Loading documents preview...
ABB Oy, Distribution Automation Vaasa, Finland
AC Motor Protection (3-phase induction and synchronous motors)
Contents 1. AC motors, brief introduction 2. Introduction to motor protection 3. Thermal Protection, general
4. Thermal Overload Protection 5. Consecutive starts 6. Start-Up Supervision
7. Short-Circuit Protection 8. Unbalance Protection 9. Loss of Load 10. Earth Fault Protection 11. Miscellaneous
1. AC Motors • •
Mechanical construction, stator and rotor Asynchronous and synchronous
Image from Machine Elements in Mechanical Design, Robert L. Mott
1. AC motor construction There are only two main components: the stator and the rotor. The stator contains a pattern of copper coils arranged in windings. As alternating current is passed through the windings, a moving magnetic field is formed near the stator. Rotor (rotating part)
Stator (stationary part)
http://fi.wikipedia.org/wiki/Tiedosto:Asynchronmotor_animation.gif
1. Asynchronous (induction) motor The rotor is constructed of a number of conducting bars running parallel to the axis of the motor and two conducting rings on the ends. The assembly resembles a squirrel cage, thus this type of motor is often called a squirrel-cage motor. Magnetic field formed by the stator induces a current in the rotor, creating its own magnetic field. The interaction of these fields produces a torque on the rotor. Note that there is no direct electrical connection between the stator and the rotor.
Image from Machine Elements in Mechanical Design, Robert L. Mott
http://fi.wikipedia.org/wiki/Tiedosto:Asynchronmotor _animation.gif
1. Synchronous motor The synchronous motor operates at exactly synchronous speed with no slip. The rotor is of a constant polarity (either a permanent magnet or an energized electromagnet) and the windings of the stator are wrapped in such a way as to produce a rotating magnetic field. Such motors provide very little torque at zero speed, and thus need some kind of separate starting apparatus. Often a squirrel-cage rotor is built into the main rotor. When the motor reaches a few percent of synchronous speed, the rotor is energized and the squirrel cage becomes ineffective.
Image from Machine Elements in Mechanical Design, Robert L. Mott
Animation © Motorola, Inc.
2. Introduction to motor protection 2.1 2.2 2.3
Need for protection Protection relays Some important definitions
2.1 Protection objectives
Protection must be able to operate for abnormal conditions
Internal faults
Insulation failure (e.g. winding short-circuits, earth-faults)
Bearing failure
Under-magnetisation (synchronous motors)
Externally imposed faults
Overloading, insufficient cooling
Start-up stress, reversed sequence starting
Supply voltage unbalance or single phasing
Over- and undervoltage
Vibration
Etc.
2.1 Causes for motor damages in industrial drives
Long time overheating 26 % Insulation faults 30 % Rotor or bearing faults 20 % Faulty protection 5 % Other causes 19 %
2.1 Protective functions needed Faulty protection 5 %
Other causes 19 %
Rotor or bearing faults 20 %
Thermal overload protection & RTD Long time overheating 26 %
Short-circuit and earth-fault protection Start-up supervision and thermal sensor (RTD) unit
Insulation faults 30 %
Continuous self-testing of the protection relay Other protective functions
2.2 Motor Protection Relays
SPAM 150C
REX521H07/H50
REF541/3/5
REM541/4/5
REF542Plus
REM610
REM615, 611, 620
REM630
2.3 Definitions
Cold motor
Warm (hot) motor motor has rated operating temperature
motor temperature is same as rated ambient temperature (40°C)
2.3 Definitions
Hot spots at start-up and overload, some parts of the motor heats up faster than others.
End of stator windings
Joints of the rotor rods and conducting rings
temperature in this hot spots is higher than in the stator iron, but after start-up/overload the temperature will level out
Photo courtesy of Lincoln Motors, USA
2.3 How Stop/Start-up/Run conditions are defined Stop
= All phase currents are below 0.12 x IN.
