Page 1 of 9 BGR ENERGY SYSTEMS LIMITED.

DOCUMENT NO. GID-091-CV-CAL-3070 C

POWER PROJECTS DIVISION

Date

Rev

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

3-1-08

A

MAHARASHTRA STATE POWER GENERATION Co. Ltd KHAPERKHEDA T.P.S EXPANSION PROJECT (1x 500 MW)

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

BGR ENERGY SYSTEMS LIMITED CHENNAI, INDIA

POWER PROJECTS DIVISION 443, ANNA SALAI TEYNAMPET, CHENNAI - 600018 PH 044 24352436, FAX 044 24315678 E Mail – [email protected]

01-03-08

A

Submitted for approval

PDS

DATE

REV

Description

PREPARED BY

CHEKCED BY

CLEARED BY

APPROVED BY

Page 2 of 9 BGR ENERGY SYSTEMS LTD. Project

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW)

Title

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

Doc. No.

GID-091-CV-CAL-3070C

A

REV

Introduction Crane Supplier - ANUPAM Industries Limitted - (Vendor drawing is attached in Annexure -1) 115MT capacity crane is mounted in AB bay at EL+30.0 top of rail. The span of crane bridge is 34-0.75-2=32.5m The Gantry Girder is analysed and designed as simply supported over Column brackets with span of 10.5m.The rail is resting over Gantry Girder and gantry girder is supported on the brackets from A & B row columns. The C/L of gantry girder from C/L of A & B row column is 750 mm. 600 mm walkway (Effective width ) @ the center and at the column location 450 mm is provided throughout the length of the building with access provided from 17m floor The load calculation are carried out for Crane Operating conditon,Crane with wind and seismic. Finally the design of gantry girder is done for operating condition For load details refer DOC no:GID-091-CV-CAL-3040C Design of Gantry Girder E.O.T Crane Data Drg. No: 1052-00-Rev 02

G.A.

-

For 115 / 25T x 32.50mt Span D/G E.O.T.Crane

Crane capacity Weight of Crane including Crab Weight of Crab

= = =

Span of crane bridge Minimum hook approch Span of Gantry

34-0.75*2 = = = 1.8

4.0

1150 1250 340

kN kN kN

32.500 1.360 10.500

m m m

1.8

Wheel Base ( 2 x 4 wheels ) (Dimensions in meters) When the trolley is near to the wheels the vertical loads are maximum. Lift load + Crab weight Crane Load without crab

= 1150 + 340 = 1250 - 340

1490 kN

= = 910

1490 910

kN kN

kN

1.360 32.500 RA

RB

Page 3 of 9 BGR ENERGY SYSTEMS LTD.

Support reaction

Project

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW)

Title

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

Doc. No.

GID-091-CV-CAL-3070C

RA =

1883

kN

RB =

517

kN

Load on each wheel of Crane Gantry

=

1883 / 4

A

REV

=

471

kN

= 1.25 x 471

=

589

kN

Lateral Load : 10% of ( Lifted Weight + Crab ) = 0.1 x (1150 + 340)

=

149

kN

Cl: 8.4, Tender Specification : PCT / V / 02 / 2005 VI: 15 Impact load

This load is transferred to Gantry: acts at any one crane track rail and equally distributed on all wheels on one side of rail track. Hence load on each wheel

= 149 / 4

37.25

=

kN

Calculation of Maximum Bending Moment: Maximum bending moment condition arises when one of the point load is at the center of the beam. 589 589 589 1.8 4 =

= 10.500 m

RA RA

760

=

Maximum bending moment

kN Mmax

RB

RB

=

1007

=

2930

kNm

kN

Assumed that Rail is CR100 with self weight 1 kN/m and self weight of gantry girder is 4kN/m Total weight assumed

= 5 kN/m

Bending moment due to self weight

=

Total moment

Mvmax

=

2930

+

kNm

69 69

=

2999

kNm (Major axis bending moment)

Maximum Bending moment due lateral horizontal force BM in minor axis

Mhmax = 2930 x 37.25 / 589

=

185

kNm

Page 4 of 9 BGR ENERGY SYSTEMS LTD. Project

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW)

Title

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

Doc. No.

GID-091-CV-CAL-3070C

Maximum Shear Force : 589 589 1.8

589

589 4

RA

A

REV

2.900

1.8

RB

10.500

For Maximum shear force, the wheel load shall be placed as shown aobve. Maximum shear Force

1503

RA =

Section Assumed 1300 mm Total Depth = Top Flange 490 mm Width Thickness Bottom Flange Width Thickness 490 mm mm2 Total area = 51136

Web Thickness 32

mm

32

mm

kN

16

=

mm

795 50 50

Y

Surge girder member MC250

Area Centre of Gravity Chequered Plate

A Cyy 6 thk

2 3867 mm 23 mm

633

211.7 X

X

600 wide (Assumed)

Moment of inertia of section about XX only for main girder Y =

15125659221

mm

4

Section Modulus of section about XX only for main girder

Zxx

=

3 23270245 mm

Moment of inertia and section Modulus for Combined section of Plate Girder top flange Section + Chequred Plate + Surge girder member (about minor axis) Total area of section at top flange level = 3867 + 6 x 600 + 490 x 32 = 3867 + 3600 + 15680 2 = 23147 mm The distance from the center of gravity of the combined section at top flange level to the axis of the girder (yy-axis) = 211.72 mm The moment of Inertia of Bracing beam W.r.t. to axis yy 4 = 2767040408 mm mm3 Section Modulus Zyy yy = 6058475

Page 5 of 9 BGR ENERGY SYSTEMS LTD. Project

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW)

Title

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

Doc. No.

