Loading documents preview...
THIS SUBMISSION IS DECLARED TO BE STRICTLY IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT
SIGNATURE:
PHASE - 12
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE XII PACKAGES - S-1, S-6, S-7 CONTRACT No. GTC/643A/2014 CONSULTANT:
SUBSTATION NAME
PROJECT DRAWING NUMBER
COMMON
0
-
29-04-16
REV.
STAT.
DATE
PH12-3A-10-40-T101
Issued Information Issued for for Comments MODIFICATION
PP
DMK
RLG
DRAWN
CHECKED
APPROVED
CONTRACTOR NAME
SUBCONTRACTOR NAME
SIEMENS CONSORTIUM – SIEMENS AG - SIEMENS WLL MANUFACTURERS DRAWING NO.
DRAWING/DOCUMENT TITLE
(4)G719EA - GG9004 – U2038 Hardware Specification of Substation Control System DATE
NAME
DRAWN
29-04-16
PP
CHECKED
29-04-16
DMK
APPROVED
29-04-16
RLG
SIGNATURE
SIZE A4
REV 0 Sheet 1 of 16
SCS HARDWARE SPECIFICATIONS Qatar Power Transmission System Expansion - GTC/643A/2014
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
TABLE OF CONTENTS 1.
GENERAL................................................................................................................................................................... 3 1.1. Introduction ...................................................................................................................................................... 3 1.2. Abbreviation Used ........................................................................................................................................... 4 2. HARDWARE FOR IPC(STATION SERVER, GATEWAY, HMI, EPC/HMI, EPC, DIP) ............................................... 6 2.1. Monitor Details ................................................................................................................................................ 6 3. HARDWARE DETAILS FOR LAPTOP......................................................................................................................... 7 4. GPS ........................................................................................................................................................................... 8 5. FIREWALL .................................................................................................................................................................. 9 6. KVM CONSOLE ....................................................................................................................................................... 10 7. ETHERNET SWITCH ................................................................................................................................................. 11 8. BAY CONTROL UNIT 6MD8 ................................................................................................................................... 12 8.1. Functions ........................................................................................................................................................ 12 8.2. Housing construction ..................................................................................................................................... 12 8.3. Binary inputs and outputs / measuring inputs.............................................................................................. 12 8.4. Secondary voltage .......................................................................................................................................... 12 8.5. Aux Supply ...................................................................................................................................................... 13 8.6. Communication Interface .............................................................................................................................. 13
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 2 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
1. GENERAL 1.1. Introduction This document describes the hardware equipment of Station Control System (SCS) at Phase XII substations of Contract GTC/643A/2014. It includes technical information requested to clarify and freeze ambiguous specification in order to meet the customer‘s requirements. The configuration of the system will be built based on these specifications. Any modification of the specifications during the project might have impacts on planning. The substation control systems for the following substation shall be covered in this document: Package Name of Substations Voltage level S1 BUL HEMMAID 400/132/11kV S1 Al SAKHAMAH SUPER 400/132/11kV S6 AL THUMAMAH CENTRAL 132/11kV S6 WAKRAH REPLACEMENT 132/66/11kV S6 TYPE B-1 132/11kV S6 TYPE B-2 132/11kV S7 WAKRAH SOUTH 66/11kV S7 DIA 66/11kV S7 KHALIFAT 2 66/11kV S7 UMM SHAHRAIN 66/11kV S7 TYPE B 66/11kV
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 3 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
1.2. Abbreviations AI BCU BDEW BI BO CFC CHAP CIP CRP CT DCC DDR3 DGCC DHCP DI DIN DIP EPC FO Gateway
