Loading documents preview...
Gunnar Stranne
©
ABB Power Technologies AB, 2005
Rio de Janeiro April 23-25, 2006
2006-04-20 PTSX Gunnar Stranne
Transformer protection IED RET 670
Transformer protection IED RET670 Introduction – features and applications Differential protection functions Restricted Earth Fault protection function High Impedance Differential protection function Some additional functions and application examples
©
ABB Power Technologies AB, 2005
Preconfigured ready-made packages Summary and conclusions
2006-04-20 PTSX Gunnar Stranne 2
Benefits of RET670 – outstanding features Half cycle operating time – a new performance standard! One or two differential functions Differential function compensated automatically for tap changer position for improved sensitivity An additional sensitive and fast differential function based on negative sequence current - ~1% sensitivity High impedance or low impedance restricted earth-fault differential protection for each winding Possibility to use multi - CT arrangements for increased differential protection stability Tap changer control
©
ABB Power Technologies AB, 2005
Breaker control , measuring, monitoring and recording
2006-04-20 PTSX Gunnar Stranne 3
Applications Power transformers, including autotransformers, reactors and generator transformer blocks Two or three vector group (or winding) transformers Single- or multi circuit breaker arrangements
©
ABB Power Technologies AB, 2005
Up to six stabilized 3-phase current inputs
2006-04-20 PTSX Gunnar Stranne 4
Three-winding Transformer Three-winding variant up to 6 restraint three-phase CT inputs Ensures enhanced throughfault stability for multibreaker arrangements
©
ABB Power Technologies AB, 2005
Tap changer control
2006-04-20 PTSX Gunnar Stranne 5
Auto Transformer Phased segregated biased differential protection for Autotransformers in 1½ CB applications Serial and common windings
©
ABB Power Technologies AB, 2005
Up to 4 three-phase CT inputs
2006-04-20 PTSX Gunnar Stranne 6
Phase Shifting Transformer Transformer key data 1400 MVA 400/ 400 kV +-25° 1200 tons 32 MUSD contract
Project aspects Cooperation between End User, Relay Manufacturer & PST Manufacturer is of outmost importance
©
ABB Power Technologies AB, 2005
Cooperation required in the very early design stage of the project
2006-04-20 PTSX Gunnar Stranne 7
Shunt Reactor Protection And Control Protection Phase segregated biased differential protection High-impedance differential protection Over/under-voltage protection
Switching control for lines and busses
©
ABB Power Technologies AB, 2005
RET 670 is optimized for each application with maximum reliability and short operating time 2006-04-20 PTSX Gunnar Stranne 8
Step-up Transformer In Power Stations Overall differential protection of a generator – transformer unit Differential protection for the step-up transformer and/or the auxiliary transformer
©
ABB Power Technologies AB, 2005
Back-up protection functionality
2006-04-20 PTSX Gunnar Stranne 9
Complementary Protection Functions Full scheme distance Overcurrent – 19 inverse Thermal overload Breaker failure Voltage functions with high reset ratio
©
ABB Power Technologies AB, 2005
RET 670 fits all power system elements that require unit and additional protection functionality
2006-04-20 PTSX Gunnar Stranne 10
Differential Protection Two-winding or three-winding functions Two-winding variant up to 4 three-phase CT inputs Enhanced through-fault stability for multi-breaker arrangements
Three-winding variant up to 6 three-phase CT inputs
©
ABB Power Technologies AB, 2005
Enhanced through-fault stability for multi-breaker arrangements
2006-04-20 PTSX Gunnar Stranne 11
Transformer Protection Terminal Differential Protection of 2- winding Power Transformers 2- winding power transformer 2- winding power transformer with unconnected delta tertiary winding 2- winding power transformer with 2 circuit breakers on primary side 2- winding power transformer with 2 circuit breakers on secondary side
©
ABB Power Technologies AB, 2005
- winding power transformer with 2 circuit breakers on both sides 2006-04-20 PTSX Gunnar Stranne 12
Transformer Protection Terminal Differential Protection of 3- winding Power Transformers 3- winding power transformer with all 3 windings connected 3- winding power transformer with 2 circuit breakers on (any) one side, (e.g. 2 parallel power lines on one side)
©
ABB Power Technologies AB, 2005
3- winding power transformer with 2 circuit breakers on 2 out of 3 sides, (e.g. a meshed power network) Note! Also 3-out of 3 with 2 breakers is possible. 2006-04-20 PTSX Gunnar Stranne 13
Differential Protection A differential current does not always mean there is a fault in the transformer Inrush current in power transformers Saturation of current transformers Overexcitation Tap changer position etc.
