THIS SUBMISSION IS DECLARED TO BE STRICTLY IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT
SIGNATURE:
PHASE-12
QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 SUBSTATIONS - PACKAGE S-10, S-13 & S-14 CONTRACT NO. GTC/643G/2014 CONSULTANT :
The Gate (16th FLOOR, Doha, Qatar, PO Box 13885. TEL: +974 4020 6450, FAX: +974 4020 6451 www.wspgroup.com / www.pbworld.com SUBSTATION NAME :
PROJECT DRAWING NUMBER :
COMMON
PH12-3G-10-40-T001
C B1
_
7/12/2016
Re-issued for Construction ar per DTA-16-4205
MV
DMK
RLG
B
B
20/10/2016
Issued for Construction ar per DTA-16-1448
MV
DMK
RLG
A
B
5/5/2016
Issued for Approval as per DTA-16-0262
MV
DMK
RLG
0
B
10/2/2016
Issued for comments
MV
DMK
RLG
REV.
STAT.
DATE
MODIFICATION
PREPARED CHECKED APPROVED
SUBCONTRACTOR NAME :
CONTRACTOR NAME :
MANUFACTURERS DRAWING NO:
DRAWING/DOCUMENT TITLE:
(4)G719EA-HG9030-U2002 SIGNATURE
Technical data sheet for Substation Control System
DATE
NAME
PREPARED
10/2/2016
MV
CHECKED
10/2/2016
DMK
SIZE
SCALE : NTS
REV.
APPROVED
10/2/2016
RLG
A4
Sheet No. 01 of 28
B1 C
VOLUME 4
SECTION 3.4.10
PAGE 2 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS
LIST OF CONTENTS
PAGE
COVER SHEET
1
LIST OF CONTENTS
2
INTRODUCTION PAGE
4
1
SUBSTATION CONTROL SYSTEM
5
2
GENERAL
5
2.1 COMMON FOR SERVER / GATEWAYS / HMI / EWS
5
2.2 STATION SERVER
6
2.3 GATEWAY COMPUTER
6
2.4 OPERATOR WORKSTATIONS / HMI
7
2.5 OPERATOR DESK
7
2.6 COLOUR VISUAL DISPLAY UNIT (VDUS)
8
2.7 SUBSTATION LOCAL AREA NETWORK (LAN)
8
2.8 MANAGED ETHERNET SWITCH
9
2.9 FIREWALL
10
2.10 COLOUR PRINTERS (ONLY FOR 400KV SUBSTATIONS)
11
BAY CONTROL UNIT HARDWARE
12
3.1 GENERAL
12
3.2 BCU ENCLOSURE
13
3.3 IEC STANDARDS (OR EQUIVALENT)
14
3.4 BCU FUNCTIONS
14
3.5 BCU CONFIGURATION
15
3.6 PROCESSING UNIT
15
3.7 COMMUNICATIONS
15
3.8 POWER SUPPLY MODULE
16
3.9 DIGITAL INPUT MODULE
17
3
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 3 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS
3.10 COMMAND OUTPUT MODULE
18
3.11 DIGITAL OUTPUT MODULE
18
3.12 ANALOGUE INPUT MODULE
19
3.13 DIRECT AC CONNECTION VOLTAGE
19
3.14 DIRECT AC CONNECTION CURRENT
20
BCU SOFTWARE
20
4.1 GENERAL REQUIREMENT
20
4.2 CAPABILITY
20
4.3 SYSTEM SOFTWARE
21
4.4 STANDARD FUNCTIONS PROGRAMS
21
4.5 ANALOGUE MEASUREMENTS, SCANNING AND TRANSMISSION PROGRAMS
21
4.6 FUNCTIONS AND CAPABILITIES
21
4.7 ALARM AND EVENT HANDLING
22
4.8 SUPERVISORY CONTROL PROGRAMS: FUNCTIONS AND CAPABILITIES
22
4.9 DATA PROCESSING PROGRAMS: FUNCTIONS AND CAPABILITIES
22
GATEWAY SOFTWARE
23
5.1 GENERAL REQUIREMENTS
23
5.2 CAPABILITY OF:
23
5.3 SYSTEM SOFTWARE
23
6
HMI SERVER /WORKSTATION SOFTWARE
24
7
GPS RECEIVER
25
8
LAPTOP
25
9
FIBER OPTIC PATCH CABLES
26
4
5
10 SYSTEM SECURITY REQUIREMENTS
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
26
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS
SECTION 3.4.10
PAGE 4 OF 27
VOLUME 4
SECTION 3.4.10
PAGE 5 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS SUBSTATION CONTROL SYSTEM 1.
Substation Control System
2.
General
UNIT
System supplier
DATA Required
Offered
Yes
SIEMENS SICAM PAS
-
SCS System Name
Yes
-
System version
Yes
-
Place of integration
Yes
V 8.x SIEMENS,INDIA
2.1.
SCS panel make/place Common for Server / Gateways / HMI / EWS
2.1.1.
Manufacturer
Yes
Siemens
2.1.2.
Model
Yes
IPC847D
2.1.3.
Type
Industrial
Yes
2.1.4.
Country of Origin
2.1.5.
Suitable for 24 x 7 operation
2.1.6.
Processor -
2.1.7.
2.1.8.
Germany
Type (Minimum)
Clock speed (minimum)
Yes
Yes
Intel core i7 (Xeon) Processor or Higher
Xeon E3-1275 v3
GHz
3.5 to 3.9 GHz
Memory size -
Supplied (minimum)
GB
-
Supportable/expandable
GB
Storage size Configuration
16GB
32GB
-
Storage Suitable for 24 x 7 operation
RAID Configuration Hot-Swappable type Yes
-
Storage Type
SCSI/SAS/ SSD
-
Supplied (minimum 1 TB)
2.1.9.
