THIS SUBMISSION IS DECLARED TO BE STRICTLY IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT

SIGNATURE:

PHASE-12

QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 SUBSTATIONS - PACKAGE S-10, S-13 & S-14 CONTRACT NO. GTC/643G/2014 CONSULTANT :

The Gate (16th FLOOR, Doha, Qatar, PO Box 13885. TEL: +974 4020 6450, FAX: +974 4020 6451 www.wspgroup.com / www.pbworld.com SUBSTATION NAME :

PROJECT DRAWING NUMBER :

COMMON

PH12-3G-10-40-T001

C B1

_

7/12/2016

Re-issued for Construction ar per DTA-16-4205

MV

DMK

RLG

B

B

20/10/2016

Issued for Construction ar per DTA-16-1448

MV

DMK

RLG

A

B

5/5/2016

Issued for Approval as per DTA-16-0262

MV

DMK

RLG

0

B

10/2/2016

Issued for comments

MV

DMK

RLG

REV.

STAT.

DATE

MODIFICATION

PREPARED CHECKED APPROVED

SUBCONTRACTOR NAME :

CONTRACTOR NAME :

MANUFACTURERS DRAWING NO:

DRAWING/DOCUMENT TITLE:

(4)G719EA-HG9030-U2002 SIGNATURE

Technical data sheet for Substation Control System

DATE

NAME

PREPARED

10/2/2016

MV

CHECKED

10/2/2016

DMK

SIZE

SCALE : NTS

REV.

APPROVED

10/2/2016

RLG

A4

Sheet No. 01 of 28

B1 C

VOLUME 4

SECTION 3.4.10

PAGE 2 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

LIST OF CONTENTS

PAGE

COVER SHEET

1

LIST OF CONTENTS

2

INTRODUCTION PAGE

4

1

SUBSTATION CONTROL SYSTEM

5

2

GENERAL

5

2.1 COMMON FOR SERVER / GATEWAYS / HMI / EWS

5

2.2 STATION SERVER

6

2.3 GATEWAY COMPUTER

6

2.4 OPERATOR WORKSTATIONS / HMI

7

2.5 OPERATOR DESK

7

2.6 COLOUR VISUAL DISPLAY UNIT (VDUS)

8

2.7 SUBSTATION LOCAL AREA NETWORK (LAN)

8

2.8 MANAGED ETHERNET SWITCH

9

2.9 FIREWALL

10

2.10 COLOUR PRINTERS (ONLY FOR 400KV SUBSTATIONS)

11

BAY CONTROL UNIT HARDWARE

12

3.1 GENERAL

12

3.2 BCU ENCLOSURE

13

3.3 IEC STANDARDS (OR EQUIVALENT)

14

3.4 BCU FUNCTIONS

14

3.5 BCU CONFIGURATION

15

3.6 PROCESSING UNIT

15

3.7 COMMUNICATIONS

15

3.8 POWER SUPPLY MODULE

16

3.9 DIGITAL INPUT MODULE

17

3

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 3 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.10 COMMAND OUTPUT MODULE

18

3.11 DIGITAL OUTPUT MODULE

18

3.12 ANALOGUE INPUT MODULE

19

3.13 DIRECT AC CONNECTION VOLTAGE

19

3.14 DIRECT AC CONNECTION CURRENT

20

BCU SOFTWARE

20

4.1 GENERAL REQUIREMENT

20

4.2 CAPABILITY

20

4.3 SYSTEM SOFTWARE

21

4.4 STANDARD FUNCTIONS PROGRAMS

21

4.5 ANALOGUE MEASUREMENTS, SCANNING AND TRANSMISSION PROGRAMS

21

4.6 FUNCTIONS AND CAPABILITIES

21

4.7 ALARM AND EVENT HANDLING

22

4.8 SUPERVISORY CONTROL PROGRAMS: FUNCTIONS AND CAPABILITIES

22

4.9 DATA PROCESSING PROGRAMS: FUNCTIONS AND CAPABILITIES

22

GATEWAY SOFTWARE

23

5.1 GENERAL REQUIREMENTS

23

5.2 CAPABILITY OF:

23

5.3 SYSTEM SOFTWARE

23

6

HMI SERVER /WORKSTATION SOFTWARE

24

7

GPS RECEIVER

25

8

LAPTOP

25

9

FIBER OPTIC PATCH CABLES

26

4

5

10 SYSTEM SECURITY REQUIREMENTS

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

26

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

SECTION 3.4.10

PAGE 4 OF 27

VOLUME 4

SECTION 3.4.10

PAGE 5 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS SUBSTATION CONTROL SYSTEM 1.

Substation Control System

2.

General

UNIT

System supplier

DATA Required

Offered

Yes

SIEMENS SICAM PAS

-

SCS System Name

Yes

-

System version

Yes

-

Place of integration

Yes

V 8.x SIEMENS,INDIA

2.1.

SCS panel make/place Common for Server / Gateways / HMI / EWS

2.1.1.

Manufacturer

Yes

Siemens

2.1.2.

Model

Yes

IPC847D

2.1.3.

Type

Industrial

Yes

2.1.4.

Country of Origin

2.1.5.

Suitable for 24 x 7 operation

2.1.6.

Processor -

2.1.7.

2.1.8.

Germany

Type (Minimum)

Clock speed (minimum)

Yes

Yes

Intel core i7 (Xeon) Processor or Higher

Xeon E3-1275 v3

GHz

3.5 to 3.9 GHz

Memory size -

Supplied (minimum)

GB

-

Supportable/expandable

GB

Storage size Configuration

16GB

32GB

-

Storage Suitable for 24 x 7 operation

RAID Configuration Hot-Swappable type Yes

-

Storage Type

SCSI/SAS/ SSD

-

Supplied (minimum 1 TB)

2.1.9.

