DOC NO : HZL-BTN-ELE-DS-SY-031
TRANSFORMER LV NEUTRAL CT Core I : 1.0 CT sizing calculation for 132kV ‐ Definite Time Ground O/C Protection 1.1 Basic Data: 800 /
Ratio
=
Accuracy class
= 5P10
Burden ( VA )
= 15
VA
IDMT Overcurrent Relay
= 0.1
VA
Cable Length ( m )
= 150
m
A
1
1.2 Burdens of relays connected :
2 Lead resistance at 70ºC for 4mm copper ( Ω/km ) = 5.54
Ω/km
Loop Resistance ( RL) (Ω)
= 1.66
(Ω)
Loop Burden ( VA )
= 1.66
VA
Total Meter Burden ( VA )
= 0.1
VA
Total Burden on CT ( VA )
= 1.76
VA
1.3 Selected burden is more than required.
HENCE SAFE.
Core II : 1.0 CT sizing calculation for132kV ‐ Restricted Earth Fault Protection (64R) 1.1 Basic Data: Ratio
= 1000 /
Voltage ( kV )
= 6.6
Accuracy Class
= PS
Transformer rating
= 7.5
MVA
Impedence of transformer
= 8.35
%
Maximum through fault, MVA
= 7.5 x 100/8.35 = 89.82 MVA
Through Fault current at primary I f
= 89.8203592814371 x 1000/(1.732 x6.6 ) = 7857.5 A
Through Fault current at secondary I fs
= 7.857
1 of 18
1 A
kV
A
DOC NO : HZL-BTN-ELE-DS-SY-031
TRANSFORMER LV NEUTRAL CT 1.2 Burdens of relays connected : Restricted Earth Fault Relay
= 1.00
VA
Cable Length ( m )
= 100
m
2 Lead resistance at 70ºC for 4 mm copper ( Ω/km ) = 5.54
Ω/km
Loop Resistance ( RL) (Ω)
= 1.1080
Ω
= 1.1080
VA
Loop Burden ( VA ) R
L
Internal resistance of CT secondary ( Ω) = 2 1.3 Required Knee point Voltage Vk
≥ (2 x Ifs(Rct+2RL)) volt ≥ 2 x7.86 x (2+ 2x1.108) ≥ 66.26
V
≥ 500
V
2 of 18
Ω