Optical Storage DVD RW
2.1.10.
Operating system
TB
As required to store 1 year Data Yes MS Windows
Updation of Microsoft recommended fixes and history to be provided
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
16GB
Up to FAC
Yes
SAS (ST1000NM0023) 1 TB
Yes
Yes Windows 7 Professional (64bit) Microsoft Recommended HQ tested hot fixes shall be provided up to FAC.
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 6 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.1.11.
Antivirus Software Validity
Years
Antivirus Updation through Centralized Client /Server in S/S
Up to FAC
Yes
Yes
Yes
2.1.12.
Operating temperature range
°C
0 to 35 °C
2.1.13.
Maximum relative humidity
%
2.1.14.
Nominal voltage
240AC
5% to 80% at 25 °C (no condensation) 240 VAC
2.1.15.
Redundant Power Supply Modules (Hot Swappable)
Yes
Yes
2.1.16.
Operating frequency
Hz
50
50Hz
2.1.17.
Power requirement
W
2.1.18.
Mean time between failure
h
VAC
300 W at 77 % efficiency 170,000 hours @ 25 °C 110,000 hours @ 35 °C
2.1.19.
Mean time to repair
2.1.20.
Mounting
2.1.21.
Type test
h
-
Witnessed by independent LAB
-
Date issued
2.1.21
Communication Protocols in Substation
2.2.
Station Server
2.2.1. 2.2.2.
Software supplied (Attach a list of software other than operating systems to be installed) Remote Access of Server through KVM Switches
2.2.3.
Configuration of Remote Access from HMI/EWS
2.3.
Gateway Computer
2.3.1.
Communication Protocols To Control Centre(s) -
2.3.2.
NCC Main & Standby IEC 60870-5-104 (101 if applicable) DCC Main and Standby IEC 60870-5-104
Dual LAN ports for Control Centre Communication
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
19” Rack
53 h, From the time, when IPC reaches the repair center. Yes
yes
Yes
Not older than 5 years IEC 61850 over dual fibre optic
Yes
Required
SICAM PAS
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 7 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.3.3.
List other operating Protocols available/supported
Yes
IEC 61850
2.3.4. 2.3.5.
Software supplied (Attach a list of software other than operating systems to be installed) Remote Access of Server through KVM Switches
Required
SICAM PAS
Yes
Yes
2.3.6.
Configuration of Remote Access from HMI/EWS
Yes
Yes
2.4.
Operator Workstations / HMI
2.4.1.
Mouse
Yes
Yes
2.4.2.
Keyboard
Yes
Yes
2.4.3.
Literature reference for principle of operation
Yes
2.4.4.
Yes
2.4.5.
Software supplied (Attach a list of software other than operating systems to be installed) MS Office Software with PDF Writer
Yes
Yes
2.4.6.
Operator interface screens
Dual
Yes
2.4.7.
LAN Interface for Remote Access from Control Center
Yes
Yes
2.4.8.
LAN Interface for PMR files uploading to Control Center
Yes
Yes
2.5.
Operator Desk
2.5.1.
Manufacturer
Yes
Knurr
2.5.2.
Type of construction
Yes
Aluminium / Steel extrusions
2.5.3.
Country of Origin
2.5.4.
Placing of the Industrial Computer with Suitable Ventilation
Yes
Yes
2.5.5.
Method of mounting VDUs
Yes
2.5.6.
Industrial Grade Power Sockets
Yes
Vertical at top the desk Yes
2.5.7.
Provision for Routing Communication Cables & Power Cables
Yes
Yes
2.5.8.
Colour of Furniture
Yes
2.5.9.
Dimension (Length, Width, Height)
Yes
2.5.10.
Number
As per approved Control desk view. As per approved Control desk view. 1 Nos. per station
2.5.11.
Operator Chairs Manufacturer
Yes. Shall be covered in FDS. SICAM SCC
Knurr
-
Type of construction
-
Type of upholstery
-
Number
Seat & Back made of PU foam PU Leather No
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
2
2
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 8 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.6.
Colour Visual Display Units (VDUs)
2.6.1.
Number per HMI Workstation
2.6.2.
2
2
Manufacturer
Yes
Fujitsu
2.6.3.
Model
Yes
2.6.4.
Screen size across diagonal
inch
B24W-7/ Equivalent 24 “(LED)
2.6.5.
Operating temperature range
°C
5 - 35 °C
2.6.6.
Operating relative humidity range
%
10%-85% at 25 °C
2.6.7.
Nominal voltage
2.6.8.
24 “(LED)
VAC
240
100 V - 240 V
Operating frequency
Hz
50Hz
50 Hz - 60 Hz
2.6.9.
Power requirement
W
2.6.10.
Approximate lifetime of monitor under continuous use
h
24W, for maximum brightness 50K hours
2.6.11.
Mean time between failure
h
70,000h
2.6.12.
Mean time to repair
h
2.6.13.
Input Connectors Type
Next Business Day 1 x DisplayPort 1.2, 1 x DVI-D (HDCP), 1 x D-SUB
2.6.14.
Monitor suitable for 24 x 7 Operation
2.6.15.
Response Time
2.7.
Substation Local Area Network (LAN)
2.7.1.
Yes
Yes
Yes
5 ms (in Video mode)
Architecture and Technology (RSTP/PRP/HSR/Others)
Yes
RSTP
2.7.2.
Literature reference for principle of operation
Yes
Yes
2.7.3.
