings. As the conductor is made of Aluminium, it comes out in the melted form, which can be clearly seen on the top of the winding. ig. 5 gives the condition of fresh oil, oil of less severely damaged transformer i.e. case A and oil of most severely damaged transformer i.e. case B respectively. The color of oil clearly shows the effect of overheating on the liquid insulation. In A, charred paper insulation present in the oil can be seen at the bottom of the jar.

8

Transformer installed in rural area which failed after 4 years and 4 months i.e. beyond warranty period (Manufacturer – Z) : Diagnosis results : It is again the case of excessive overloading on B phase. The reason of powdered form (as shown in Fig. 7 on next slide) is an impurity of Iron in Aluminium i.e. pure Aluminium is not used for conductor. The excessive overloading on B phase would have been caused by power theft by hooking. With this unauthorized connection they run their agricultural pump sets.

Results of DGA of all cases (given in Table I) also agree with the diagnosis. As, ethylene is the principal gas with some amount of ethane and methane, the cause of which is overheating of the oil. Presence of carbon dioxide and carbon mono oxide indicate the paper degradation. 9

Fig 6. Burnt B phase of HV windings

Fig 7. B phase of LV windings in powdered form

It was found by inspection that one phase of both HV and LV windings were severely burnt/damaged as shown in Fig. 6. The overloading has increased the temperature of B phase of LV winding to such an extent that Aluminium conductor of winding became brittle and came out in the powdered form as shown in Fig. 7.

10

TABLE I. Results of dissolved gas analysis Amount in ppm Component Normal

Case A

Case B

Case C

Hydrogen H2

0.6646

36.451

57.464

41.97

Methane CH4

0.3326

50.508

310.667

114.76

Ethane C2H6

2.31E - 03

5.957

112.778

67.12

Ethylene C2H4

6.07E - 02

122.088

2512.33

571.14

Acetylene C2H2

0.1126

1.13E - 03

0.0197

0.121

104.53

156.56

3539.12

246.44

1.5542

3.451

101.745

21.64

Carbon di-oxide CO2 Carbon monooxide CO

11

`

It was found that overloading, due to various reasons such as power theft by hooking the mains, harmonics and CLP current etc., is the prime cause of failure.

`

Two main reasons for low maintenance are - (i) Most of them are located in remote areas and special attention cannot be given to the operating conditions of the transformers. (ii) A shortage of maintenance personnel working in State Electricity Boards (SEBs).

`

Some states in India have given one point legal connections per family free of charge to all families who are economically weak. This highly appreciable gesture of the government is misused by almost 90 percent public, by drawing more power than legally permitted, to run their appliances without paying for them.

`

Solution to the problem of power theft is to use “armored cable”. The armored cable network will cut short the problem of illegal electricity connection and reduce distribution losses [6]. 12

The authors would like to express their sincere gratitude to Mr. R. Chansoria, Proprietor of Transformer Manufacturing and Repairing Company for providing photographs and details of transformers. 1.IEEE Guide for loading Mineral – Oil – Immersed Transformers, IEEE C57.91 – 1995 2.D.P.Gupta, “Loading and life of transformers” TRANSFORMERS, Bharat Heavy Electricals Limited Bhopal (M P), Tata McGraw-Hill Publishing Company Limited. 3.P. K. Sen, Pansuwan Sarunpong, “Overloading and loss-of-life assessment guidelines of oil-cooled transformers”, Rural Electric Power Conference, 2001 Little Rock, AR, USA, pp B4/1-B4/8, April-May 2001. 4.N. A. Muhamad, B. T. Phung, T. R. Blackburn, K. X. Lai, “Comparative Study and Analysis of DGA Methods for Transformer Mineral Oil”, IEEE Power Tech, Lausanne, pp 45-50, July 2007 5.“Transformer precaution”, [Online]. Available http://www.mahadiscom.in/emagazine/jan07. , [Accessed Jan 9, 2009] 6.Staff Reporter, “MPERPDCL succeeds in reducing distribution losses to 1.5 per cent”, The Hitvada newspaper, Jabalpur Edition, dated Nov.15, 2009

13

- Ranjana Singh & Amarjit Singh India

14

Related Documents


More Documents from "Isaac Abayomi Oshin"