Optical Storage DVD RW

2.1.10.

Operating system

TB

As required to store 1 year Data Yes MS Windows

Updation of Microsoft recommended fixes and history to be provided

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

16GB

Up to FAC

Yes

SAS (ST1000NM0023) 1 TB

Yes

Yes Windows 7 Professional (64bit) Microsoft Recommended HQ tested hot fixes shall be provided up to FAC.

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 6 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.1.11.

Antivirus Software Validity

Years

Antivirus Updation through Centralized Client /Server in S/S

Up to FAC

Yes

Yes

Yes

2.1.12.

Operating temperature range

°C

0 to 35 °C

2.1.13.

Maximum relative humidity

%

2.1.14.

Nominal voltage

240AC

5% to 80% at 25 °C (no condensation) 240 VAC

2.1.15.

Redundant Power Supply Modules (Hot Swappable)

Yes

Yes

2.1.16.

Operating frequency

Hz

50

50Hz

2.1.17.

Power requirement

W

2.1.18.

Mean time between failure

h

VAC

300 W at 77 % efficiency 170,000 hours @ 25 °C 110,000 hours @ 35 °C

2.1.19.

Mean time to repair

2.1.20.

Mounting

2.1.21.

Type test

h

-

Witnessed by independent LAB

-

Date issued

2.1.21

Communication Protocols in Substation

2.2.

Station Server

2.2.1. 2.2.2.

Software supplied (Attach a list of software other than operating systems to be installed) Remote Access of Server through KVM Switches

2.2.3.

Configuration of Remote Access from HMI/EWS

2.3.

Gateway Computer

2.3.1.

Communication Protocols To Control Centre(s) -

2.3.2.

NCC Main & Standby IEC 60870-5-104 (101 if applicable) DCC Main and Standby IEC 60870-5-104

Dual LAN ports for Control Centre Communication

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

19” Rack

53 h, From the time, when IPC reaches the repair center. Yes

yes

Yes

Not older than 5 years IEC 61850 over dual fibre optic

Yes

Required

SICAM PAS

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 7 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.3.3.

List other operating Protocols available/supported

Yes

IEC 61850

2.3.4. 2.3.5.

Software supplied (Attach a list of software other than operating systems to be installed) Remote Access of Server through KVM Switches

Required

SICAM PAS

Yes

Yes

2.3.6.

Configuration of Remote Access from HMI/EWS

Yes

Yes

2.4.

Operator Workstations / HMI

2.4.1.

Mouse

Yes

Yes

2.4.2.

Keyboard

Yes

Yes

2.4.3.

Literature reference for principle of operation

Yes

2.4.4.

Yes

2.4.5.

Software supplied (Attach a list of software other than operating systems to be installed) MS Office Software with PDF Writer

Yes

Yes

2.4.6.

Operator interface screens

Dual

Yes

2.4.7.

LAN Interface for Remote Access from Control Center

Yes

Yes

2.4.8.

LAN Interface for PMR files uploading to Control Center

Yes

Yes

2.5.

Operator Desk

2.5.1.

Manufacturer

Yes

Knurr

2.5.2.

Type of construction

Yes

Aluminium / Steel extrusions

2.5.3.

Country of Origin

2.5.4.

Placing of the Industrial Computer with Suitable Ventilation

Yes

Yes

2.5.5.

Method of mounting VDUs

Yes

2.5.6.

Industrial Grade Power Sockets

Yes

Vertical at top the desk Yes

2.5.7.

Provision for Routing Communication Cables & Power Cables

Yes

Yes

2.5.8.

Colour of Furniture

Yes

2.5.9.

Dimension (Length, Width, Height)

Yes

2.5.10.

Number

As per approved Control desk view. As per approved Control desk view. 1 Nos. per station

2.5.11.

Operator Chairs Manufacturer

Yes. Shall be covered in FDS. SICAM SCC

Knurr

-

Type of construction

-

Type of upholstery

-

Number

Seat & Back made of PU foam PU Leather No

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

2

2

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 8 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.6.

Colour Visual Display Units (VDUs)

2.6.1.

Number per HMI Workstation

2.6.2.

2

2

Manufacturer

Yes

Fujitsu

2.6.3.

Model

Yes

2.6.4.

Screen size across diagonal

inch

B24W-7/ Equivalent 24 “(LED)

2.6.5.

Operating temperature range

°C

5 - 35 °C

2.6.6.

Operating relative humidity range

%

10%-85% at 25 °C

2.6.7.

Nominal voltage

2.6.8.

24 “(LED)

VAC

240

100 V - 240 V

Operating frequency

Hz

50Hz

50 Hz - 60 Hz

2.6.9.

Power requirement

W

2.6.10.

Approximate lifetime of monitor under continuous use

h

24W, for maximum brightness 50K hours

2.6.11.

Mean time between failure

h

70,000h

2.6.12.

Mean time to repair

h

2.6.13.

Input Connectors Type

Next Business Day 1 x DisplayPort 1.2, 1 x DVI-D (HDCP), 1 x D-SUB

2.6.14.

Monitor suitable for 24 x 7 Operation

2.6.15.

Response Time

2.7.

Substation Local Area Network (LAN)

2.7.1.

Yes

Yes

Yes

5 ms (in Video mode)

Architecture and Technology (RSTP/PRP/HSR/Others)

Yes

RSTP

2.7.2.

Literature reference for principle of operation

Yes

Yes

2.7.3.

Transmission medium (e.g. optical fiber) and physical specification Protocols

Optical

Optical

Yes for remote access Yes

Yes

2.7.4.

ms

-

TCP/IP

-

Redundancy

-

IEC 61850 – Fiber Optic

Yes

Yes, RSTP, eRSTP Yes

-

List all other protocols

Yes

IEC104 Slave

1 (at substation level)

1Gb/s (at substation level) Shall be part of configuration

2.7.5.