Transmission medium (e.g. optical fiber) and physical specification Protocols
Optical
Optical
Yes for remote access Yes
Yes
2.7.4.
ms
-
TCP/IP
-
Redundancy
-
IEC 61850 – Fiber Optic
Yes
Yes, RSTP, eRSTP Yes
-
List all other protocols
Yes
IEC104 Slave
1 (at substation level)
1Gb/s (at substation level) Shall be part of configuration
2.7.5.
Data transmission rate(s)
2.7.6.
Physical arrangement - Identify all main elements in the network e.g. switches, routers, gateways switches, etc. and
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
Gb/s
Yes
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 9 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS drawing
the number of each 2.7.7.
For each element of the LAN indicate the -
-
RSG2488 - Max. 28 Ports, can be configured as per substation requirement.
No and type of ports
% of spare for each type of port
2.7.8.
Management software package, functions and facilities, etc.
2.7.9.
% Loading under various system activity scenarios including
%
20 % Yes
Type of Ports LC/ST/RJ45 20 % Yes
-
normal loading for performance testing
%
-
high loading for performance testing
%
<=80
-
system power up
%
<=50
%
<=50
2.7.10.
main server fail-over and database resynchronization Overall availability
%
2.7.11.
Network Recovery time at Station level and bay Level
ms
Yes
2.7.12.
Capacity in the network for connecting IEDs of future bays to the proposed network architecture
%
As per future bays.
For Ruggedcom Switches, 85% (MTBF/(MTBF+MT TR) Based on the availability of the spare. Max. 200ms for RSTP 20% Spare capacity of offered system shall be provided. The confirmation for each substation for future bays shall be given in each system configuration.
2.8.
Managed Ethernet Switch
2.8.1.
Manufacturer
2.8.2.
Type
2.8.3.
Country of Origin
2.8.4.
Nominal voltage
-
<=40
Yes
RUGGEDCOM
Yes (IEC 61850 compatible, industrial grade switch)
RSG2488
Canada VDC / VAC
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
Dual Power Supply
red. 88-300 VDC / red. 85-264VAC
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 10 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.8.5.
61850 Interoperability Test
2.8.6.
Power requirements
W
2.8.8.
Range of ambient temp. and max relative humidity for continuous reliable operation Mean time between failures
o
2.8.9.
Mean time to repair
2.8.10.
For each LAN Switch indicate the
2.8.7.
-
Yes
C, %RH h
max. 66 W Yes
-40ºC / 85ºC 6.1 Yrs @ 55 ºC 9.2 Yrs @ 25 ºC Approx. 24 h Based on the availability of the spare.
h
RSG2488 - Max. 28 Ports, can be configured as per substation requirement.
No and type of ports
Type of Ports LC/ST/RJ45
-
% of spare for each type of port
%
20 %
Ports & Spare for each switch mentioned in architecture along with spares. 20%
2.8.11.
Tagging support
Yes
Yes
2.8.12.
VLAN support
Yes
Yes
2.8.13.
SNTP Time Synchronization
Yes
Yes
2.8.14.
Redundancy Protocol Supported
Yes
Yes
2.8.15.
Product function Web Based Management
Yes
Yes
2.8.16.
SNMP support
Yes
Yes
2.8.17.
Suitable Cover for unused Communication Ports
Yes
Yes
2.8.18.
EMC Compliance
Yes
Yes
2.8.19.
LAN configuration to support availability and failure scenario to be specified. Type test
Yes
Yes
yes
Yes
Not older than 5 years
Yes
2.8.20.
-
Witnessed by independent LAB
-
Date issued
2.9.
Firewall
2.9.1.
Manufacturer
Siemens (Model : RX1500)
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 11 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.9.2.
Type
2.9.3.
Country of Origin
2.9.4.
Dual Firewalls for IEC 60870-5-104
Yes
Yes
2.9.5.
Firewall for PMR/Remote Access
Yes
Yes
2.9.6.
Firewall for Condition Monitoring system
Yes
2.9.7.
Routing (static, Dynamic, policy Based)
wherever applicable Yes
2.9.8.
V LAN Supporting
Yes
Yes
2.9.9.
Alarms & Notification through SNMP
Yes
Yes
2.9.10.
Web Based User Interfaces
Yes
Yes
2.9.11.
Real time violation alarms & Rules (IPS/IDS)
Yes
Yes
2.9.12.
MAC Filtering
Yes
Yes
2.9.13.
Source/Destination Port Filtering
Yes
Yes
2.9.14.
Stateful Packet Inspection
Yes
Yes
2.9.15.
SCADA Specific protocol filtering
Yes
Yes
2.9.16.
Nominal voltage
Yes
HI (88 – 300VDC/ 85 – 264 VAC)
2.9.17.
Power requirements
W
2.9.18.
Range of ambient temp. and max relative humidity for continuous reliable operation
o
2.9.19.
Firewall (Hardware Appliance) 06/12 RJ45 Ports Canada
VAC/VD C
Yes
50 Watts (max)
C, %RH
-40°C to +85°C
Mean time between failures
h
Around 29 Years
2.9.20.
Mean time to repair
h
2.9.21.
No and Type of Ports (as per scope requirement)
RX1500 has a field replaceable media modules and hot swappable power supplies. So depending upon spare availability repair can be done within Approx. 2-hours 6/12 Copper Interfaces 10/100MBit
2.9.22.
% of spare for each type of port
20%
Yes
2.9.23.
Suitable Cover for unused Ports
Yes
Yes
2.10.
Colour Printers
Only for 400Kv Substations
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 12 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.10.1.
Manufacturer
Yes
HP
2.10.2.
Model
Yes
2.10.3.
Print speed (minimum)
2.10.4.
Technology
CP5225N/ Equivalent Up to 20 ppm, letter/A4 and black-andwhite/color Color LaserJet
2.10.5.
Resolution
2.10.6.
Paper size
2.10.7.