Start-up = The phase currents rise from a value below 0.12 x IN to a value exceeding 1.5 x IN in less than 60 ms. The starting situation ends when the currents fall below 1.25 x IN (more than 100 ms). Run
= The phase currents are over 0.12 x IN and the start condition is not active. < 60ms
Check the exact values from the relay manual
Overload
1.50 xIn 1.25 xIn 0.12 xIn Stop Start-up Running
Stop
3. Thermal protection, general 3.1 3.2
Motor thermal behaviour Direct temp.meas. / current based model
3.1 Motor Thermal Behaviour
Heat is developed at a constant rate due to the current flow
Light load => low current
Electrical energy
=> small heat development
Rated => rated current
Motor Heat
Cooling air etc.
=> adequate heat development
=> temperature rises up to the motor operation temperature
Overload => high current
=> high heat development
=> operation temperature will be exceeded
=> shortened life-time or damages
Mech. energy
3.1 Motor Thermal Behaviour
Developed heat is proportional to the motor current (I2)
Dissipation rate of the heat is proportional to the motor temperature
The higher the motor temperature is the faster heat is dissipated
Motor temperature will increase or decrease until the developed heat and the dissipated heat are in balance +
Developed heat I2 R
-
Dissipated heat T
3.1 Motor Thermal Behaviour
Heating follows an exponential curve
Rate of temperature rise depends on motor thermal time constant t and is proportional to square of current
I K I FLC
2
t 1 e t
Load
t
t
K e t t I IFLC
= constant = 2.7183 (Neper) = time = time constant = highest phase current = Full Load Current
3.1 Motor Thermal Behaviour
Cooling also follows an exponential curve
Rate of temperature drop depends on cooling time constant. (Can be different when the motor is stopped.)
Load
t
t
3.1 Motor Thermal Behaviour
Heating with different loads
High load
Low load Time
Heating with different time constants Small t Big t Time
3.2
Direct temperature measurement and current based thermal model
I K I FLC
2
t 1 e t
3.2 Direct temperature measurement
Sensor types
RTD (resistance temperature detector)
Pt 100, Pt250, Ni 100, Cu 10 etc
Linear (or almost linear)
Thermistors (NTC or PTC)
Typically only PTC (positive temperature coefficient) is supported
PTC curve is of S-shape are like a switch which operates at designed temperature cannot be used as thermometer
PTC
3.2 Direct temperature measurement
Location
Winding: embedded into the winding slot this is overheating protection
Bearing
Other: ambient temperature, cooling air
3.2 Direct temperature measurement
Disadvantages
Slow, does not detect rapid change (start-up, heavy overload)
Advantages
True information, i.e. detects also
failures in the cooling system
reduced cooling because of a dirt etc
3.2 Current based thermal model
I K I FLC
2
t 1 e t
Relay models the motor thermal behaviour based on the phase currents this is overload protection
Disadvantages
Does not see cooling problems
Advantages
No direct temperature measurement needed
Fast => more “accurate" in starts and heavy overloads
Protection both for long time-constant (stator iron) and short time-constant (winding ends, rotor bars) parts in the motor
4. Thermal overload protection (current based) 4.1 4.2 4.3 4.4 4.5 4.6 4.7
Time/current and thermal capability curves Protection considerations Different approaches for finding settings SPAM 150C, REM610, 611, 615, 620 & 630 REM 54_, REF 54_, REX 521 (TOL3Dev) REF 542Plus Other settings
4.1 Time - current curves Motor start-up curves 10000
Time in sec.
1000
Start-up, U=90%
100
Start-up, U=100%
10
1 1
2
3
4
5
Stator current / rated current
6
7
4.1 Thermal limit curves Thermal capability, running Thermal capability for COLD motor (motor started from (rated) ambient temperature)
10000
Time in sec.