Data transmission rate(s)

2.7.6.

Physical arrangement - Identify all main elements in the network e.g. switches, routers, gateways switches, etc. and

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

Gb/s

Yes

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 9 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS drawing

the number of each 2.7.7.

For each element of the LAN indicate the -

-

RSG2488 - Max. 28 Ports, can be configured as per substation requirement.

No and type of ports

% of spare for each type of port

2.7.8.

Management software package, functions and facilities, etc.

2.7.9.

% Loading under various system activity scenarios including

%

20 % Yes

Type of Ports LC/ST/RJ45 20 % Yes

-

normal loading for performance testing

%

-

high loading for performance testing

%

<=80

-

system power up

%

<=50

%

<=50

2.7.10.

main server fail-over and database resynchronization Overall availability

%

2.7.11.

Network Recovery time at Station level and bay Level

ms

Yes

2.7.12.

Capacity in the network for connecting IEDs of future bays to the proposed network architecture

%

As per future bays.

For Ruggedcom Switches, 85% (MTBF/(MTBF+MT TR) Based on the availability of the spare. Max. 200ms for RSTP 20% Spare capacity of offered system shall be provided. The confirmation for each substation for future bays shall be given in each system configuration.

2.8.

Managed Ethernet Switch

2.8.1.

Manufacturer

2.8.2.

Type

2.8.3.

Country of Origin

2.8.4.

Nominal voltage

-

<=40

Yes

RUGGEDCOM

Yes (IEC 61850 compatible, industrial grade switch)

RSG2488

Canada VDC / VAC

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

Dual Power Supply

red. 88-300 VDC / red. 85-264VAC

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 10 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.8.5.

61850 Interoperability Test

2.8.6.

Power requirements

W

2.8.8.

Range of ambient temp. and max relative humidity for continuous reliable operation Mean time between failures

o

2.8.9.

Mean time to repair

2.8.10.

For each LAN Switch indicate the

2.8.7.

-

Yes

C, %RH h

max. 66 W Yes

-40ºC / 85ºC 6.1 Yrs @ 55 ºC 9.2 Yrs @ 25 ºC Approx. 24 h Based on the availability of the spare.

h

RSG2488 - Max. 28 Ports, can be configured as per substation requirement.

No and type of ports

Type of Ports LC/ST/RJ45

-

% of spare for each type of port

%

20 %

Ports & Spare for each switch mentioned in architecture along with spares. 20%

2.8.11.

Tagging support

Yes

Yes

2.8.12.

VLAN support

Yes

Yes

2.8.13.

SNTP Time Synchronization

Yes

Yes

2.8.14.

Redundancy Protocol Supported

Yes

Yes

2.8.15.

Product function Web Based Management

Yes

Yes

2.8.16.

SNMP support

Yes

Yes

2.8.17.

Suitable Cover for unused Communication Ports

Yes

Yes

2.8.18.

EMC Compliance

Yes

Yes

2.8.19.

LAN configuration to support availability and failure scenario to be specified. Type test

Yes

Yes

yes

Yes

Not older than 5 years

Yes

2.8.20.

-

Witnessed by independent LAB

-

Date issued

2.9.

Firewall

2.9.1.

Manufacturer

Siemens (Model : RX1500)

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 11 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.9.2.

Type

2.9.3.

Country of Origin

2.9.4.

Dual Firewalls for IEC 60870-5-104

Yes

Yes

2.9.5.

Firewall for PMR/Remote Access

Yes

Yes

2.9.6.

Firewall for Condition Monitoring system

Yes

2.9.7.

Routing (static, Dynamic, policy Based)

wherever applicable Yes

2.9.8.

V LAN Supporting

Yes

Yes

2.9.9.

Alarms & Notification through SNMP

Yes

Yes

2.9.10.

Web Based User Interfaces

Yes

Yes

2.9.11.

Real time violation alarms & Rules (IPS/IDS)

Yes

Yes

2.9.12.

MAC Filtering

Yes

Yes

2.9.13.

Source/Destination Port Filtering

Yes

Yes

2.9.14.

Stateful Packet Inspection

Yes

Yes

2.9.15.

SCADA Specific protocol filtering

Yes

Yes

2.9.16.

Nominal voltage

Yes

HI (88 – 300VDC/ 85 – 264 VAC)

2.9.17.

Power requirements

W

2.9.18.

Range of ambient temp. and max relative humidity for continuous reliable operation

o

2.9.19.

Firewall (Hardware Appliance) 06/12 RJ45 Ports Canada

VAC/VD C

Yes

50 Watts (max)

C, %RH

-40°C to +85°C

Mean time between failures

h

Around 29 Years

2.9.20.

Mean time to repair

h

2.9.21.

No and Type of Ports (as per scope requirement)

RX1500 has a field replaceable media modules and hot swappable power supplies. So depending upon spare availability repair can be done within Approx. 2-hours 6/12 Copper Interfaces 10/100MBit

2.9.22.

% of spare for each type of port

20%

Yes

2.9.23.

Suitable Cover for unused Ports

Yes

Yes

2.10.

Colour Printers

Only for 400Kv Substations

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 12 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 2.10.1.

Manufacturer

Yes

HP

2.10.2.

Model

Yes

2.10.3.

Print speed (minimum)

2.10.4.

Technology

CP5225N/ Equivalent Up to 20 ppm, letter/A4 and black-andwhite/color Color LaserJet

2.10.5.

Resolution

2.10.6.

Paper size

2.10.7.

Sheet feed paper tray capacity

2.10.8.