Sheet feed paper tray capacity
2.10.8.
Internal memory Upto
Mb
2.10.9.
Operating temperature range
°C
2.10.10.
Maximum relative humidity
%
2.10.11.
Nominal voltage
2.10.12.
PPM
Colour Laser Printer dpi Upto A3 Sheets
Up to 600 x 600 dpi Yes 100-sheet multipurpose tray1, 250-sheet tray 2 192 MB Operating: 10 to 30º C 20 to 60% RH
V ac
240V AC
Operating frequency
Hz
50Hz
2.10.13.
Power requirement
W
2.10.14.
Max noise level at 1 m
2.10.15.
Mean time between failure
h
Active: 440 watts; Standby: 30 watts; PowerSave: 4.4 watts; Off: 0.5 watts Acoustic pressure emissions – 49dB(A) ----
2.10.16.
Mean time to repair
h
----
2.10.17.
Functions
dB(A)
220 to 240 VAC (+/- 10%) 50 Hz (+/- 2 Hz)
Event &alarm printing Yes Display printing Yes
3.
Bay Control Unit Hardware
3.1.
General
3.1.1.
Manufacturer
3.1.2.
Country of Origin
3.1.3.
Model designation
Yes
Yes Yes
SIEMENS Germany
Yes
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
6MD85
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 13 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.1.4.
Literature reference for principle of operation
3.1.5.
Normal Power supply
VDC
3.1.6.
Power requirements
W
3.1.7.
Interface to substation LAN
3.1.8.
Maximum Number of expansion modules of different types
3.1.9.
Mean-time to repair
H
24 h
3.1.10.
Mean-time between failure
H
87,600 h
3.1.11.
Local LCD Display (mimic)
Yes
Yes
3.1.12.
Password facility for access to setting/configuration available
Yes
Yes
3.1.13.
Operating temperature range
°C
0 – 50
-25 to 70°C
3.1.14.
Operating relative humidity range
%
3.1.15.
I/O Capacity (equipped)
3.1.16.
Type test
3.1.17.
-
Witnessed by independent LAB
-
Date issued
Yes
SIPROTEC 5
110
60-250VDC 110-230VAC 16-35W Varies according to Modules IEC-61850 Fiber-optic loop 9
IEC-61850 over fiber
As required to meet signal requirement + 20% spare for each type of IO
75 % (Annual Average) Relative Humidity, on 56 days a year up to 95% Relative Humidity, condensation not permitted Yes
Yes
Yes
Not older than 5 years
Yes
Yes
Yes
Not older than 3 years
Yes
IEC 61850 conformance test -
Witnessed by independent LAB
-
Date issued
3.2.
BCU Enclosure
3.2.1.
Manufacturer
Yes
SIEMENS
3.2.2.
Module designation
Yes
SIPROTEC 5
3.2.3.
Literature reference for enclosure
Yes
SIPROTEC 5
3.2.4.
Weight
Yes
3.2.5.
Dimensions
Yes
3.2.6.
Degree of protection
Yes
Approx. 10-27 kg (6MD85) Varies according to Modules As per the configuration Front IP51 Rear IP50
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 14 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.2.7.
Flush Mounted housing
Yes
Yes
3.2.8.
Surface mounted housing
Yes
Optional
3.3.
IEC Standards ( or Equivalent )
3.3.1.
Type tests (Provide Class/Level or Severity rating)
3.3.2.
-
Dielectric withstand test IEC 60255-4/-5
Yes
Yes
-
High Voltage impulse test IEC 60255-4/-5
Yes
Yes
-
Fast transient disturbance test IEC 61000-4-4
Yes
Yes
-
Oscillatory transient IEC 61000-4-12
Yes
Yes
-
Radiated immunity test IEC 61000-4-6
Yes
Yes
-
Electrostatic discharge test IEC 61000-4-2
Yes
Yes
-
Emitted interference test IEC 61000-4-3
Yes
Yes
Yes
Yes
Mechanical test Compliance -
Vibration test IEC 60255-21-1
Yes
Yes
-
Shock test IEC 60255-21-2
Yes
Yes
-
Seismic test IEC 60255-21-3
Yes
Yes
-
Temperature rise test IEC 60068-2-2
Yes
Yes
Not older than 5 years
Yes
3.3.3.
Date of Type test certificate by independent LAB
3.4.
BCU Functions The monitoring functions include:
3.4.1.
Switching status monitoring (breakers)
Yes
Yes
3.4.2.
Indication & alarm status monitoring
Yes
Yes
3.4.3.
Analogue measurements (currents, voltages, etc.)
Yes
Yes
3.4.4.
Resolution of time tagging
1
1 ms
ms
The control functions include: 3.4.5.
-
Close / open of circuit breakers
Yes
Yes
3.4.6.
-
Close / Open of isolators / disconnectors
Yes
Yes
3.4.7.
-
Transformer Automatic tap change control
Yes
Yes
3.4.8.
-
Breaker Voltage Synchronization Check Control
Yes
Yes
3.4.9.
-
Bay interlocking facilities
Yes
Yes
Yes
Yes
If applicable
Yes
The reporting functions include: 3.4.10.
-
Sequence of Events recording
3.4.11.
-
Post – Mortem Review / Fault waveform capture
3.4.12.
-
Tenders to state memory capacity and functionality
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
Maximum 128 TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 15 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS
3.4.13.
of Sequence of events (and fault waveform capture, if applicable) Remote end status/ indication
faults records Yes
Yes
-
Mimic of remote end
Yes
Yes
-
Status / indications for remote end
Yes
Yes
Yes
1
3.5.
BCU Configuration
3.5.1.
Number of processors
3.5.2.
Main processor
3.5.3.
Secondary processors
3.5.4.
