Loading documents preview...
This document is, unless otherwise agreed in writing, the property of TECPRO SYSTEMS LIMITED, and shall not be reproduced, copied, disclosed to any third party or used any purpose other than that for which it is supplied or disclosed. 5 4 3 2 1
REVISED AS PER COMMENTS
DOC.
Approval
P.K.M.
SOURAV
S.M.
18.07.11
0
FIRST SUBMISSION
DOC.
Approval
P.K.M.
SOURAV
S.M.
31.05.11
REV.
STATUS
TYPE
REASONS FOR REVISION
PREPARED CHECKED APPROVED BY BY BY
DATE
INDIA KMPCL 6X600MW Sub Critical Coal – Fired Power Station Project OWNER
KSK MAHANADI POWER CONSTRUCTION CO. LTD. : OWNER'S ENGINEERS
:
DEVELOPMENT CONSULTANTS PVT. LTD. CONSULTING ENGINEERS KOLKATA, MUMBAI, CHENNAI, NEW DELHI
CONTRACTOR
SEPCO ELECTRIC POWER CONSTRUCTION CORP. JINAN , CHINA : CONTRACTOR'S
ENGINEERS:
NORTHEAST ELECTRIC POWER DESIGN INSTITUTE (OF CHINA POWER ENGINEERING CONSULTING GROUP) Changchun, China
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
T
KOLKATA PUNE
CONTROL WRITE UP TSL DOC. No. 563-C&I-203 29/7/2011 B. G. Zarbade
Space for Approval Stamp
As attached
CLIENT DOC. No. KMP-0-AHSV404-N-203
REV.NO.: 1
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
CONTROL WRITE – UP CHAPTER – I 1.0
HIGH CONCENTRATION SLURRY DISPOSAL SYSTEM
1.1
INTRODUCTION Ash handling system is provided with High concentration slurry disposal system for which two common Fly ash silos for each 3x600 MW unit are provided. This Fly ash Silos will feed ash to three independent streams of HCSD system. Two streams shall normally be working and one stream will be available as standby. The silo shall have three openings. These three openings of Fly ash silo will be connected to three independent streams of high concentration slurry disposal system for continuous disposal of high concentrated slurry to ash disposal area with 65‐70% ash concentration. Water is added in mixing tank with moist ash in a controlled manner through continuous automatic “Instrument Based” monitoring system to ensure that the basic slurry parameters remain constant during the transportation of slurry through the pipe line. The pump speed shall be varied through VFD drive over the range of 10% to 100% of maximum flow rate. Necessary remote and manual speed control provision is there. There are two nos. of dedicated transformer to feed the power supply to VFD and after VFD to HCSD motor. The following aspects govern the basic arrangement of high concentration slurry system.
a) b) c) d)
Controlled Ash Feed. Controlled water supply to maintain proper slurry density. HCSD Pump. Disposal Pipe line. 1
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
There are many control features, which have to work for guaranteed monitoring of proper slurry density in a continuous manner so that the slurry pump can operate uninterruptedly. 1.2 MAJOR EQUIPMENTS FOR HCSD SYSTEM • ROTARY FEEDER WITH VFD [ SEPCO SCOPE] One (1) no. Rotary Feeder is provided in upstream of each screw Feeder and takes fly ash input from HCSD silo. It is to be noted that the Rotary Feeder has variable speed control and have ash disposal capacity of 225 TPH. The speed of Rotary Feeder is automatically adjusted as per the reading of Mass Flow meter to maintain required ash flow for slurry consistency (60% ‐ 70%).For variation of Rotary Feeder speed a VVVF drive is provided. Mass flow meter is continuously monitor the feeding rate of fly ash from Rotary Feeder to Mixer tank through Screw Feeder and Paddle Feeder and thus control of ash feeding rate into the system is achieved. • SCREW FEEDER [ SEPCO SCOPE] Screw Feeder is provided in between Rotary Feeder and Paddle Feeder for transportation of dry fly ash from Rotary Feeder to Paddle Feeder because of their eccentric location. The capacity of Screw Feeder shall be same as Rotary Feeder. • PADDLE FEEDER [ SEPCO SCOPE] This is a twin Paddle mixture unloader having capacity 225 TPH. This is provided in upstream of Slurry mixing tank where dry fly ash is been moist and discharge to ART (Agitated Retention Tank). 2
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