Internal memory Upto

Mb

2.10.9.

Operating temperature range

°C

2.10.10.

Maximum relative humidity

%

2.10.11.

Nominal voltage

2.10.12.

PPM

Colour Laser Printer dpi Upto A3 Sheets

Up to 600 x 600 dpi Yes 100-sheet multipurpose tray1, 250-sheet tray 2 192 MB Operating: 10 to 30º C 20 to 60% RH

V ac

240V AC

Operating frequency

Hz

50Hz

2.10.13.

Power requirement

W

2.10.14.

Max noise level at 1 m

2.10.15.

Mean time between failure

h

Active: 440 watts; Standby: 30 watts; PowerSave: 4.4 watts; Off: 0.5 watts Acoustic pressure emissions – 49dB(A) ----

2.10.16.

Mean time to repair

h

----

2.10.17.

Functions

dB(A)

220 to 240 VAC (+/- 10%) 50 Hz (+/- 2 Hz)

Event &alarm printing Yes Display printing Yes

3.

Bay Control Unit Hardware

3.1.

General

3.1.1.

Manufacturer

3.1.2.

Country of Origin

3.1.3.

Model designation

Yes

Yes Yes

SIEMENS Germany

Yes

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

6MD85

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 13 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.1.4.

Literature reference for principle of operation

3.1.5.

Normal Power supply

VDC

3.1.6.

Power requirements

W

3.1.7.

Interface to substation LAN

3.1.8.

Maximum Number of expansion modules of different types

3.1.9.

Mean-time to repair

H

24 h

3.1.10.

Mean-time between failure

H

87,600 h

3.1.11.

Local LCD Display (mimic)

Yes

Yes

3.1.12.

Password facility for access to setting/configuration available

Yes

Yes

3.1.13.

Operating temperature range

°C

0 – 50

-25 to 70°C

3.1.14.

Operating relative humidity range

%

3.1.15.

I/O Capacity (equipped)

3.1.16.

Type test

3.1.17.

-

Witnessed by independent LAB

-

Date issued

Yes

SIPROTEC 5

110

60-250VDC 110-230VAC 16-35W Varies according to Modules IEC-61850 Fiber-optic loop 9

IEC-61850 over fiber

As required to meet signal requirement + 20% spare for each type of IO

75 % (Annual Average) Relative Humidity, on 56 days a year up to 95% Relative Humidity, condensation not permitted Yes

Yes

Yes

Not older than 5 years

Yes

Yes

Yes

Not older than 3 years

Yes

IEC 61850 conformance test -

Witnessed by independent LAB

-

Date issued

3.2.

BCU Enclosure

3.2.1.

Manufacturer

Yes

SIEMENS

3.2.2.

Module designation

Yes

SIPROTEC 5

3.2.3.

Literature reference for enclosure

Yes

SIPROTEC 5

3.2.4.

Weight

Yes

3.2.5.

Dimensions

Yes

3.2.6.

Degree of protection

Yes

Approx. 10-27 kg (6MD85) Varies according to Modules As per the configuration Front IP51 Rear IP50

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 14 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.2.7.

Flush Mounted housing

Yes

Yes

3.2.8.

Surface mounted housing

Yes

Optional

3.3.

IEC Standards ( or Equivalent )

3.3.1.

Type tests (Provide Class/Level or Severity rating)

3.3.2.

-

Dielectric withstand test IEC 60255-4/-5

Yes

Yes

-

High Voltage impulse test IEC 60255-4/-5

Yes

Yes

-

Fast transient disturbance test IEC 61000-4-4

Yes

Yes

-

Oscillatory transient IEC 61000-4-12

Yes

Yes

-

Radiated immunity test IEC 61000-4-6

Yes

Yes

-

Electrostatic discharge test IEC 61000-4-2

Yes

Yes

-

Emitted interference test IEC 61000-4-3

Yes

Yes

Yes

Yes

Mechanical test Compliance -

Vibration test IEC 60255-21-1

Yes

Yes

-

Shock test IEC 60255-21-2

Yes

Yes

-

Seismic test IEC 60255-21-3

Yes

Yes

-

Temperature rise test IEC 60068-2-2

Yes

Yes

Not older than 5 years

Yes

3.3.3.

Date of Type test certificate by independent LAB

3.4.

BCU Functions The monitoring functions include:

3.4.1.

Switching status monitoring (breakers)

Yes

Yes

3.4.2.

Indication & alarm status monitoring

Yes

Yes

3.4.3.

Analogue measurements (currents, voltages, etc.)

Yes

Yes

3.4.4.

Resolution of time tagging

1

1 ms

ms

The control functions include: 3.4.5.

-

Close / open of circuit breakers

Yes

Yes

3.4.6.

-

Close / Open of isolators / disconnectors

Yes

Yes

3.4.7.

-

Transformer Automatic tap change control

Yes

Yes

3.4.8.

-

Breaker Voltage Synchronization Check Control

Yes

Yes

3.4.9.

-

Bay interlocking facilities

Yes

Yes

Yes

Yes

If applicable

Yes

The reporting functions include: 3.4.10.

-

Sequence of Events recording

3.4.11.

-

Post – Mortem Review / Fault waveform capture

3.4.12.

-

Tenders to state memory capacity and functionality

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

Maximum 128 TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 15 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS

3.4.13.

of Sequence of events (and fault waveform capture, if applicable) Remote end status/ indication

faults records Yes

Yes

-

Mimic of remote end

Yes

Yes

-

Status / indications for remote end

Yes

Yes

Yes

1

3.5.

BCU Configuration

3.5.1.

Number of processors

3.5.2.

Main processor

3.5.3.

Secondary processors

3.5.4.

Communication processor (module)

Yes

Yes

3.5.5.