Communication processor (module)
Yes
Yes
3.5.5.
LCD Display and selector Buttons on front of BCU
Yes
Yes
CP300 Not Applicable
Functionality to include -
Full control of circuit bay
Yes
Yes
-
Status of bay plant
Yes
Yes
-
Circuit active line diagram
-
Power system Measurements
-
Display alarms and events
Yes Yes
Yes Yes
3.6.
Processing Units
3.6.1.
Main CPU
Yes
Yes
3.6.2.
Manufacturer
Yes
FREESCALE
3.6.3.
Module designation
3.6.4.
Literature reference for principle of operation
3.6.5.
Mean - time between failure
h
87,600 h
3.6.6.
Power requirements
W
<3W
3.6.7.
Type of processor
3.6.8.
Word length
bit
FREESCALE MPC8343 32Bit
3.6.9.
Clock speed
MHz
400 MHz
3.6.10.
Type of memory used:
3.6.11.
Type, size and extension capabilities
3.6.12.
Simultaneous communication towards multiple IEC 61850 clients (indicate max. number supported)
3.7.
Communications
3.7.1.
Manufacturer
CP300 Not Applicable
KByte
Yes
Yes _1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
DRAM / SRAM / Flash D-RAM 256MByte S-RAM 512MByte Flash 128Mbyte Yes (6 max. number supported)
SIEMENS
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 16 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.7.2.
Module designation
3.7.3.
Literature reference for principle of operation
3.7.4.
Number of communications channels
3.7.5.
Type of processor
If applicable
2 (Transmission / Reception) NA
3.7.6.
Word length
If applicable
NA
3.7.7.
Clock speed
bit
If applicable
NA
3.7.8.
Type and size of memory
MHz
If applicable
NA
3.7.9.
Line interface to communication channel
3.7.10.
Speed of transmission
B/s
100Mbps
100Mbps
3.7.11.
Number and type of communication ports
No
2 Channels (FO port)
3.7.12.
Meantime between failure
h
2x LC-FO ports for 61850 NA
3.7.13.
Power requirement
W
2.5W
3.7.14.
Communication Interfaces
Ethernet module ETH-BB-2FO SIPROTEC 5
NA
-
IEC60870-5-101 direct to Control Centre(s)
--
-
IEC60870-5-103 interface to protection IED
--
-
IEC61850 interface to substation LAN
-
IEC60870-5-101 for remote downloading of BCU data List all Protocols available at BCU
3.7.15.
Local interface for Laptop Computer
3.7.16.
IED Interface
Yes
Yes --Yes
-
List of manufactures the BCU has interfaced
Yes
-
Standard communication protocols available
Yes
ABB, ALSTOM, TAPCON, AEBERLE Yes
-
Optional communication protocols available
Yes
Yes
3.8.
Power Supply Module
3.8.1.
Module designation
3.8.2.
Literature reference for principle of operation
SIPROTEC 5
3.8.3.
Maximum number of modules per processor
2
3.8.4.
Nominal Input voltage
3.8.5.
Operating voltage range (Min/Max)
3.8.6.
Power requirement
PS201, PS203
VDC
W
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
110V DC
60-250 VDC 110-230 VAC -20% to +20% PS201 / PS203: 13W – additional expansion
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 17 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS module: 3W 3.8.7.
Isolation
3.8.8.
Meantime between failure
h
87,600 h
3.8.9.
Power requirement
W
16-35W Varies according to Modules
3.9.
Digital Input Module
3.9.1.
Module designation
3.9.2.
Literature reference for principle of operation
3.9.3.
Maximum number of modules supported
3.9.4.
Input voltage
3.5 kV DC
PS201 / IO202/ IO207 / IO230 SIPROTEC 5 9 VDC
24 – 250 Vdc
Is contact input type configurable as
NA
3.9.5.
Status and alarms
Yes
3.9.6.
Sequence of events
Yes
3.9.7.
SP, DP, BCD or parallel inputs
Yes
3.9.8.
Pulse accumulator
Yes
3.9.9.
Or any combination of these
Yes
3.9.10.
Standard number of inputs per module:
3.9.11.
double position
PS201 (3 common potentcial) IO202 (8 isolated); IO207 (16 isolated); IO230 (48 common potential); Yes
3.9.12.
single position
Yes
3.9.13.
Minimum Binary Input threshold
3.9.14.
Type of input circuit isolation
3.9.15.
Input galvanic separation
3.9.16.
Impulse voltage withstand
kV
5 kV
3.9.17.
Scan time
ms
Each 250 Microseconds
3.9.18.
Minimal pulse duration
ms
3.9.19.
Input impedance
3.9.20.
Filter time constant
3.9.21.
Meantime between failure
Vdc
optical coupler NA
ohm
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
DC 24 V-250 V
6MD8:
4.3 ms
ms
Variable Impedance NA
h
NA TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 18 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.9.22.
Power requirement
W
3.10.
Command Output Module
3.10.1.
Module designation
IO202 / IO207
3.10.2.
Literature reference for principle of operation
SIPROTEC 5
3.10.3.
Maximum number of modules supported
3.10.4.
Contact ratings
3.10.5.
Switched voltage
V
<250Vdc
3.10.6.
Switched power
VA max
1000 W/VA
3.10.7.
Switched current
A
5A
3.10.8.
Range of duration of command output
S
3.10.9.
Number of two position output channels per module
3.10.10.
Are outputs activated by select-check-actuate procedure?
Yes
3.10.11.
Are welded contacts checked prior to command output?
Yes
3.10.12.
Are the outputs fused and fuse status monitored?
Yes
3.10.13.
Impulse voltage withstand
kV
5 kV
3.10.14.
Meantime between failure
h
87,500 h
3.10.15.