• AGITATED RETENTION TANK (ART) [ TSL SCOPE] The ART is a rubber lined cylindrical tank with vertical spindle, twin blade, dual impeller type high torque agitator. The output of Paddle Feeder fed into ART where required slurry concentration and rheology is maintained and monitored. The ART is provided with Level Transmitter for continuous level control measurement, Nucleonic and Non‐nucleonic type Density meter for density measurement and PH meter for measurement of PH value of ash slurry. The ART is provided with proper flushing and drain connection. The mixing tank (ART) will have five level controls. a) High High Level (90 %). b) High Level (80%) c) Operating level (70%). d) Low level (10%). e) Danger low level (0%). Zero level (0%) is set at the start of the lower part of tank. The 90% level is the maximum slurry level allowable in the tank. • CHARGE PUMP [ SEPCO SCOPE] Total Three (3) nos. charge pump, one for each HCSD stream has been providing at the suction of HCSD pumps for each 3X600 MW unit. The pump parameters are 265 cu.M/Hr. @30 MWC. Charge pump can be started under the following condition: o Either suction valve or water line valve should be open. o If suction valve is open, then agitator tank level should be high. o If water line valve is open, then water pressure should be above preset value. 3
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
The pump will trip is the above conditions are not fulfilled. • MEASURING LOOP PUMP [ TSL SCOPE]
One Hose pump each having capacity 1.5 cu.M/Hr. @30 MWC provided with each slurry mixing tank for measuring the slurry density of a mixing tank by non nucleonic density meter. 1.3 HCSD PUMP [ SEPCO SCOPE] There are three sets of HCSD Pump (2W + 1S) each having ash disposal of 225 TPH (Dry ash basis) for two Fly ash silo with motor and VFD are provided for total three streams. Capacity of HCSD Pump is 265cu.m/hr @ 300 MWC. Among the three independent high concentration slurry disposal streams, two are working for two F.A Silo and one is common standby. Three HCSD Pumps are connected with three nos. slurry disposal line with necessary interconnection and instrumentation. The starting permissive of HCSD Pump from HCSD PLC are as follows: • HCSD Pump not failed. • HCSD Pump ready to run (Feed back from HCSD PLC to main PLC) under the following condition: a) VFD ready to run. b) Pump ready to run. c) Propelling pump on. d) Lub pump on. e) Suction flow normal. f) Propelling liquid pressure normal. g) Air pressure normal. 4
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
• HCSD Pump Auto/manual selection from HCSD SCADA. The starts permissive of HCSD Pump from main PLC are as follows: • Manual suction valve open. • Mixture run feed back. • Mixture tank level not low. • IAC Pressure normal. • HCSD PLC ready. • Paddle feeder health. • Rotary feeder healthy. • Mixing tank density (minimum) below preset value. • VFD Ready to RUN
*****************
5
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
CHAPTER II Control Systems 1. HCSD CONTROL SYSTEM The entire HCSD system for unit‐1,2,3,4,5&6 is PLC based control system. The overall control and sequential operation of the total HCSD system is achieved through this main programmable logic controller (SEPCO Scope). The control of the HCSD system is basically from main system PLC and HCSD pump PLC when the ART control panel shall act as a local panel with local actuation facility of Agitator and Measuring loop pump with local feedback and annunciation.
The ART control panel (TSL SCOPE) shall be connected with main system PLC through hardwire cable (By SEPCO). PLC of HCSD system shall correct the speed of the pump, control ash feeding from silo and for other necessary action on the feedback given by ART control panel.
The Agitator and Hose pump shall be running from main PLC as well as through ART control panel. All interlocks / annunciations from field instruments related to ART tank provided by TSL shall be demonstrated during commissioning. The control and Instrumentation scope for the HCSD System is limited to the supply of Control panels & field Instruments related to ART Tank as per P&ID 563‐01‐02 REV 3. Various voltages / currents for the system are as follows. 1) ART Panel Output for lamp: 24V DC 2) ART Panel light, space heater: 240V AC
6
TECPRO SYSTEMS LTD. (ASHTECH DIVISION)
KSK MAHANADI THERMAL POWER PROJECT HCSD SYSTEM (6 x 660 MW)
CONTROL WRITE UP CLIENT DOC. NO.: KMP0-AHS-V007-N-203 REV.-1
CHAPTER III PROTECTION AND INTERLOCK Protection and interlock for the HCSD System is attached herewith.
7
PROTECTION INTERLOCK
1
2
1
2
HCSD PUMP [ 6 nos.]
MIXING TANK AGITATOR [ 6 nos.]
Ref. Drg. 3
563-01-02
Equipment
563-01-02
S.N.
Interlocks Starting Permissive 4
Running Permissive 5
Annunciation
Indications/ Mimic
6
7
1.Manual suction valve open.
1.Manual suction valve open.
1.VFD Trip (OS)
1.HCSD Pump ON Red Lamp (OS)
2.Agitatot run feed back.
2.Agitatot run feed back.
2.HCSD Pump Failed (OS)
2.HCSD Pump OFF Green Lamp (OS)
3.Agitatot tank level not low.
3.Agitatot tank level above Danger 3.Mixing Tank Level Danger Low. Low (OS)
3.GEHO Pump Trip Amber Lamp (OS)
4.IAC Pressure normal.