LCD Display and selector Buttons on front of BCU

Yes

Yes

CP300 Not Applicable

Functionality to include -

Full control of circuit bay

Yes

Yes

-

Status of bay plant

Yes

Yes

-

Circuit active line diagram

-

Power system Measurements

-

Display alarms and events

Yes Yes

Yes Yes

3.6.

Processing Units

3.6.1.

Main CPU

Yes

Yes

3.6.2.

Manufacturer

Yes

FREESCALE

3.6.3.

Module designation

3.6.4.

Literature reference for principle of operation

3.6.5.

Mean - time between failure

h

87,600 h

3.6.6.

Power requirements

W

<3W

3.6.7.

Type of processor

3.6.8.

Word length

bit

FREESCALE MPC8343 32Bit

3.6.9.

Clock speed

MHz

400 MHz

3.6.10.

Type of memory used:

3.6.11.

Type, size and extension capabilities

3.6.12.

Simultaneous communication towards multiple IEC 61850 clients (indicate max. number supported)

3.7.

Communications

3.7.1.

Manufacturer

CP300 Not Applicable

KByte

Yes

Yes _1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

DRAM / SRAM / Flash D-RAM 256MByte S-RAM 512MByte Flash 128Mbyte Yes (6 max. number supported)

SIEMENS

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 16 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.7.2.

Module designation

3.7.3.

Literature reference for principle of operation

3.7.4.

Number of communications channels

3.7.5.

Type of processor

If applicable

2 (Transmission / Reception) NA

3.7.6.

Word length

If applicable

NA

3.7.7.

Clock speed

bit

If applicable

NA

3.7.8.

Type and size of memory

MHz

If applicable

NA

3.7.9.

Line interface to communication channel

3.7.10.

Speed of transmission

B/s

100Mbps

100Mbps

3.7.11.

Number and type of communication ports

No

2 Channels (FO port)

3.7.12.

Meantime between failure

h

2x LC-FO ports for 61850 NA

3.7.13.

Power requirement

W

2.5W

3.7.14.

Communication Interfaces

Ethernet module ETH-BB-2FO SIPROTEC 5

NA

-

IEC60870-5-101 direct to Control Centre(s)

--

-

IEC60870-5-103 interface to protection IED

--

-

IEC61850 interface to substation LAN

-

IEC60870-5-101 for remote downloading of BCU data List all Protocols available at BCU

3.7.15.

Local interface for Laptop Computer

3.7.16.

IED Interface

Yes

Yes --Yes

-

List of manufactures the BCU has interfaced

Yes

-

Standard communication protocols available

Yes

ABB, ALSTOM, TAPCON, AEBERLE Yes

-

Optional communication protocols available

Yes

Yes

3.8.

Power Supply Module

3.8.1.

Module designation

3.8.2.

Literature reference for principle of operation

SIPROTEC 5

3.8.3.

Maximum number of modules per processor

2

3.8.4.

Nominal Input voltage

3.8.5.

Operating voltage range (Min/Max)

3.8.6.

Power requirement

PS201, PS203

VDC

W

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

110V DC

60-250 VDC 110-230 VAC -20% to +20% PS201 / PS203: 13W – additional expansion

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 17 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS module: 3W 3.8.7.

Isolation

3.8.8.

Meantime between failure

h

87,600 h

3.8.9.

Power requirement

W

16-35W Varies according to Modules

3.9.

Digital Input Module

3.9.1.

Module designation

3.9.2.

Literature reference for principle of operation

3.9.3.

Maximum number of modules supported

3.9.4.

Input voltage

3.5 kV DC

PS201 / IO202/ IO207 / IO230 SIPROTEC 5 9 VDC

24 – 250 Vdc

Is contact input type configurable as

NA

3.9.5.

Status and alarms

Yes

3.9.6.

Sequence of events

Yes

3.9.7.

SP, DP, BCD or parallel inputs

Yes

3.9.8.

Pulse accumulator

Yes

3.9.9.

Or any combination of these

Yes

3.9.10.

Standard number of inputs per module:

3.9.11.

double position

PS201 (3 common potentcial) IO202 (8 isolated); IO207 (16 isolated); IO230 (48 common potential); Yes

3.9.12.

single position

Yes

3.9.13.

Minimum Binary Input threshold

3.9.14.

Type of input circuit isolation

3.9.15.

Input galvanic separation

3.9.16.

Impulse voltage withstand

kV

5 kV

3.9.17.

Scan time

ms

Each 250 Microseconds

3.9.18.

Minimal pulse duration

ms

3.9.19.

Input impedance

3.9.20.

Filter time constant

3.9.21.

Meantime between failure

Vdc

optical coupler NA

ohm

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

DC 24 V-250 V

6MD8:

4.3 ms

ms

Variable Impedance NA

h

NA TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 18 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.9.22.

Power requirement

W

3.10.

Command Output Module

3.10.1.

Module designation

IO202 / IO207

3.10.2.

Literature reference for principle of operation

SIPROTEC 5

3.10.3.

Maximum number of modules supported

3.10.4.

Contact ratings

3.10.5.

Switched voltage

V

<250Vdc

3.10.6.

Switched power

VA max

1000 W/VA

3.10.7.

Switched current

A

5A

3.10.8.

Range of duration of command output

S

3.10.9.

Number of two position output channels per module

3.10.10.

Are outputs activated by select-check-actuate procedure?

Yes

3.10.11.

Are welded contacts checked prior to command output?

Yes

3.10.12.

Are the outputs fused and fuse status monitored?

Yes

3.10.13.

Impulse voltage withstand

kV

5 kV

3.10.14.

Meantime between failure

h

87,500 h

3.10.15.

Power requirement

W

NA

3.11.

Digital Output Module

3.11.1.