Power requirement
W
NA
3.11.
Digital Output Module
3.11.1.
Module designation
3.11.2.
Literature reference for principle of operation
3.11.3.
Number of outputs per module
3.11.4.
Maximum number of modules per processor
3.11.5.
Maximum output current
3.11.6.
NA
9 NA
10 ms (standard relays) 5ms (fast relays) NA
PS101 IO202 IO207 SIPROTEC 5 IO202 (8 isolated / 4 NO); IO207 (16 isolated / 8 common potential); IO230 (48 common potential) 9 mA
NA
Maximum switched output voltage
V
<250Vdc
3.11.7.
Impulse voltage withstand
kV
5 kV
3.11.8.
Type of protection against back EMF
kV
NA
3.11.9.
Command duration adjustable in the range
s
NA
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 19 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.11.10.
Meantime between failure
h
NA
3.11.11.
Power requirement
W
NA
3.12.
Analogue Input Module
3.12.1.
Module designation
3.12.2.
Literature reference for principle of operation
3.12.3.
Maximum number of modules supported.
3.12.4.
Scanning resolution
3.12.5.
Accuracy
3.12.6.
How are overflow and conversion failures dealt with?
3.12.7.
Conversion time
3.12.8.
Input filter attenuation at 50 Hz
3.12.9.
Input signal types (e.g. 4-20 mA)
3.12.10.
Method of isolation
3.12.11.
Impulse voltage withstand
3.12.12.
Input impedance
3.12.13.
Type of ADC switching
3.12.14.
Standard number of inputs per module
3.12.15.
Mean time between failure
h
87,500h
3.12.16.
Power requirement
W
5.8mW
3.13.
Direct AC Connection Voltage
3.13.1.
Module designation
3.13.2.
Literature reference for principle of operation
3.13.3.
Maximum number of modules supported
5
3.13.4.
Number of inputs per module
4
3.13.5.
Input voltage ranges
3.13.6.
ANAI- CA- 4EL SIPROTEC 5 5 bits
NA
%
<1 % of Nominal Value NA NA
dB
NA -24mA to +24mA NA
kV
5 kV
ohm
140 ohm resistance NA 4
IO202 SIPROTEC 5
V ac
0V - 200VAC
Input filter attenuation at 50 Hz
dB
NA
3.13.7.
Burden on instrument transformer circuit
VA
3.13.8.
Conversion time
ms
<0.1VA at 57,735V/phase NA
3.13.9.
Scanning resolution
bits
NA
3.13.10.
Accuracy
%
3.13.11.
What calculations are supported
<0.5% of measured value NA
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 20 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.13.12.
How are overflow and conversion failures dealt with?
NA
3.13.13.
Method of isolation
NA
3.13.14.
Impulse voltage withstand kV
3.14.
Direct AC Connection Current
3.14.1.
Module designation
3.14.2.
Literature reference for principle of operation
3.14.3.
Maximum number of modules processor
5
3.14.4.
Number of inputs per module
4
3.14.5.
Input current ranges
A
1A or 5A
3.14.6.
Input filter attenuation at 50 Hz
dB
NA
3.14.7.
Burden on instrument transformer circuit
VA
3.14.8.
Conversion time
ms
<0.1VA at rated current NA
3.14.9.
Scanning resolution
bits
NA
3.14.10.
Accuracy
%
3.14.11.
What calculations are supported
<0.5% of measured value NA
3.14.12.
How are overflow and conversion failures dealt with?
NA
3.14.13.
Method of isolation
NA
3.14.14.
Impulse voltage withstand kV
4.
BCU Software
4.1.
General Requirements
4.1.1.
Software Name and Version
4.1.2.
Program structure
4.1.3.
System software
4.1.4.
Standard functions programs
4.1.5.
User functions programs
4.2.
Capability
4.2.1.
kV 5 kV
IO202 SIPROTEC 5
5 kV
kV
Yes
Std. DIGSI Software Std. DIGSI Software CFC, Interlocking, Logic gates SP. DP informations, Grouping in CFC NA
BCU program downloading from HMI/Control Centre
Yes
4.2.2.
Application configuration from HMI/Control Centre
Yes
4.2.3.
Remote selection of processing parameters
Through HWS on LAN Through HWS on LAN On demand
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 21 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 4.2.4.
Selection of communication protocols
4.2.5.
Selection of operation modes (cyclic, polled, etc.)
4.2.6.
Appropriate protection of software against power failure
Only one protocol is offered Through remote DIGSI Yes
4.2.7.
Automatic BCU re-start without software down-loading
Yes
4.3.
System Software
4.3.1.
Operating System (Monitor) Functions and capabilities
4.3.2.
Calendar program Type, functions and capabilities
NA
4.3.3.
Time Synchronization Program Functions and capabilities
Yes
4.3.4.
Data Base Updating program Functions and capabilities
Yes
4.3.5.
Testing and Diagnostics Programs Functions and capabilities
4.4.
Standard Functions Programs
4.4.1.
Data Communication Programs: Functions and capabilities
Yes
4.4.2.
Capability of communication protocol selection
Yes
4.4.3.
Capability of operating modes selection
Yes
4.5. 4.5.1.
Analogue Measurements, Scanning and Transmission Programs Capabilities of adjustments
4.5.2.
Transducers constants
4.5.3.
Periodic transmission/transmission by exception
Cyclic
4.5.4.
Automatic checking of A/D-conversion accuracy
Yes
4.5.5.
Smoothing
Yes
4.5.6.
Threshold values
Yes
4.5.7.
Limits
4.5.8.
Scan duration (range)
4.5.9.
Cycle duration (range)
s
NA
4.5.10.
Priority of transmission
s
Yes
4.5.11.