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Analog Input Card Bay Control Unit Bundesverband der Energie- und Wasserwirtschaft. Binary Input Card Binary Output Continuous Function Chart Challenge Handshake Authentication Protocol Critical Infrastructure Protection Control & Relay Panel Current Transformer Distribution Control Centre Double Data Rate type three Doha Grid Control Centre Dynamic Host Configuration Protocol Digital Input Card Deutsches Institut für Normung Device Interface Processor Engineering PC Fiber Optic Communication Interface for NCC / DGCC / DCC interface
Page 4 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
GPS HWS IEC IMS IPC KVM LED MAC NERC OSD PAP PC RAID RAM RJ45 RSG2488 SATA SCS SNMP SS SSH SSL TCP/IP USB VRRP VT
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Global Positioning System HMI Work Station International Electrotechnical Commission Integrated Monitoring Station Industrial PC Keyboard Video Mouse Light-emitting Diode Media Access Control North American Electric Reliability Corporatio On Screen Display Password Authentication Protocol Personal Computer Redundant Array of Independent Disks Random Access Memory Registered Jack 45 Ruggedcom IEC 61850 switches Serial Advanced Technology Attachment Substation Control System Simple Network Management Protocol Station Server Secure Shell Secure Socket Layer Transmission Control Protocol / Internet Protocol Universal Serial Bus Virtual Router Redundancy Protocol Voltage Transformer
Page 5 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
2. Hardware for IPC(Station Server, Gateway, HWS, EPC/HMI, EPC, DIP) Description
Specification
Model
SIMATIC IPC847D
Chassis Processor
RACK PC, 19", 4U XEON E3-1275 V3, 3.5(3.9) GHZ, 8MB CACHE, TB, VT-D, AMT)
RAM Memory Optical Drive
16 GB DDR3 SDRAM (2X 8GB), DUAL CHANNEL DVD +/- RW (SLIM) RAID1, 1 TB (2X 1 TB HDD SAS, DATA MIRRORING), DATA MIRRORING), REMOVABLE DISK, HOT-SWAP 4X GBIT ETHERNET (IE/PN), RJ45
Hard Disks Network Ports Operating System
4 X FO LAN Ports Windows 7 Professional (64bit) 1X DVI-I; 2X DISPLAYPORT;
Ports
1X COM1; 2X PS/2; AUDIO; 4X USB 3.0 INCL.1X INTERNALLY; 3X USB 2.0
Slots
BOARD WITH 11 SLOTS: 7X PCI, 3X PCIE X4,1X PCIE X16;
Graphics Card
on Motherboard
Power Supply
2 X 110/240V REDUNDANT POWER
Power Input
240VAC, 50Hz
Operating Temperature
0 to 35° C
Place of Manufacture
Germany
2.1. Monitor Details Description Model
Specification FUJITSU B24W-7 LED
Diagonal Size Aspect ratio Resolution (native) Height adjust range Swivel angle Rated voltage range
61 cm (24-inch) 16:10 1,920 x 1,200 pixel 130mm 340° 100 V - 240 V
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 6 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
3. Hardware details for LAPTOP Description
Specification
Model
Fujitsu CELSIUS H730
Processor RAM Memory
CORE I7-3540M Processor, (3.0 GHz, upto 3.7 GHz,4MB) 8 GB DDR3 SDRAM
Optical Drive Hard Disks Display
DVD RW 1 TB 15.6 Inch
Operating System
Windows 7 Professional (64bit)
Power supply Rated voltage range
100 V - 240 V (AC Input)
Rated frequency range
50 Hz - 60 Hz
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 7 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
4. GPS Description Model Housing Network Interface Display
Ports
Network Time Protocol Power Input Operating Temperature Humidity Place of Manufacture Antenna Connector
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Specification LANTIME M300 19" Rack mounted 6x10/100Mbit with RJ45 LC-display, 2x40 characters, with backlight Power Supply (AC/DC) Error relay output GLN antenna Network interface 10/100 Mbps Rj45 NTP ,SNTP 100-240 V AC (50/60 Hz) 0 to 50° C 85% max. Germany dielectric patch antenna N-Type, female
Page 8 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
5. Firewall Description Model Ports
Protocols
Security Application Function
Power Supply Power Input Power Consumption Operating Temperature Design Place of Manufacture
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Specification RX1500 12-ports 10/100TX WAN: - Frame Relay RFC 1490 or RFC 1294 - PPP RFC 1661, 1321, 1334, PAP, CHAP Authentication - Multilink PPP RFC 1990 - GOOSE messaging support IP: - Routing :OSPF, BGP, RIPv1 and 2 - VRRP - Traffic control, NTP Server, IP Multicast Routing - DHCP Agent (Option 82 Capable) Multi-level passwords SSH/SSL encryption Enable/disable ports, MAC based port security Port based network access control SNMPv3 encrypted authentication and access security Hot Swapable 85 to 264 V AC 50W -40 to 85° C 19" rack Mount Canada
Page 9 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
6. KVM Console Description
Specification
Model
KL1508AM / KL1516AM
Chassis Diagonal Size
1U Rack mounted 17" LED-backlit LCD monitor
Max. Resolution
Port Selection
1280 x 1024 The LCD module rotates up to 120 degrees for a more comfortable viewing angle. KL1508AM : 8 KL1516AM : 16 OSD, Hotkey, Pushbutton Switches
Keyboard & Mouse
PS/2
Flexibility Computer Connections
Keyboard : 1x6 pinMini-DIN F Viedo :1xHDB-15F Mouse : 1x6 pin Mini-DIN F Connectors
KVM Ports : 8x RJ-45 F Daisy Chain : 1xDB-25 M FW Upgrade : 1xRJ-11 F Power : 1x3 prong AC socket External Mouse : 1x6 pin Mini-DIN F
Scan Interval (OSD Select)
1-255 secs.