1000
Thermal capability for WARM motor (long time motor temperature with rated load)
100
10
1 1
2
3
4
5
Stator current / rated current
6
7
4.1 Thermal withstand curves Thermal capability, running & locked rotor
10000
Time in sec.
1000
100
COLD motor
10
WARM motor
1 1
2
3
4
5
Stator current / rated current
6
7
4.1 Example 1
Squirrel cage motor HXR 500 • 900 kW • 3 kV • 200 A • 1492 rpm
4.1 Example 2
4.2 Protection consideration
Thermal overload protection should operate
Before the motor thermal limits for running motor are exceeded
Locked rotor curves can be handled with start-up supervision
Note: relay thermal curve does not have to follow motor thermal limit curves, it only must be below
Relay should not operate
At normal start-up conditions
4.2 Protection consideration Example 1: relay cold curve goes below start-up curves Not good, motor can never be started (trips every time) 1000
Operation time (sec.)
100
10
1 1
2
3 Stator current / rated current
4
5
4.2 Protection consideration Example 2: relay warm curve is below start-up curves OK, but motor can be started only after some cooling time 1000
Operation time (sec.)
100
10
1 1
2
3 Stator current / rated current
4
5
4.2 Protection consideration Example 3: relay curves are between start-up and motor thermal limit curves OK, but how much protection margin do you want? 10000
1000 Operation time (sec.)
100
10
1 1
2
3 Stator current / rated current
4
5
4.3
Different approaches for finding settings
4.3 Motor thermal limit curves are known We have motor curves relay thermal overload curves must be below running motor thermal limit curves (locked rotor curves can be taken care in start-up supervision) 10000
1000 Operation time (sec.)
100
10
1 1
2
3 Stator current / rated current
4
5
4.3 Motor locked rotor time We know locked rotor time, but no curves Relay warm curve must be same or below given locked rotor time 10000
1000 Operation time (sec.)
Locked rotor time (warm) 100
10
1 1
2
3 Stator current / rated current
4
5
4.3 Process oriented approach
Find smallest possible setting which gives the required number of starts without any problems.
Must know: motor start-up time and current
Must know: how many starts is allowed
Settings allow you to “take out” from the motor all you need but nothing more
We simply assume that motor is big enough for this
4.4
Thermal overload protection in REM610, REM611, REM615, REM 620, REM630 & SPAM 150C
4.4 Thermal Overload Protection
All these relays have basically same thermal overload protection
Single time-constant thermal model
But motor has many parts, with own time-constants using only one time-constant is not good enough especially with big motors
Good protection needs two time-constant
Short time-constant: winding, rotor
Long time-constant: iron case
These relays uses a weighting factor –setting (p)
Commonly p = 50%
Practically gives same result as if using 2 time-constants
4.4 Thermal Overload Protection
“Hot-spot” operation mode (p=50%)
Motors designed for Direct-On-Line (DOL) starts
At start-up or any overload situation the relay follows the temperature of the “hot spots” (short time heating/cooling)
After start-up or overload the temperatures inside the motor will level out. Relay simulates this by “remembering only 50% of the thermal rise during the start-up/overload” % 100
Thermal capacity A
A 80 B 60
ΘA ≈ short time heating/cooling ΘB ≈ long time heating/cooling
B
I > I
I < I
Thermal level for eg. at start-up.
Thermal level at rated current.
