Ring Main Unit: 8DJH ST Cost efficient solution for secondary power distribution Presentation, Ver 1.0 siemens.com/answers

8DJH ST: Secondary distribution

Page 2

April 14

IC LMV MS S GIS

8DJH ST: Applications

RRR

Page 3

April 14

IC LMV MS S GIS

8DJH ST: Applications

Page 4

April 14

IC LMV MS S GIS

8DJH ST: SF6 gas for insulation

Vacuum for switching & SF6 for insulation No toxic gases due to interruption in vacuum Climate independent and maintenance free design High dielectric strength thereby reducing volume of switchgear Sealed for life Safe and low-tolerance pressure co-ordination for pressure relief system

Page 5

April 14

IC LMV MS S GIS

8DJH ST: Technical details

Ratings up to 12kV, 630A, 21kA 3s STC Internal arc classification IAC A FLR 20kA 0.1s [21kA 1.0s available on request] Factory-assembled, type-tested, metal-enclosed switchgear according to IEC 62271-200 Blocks consisting up to 5 feeders in a single tank

Page 6

April 14

IC LMV MS S GIS

8DJH ST: Technical details Technical features Rated values up to

12kV, 21kA 3s

Rated frequency

50Hz

Busbar current up to

630A

Feeder current up to

630A

Busbars

Single busbar

Rated power frequency withstand voltage

28kV

38kV

Rated lighting impulse withstand voltage

75kVp

95kVp

Rated making current

52.5kAp

Rated breaking current

21kA

Insulation

Gas insulated

Switchgear vessel

Hermetically sealed

Page 7

April 14

IC LMV MS S GIS

8DJH ST: Technical details Classification according to IEC 62271-200 Partition class

PM

Loss of service continuity category

LSC 2

Accessibility to compartments

Busbar compartment: Non-accessible Switching-device compartment: Non-accessible Cable compartment: Interlock-controlled

Degree of protection

For switchgear enclosure [Indoor]: IP3X For switchgear enclosure [Outdoor]: IP54 For gas filled vessel: IP65

Internal arc classification

IAC A FLR 20 kA, 0.1 s IAC A FLR 21 kA, 1.0 s

Page 8

April 14

IC LMV MS S GIS

8DJH ST: Technical details One way typical [310mm]

Two way typical [620mm]

Three way typical [930mm]

Four way typical [1240mm]

Five way typical [1550mm]

R

RK

RRR

RRRR

RRRRR

L

RR

RRL

RRRL

LRRLL

K

RL

RLR

LRRL

LLLLL

S*

LK

ME 1 $ ME 2 $ Legends:

R [Ring main feeder] S [Bus coupler feeder]

L [Circuit breaker feeder] ME1 [Line metering feeder]

K [Cable connection feeder] ME2 [Bus metering feeder]

Extensibility options: on both side, on right hand side, on left hand side Panel combination with metering will be on right side always. No further extensibility on right side possible with metering Bus coupler feeder will always have extensibility on both sides Width indicated above is for vessel * - Width of Bus coupler feeder vessel is 620mm $ - Width of metering feeder vessel is 630mm Page 9

April 14

IC LMV MS S GIS

8DJH ST: Technical details Dimensions Block width depending on number and type of panels

645mm, 955mm, 1265mm, 1575mm

Panel height

1620 mm

Operating height

<1500mm

Panel depth

Bottom explosion: 820 mm Top explosion: 918 mm

Page 10

April 14

IC LMV MS S GIS

8DJH ST: Vacuum circuit breaker Technical details Rated voltage

12kV

Rated current

630A

Basic insulation level

12kV / 28kV / 75kVp

Rated short time withstand current

21kA, 3s

Rated short circuit breaking / making current

21kA / 52.5kAp

Rated operating sequence

O-3min-CO-3min-CO

Endurance class Breaking [2,000 times mechanically without maintenance]

M1 [IEC62271-100]

Breaking [2,000 times rated normal current without maintenance]

E2 [IEC62271-100]

Breaking [Low probability of restrikes]

C1 [IEC62271-100]

Breaking [For cable systems]

S1 [IEC62271-100]

Page 11

April 14

IC LMV MS S GIS

8DJH ST: Three position disconnector for CB Technical details Rated short time withstand current

21kA, 3s

Endurance class Disconnecting [1,000 times mechanically]

M0

Earthing [1,000 times mechanically] Earthing [5 making operations through VCB]

Page 12

April 14

IC LMV MS S GIS

E2

8DJH ST: Three position switch for Ring main feeder Technical details Rated voltage