©
ABB Power Technologies AB, 2005
Means of coping with these situations must be included in the design
2006-04-20 PTSX Gunnar Stranne 14
Differential Protection Ability is included to handle two tap changers, i.e. one tap changer per winding on any two windings Functionality Three-section settable restrain characteristic High set unrestrained operation Idiff Idunre
Unrestrained operation
operate
©
ABB Power Technologies AB, 2005
1.0 pu restrain
Idmin 1.25 pu 2006-04-20 PTSX Gunnar Stranne 15
Ibias
Transformer Inrush Current Stabilization Second harmonic stabilisation Wave form stabilisation wave block
CT saturation cause a second harmonic component in the secondary current
©
ABB Power Technologies AB, 2005
Transformer inrush currents contain a percentage of second harmonic current. This is used for discrimination but second harmonic blocking normally causes delayed operation in case of CT saturation. It is also possible to monitor the shape of the differential current signal. The low-current gap measurement indicates inrush. 2006-04-20 PTSX Gunnar Stranne 16
Transformer Inrush Current Stabilisation Internal fault followed by CT saturation
©
ABB Power Technologies AB, 2005
Delayed trip of the restrained differential function due to the traditional use of second harmonic blocking (Set level 15 %)
2006-04-20 PTSX Gunnar Stranne 17
Overvoltage Stabilization The fifth harmonic component is used for stabilization
Magnetizing current at system overvoltage
3
iL1
2
iL2
1
iL3 0
-1 -2 -3
©
ABB Power Technologies AB, 2005
The fifth harmonic component appears as a characteristic quantity in the transformer magnetizing current during overvoltage.
2006-04-20 PTSX Gunnar Stranne 18
Differential Protection DIFP- application
Two- and three winding applications Stabilization of up to 6 inputs Inrush current stabilization Second harmonic Waveform Phase segregated Selectable ”Cross-blocking” 5th harmonic stabilization at overvoltage
©
ABB Power Technologies AB, 2005
Sensitivity influenced by tap changer position (selectable) Selectable subtraction of zero sequence currents 2006-04-20 PTSX Gunnar Stranne 19
Differential Protection Blocking condition: 2nd harmonic, 5th harmonic waveblock, cross block Neg Seq Int / internal Ext Fault Discriminator sensitive
restrained
&
&
≥1
TRIP
unrestrained
©
ABB Power Technologies AB, 2005
START
2006-04-20 PTSX Gunnar Stranne 20
Differential Protection
©
ABB Power Technologies AB, 2005
Testing RET670 for maximum performance Fault detection in 7 ms!
2006-04-20 PTSX Gunnar Stranne 21
Negative sequence current differential function Internal / external fault discriminator
©
ABB Power Technologies AB, 2005
Based on the measurement of negative sequence current
2006-04-20 PTSX Gunnar Stranne 22
Negative sequence current differential function Before comparison, all negative sequence currents are compensated for turns ratio and vector group phase displacement External fault: 180°relative phase displacement Internal fault: 0°relative phase displacement
IminNegSeq 2% - 20% Default 4%
©
ABB Power Technologies AB, 2005
NegSeqROA 30°– 120° Default 60°
2006-04-20 PTSX Gunnar Stranne 23
Negative sequence current differential function An internal fault with heavy CT saturation Directional Comparison Criterion: Internal fault as seen from the HV side 90
excursion from 0 degrees due to CT saturation
60
120 35 ms
30
150
180 external fault region
0
0.5 kA
210
330 1.0 kA
ABB Power Technologies AB, 2005
©
definitely an internal fault
240
300 1.5 kA
trip command in 12 ms Internal fault declared 7 ms after internal fault occurred
270 HV side contribution to the total negative sequence differential current in kA Directional limit (within the region delimited by ± 60 degrees is internal fault) 2006-04-20 PTSX Gunnar Stranne 24
Negative Sequence Differential Protection An internal small transformer interturn fault was cleared by Buckholz relay and existing differential protection failed to detect fault Test of RET 670 with recorded signals proved successful Directional Comparison Criterion: Internal fault as seen from the HV side 90
If one or the other of currents is too low, then no measurement is done
60 (negSeqROA = ± 60 deg)
120
150
30
8