4.4 Thermal Overload Protection
But first we must tell motor rated (FLC) current
SPAM 150C
PU scale
I N 1 I NR I NM I N 2
effects to ALL protection stages, except earth-fault
REM615/MTPPR
I NM I N 2 I N 1 I NR
effects ONLY in thermal and undercurrent protection
REM610
I
Rated current
effect only in the function itself
REM630/MTPPR
I NM I N 2 I N 1 I NR
Base value setting (s)
IN1 = CT rated primary current INM = Motor rated current (FLC)
IN2 = CT rated secondary current INR = relay rated current
4.4 Thermal Overload Protection
Heating time constant -setting
SPAM 150C, REM610:
t6x
REM615, REM630:
Time constant start, Time constant normal (sec)
(sec) = op.time for cold motor at 6 x rated current
Time constant (t) = 32.15 x t6x
Cooling time constant - setting
SPAM 150C, REM610:
Cooling factor Kc
REM615, REM630:
Time constant stop (sec)
Time constant stop(t) = Kc x 32.15 x t6x
4.4 Thermal Overload Protection New features in REM615, REM620, REM630 to give flexibility
Separate time constants for normal run and starting
Overload factor setting (SPAM/610 has fixed 1.05)
Negative sequence factor (factory default = 0) if you want to emphasize effect of unbalance to the thermal overload
Initial thermal value (SPAM/610 has fixed 74%): Defines thermal level after power up or clearing of thermal content Cold Curve
Warm Curve
Motor rated
10000
1000 Operation time (sec)
100
10
1 0
100
200 300 Phase current (Amps)
400
500
600
4.5
Thermal overload protection in REM 54_, REF 54_ & REX 521 (TOL3Dev function block)
4.5 Thermal Overload Protection
Motor rated (FLC) current
Protective unit scaling
I N 1 I NR scaling I NM I N 2 Where
IN1
= CT rated primary current
IN2
= CT rated secondary current
INM
= Motor rated current (FLC)
INR
= relay rated current
Scaling must be done in all phases (channels) and it effects to ALL functions using these channels
4.5 Thermal Overload Protection
Protective unit scaling
4.5 Thermal Overload Protection
Separete two time-constant thermal models for stator and rotor
Thermal curves ready for 4 type of motors, 2 type of generators and one transformer Warm motor start-up after 15 min standstill, an example 100 % 90 %
Stator Used thermal capacity [%]
80 % 70 %
Rotor 60 % 50 % 40 % 30 % 20 % 10 % 0% 0
500
1000
1500 Tim e [sec.]
2000
2500
4.5 Thermal Overload Protection
Basic settings = “motor data” etc.
Advanced settings = “real settings”
Advanced settings is automatically re-calculated by the relay whenever Basic settings has been changed
In the CAP tool, do not send the advance settings to the relay if the values are nonsense
4.5 Motor rated current, exercise
Motor rated current is 345A, CT = 500/5A, we want short-circuit protection I>> = 3100A, calculate
protected unit scaling factor for REM 543
I>> setting for REM 543
I setting for SPAM 150C
I>> setting for SPAM 150C
4.6
Thermal overload protection in REF 542Plus
4.6 Thermal Overload Protection
Single time-constant thermal module, but three time-constant settings
Time Constant Off = motor is standstill
Time Constant Normal = motor is running < 2×IMn
Time Constant Overheat = heavy overload or start-up
4.6 Thermal Overload Protection Warm
Cold
10000
Operation time (sec)
Time constant normal Time constant overload
1000
Time constant Off
100
10 0
1
2
3 Current (xIMn)
4
5
6
4.7
Other settings in thermal protection
4.7 Other settings: Cooling time-constant
Cooling when motor is at standstill
Methods of cooling (IC-code) standard IEC 34-6
Self-circulated cooling (IC_11) stop the motor and cooling is 4..6 times slower because fan is stopped also
Heat exchangers cooling is 1..2 times slower
Setting names: cooling factor Kc, time constant stop/off
IC411
IC71W
IC86W
4.7 Other settings: Prior alarm level
Setting considerations
Should be higher than the thermal level of the motor which has been running for a long time with full load
Should give enough time to reduce the load
Generally, prior alarm level is set to 80 .. 95 % of the trip level
Undesirable alarms?
At motor restart (compare alarm level to restart-inhibit margin)
At relay power-on
Relay has no memory of the situation before power-off, therefore a hot (warm) motor condition is assumed. For example SPAM 150C begins from 74% after power-on.