4.IAC Pressure normal.
4.Density Low (OS)
4.Mixure Tank Level Danger Low Red Lamp (OS)
5.HCSD PLC ready.
5.HCSD PLC ready.
5.Density High (OS)
5.Mixure Tank Level Low Red Lamp (OS)
6.Paddle feeder health.
6.Paddle feeder health.
6.Mixure Tank Level High Red Lamp (OS)
7.Rotary feeder healthy.
7.Rotary feeder healthy.
7.Density High Red Lamp (OS)
8.Mixing tank density (minimum) below preset value
8.Mixing tank density (minimum) below preset value
8.Density Low Red Lamp (OS)
9.VFD Ready to RUN
9.VFD Ready to RUN
1.Start Command Initiated
1.Stop Command NOT Initiated
1.Mixure Tank Level Low (OS)
1.Start Red Lamp (OS/ ART Panel)
2.MCC Available
2.MCC Available
2.Agitator TRIP (OS / ART Panel)
2.Stop Green Lamp (OS/ ART Panel)
3.MCC Not disturbed
3.MCC Not disturbed
3.Mixure Tank Level Danger Low (ART Panel)
3.Trip Amber Lamp (OS/ ART Panel)
4.Tank Level above LOW
4.Tank Level above DANGER LOW
4.Mixure Tank Level Low (ART 4.Tank Level Danger Low Red Panel) lamp (OS)
5. Remote Selected from OS
5. STOP push button not pressed.
5.Mixure Tank Level High (ART 5.Tank Level Low Red lamp (OS) Panel) 6.Tank Level High Red Lamp (OS)
Controls Provided 8
Controlled From 9
Start / Stop P.B. Switch (OS)
OS
Start / Stop P.B. OS / ART Switch (OS / PANEL ART Panel)
PROTECTION INTERLOCK
2
3
CHARGE PUMP [ 6 nos.]
4
ROTARY FEEDER VFD [ 6 Nos.]
5
MEASURIN G LOOP PUMP / HOSE PUMP [ 6 Nos.]
Interlocks Starting Permissive 4
Running Permissive 5
7
1.Stop Command NOT Initiated
1.TRIP (OS)
2. MCC available. 3. Seal water Pressure NORMAL. 4. MCC NOT Disturbed. 5. Agitator Tank Disc. valve open 6. Agitator tank Level above LOW
2. MCC available. 3. Seal water Pressure NORMAL. 4. MCC NOT Disturbed. 5. Agitator Tank Disc. valve open 6. Agitator tank Level above
2.Seal water Pressure LOW (OS) 2.Stop Green Lamp (OS) 3.Trip Amber Lamp (OS)
1.Start command initiated.
1.Stop Command NOT Initiated
1.TRIP (OS)
2.MCC not disturbance.
2.MCC not disturbance.
2.Stop Green Lamp (OS)
3. VFD ready to run
3. VFD ready to run
3.Trip Amber Lamp (OS)
4. Screw feeder RUNNING
4. Screw feeder RUNNING
1.Start command initiated.
1.Stop command not initiated.
2.MCC not disturbance.
2.MCC not disturbance.
3.MCC available.
3.MCC available.
563-01-02
6
6
Indications/ Mimic
1.Start command initiated.
4.Mixing tank Level above LOW
SCREW FEEDER [ 6 Nos.]
Annunciation
563-01-02
1
Ref. Drg. 3
563-01-02
Equipment
563-01-02
S.N.
4.Mixing tank Level above DANGER LOW 5. Discharge pressue Not LOW
1.Start command initiated.
1.Stop Command NOT Initiated
2.MCC not disturbance. 3. VFD ready to run 4. Paddle feeder RUNNING
2.MCC not disturbance. 3. VFD ready to run 4. Paddle feeder RUNNING
1
1.TRIP (OS / ART Panel)
Controls Provided 8
Controlled From 9
Start / Stop P.B. Switch (OS)
OS
1.Start Red Lamp (OS)
1.Start Red Lamp (OS)
Start / Stop P.B. Switch (OS) OS
Start / Stop P.B. 1.Start Red Lamp (OS/ ART Panel) Switch (OS/ ART PANEL)
2. Discharge Pressure HIGH (OS 2.Stop Green Lamp (OS/ ART / ART PANEL) Panel) 3.Trip Amber Lamp (OS/ ART Panel) 4. Discharge Pressure HIGH Red Lamp (OS) 5. Discharge Pressure NORMAL Red Lamp (OS) 1.TRIP (OS)
1.Start Red Lamp (OS) 2.Stop Green Lamp (OS) 3.Trip Amber Lamp (OS)
OS / ART PANEL
Start / Stop P.B. Switch (OS) OS