Digital Input Data Scanning and transmission Program
4.6.
Functions and capabilities
4.6.1.
Capability of adjustments;
4.6.2.
Scan duration (range)
4.6.3.
Transient time of status information (range)
4.6.4.
Cycle duration (range)
4.6.5.
Debouncing filter
Yes
PSOS
Yes
Yes
Self calibrated 4-20 mA
±0.25% NA
--
Yes ms
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
NA Configurable
ms
NA
s
Yes, Configurable TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 22 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS Chatter blocking Yes
4.6.6.
Suppression of intermediate status information
4.6.7.
Time tagging
4.6.8.
Transmission mode
4.6.9.
Priority of transmission
4.7.
Alarm and Event handling
4.7.1.
Grouping of alarms and events
4.7.2.
Maximum number of groups
4.8. 4.8.1.
Supervisory Control Programs: Functions and capabilities Select before execute
Yes
4.8.2.
Target check
Yes
4.8.3.
Cancelling control after adjustable time delay
Yes
4.8.4.
Capability of adjustments:
4.8.5.
Duration of output (range)
s
Settable
4.8.6.
Allowed duration of execution (range)
s
Settable
4.8.7.
Sequence of Events programs
4.8.8.
Minimal sequence of events time resolution
ms
Yes standard SOE as per applicable protocol/ (in SCC) 1
4.8.9.
Sequence of events memory capacity
4.8.10.
Events time resolution (adjustable range)
4.8.11.
Priority of transmission
4.8.12.
Post - Mortem Review / Program
4.8.13.
Selection of analogues for post-mortem review
4.8.14.
Short interval time resolution (adjustable range)
s
NA
4.8.15.
Long interval time resolution (adjustable range)
s
NA
4.9. 4.9.1.
Data processing programs: Functions and capabilities Required minimum data processing:
Yes
4.9.2.
Logic functions
Yes
4.9.3.
Arithmetical functions (MW , Mvar etc )
Yes
4.9.4.
Limiting functions
4.9.5.
Comparative functions
Yes
4.9.6.
Time functions
Yes
Yes, 1ms Spontaneous, cyclic Yes
Yes 2
200 1ms (fixed) Yes COMTRADE View/ SIGRA Yes
s
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
Yes
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 23 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 5.
Gateway Software
5.1.
General Requirements
5.1.1.
Software Name and Version
5.1.2.
No. of IEDs Software can handle
5.1.3.
Yes
SICAM PAS
No
Yes
No. of Tags Software can handle
No
Yes
5.1.4.
Software has provision for future IEDs.
%
5.1.5.
No. of Spare tags for future use
%
5.1.6.
Alarm and Event Grouping
Max: 450 (dependent on number of IPCs in parallel) 15.000-25.000 (from IEDs) 30.000-50.000(to HMI and CC) (dependent on number of IPCs in parallel) 20% spare is available for future use 20% spare is available for future use Yes
5.1.7.
Alarm and Event Separation for NCC and DCC
Yes
5.1.8.
Alarm and Event storage and remote / local access
Yes
5.1.9.
5.2.
All IEDs (including Third Party) can be interfaced on IEC61850 Protocol IEC 61850/IEC 60870-5-101/IEC60870-5-104 Logging Facility Capability of:
5.2.1.
Gateway program downloading from Control Centre
Yes
5.2.2.
Application configuration from Control Centre
Yes
5.2.3.
Remote selection of processing parameters
Yes
5.2.4.
Selection of communication protocols
5.2.5.
Selection of operation modes (cyclic, polled, etc.)
5.2.6.
Appropriate protection of software against power failure
Yes
5.2.7.
Automatic re-start without software down-loading
Yes
5.2.8.
Online Modification of Gateway Software
Yes
5.3.
System Software
5.3.1.
Operating System (Monitor) Functions and capabilities
5.3.2.
Calendar program Type, functions and capabilities
5.3.3.
Time Synchronization Program Functions and capabilities
5.1.10.
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
Yes
Yes Yes
As per Specification Requirement Yes
Yes, Part of FDS NA Yes, Part of FDS TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 24 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 5.3.4.
Data Base Updating program Functions and capabilities
Yes, Part of FDS
5.3.5.
Testing and Diagnostics Programs Functions and capabilities
Yes, Part of FDS
6.
HMI Server /Workstation Software
6.1.
Software Name and Version
6.2.
No. of IEDs Software can handle
6.3.
Yes
SICAM SCC
No
Yes
No. of Tags Software can handle
No
Yes
6.4.
Software has provision for future IEDs.
%
6.5.
No. of Spare tags for future use
%
6.6.
Status updating Time
Yes
Max. 450 Via PAS Server Max. 65536 Via PAS Server 20% spare is available for future use 20% spare is available for future use Yes
6.7.
Analog value Updating Time
Yes
Yes
6.8.
Command operation Time
Yes
Yes
6.9.
Event List
Yes
Yes
6.10.
Dynamic Single Line Diagram
Yes
Yes
6.11.
Dynamic Communication Overview
Yes
Yes
6.12.
Alarm list, Event, reports and Trends with filter option.
Yes
Yes
6.13.
Export of Analogues in CSV/Excel format
Yes
Yes
6.14.
Export of Events in CSV or Standard Format
Yes
Yes
6.15.
Export of Events, Graphical trends and Reports in PDF format
Yes
Yes
6.16.
Online modification and DB generation
Yes
6.17.
Monitoring healthiness of all components of SCS including the LAN cables
Yes
6.18.
Yes
6.19.
Monitoring Healthiness of ports in Ethernet Switches, GPS ,Router, etc Remote end bay details in SCS
Yes Modification of screens/Texts is possible By monitoring port status and SNMP Signals Yes
Yes
Yes
6.20.
