CLIENT : M/s. Bharat Heavy Electricals Ltd- PSER.

DATE :13/07/2013 Sheet No 1 of 5

PROJECT-2X520 MW HNPCL,VIZAG

TEST REPORT FOR TRANSFORMERS

1. Location & Feeder Name: FOPH

2. Equipment Details

:

Make

: KANOHAR

Type of cooling

: ONAN

Rating (KVA )

: 2000

HV Volts

: 11000

PH

LV Volts

: 433

Freq: 50 HZ

%Z

: 10%

Vector Group

: Dyn1

HV Rated Current

: 105A

LV Rated Current

: 2666.7A

Sl.No.

: KT-2000 / 154

Temp Rise Oil

: 50 ºC

Temp Rise Winding

: 55 ºC

Mfg Year

: 2012

: 3

3. General Inspection : OK

4. Insulation Resistance Test: Ref HV to Earth 5000V LV to Earth 500V HV to LV 5000V

Test Performed by IMC Name : Design : Signature & Date

15 SEC 2.3G 1.48G 2.78G

60 SEC 3.70G 1.70G 4.75G

600 SEC 5.58G 2.32G 6.01

PI 1.57 1.37 1.27

Witnessed by MEL Name

Witnessed by BHEL Name

Witnessed by HNPCL/STEAG Name

Designation Signature & Date

Designation Signature & Date

Designation Signature & Date

CLIENT : M/s. Bharat Heavy Electricals Ltd- PSER.

DATE :13/07/2013 Sheet No 2 of 5

PROJECT-2X520 MW HNPCL,VIZAG

TEST REPORT FOR TRANSFORMERS 5. Ratio Test : Tap

Applied HV Volts

Measured LV Volts

Measured LV Volts

Position 1U1V

1V1W

1W1U

2U2V

2V2W

2W2U

2U-N

2V-N

2W-N

1

415

416

415

15.64

15.72

15.78

9.01

9.02

9.04

2

413

415

416

16.24

16.25

16.21

9.36

9.36

9.30

3

416

416

415

16.65

16.48

16.49

9.57

9.56

9.55

4

417

415

417

16.96

16.98

16.97

9.73

9.75

9.80

5

415

416

417

17.28

17.45

16.46

9.81

9.94

9.96

6. Magnetising Current Test :

Applied Volts ( HV Side ) 1U1V 413

1V1W 417

1W1U 412

Measured Current in Ma 1U 11.9mA

1V 7.9mA

1W

7.6mA

7.Magnetic Balance Test :

Applied Voltage in Primary

Measured Voltage in Secondary

1U1V

1V1W

1W1U

2U2V

2V2W

2W2U 2UN

2VN

2WN

209.4

413

211.8

14.45

14.39

0.144

4.94

9.34

5.01

116.2

314

417

16.66

4.67

11.65

9.36

7.14

2.42

415

316.7

104.2

4.56

16.75

11.46

2.46

7.26

9.56

8.Winding Resistance Test : Test Performed by IMC Name : Design : Signature & Date

Witnessed by MEL Name

Witnessed by BHEL Name

Witnessed by HNPCL/STEAG Name

Designation Signature & Date

Designation Signature & Date

Designation Signature & Date

CLIENT : M/s. Bharat Heavy Electricals Ltd- PSER.

DATE :13/07/2013 Sheet No 3 of 5

PROJECT-2X520 MW HNPCL,VIZAG

TEST REPORT FOR TRANSFORMERS

Tap Position

HV Side ( mΩ )

Measured Values 1V1W 1W1U 707.5 706.3

1

1U1V 709.2

2

700.2

699.2

701.3

3

685.8

686.6

685.3

4

664.2

665.8

664.2

5

647.5 2U2N

647.9 2V2N

648.8 2W2N

3

0.3

0.4

0.4

LV Side( mΩ )

9.Vector Group Test : Dyn1 Applied Volts 1U-1V = 400V 1V-1W =416V

1U,2U

1W-1U =419V

Test Performed by IMC Name : Design : Signature & Date

Witnessed by MEL Name

Witnessed by BHEL Name

Witnessed by HNPCL/STEAG Name

Designation Signature & Date

Designation Signature & Date

Designation Signature & Date

CLIENT : M/s. Bharat Heavy Electricals Ltd- PSER.

DATE :13/07/2013 Sheet No 4 of 5

PROJECT-2X520 MW HNPCL,VIZAG

TEST REPORT FOR TRANSFORMERS Conditions to be Satisfied 1) 1U-1W = ( 1U-N ) + (1W-N )

2w

2n

W

418V=10.06V+408.2V

2v

2) 1U-2W = 1U-2V 403V=403V 3)1V-2V < 1V-2W 409V<423V

1V

1W 10. Functional Checks 1

OTI

2

WTI

3

: Alarm Trip Alarm

OK OK OK

Trip

OK

Buchholz Relay

OK

Alarm 4

Low Oil Level

Trip

OK

Alarm

OK

1. WTI CT : RATIO

: 2667 / 1.5 A

VA : 7.5

CLASS : 5.0

IR TEST: Primary-Secondary: not possible Resistance: Test Performed by IMC Name : Design : Signature & Date

Secondary-Earth

: 248 MΩ

S1-S2:4.2 Ω Witnessed by MEL Name

Witnessed by BHEL Name

Witnessed by HNPCL/STEAG Name

Designation Signature & Date

Designation Signature & Date

Designation Signature & Date

CLIENT : M/s. Bharat Heavy Electricals Ltd- PSER.

DATE :13/07/2013 Sheet No 5 of 5

PROJECT-2X520 MW HNPCL,VIZAG

TEST REPORT FOR TRANSFORMERS

2. NCT: RATIO

: 3150 / 1 A

CLASS : PS

Vk : (40 RCT+200 V) I e =<30 mA @ Vk / 2 (i) Insulation Resistance Test : C1 – C2

-6.7 M

C1 – E - 7.06 M C2 – E - 1.8 M

(ii)

Winding Resistance

:

C1 – 12.5Ω C2 – 19.7 Ω

(iii) Polarity Test

:

(iv) Ratio Test

:

Applied current in primary

OK 3150 / 1A

Measured Current in Secondary Core 1

Core 2

315

100 mA

100.0mA

787.6

0.26A

0.26A

1575

0.5

0.49

Saturation Test for NCT : Test Performed by IMC Name : Design : Signature & Date

Witnessed by MEL Name

Witnessed by BHEL Name

Witnessed by HNPCL/STEAG Name

Designation Signature & Date

Designation Signature & Date

Designation Signature & Date

CLIENT : M/s. Bharat Heavy Electricals Ltd- PSER.

DATE :13/07/2013 Sheet No 6 of 5

PROJECT-2X520 MW HNPCL,VIZAG

TEST REPORT FOR TRANSFORMERS Vk: ≥ (40RCT+200V) Ie : <30mA@ Vk ∕ 2=310 V Injected Voltage in sec (volts) 123.5 247 370.5 494 543.4

Test Performed by IMC Name : Design : Signature & Date

Measured Current in sec (mA) 0.62 1.13 1.52 1.93 2.08

Witnessed by MEL Name

Witnessed by BHEL Name

Witnessed by HNPCL/STEAG Name

Designation Signature & Date

Designation Signature & Date

Designation Signature & Date