GID-091-CV-CAL-3070C

Radius of gyration about yy

346

=

A

REV

mm

Bending Compressive Stress due to Major Axis Bending moment = Mvmax / Z xx = 2999000000 / 23270245

= 129 Mpa

Bending Compressive Stress due to Minor Axis Bending moment = Mhmax / Zyy = 185000000 / 6058475

=

31 Mpa

Total Bending Compressive Stress = 129 + 31 = 159 Mpa Since the compression flange is fully restrained by surge girder through out the length, full bending stress is considered. As per clause 3.9.3 of IS 800-1984 permissible stresses shall be increased by 10% Allowable bending compressive stress

= 0.66 fy x 1.1 = 181.5 Mpa > Hence Safe.

159.4 Mpa

Check for deflection Service bending moment = 2930 / 1.25 + 69 Deflection

2413 kNm

2 = M L / ( 10 x E x Ixx)

Allowable deflection L / 1000

=

=

8.58 mm

IS 800-1984, Cl :3.13.1.13

= 10500 / 1000

=

10.5 mm

>

mm

8.58

Hence Safe.

Longitudinal force: Horizontal ( Longitudinal ) Force along rails = 5% of Static wheel load

=

Bending moment due to longitudinal force = 94.2 x (0.65 + 0.15)

= 75.36 kNm

Stress in longitudinal direction

94.2 kN

= F/A +M/Z = 5.08 Mpa

Very small and it is negligible.

Check for Shear stress Actual shear stress

= 1503000 / ((1236 x 16))

=

76

Mpa p

Page 6 of 9 BGR ENERGY SYSTEMS LTD. Project

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW)

Title

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

Doc. No.

GID-091-CV-CAL-3070C

Allwable stress

=

=

0.4 x fy

A

REV

Mpa

100

Support Rib

Hence OK

Assume the support rib is 1290

x

490 x

32 thk resting over 650 SQ x 25thk plate.

Crushing area = 490 x 32

=

2 15680 mm

Bearing stress = 1503000 / 15680

=

96

Mpa

< 0.75 x fy

=

187.5 Mpa

Hence safe. Vertical Stiffner Plates. Cl: IS800-1984 , Cl: 6.7.3.1 d1/t = 1236 / 16 = 77 < 85 Vertical stiffners are not required, however 200x10thk vertical stiffner plates are provided at 1500mm centers, edge. centers starting with first stiffner at 750mm from edge Check for outstand of Flange Plates Cl: IS800-1984 , Cl: 3.5.2.1(b) Outstand of flange provided = (490 - 16)/2 = Case 1: = 256 x Thickness of flange / sqrt (250) = Case 2: 16 x 32 = 16 x Thk. Of flange = =

237

mm

518

mm >

237

512

mm >

237

Hence safe. Check for outstand of Stiffener Plates Cl: IS800-1984 , Cl: 6.7.4.4 Outstand of flange provided 202 = (490 - 16)/2-35 = Case 1: 518 = 256 x Thickness of flange / sqrt (250) = Hence safe.

mm mm >

202

WELD B/W BOTTOM FLANGE TO WEB The top flange welds are made with penetration over the entire thickness of the web. The joint between flange and web is subjected to shear stress. The shear stress = 988 N/mm Assume 8 mm thk. Weld on bothsides with contineous fillet weld. Strength of the weld = 2 x 0.707 x 8 x 108 = 1222 N/mm >

988

Hence safe

Page 7 of 9 BGR ENERGY SYSTEMS LTD. Project

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW)

Title

STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION

Doc. No.

GID-091-CV-CAL-3070C

REV

A

WELD B/W STIFFENER PLATE TO WEB PLATE Cl: IS800-1984 , Cl: 6.7.4.6 The weld between the stiffener and the web plate to be designed for a shearing force of not less than those given below Shearing force

= 125*t^2/h

=

158.4 kN/m

t = web thickness h = outstand of stiffener plate

Assume 6 mm fillet weld Capacity of 6 mm weld

= 0.707*6*108

= 458.1 kN/m

Hence safe

WELD B/W WEB PLATE TO BEARING STIFFENER The maximum end reactions to be transffered

=

1503 kN

Assume g of 1230 10 mm thk. Weld on bothsides with contineous fillet weld with weld length Strength of the weld = 2 x 0.707 x 10 x 108 x 1230 =

1878 kN

>

1503

Hence safe

Page 8 of 9 BGR ENERGY SYSTEMS LTD. Project Title Doc No.

KHAPERKHEDA T.P.S EXPANSION PROJECT, (1X500MW) STG BUILDING - CRANE GANTRY GIRDER DESIGN CALCULATION REV GID-091-CV-CAL-3070 C A

CRANE VENDOR DRAWINGS - ANNEXURE 1

Page 9 of 9