Module designation

3.11.2.

Literature reference for principle of operation

3.11.3.

Number of outputs per module

3.11.4.

Maximum number of modules per processor

3.11.5.

Maximum output current

3.11.6.

NA

9 NA

10 ms (standard relays) 5ms (fast relays) NA

PS101 IO202 IO207 SIPROTEC 5 IO202 (8 isolated / 4 NO); IO207 (16 isolated / 8 common potential); IO230 (48 common potential) 9 mA

NA

Maximum switched output voltage

V

<250Vdc

3.11.7.

Impulse voltage withstand

kV

5 kV

3.11.8.

Type of protection against back EMF

kV

NA

3.11.9.

Command duration adjustable in the range

s

NA

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 19 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.11.10.

Meantime between failure

h

NA

3.11.11.

Power requirement

W

NA

3.12.

Analogue Input Module

3.12.1.

Module designation

3.12.2.

Literature reference for principle of operation

3.12.3.

Maximum number of modules supported.

3.12.4.

Scanning resolution

3.12.5.

Accuracy

3.12.6.

How are overflow and conversion failures dealt with?

3.12.7.

Conversion time

3.12.8.

Input filter attenuation at 50 Hz

3.12.9.

Input signal types (e.g. 4-20 mA)

3.12.10.

Method of isolation

3.12.11.

Impulse voltage withstand

3.12.12.

Input impedance

3.12.13.

Type of ADC switching

3.12.14.

Standard number of inputs per module

3.12.15.

Mean time between failure

h

87,500h

3.12.16.

Power requirement

W

5.8mW

3.13.

Direct AC Connection Voltage

3.13.1.

Module designation

3.13.2.

Literature reference for principle of operation

3.13.3.

Maximum number of modules supported

5

3.13.4.

Number of inputs per module

4

3.13.5.

Input voltage ranges

3.13.6.

ANAI- CA- 4EL SIPROTEC 5 5 bits

NA

%

<1 % of Nominal Value NA NA

dB

NA -24mA to +24mA NA

kV

5 kV

ohm

140 ohm resistance NA 4

IO202 SIPROTEC 5

V ac

0V - 200VAC

Input filter attenuation at 50 Hz

dB

NA

3.13.7.

Burden on instrument transformer circuit

VA

3.13.8.

Conversion time

ms

<0.1VA at 57,735V/phase NA

3.13.9.

Scanning resolution

bits

NA

3.13.10.

Accuracy

%

3.13.11.

What calculations are supported

<0.5% of measured value NA

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 20 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 3.13.12.

How are overflow and conversion failures dealt with?

NA

3.13.13.

Method of isolation

NA

3.13.14.

Impulse voltage withstand kV

3.14.

Direct AC Connection Current

3.14.1.

Module designation

3.14.2.

Literature reference for principle of operation

3.14.3.

Maximum number of modules processor

5

3.14.4.

Number of inputs per module

4

3.14.5.

Input current ranges

A

1A or 5A

3.14.6.

Input filter attenuation at 50 Hz

dB

NA

3.14.7.

Burden on instrument transformer circuit

VA

3.14.8.

Conversion time

ms

<0.1VA at rated current NA

3.14.9.

Scanning resolution

bits

NA

3.14.10.

Accuracy

%

3.14.11.

What calculations are supported

<0.5% of measured value NA

3.14.12.

How are overflow and conversion failures dealt with?

NA

3.14.13.

Method of isolation

NA

3.14.14.

Impulse voltage withstand kV

4.

BCU Software

4.1.

General Requirements

4.1.1.

Software Name and Version

4.1.2.

Program structure

4.1.3.

System software

4.1.4.

Standard functions programs

4.1.5.

User functions programs

4.2.

Capability

4.2.1.

kV 5 kV

IO202 SIPROTEC 5

5 kV

kV

Yes

Std. DIGSI Software Std. DIGSI Software CFC, Interlocking, Logic gates SP. DP informations, Grouping in CFC NA

BCU program downloading from HMI/Control Centre

Yes

4.2.2.

Application configuration from HMI/Control Centre

Yes

4.2.3.

Remote selection of processing parameters

Through HWS on LAN Through HWS on LAN On demand

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 21 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 4.2.4.

Selection of communication protocols

4.2.5.

Selection of operation modes (cyclic, polled, etc.)

4.2.6.

Appropriate protection of software against power failure

Only one protocol is offered Through remote DIGSI Yes

4.2.7.

Automatic BCU re-start without software down-loading

Yes

4.3.

System Software

4.3.1.

Operating System (Monitor) Functions and capabilities

4.3.2.

Calendar program Type, functions and capabilities

NA

4.3.3.

Time Synchronization Program Functions and capabilities

Yes

4.3.4.

Data Base Updating program Functions and capabilities

Yes

4.3.5.

Testing and Diagnostics Programs Functions and capabilities

4.4.

Standard Functions Programs

4.4.1.

Data Communication Programs: Functions and capabilities

Yes

4.4.2.

Capability of communication protocol selection

Yes

4.4.3.

Capability of operating modes selection

Yes

4.5. 4.5.1.

Analogue Measurements, Scanning and Transmission Programs Capabilities of adjustments

4.5.2.

Transducers constants

4.5.3.

Periodic transmission/transmission by exception

Cyclic

4.5.4.

Automatic checking of A/D-conversion accuracy

Yes

4.5.5.

Smoothing

Yes

4.5.6.

Threshold values

Yes

4.5.7.

Limits

4.5.8.

Scan duration (range)

4.5.9.

Cycle duration (range)

s

NA

4.5.10.

Priority of transmission

s

Yes

4.5.11.

Digital Input Data Scanning and transmission Program

4.6.

Functions and capabilities

4.6.1.