180 External fault region
20 A
210
10
19
0
330
steady-state position for this internal fault Internal fault declared 12 ms after fault
30 A 40 A
©
ABB Power Technologies AB, 2005
240
50 A
300 270 Contribution to total neg. seq. diff. current from HV side (in A) Directional limit (within ± negSeqROA degrees is internal fault)
2006-04-20 PTSX Gunnar Stranne 25
Negative sequence current function - summary Fast operating times – half cycle Start from ordinary differential protection required, but blocking conditions are bypassed Sensitive negative sequence protection Gives sensitive turn-to-turn fault protection The trip request must be confirmed several times in succession before the final trip request is placed – this security feature causes an increase in the operating time
©
ABB Power Technologies AB, 2005
The operating time is about 30ms for very lowlevel turn-to-turn faults This sensitive negative sequence protection is blocked for high fault current conditions 2006-04-20 PTSX Gunnar Stranne 26
Restricted Earth Fault Protection Operate characteristic diff current in pu
minimum base sensitivity 50 % default base sensitivity 30 % maximum base sensitivity 5 %
©
ABB Power Technologies AB, 2005
Step : 1 % transformer rated current
0 6
2006-04-20 PTSX Gunnar Stranne 27
1
2
1.25 pu
3
4
5
bias current in per unit
Restricted Earth Fault Protection Internal fault
External fault
zone of protection
IL1
IL1
IL2
IL2
IL3
IL3
3I0
IN
IFAULT
IN
IFAULT
zone of protection
IN
3I0
internal fault 3I0
external fault ROA
MTA ABB Power Technologies AB, 2005
©
reference is neutral current -IN
operate for internal fault
IN
ROA
restrain for external fault
3I0
ROA
MTA
operate for internal fault
ROA
-IN restrain for external fault reference is neutral current
2006-04-20 PTSX Gunnar Stranne 28
Differential Protection Switch-on-to-fault Built-in logic to improve operating speed for switch-on-to-fault condition Possible to record the differential currents and/or bias current by the disturbance recorder channels 31-40 Differential currents Instantaneous or RMS Bias current
©
ABB Power Technologies AB, 2005
RMS
2006-04-20 PTSX Gunnar Stranne 29
Restricted Earth Fault Protection
3I0 < 3% of Ibase IN > 50% of Idset Directional check
≥1
≥1
TRIP
©
ABB Power Technologies AB, 2005
START
2006-04-20 PTSX Gunnar Stranne 30
Restricted Earth Fault Protection Up to 4 three-phase CT inputs makes it possible to handle autotransformers in 1½ CB applications Enhanced function for autotransformer applications I1 I2 I3
I3P
I1 I2 I3
I3P
©
ABB Power Technologies AB, 2005
I1 I2 I3
I
2006-04-20 PTSX Gunnar Stranne 31
I3P
I1N
REFx I1 I3PRI1 I3PRI2 I3SEC1 I3SEC2
Restricted Earth Fault Protection Switch-on-to-fault Built-in logic to improve operating speed for switch-on-to-fault condition Possible to record differential currents and/or bias current by the disturbance recorder Differential currents Instantaneous or RMS Bias current
©
ABB Power Technologies AB, 2005
RMS
2006-04-20 PTSX Gunnar Stranne 32
High Impedance Differential Protection Three instances → 1 or 3 high impedance differential External stabilizing resistors & metrosils are used Typical applications High impedance REF – Restricted Earth Fault protection Tee - feeder differential protection
©
ABB Power Technologies AB, 2005
Bus differential
2006-04-20 PTSX Gunnar Stranne 33
Overexcitation Protection V/Hz measurement Positive sequence or single phase-to-phase voltage Transformer magnetic core cooling time constant setting IEEE inverse time and User defined trip curves available
©
ABB Power Technologies AB, 2005
Alarm level as percentage of trip level
2006-04-20 PTSX Gunnar Stranne 34
Thermal Overload protection function
49-1 Ith
86/94 I->O
©
ABB Power Technologies AB, 2005
49-1 Ith
2006-04-20 PTSX Gunnar Stranne 35
•Two thermal overload functions •Tripping of load will give cooling chance to restore normal temperatures. •Settable thermal time constants for short circuits and low overloads •Measures RMS current •Lockout reset level (in % of heat content trip value)
86/94 I->O
Alarm levels 1 and 2 (each in % of heat content trip value)