4.7 Other settings: restart inhibit
How to prevent motor start when the temperature is too high?
Exampe: motor temperature is high, but below relay trip level. If we start motor, the temperature will rise too high and relay trips.
Answer: set and use the “restart inhibit” correctly Relay prevents starting untill the motor cools down enough
WAIT
4.7 Other settings: restart inhibit
Typical error: restart inhibit is in series of OPEN circuit, when it should be in series of the CLOSE button
4.7 Other settings: restart inhibit
Setting (inh ):
100% - “consumption of one start-up” - margin
100%
Margin Consumption of a single start-up
inh
time
4.7 Other settings: restart inhibit
Consumption of a single start can can be calculated, if the operation time for a cold motor with start-up current is known start up time consumptio n 100% trip time
4.7 Other settings: restart inhibit
Exercise 1, propose a suitable setting for restart inhibition
Thermal level before start-up was 15% and immediately after 60%
Exercise 2, propose a suitable setting for restart inhibition
Start-up time = 7.5 sec
Trip time = 22 sec
5. Consecutive starts
Cumulative start-up counter
General
Supplementary & Backup protection to the thermal overload
Limits the number of consecutive starts protection against cumulative thermal stress caused by the starts
Does not Trip but inhibits restarting!
Cumulative start-up counter
Number of consecutive starts?
Typically 2 cold / 1hot (or 3 cold / 2 hot) starts within an hour
Typically 10 min cooling time after previous start/running before restarting.
Check the motor manufacturer data, there can be surprises
Sometimes the process / devices connected to the motor limits the number of starts or set requirements for the minimum standstill-time
speed reduction gear
etc
Cumulative start-up counter
Operation of a Cumulative Start-Up Counter
The motor start-up time is added to the counter
If the counter value exceeds the set inhibit-limit the motor is not allowed to be restarted
Inhibition is activated at the begin of the last start-up. This does not abort starting!
The counter value is decreased with a fixed countdown rate
Only after the counter value falls below inhibitlimit the motor is allowed to be restarted
Cumulative start-up counter
Settings
The inhibit level tsi = (n-1) ts +10% where n = number of allowed start-ups ts = starting time (in seconds)
Countdown rate Dts = ts / Dt where
ts = starting time (in seconds) Dt = count time for one start-up (in hours)
Compromising number of starts at nominal and under-voltage
If calculated with nominal start-up time, fewer starts will be allowed at under-voltage situation
Cumulative start-up counter
Exercise: calculate the settings
Starting time = 60 sec.
3 cold start-up is allowed in 4 hours
6. Start-up Supervision = Locked Rotor (LR) protection
Start-up supervision with O/C protection Protection against prolonged start-up
Definite time O/C protection time setting must be long enough to allow starting at undervoltage
I> Time in sec.
1000
100
t> 10
1 1
2
3
4
5
Stator current / rated current
10
Start-up supervision, thermal stress principle Thermal stress is proportional to I2t
Represents energy needed to get the rotor to run full speed
Represents thermal stress in case of stall
Time in sec.
1000
Max permitted locked rotor time
I2t
100
10
1 1
2
3
4
5
Stator current / rated current
10
Safe stall time less than start-up time Typically Exe -type of motor
Protection operation time set below the start-up time
Protection must be blocked by a speed switch when the rotor is speeding up Time in sec.
1000
100
Max permitted locked rotor time
10
1 1
2
3
4
5
Stator current / rated current
10
Safe stall time less than start-up time Have both
Stall = for locked rotor (LRT) protection
I2t = for allowable running-up time (ART) protection (max. start-up time allowed for the motor in case the rotor starts to rotate, but because of external problem or too high mechanical load the start-up is prolonged)
Time in sec.