Capability of adjustments;

4.6.2.

Scan duration (range)

4.6.3.

Transient time of status information (range)

4.6.4.

Cycle duration (range)

4.6.5.

Debouncing filter

Yes

PSOS

Yes

Yes

Self calibrated 4-20 mA

±0.25% NA

--

Yes ms

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

NA Configurable

ms

NA

s

Yes, Configurable TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 22 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS Chatter blocking Yes

4.6.6.

Suppression of intermediate status information

4.6.7.

Time tagging

4.6.8.

Transmission mode

4.6.9.

Priority of transmission

4.7.

Alarm and Event handling

4.7.1.

Grouping of alarms and events

4.7.2.

Maximum number of groups

4.8. 4.8.1.

Supervisory Control Programs: Functions and capabilities Select before execute

Yes

4.8.2.

Target check

Yes

4.8.3.

Cancelling control after adjustable time delay

Yes

4.8.4.

Capability of adjustments:

4.8.5.

Duration of output (range)

s

Settable

4.8.6.

Allowed duration of execution (range)

s

Settable

4.8.7.

Sequence of Events programs

4.8.8.

Minimal sequence of events time resolution

ms

Yes standard SOE as per applicable protocol/ (in SCC) 1

4.8.9.

Sequence of events memory capacity

4.8.10.

Events time resolution (adjustable range)

4.8.11.

Priority of transmission

4.8.12.

Post - Mortem Review / Program

4.8.13.

Selection of analogues for post-mortem review

4.8.14.

Short interval time resolution (adjustable range)

s

NA

4.8.15.

Long interval time resolution (adjustable range)

s

NA

4.9. 4.9.1.

Data processing programs: Functions and capabilities Required minimum data processing:

Yes

4.9.2.

Logic functions

Yes

4.9.3.

Arithmetical functions (MW , Mvar etc )

Yes

4.9.4.

Limiting functions

4.9.5.

Comparative functions

Yes

4.9.6.

Time functions

Yes

Yes, 1ms Spontaneous, cyclic Yes

Yes 2

200 1ms (fixed) Yes COMTRADE View/ SIGRA Yes

s

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

Yes

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 23 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 5.

Gateway Software

5.1.

General Requirements

5.1.1.

Software Name and Version

5.1.2.

No. of IEDs Software can handle

5.1.3.

Yes

SICAM PAS

No

Yes

No. of Tags Software can handle

No

Yes

5.1.4.

Software has provision for future IEDs.

%

5.1.5.

No. of Spare tags for future use

%

5.1.6.

Alarm and Event Grouping

Max: 450 (dependent on number of IPCs in parallel) 15.000-25.000 (from IEDs) 30.000-50.000(to HMI and CC) (dependent on number of IPCs in parallel) 20% spare is available for future use 20% spare is available for future use Yes

5.1.7.

Alarm and Event Separation for NCC and DCC

Yes

5.1.8.

Alarm and Event storage and remote / local access

Yes

5.1.9.

5.2.

All IEDs (including Third Party) can be interfaced on IEC61850 Protocol IEC 61850/IEC 60870-5-101/IEC60870-5-104 Logging Facility Capability of:

5.2.1.

Gateway program downloading from Control Centre

Yes

5.2.2.

Application configuration from Control Centre

Yes

5.2.3.

Remote selection of processing parameters

Yes

5.2.4.

Selection of communication protocols

5.2.5.

Selection of operation modes (cyclic, polled, etc.)

5.2.6.

Appropriate protection of software against power failure

Yes

5.2.7.

Automatic re-start without software down-loading

Yes

5.2.8.

Online Modification of Gateway Software

Yes

5.3.

System Software

5.3.1.

Operating System (Monitor) Functions and capabilities

5.3.2.

Calendar program Type, functions and capabilities

5.3.3.

Time Synchronization Program Functions and capabilities

5.1.10.

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

Yes

Yes Yes

As per Specification Requirement Yes

Yes, Part of FDS NA Yes, Part of FDS TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 24 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 5.3.4.

Data Base Updating program Functions and capabilities

Yes, Part of FDS

5.3.5.

Testing and Diagnostics Programs Functions and capabilities

Yes, Part of FDS

6.

HMI Server /Workstation Software

6.1.

Software Name and Version

6.2.

No. of IEDs Software can handle

6.3.

Yes

SICAM SCC

No

Yes

No. of Tags Software can handle

No

Yes

6.4.

Software has provision for future IEDs.

%

6.5.

No. of Spare tags for future use

%

6.6.

Status updating Time

Yes

Max. 450 Via PAS Server Max. 65536 Via PAS Server 20% spare is available for future use 20% spare is available for future use Yes

6.7.

Analog value Updating Time

Yes

Yes

6.8.

Command operation Time

Yes

Yes

6.9.

Event List

Yes

Yes

6.10.

Dynamic Single Line Diagram

Yes

Yes

6.11.

Dynamic Communication Overview

Yes

Yes

6.12.

Alarm list, Event, reports and Trends with filter option.

Yes

Yes

6.13.

Export of Analogues in CSV/Excel format

Yes

Yes

6.14.

Export of Events in CSV or Standard Format

Yes

Yes

6.15.

Export of Events, Graphical trends and Reports in PDF format

Yes

Yes

6.16.

Online modification and DB generation

Yes

6.17.

Monitoring healthiness of all components of SCS including the LAN cables

Yes

6.18.

Yes

6.19.

Monitoring Healthiness of ports in Ethernet Switches, GPS ,Router, etc Remote end bay details in SCS

Yes Modification of screens/Texts is possible By monitoring port status and SNMP Signals Yes

Yes

Yes

6.20.

Offered SCS is expandable in future

Yes

Yes

6.21.