Offered SCS is expandable in future
Yes
Yes
6.21.
Lockout trip relay reset from HMI
Yes
Yes
6.22.
All HMI displays mentioned in specifications
Yes
Yes
6.23.
Third Party IED interfaces on IEC 61850 Protocol.
Yes
Yes
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 25 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 7.
GPS Receiver
7.1.1.
Make & Model No
7.1.2.
Country of Origin
7.1.3.
Lighting Protection
Yes
MBG S-PRO
7.1.4.
Display
Yes
Yes
7.1.5.
Network Interfaces to Ethernet LAN
RJ45 or FO
RJ45
7.1.6.
MEINBERG LANTIME M300 Germany
7.1.7.
Range of ambient temp. and max relative humidity for continuous reliable operation Types of port available
7.1.8.
No. Of SNTP ports (Minimum)
7.1.9.
o
C, %RH
0-50°C /85% RJ45
3
6
SNMP based alarm Messaging
Yes
Yes
7.1.10.
Remote user Interfaces for configuration
Yes
Yes
7.1.11.
Time Syhcronization of online Monitoring Systems
Yes
7.1.12.
Time Synchronization of Telecom Equipment
Yes
7.1.13.
Nominal Input voltage
Yes
Yes, Provided systems can be synchronized via NTP Yes, Provided systems can be synchronized via NTP 100-240 VAC
7.1.14.
% of spare for each type of port
20%
Yes
7.1.15.
Power Requirements
7.1.16.
Mean Time Between failure
8.
Laptop
8.1.1.
Manufacturer
Yes
Fujitsu
8.1.2.
Model
Yes
8.1.3.
Country of Origin
CELSIUS H730/ Equivalent Germany
8.1.4.
Processor Intel core i7 Processor or Higher
Intel Core i7
8.1.5.
VAC / VDC % W
-
Type (Minimum)
-
Clock speed (minimum)
30 W 118294 Hours
GHz
up to 3.7GHz
Memory size -
Supplied (minimum)
GB
-
Supportable/expandable
GB
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
8GB
8GB 32GB
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 26 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 8.1.6.
Storage Type Hard disk
8.1.7.
Optical Storage DVD RW
8.1.8.
Display Screen Size
8.1.9.
Operating system
8.1.10.
Updation of Microsoft recommended fixes and history to be provided Antivirus Software
TB
Inches
Validity
1TB
1TB
Yes
Yes
15.6
Yes
MS Windows
Yes
Up to FAC
Yes
Up to FAC
Trend micro Latest Version Yes
Yes
Yes
Yes
240VAC
Make & Version Years
Antivirus Updation through Centralized Client /Server in S/S 8.1.11.
Nominal Input voltage
VAC
8.1.12.
Power Requirements
W
9.
Fiber Optic Patch Cables
9.1.1.
Make
Yes
Preston
9.1.2.
No. of Fiber cores
Yes
2/4
9.1.3.
Type of Fiber Cable
Yes
Ruggedize
9.1.4.
Flame Retardant Low Smoke Zero Halogen
Yes
Yes
9.1.5.
Maximum tensile strength Short term
N
800
800
9.1.6.
Maximum tensile strength long term
N
200
200
9.1.7.
Outer Sheath Colour
Yes
Orange
10.
System Security Requirements
10.1.1.
Cyber Security shall be implemented as mentioned in specifications. Cyber Security implementations shall be carried out strictly under the guide lines of ICT Qatar, QCERT “National ICS Security Standard” with a broad band to adopt IEC 62351 and ISO/IEC 27002 and/or ISA99 standards All User accounts shall be configured as Role based access model (RBAC). All the Removable media usage in SCS system shall be restricted All the latest security patterns/hot fixes shall be implemented up to FAC Application White listing software shall be adopted in all Computers
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
10.1.2.
10.1.3. 10.1.4. 10.1.5. 10.1.6. 10.1.7.
10.1.8.
10.1.9.
All default and unused accounts in operating systems and in all real time applications shall be disabled. All unnecessary software shall be removed from the SCS System. Use of latest stable release of operating system on all
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
150W
Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
TECHNICAL AFFAIRS Electrical Projects Dept.
VOLUME 4
SECTION 3.4.10
PAGE 27 OF 27
GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS machines and network devices. 10.1.10.
Operating System, SCS software, Antivirus and Firewall/switch firmware updates shall be provided during the period of warranty.
_1.DOCX
SECTION 3.4.10 SUBSTATION CONTROL SYSTEM
Yes
Yes
TECHNICAL AFFAIRS Electrical Projects Dept.
Software List Station Server Windows 7 Operating System Professional SICAM PAS "full Server" Software – Runtime License OPC Client License CFC Automation License - IEC 61850 (Client) Teaming Utility Software Trend Micro Office Scan Client Gateway Windows 7 Operating System Professional SICAM PAS "full Server" Software – Runtime License OPC Client License CFC Automation License - IEC 61850 (Client) License - IEC 104 (Slave) Teaming Utility Software Trend Micro Office Scan Client HWS PC Windows 7 Operating System Professional SICAM SCC SIMATIC Win CC System Software Teaming Utility Software PDF Writer Trend Micro Office Scan Client EPC/HMI Windows 7 Operating System Professional Trend Micro Office Scan Server SICAM SCC SIMATIC Win CC System Software Teaming Utility Software PDF Writer Microsoft Office SICAM PAS Configuration Tool Incident Explorer for Evaluation of Fault records Watch Directory - Professional Firewall Software Digsi ABB PCM600, if applicable ALSTOM MICOM S1 Agile SCHNEIDER MiCOM S1 Studio AVR Software Net view WinZip
Unrestricted