1000
Stall
I2t
100
Max permitted locked rotor time
10
1 1
2
3
4
5
Stator current / rated current
10
7. Shot-circuit protection
High-set Overcurrent Protection
Interwinding short-circuit protection for the motor
Phase-to-phase short-circuit protection for the feeder cable
Typical setting 1.5 x start-up current
Fast operation needed!
High-set Overcurrent Protection
Doubling effect
I>> setting can be set for automatic doubling during a motor start-up. Setting is selected 75% - 90% of start-up current
High-set Overcurrent functions as a fast run-time stall protection
I
Phase current I>> setting
Start-up
Run-time STALL
time
High-set Overcurrent Protection
But when you have more than one OC stages
Use one stage only for short-circuit, fast op.time
Use another stage for run time stall (=jam protection)
Blocked (or setting doubling) during start up
Op.time can be longer, for example 2 sec
REM615/630 has JAMPTOC function, which basically is OC function with blocking during start up
8. Unbalance protection
Unbalance protection
Unbalance causes negative sequence component of phase current => causes a 2fN rotating flux to the rotorcircuit => the rotor temperature starts to rise.
Squirrel-cage induction motors can withstand unbalance pretty good, but a full broken phase condition is not allowed (about as severe situation as locked rotor)
Two principles are used: NPS and Min-Max
Inverse time characteristics gives selective operation when multible motorfeaders.
Unbalance Protection
3 phase currents are required
In case of 2 x CT
The sum of two phase currents is connected to the relay
NPS function block will work nicely, but if possible set for two-phase operation mode
E/F current will cause errors L1
L1
L1+L3
-(L1+L3) L3
L3
Unbalance Protection
Small voltage unbalance can cause high current unbalance DI DU
I Start-up I FLC
If, for example, the start-up current is 5 x FLC, a 2% voltage unbalance causes 2% x 5 = 10% current unbalance
Positive Phase Sequence Reactance I Startup DI Negative Phase SequenceReactance I FLC DU
Unbalance protection, NPS principle
Negative Phase Sequence Current (NPS, I2) is calculated from the phase currents vectors
Inverse operation, a good estimation of the time constant K is K
175 Istart 2
where Istart = start-up current of the motor x FLC
Unbalance protection, Min-Max Principle
Phase discontinuity protection (SPAM 150C)
The unbalance DI is calculated
DI
IL max IL min 100% IL max
If the phase currents are less than the FLC
IL max IL min DI 100% IFLC
DI and negative phase sequence (NPS) are not the same!
For example 12% NPS sensitivity requires a setting of 12%3 = 20.7%
9. Loss of Load = Undercurrent protection
Undercurrent Protection
Operates upon a sudden loss of load
Can be used in applications where the loss of load indicates a fault condition
submersible pumps, when cooling is based on the constant flow of liquid
conveyor motors, broken belt
Automatically blocked when the phase currents falls below blocking level (8..12%)
10. Earth-fault Protection
Earth Fault Protection
Protection typically nondirectional, definite time
Core Balanced CT (ring CT, toroidal CT)
a must for sensitive protection
recommended CT ratio 50/1 or higher
CT construction
Secondary side voltage
Efficiency
Cable terminal box
Isolation
Sheath earthing
Cable Sheath
Earth Fault Protection
When using sum connection of CTs (known as Holmgren circuit) an apparent EF-current will occur
differencies of CTs
saturation of CTs mainly at start-up because of the DC-component
Minimum recommended setting 10% of the CT rated primary current
Earth Fault Protection
Apparent E/F current will occur at startup due to the saturation of CT when sum connection of CTs is used.
Earth Fault Protection
Avoiding problems of apparent E/F current
Stabilising resistor
Uo condition (directional protection)
Long operation time, or
Temporary blocking of operation at start-up
11. Miscellaneous
Contactor controlled drives
Relay must have normally closed trip contact
Contactor cannot break high currents
High-set O/C protection should be set out-ofuse
E/F protection should be inhibited on high overcurrents