Lockout trip relay reset from HMI

Yes

Yes

6.22.

All HMI displays mentioned in specifications

Yes

Yes

6.23.

Third Party IED interfaces on IEC 61850 Protocol.

Yes

Yes

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 25 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 7.

GPS Receiver

7.1.1.

Make & Model No

7.1.2.

Country of Origin

7.1.3.

Lighting Protection

Yes

MBG S-PRO

7.1.4.

Display

Yes

Yes

7.1.5.

Network Interfaces to Ethernet LAN

RJ45 or FO

RJ45

7.1.6.

MEINBERG LANTIME M300 Germany

7.1.7.

Range of ambient temp. and max relative humidity for continuous reliable operation Types of port available

7.1.8.

No. Of SNTP ports (Minimum)

7.1.9.

o

C, %RH

0-50°C /85% RJ45

3

6

SNMP based alarm Messaging

Yes

Yes

7.1.10.

Remote user Interfaces for configuration

Yes

Yes

7.1.11.

Time Syhcronization of online Monitoring Systems

Yes

7.1.12.

Time Synchronization of Telecom Equipment

Yes

7.1.13.

Nominal Input voltage

Yes

Yes, Provided systems can be synchronized via NTP Yes, Provided systems can be synchronized via NTP 100-240 VAC

7.1.14.

% of spare for each type of port

20%

Yes

7.1.15.

Power Requirements

7.1.16.

Mean Time Between failure

8.

Laptop

8.1.1.

Manufacturer

Yes

Fujitsu

8.1.2.

Model

Yes

8.1.3.

Country of Origin

CELSIUS H730/ Equivalent Germany

8.1.4.

Processor Intel core i7 Processor or Higher

Intel Core i7

8.1.5.

VAC / VDC % W

-

Type (Minimum)

-

Clock speed (minimum)

30 W 118294 Hours

GHz

up to 3.7GHz

Memory size -

Supplied (minimum)

GB

-

Supportable/expandable

GB

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

8GB

8GB 32GB

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 26 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS 8.1.6.

Storage Type Hard disk

8.1.7.

Optical Storage DVD RW

8.1.8.

Display Screen Size

8.1.9.

Operating system

8.1.10.

Updation of Microsoft recommended fixes and history to be provided Antivirus Software

TB

Inches

Validity

1TB

1TB

Yes

Yes

15.6

Yes

MS Windows

Yes

Up to FAC

Yes

Up to FAC

Trend micro Latest Version Yes

Yes

Yes

Yes

240VAC

Make & Version Years

Antivirus Updation through Centralized Client /Server in S/S 8.1.11.

Nominal Input voltage

VAC

8.1.12.

Power Requirements

W

9.

Fiber Optic Patch Cables

9.1.1.

Make

Yes

Preston

9.1.2.

No. of Fiber cores

Yes

2/4

9.1.3.

Type of Fiber Cable

Yes

Ruggedize

9.1.4.

Flame Retardant Low Smoke Zero Halogen

Yes

Yes

9.1.5.

Maximum tensile strength Short term

N

800

800

9.1.6.

Maximum tensile strength long term

N

200

200

9.1.7.

Outer Sheath Colour

Yes

Orange

10.

System Security Requirements

10.1.1.

Cyber Security shall be implemented as mentioned in specifications. Cyber Security implementations shall be carried out strictly under the guide lines of ICT Qatar, QCERT “National ICS Security Standard” with a broad band to adopt IEC 62351 and ISO/IEC 27002 and/or ISA99 standards All User accounts shall be configured as Role based access model (RBAC). All the Removable media usage in SCS system shall be restricted All the latest security patterns/hot fixes shall be implemented up to FAC Application White listing software shall be adopted in all Computers

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

10.1.2.

10.1.3. 10.1.4. 10.1.5. 10.1.6. 10.1.7.

10.1.8.

10.1.9.

All default and unused accounts in operating systems and in all real time applications shall be disabled. All unnecessary software shall be removed from the SCS System. Use of latest stable release of operating system on all

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

150W

Yes Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

TECHNICAL AFFAIRS Electrical Projects Dept.

VOLUME 4

SECTION 3.4.10

PAGE 27 OF 27

GTC/643G/2014 QATAR POWER TRANSMISSION SYSTEM EXPANSION - PHASE 12 – SUBSTATIONS machines and network devices. 10.1.10.

Operating System, SCS software, Antivirus and Firewall/switch firmware updates shall be provided during the period of warranty.

_1.DOCX

SECTION 3.4.10 SUBSTATION CONTROL SYSTEM

Yes

Yes

TECHNICAL AFFAIRS Electrical Projects Dept.

Software List Station Server Windows 7 Operating System Professional SICAM PAS "full Server" Software – Runtime License OPC Client License CFC Automation License - IEC 61850 (Client) Teaming Utility Software Trend Micro Office Scan Client Gateway Windows 7 Operating System Professional SICAM PAS "full Server" Software – Runtime License OPC Client License CFC Automation License - IEC 61850 (Client) License - IEC 104 (Slave) Teaming Utility Software Trend Micro Office Scan Client HWS PC Windows 7 Operating System Professional SICAM SCC SIMATIC Win CC System Software Teaming Utility Software PDF Writer Trend Micro Office Scan Client EPC/HMI Windows 7 Operating System Professional Trend Micro Office Scan Server SICAM SCC SIMATIC Win CC System Software Teaming Utility Software PDF Writer Microsoft Office SICAM PAS Configuration Tool Incident Explorer for Evaluation of Fault records Watch Directory - Professional Firewall Software Digsi ABB PCM600, if applicable ALSTOM MICOM S1 Agile SCHNEIDER MiCOM S1 Studio AVR Software Net view WinZip

Unrestricted