I/P Rating
100-240V AC; 50/60Hz; 1A
Power Consumption
230V 27.4W
Power Input
100-240 V AC; 50/60Hz; 1A
Operating Temperature
0 to 40° C
Make
ATEN
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 10 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
7. Ethernet Switch IEC 61850 communication compliant Ruggedcom Ethernet switches shall be used for providing this Ethernet communication system. The Ruggedcom switches shall be having Copper and Fibre Optic ports for various types of interfaces Technical specification of Ethernet switches is as follows Description Model Transmission rate Number of electrical/optical connections / for network components or terminal equipment / maximum
Protocols
Security Application Function
Power Supply Power Input Power Consumption Operating Temperature Design Dimensions (H x W x D) Place of Manufacture
Specification RSG2488 10/100/1000 Mbit/s 28 (6x4-port modules plus 2x2-port modules) WAN: - Frame Relay RFC 1490 or RFC 1294 - PPP RFC 1661, 1321, 1334, PAP, CHAP Authentication - Multilink PPP RFC 1990 - GOOSE messaging support IP: - Routing :OSPF, BGP, RIPv1 and 2 - VRRP - Traffic control, NTP Server, IP Multicast Routing - DHCP Agent (Option 82 Capable) Multi-level passwords SSH/SSL encryption Enable/disable ports, MAC based port security Port based network access control SNMPv3 encrypted authentication and access security Hot Swappable 85 to 264 V AC 40W -40 to 50° C 19" rack Mount 1.74" x 17.36" x 11.9 Canada
Refer to the SCS Architecture document for connection details and the port quantities.
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 11 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
8. Bay Control Unit 6MD8
The Bay Controller is a universal control and automation device with optional protection function. It is designed for use in all voltage levels from distribution to transmission. The flexible hardware concept enables the exact fitting to all amounts of process data.
8.1. Functions Integrated bay controller with versatile protection functions for applications from medium to extra high voltage Control of up to 20 switching devices Synchrocheck, switchgear interlocking system and protection functions related to the switching device, such as circuit breaker tripping signal and automatic reclosing Integrated electrical Ethernet port J for engineering PC Supports integration into the station automation system with IEC 61850 Further communication protocols: IEC 60870-5-103, DNP3 over IP Up to four communication modules usable for different and redundant protocols (IEC 61850, IEC 60870-5-103, IEC 60870-5-104, DNP3 (serial+TCP), Modbus TCP) Ethernet redundancy protocols PRP and HSR Cyber Security in accordance with NERC CIP and BDEW whitepaper Powerful automation with CFC (Continuous Function Chart)
8.2. Housing construction Rugged hardware with an enclosed dust-proof housing for highest resilience against voltage, EMC, climate and mechanical stress according the product standard IEC 60255 and an extended temperature range from -25°C to + 70°C. Housing : 8/6 19”
8.3. Binary inputs and outputs / measuring inputs CT : 4 VT : 4 BO : 9 BI : 251 or as per requirement. LED : 32
8.4. Secondary voltage
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 12 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
CT Secondary : 1A PT Secondary : 110V AC
8.5. Aux Supply Aux Supply : 60-250 V DC or 100-230V AC
8.6. Communication Interface Communication interface : IEC 61850, Optical,Double, LC connector (EN 100)
9. SCS Panel Equipments 9.1. Exhaust Fan Description
Specification
Model
Rittal SK 3325107
Power Input Air Flow
230V AC 1Ph 156 cfm
Body Material Temperature Rating
Heat Resistant Self Extinguishing Plastic -10 to 55 deg C
9.2. Temperature Regulator Description
Specification
MLFB
Siemens 8MR2170-4E
Power Input
230V AC 1Ph
Type of mounting Response time Operating Temperature
terminal mounting 50 s 0 – 60 °C
9.3. Cubicle Illumination Lamp Description
Specification
Make
Philips CFL 14W
Power Input
240V AC 1Ph
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 13 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
9.4. Power Socket Description
Specification
Make
CPL
Rating Type
5A / 15A 3 Pin for Flat pin plug & ON / OFF Switches British Standards
9.5. Auto Regulated Resistor Anticondensation Description
Specification
Model
Siemens 8MR2130
Power Continuous heat output
AC/DC 120-240V 100W to 20 deg. C
9.6. Electronic Hooter Description
Specification
Model
Alan AUH - 1122
Power Input Type
110V DC / 220V AC Din rail mounting type Variable tone with adjustable tone control
9.7. Timer Description
Specification
MLFB
3RP1505-1AW30
Aux. Voltage
24-240V DC
Contact Mounting
1 CO Front Mount
9.8. DC Changeover relay . Description
Specification
MLFB
3RT2516-1BF40, 3RT2916-1BC00
Aux. Voltage
110V DC
Contacts Operating range Case Size
2NO+2NC 0.8-1.11 of rated voltage S00
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 14 of 15
Revision No.: 0
QATAR POWER TRANSMISSION SYSTEM EXPANSION – PHASE 12 Contract GTC/643A/2014 SCS Hardware Specification
9.9. AC MCB Description
Specification
Model
Siemens 5SL41
Poles Current ratings Tripping characteristic Breaking current capacity
Single 2A, 4A, 10A, 16A C 10KA
Aux contacts
1NO+1NC
9.10. DC MCB Description
Specification
Model
Siemens 5SL42
Poles Current ratings
Double 2A, 4A
Tripping characteristic Breaking current capacity Aux contacts
C 10KA 1NO+1NC
Project No.: GTC/643A/2014 Doc. No. : PH12-3A-10-40-T101
Page 15 of 15
Revision No.: 0