TOF/TUF/RVF(df/dt) – Frequency Protection Over-frequency and under-frequency Six steps OF & UF – settable frequency and time delay Measures Ph-Ph or Positive sequence voltage Under-voltage blocking Df/dt with positive or negative derivative setting High accuracy Short operating time Accuracy 2 mHz for three phase
©
ABB Power Technologies AB, 2005
Accuracy 10 mHz for single phase
Voltage dependent tripping time possible! 2006-04-20 PTSX Gunnar Stranne 36
Frequency Protection - Applications Under frequency Load shedding systems Remedial action schemes
Over frequency Generation shedding Remedial action schemes
Rate-of-change of frequency Generation shedding Load shedding
©
ABB Power Technologies AB, 2005
Remedial action schemes
2006-04-20 PTSX Gunnar Stranne 37
Six Pre-configured RET 670 - Ready To Use RET 670-A30 Two winding transformer, single circuit breaker RET 670-B30 Two winding transformer, multi circuit breaker (1½ CB or double CB on either, or both, sides of the transformer) RET 670-A20 Three winding transformer, single circuit breaker RET 670-A31 Three winding transformer, single circuit breaker, current and voltage inputs RET 670-A40 Three winding transformer, single circuit breaker (1½ CB or double CB on any, or all, sides of the transformer)
©
ABB Power Technologies AB, 2005
RET670 –B40 Three winding transformer, multi circuit breaker (1½ CB or double CB on any, or all, sides of the transformer)
2006-04-20 PTSX Gunnar Stranne 38
Two Winding Transformer – Single Circuit Breaker RET 670-A30
DR 50BF 3I>BF 50/51-1 3I> 51N-1
I
86/94 I->O
87N-1 Ind> 87T 3Id/I>
52PD PD
87N-2 Ind>
59N UN
24 U/f>
59N UN
59 3U>
51N-2
50BF 3I>BF
©
ABB Power Technologies AB, 2005
25/27 SC/VC
90 VCTR 50/51-2 3I> 59 3U> 27 3U<
60 FF
2006-04-20 PTSX Gunnar Stranne 39
DR
O5
O4
O2
27 3U<
I
60 FF
81O/81U f>
86/94
21 Z<
I->O Contr Interl
O1
O3
Two Winding Transformer – Multi Circuit Breaker RET 670-B30 25/27
50BF 3I>BF
2* SC/VC
DR 50BF 3I>BF
Σ 51N-1
I
50/51-1 3I>
86/94 I->O
87N-1 Ind> 87T 3Id/I>
ABB Power Technologies AB, 2005
©
SC/VC
2006-04-20 PTSX Gunnar Stranne 40
O6 O4 O5
O2
27 3U<
50/51-2 3I>
86/94 I->O
21 Z<
59 3U> 27 3U<
60 FF
52PD 2* PD
59 3U>
I
25/27
O8
59N UN
51N-2
50BF 3I>BF
2* f>
50BF 3I>BF
59N UN
60 FF
81O/81U
24 U/f>
87N-2 Ind>
O7
DR
Contr Interl
O1
O3
Three Winding Transformer – Single Circuit Breaker DR 50BF 3I>BF 50/51-1 3I>
RET 670-A20 86/94 I->O
60 FF 25/27
O6
SC/VC 24 U/f>
O4
51N-3 51N-1
I
50BF 3I>BF
I
87N-1 Ind> 87T 3Id/I>
87N-3 INd>
87N-2 Ind>
59N UN
59N UN
50/51-3 3I>
59 3U>
51N-2
50BF 3I>BF 25/27
©
ABB Power Technologies AB, 2005
SC/VC
60 FF 2006-04-20 PTSX Gunnar Stranne 41
50/51-2 3I> 59 3U> 27 3U<
DR
O2
27 3U<
I
60 FF
O5
86/94 I->O 86/94 I->O
21 Z< O1 Contr Interl 81O/81U f> 52PD PD
O3
O7
Three Winding Transformer – Multi Circuit Breaker 81O/81U
RET670 –B40 DR
50BF 3I>BF
Σ 51N-1
I
50BF 3I>BF 50/51-1 3I>
86/94 I->O
24 U/f>
87N-1 Ind> 87T 3Id/I>
ABB Power Technologies AB, 2005
©
25/27 SC/VC
59 3U>
42
60 FF
DR
O4
O5
59N UN 59 3U>
27 3U<
2006-04-20 PTSX Gunnar Stranne
87N-3 INd>
I
50/51-2 3I>
O6
I
51N-2
50BF 3I>BF
O8
51N-3
59N UN
60 FF
52PD PD 60 FF 25/27
O7
SC/VC
87N-2 Ind>
50BF 50/51-3 3I>BF 3I>
f>
86/94 I->O 86/94 I->O
O2
27 3U< 21 Z<
Contr Interl
O1
O3
Benefits of RET670
©
ABB Power Technologies AB, 2005
Functional flexibility Configuration flexibility High performance User friendly Pre-defined packages IED 670 series member means;
Every step you take - ABB has the solution 2006-04-20 PTSX Gunnar Stranne 43
Less spare parts needed Simplified engineering and maintenance Common look and feel and common tools Extensive Self-supervision Remote communication flexibility Easy integration in Substation Automation Systems
Benefits of RET670 – outstanding features Fast, sensitive and secure differential function – tap-changer compensated Fast and sensitive negative sequence differential function -> half cycle operation Multi-CT inputs increases security and functionality High or low impedance restricted earthfault winding differential funcions Extensive function library and options Up to 12 general I -V functions; distance and extra differential functions High reset voltage functions
©
ABB Power Technologies AB, 2005
Extendable analog and digital I/O Full control functionality Large HMI option 2006-04-20 PTSX Gunnar Stranne 44