12kV

Rated current

630A

Basic insulation level

12kV / 38kV / 95kVp

Rated short time withstand current

21kA, 3s

Rated short circuit making current

52.5kA

Rated breaking current

630A

Endurance class Disconnecting [1,000 times mechanically]

M0 [IEC62271-102]

Earthing [5 times rated short-circuit making current]

E2 [IEC62271-102]

Load breaking [1,000 times mechanically]

M1 [IEC 60265-1]

Load breaking [100 times rated breaking current 5 times rated short-circuit making current]

E3 [IEC 60265-1]

Page 13

April 14

IC LMV MS S GIS

8DJH ST: Technical details Standards Switchgear Devices

IEC 62271-1 IEC 62271-100

Circuit Breakers Disconnector & Earthing Switch Switch-disconnector Voltage detection systems

IEC 62271-200 IEC 62271-102 IEC 62271-103 IEC 61243-5

Degree of protection

IEC 60529

Insulation

IEC 60071

Instrument transformers Current transformer Voltage transformer

IEC 61869-2 IEC 61869-3

Installation & commissioning

IEC 61936-1

Page 14

April 14

IC LMV MS S GIS

8DJH ST: One way typical

Page 15

April 14

IC LMV MS S GIS

8DJH ST: Two way typical

Page 16

April 14

IC LMV MS S GIS

8DJH ST: Three way typical

Page 17

April 14

IC LMV MS S GIS

8DJH ST: Four way typical

Page 18

April 14

IC LMV MS S GIS

8DJH ST: Five way typical

Page 19

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Vessel]

Stainless steel vessel Insensitive to temperature and pressure variations Stable dew-point behavior Modern and safe laser welding technology Maximum flexural and burst strength Safe and low-tolerance pressure co-ordination for pressure relief system Maintenance-free [leakage of 0.1% p.a.] High quality non magnetic SS

Page 20

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Pressure detection systems]

Manometer Clearly visible indication [Red/Green] Refilling of gas possible Optionally with signaling contact

Page 21

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Pressure detection systems]

Ready for service indication [with aux contacts] Temperature and pressure compensated gas density measurement (2) Magnetic coupling (3) between measurement box and indication Independent of site altitude & ambient temperature Optionally with signaling contact

Indication: 4 Not ready for service 5 Ready for service

Page 22

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Cable connection]

Climate independent connection system Cable connections for bushings with outside cone Insensitive to pollution and condensation Switchgear or panel extension possible without gas work Corrosion free and maintenance free connection

Page 23

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Extension]

High flexibility for creation of switchgear configurations Busbar extension possible on all individual panels & panel blocks [optional] Plug-in unit consisting of contact coupling & screened silicone coupling Centering via guide bolts & stop angles Corrosion free and maintenance free connection

Page 24

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Interlocks]

Switchgear interlocking with logical mechanical interlocks Switching gate prevents direct operation from CLOSE to EARTH and EARTH to CLOSE Cable compartment can be removed only after feeder is eatthed and operating lever removed Active interlocks between circuit breaker and three position disconnector Closing and opening of circuit breaker not possible if operating lever is inserted

Page 25

April 14

IC LMV MS S GIS

8DJH ST: Constructional features [Interlocks]

Switchgear interlocking with logical mechanical interlocks Optional Three position disconnector can be operated only if cable cover is closed Closing & opening lock-out in case cable cover is removed for three position disconnector Padlocking in all three positions

Page 26

April 14

IC LMV MS S GIS

8DJH ST: Fault passage indicator

Short circuit / Earth fault indicator Indication at the switchgear front Factory assembled including sensor mounting Manual / Automatic reset Optical signals for a preselected pick-up values Optionally remote electrical indication

Short circuit indicator Page 27

April 14

IC LMV MS S GIS

Earth fault indicator

8DJH ST: Voltage detection systems

Safe to touch With voltage indicator Verification of safe isolation from supply phase by phase Voltage indicator flashes in presence of high voltage Indicator suitable for continuous operation Measuring system and voltage indicator can be tested

Page 28

April 14

IC LMV MS S GIS

8DJH ST: SCADA compatibility

Ease of communication Motorized VCB / LBS Self powered numerical relay Mini RTUs Power pack Control MCCBs Pre wired auxiliary contacts

Page 29

April 14

IC LMV MS S GIS

8DJH ST: Safe and Reliable Safe and Reliable Dielectric test Temperature rise test Short time withstand current Peak withstand current Verification of IP code Pressure withstand test for gas-filled compartment Tightness test Internal arc test Alternating pressure test [10,000 cycles] Climatic tests on components Switching performance test Mechanical endurance test Disconnector switch switching test Page 30

April 14

IC LMV MS S GIS

8DJH ST: Customer benefits