THERMAX LIMITED BOILER & HEATER GROUP Document No.: DORL-FGSG-7940-059 (TL DOC. NO. :- D65-WH-CS-00661) DORC Doc No.: A545-7950-5043-VD-LW1001-3007-00 & A545-7950-5043-VD-LW1002-3007-00 Rev: 04 Date: 17/09/2019 Pages: 35 DOCUMENT TITLE : SB-PLC IO LIST (POINT DATABASE FOR SB-PLC)

EIL JOB NO. : A545 PACKAGE/UNIT NO.: 115-LW-1001 & 1002 PR CODE : A545-111-LW-PR-7940 THERMAX OC NO. : QL1221/1222 SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

OWNER :- DANGOTE OIL REFINING COMPANY  

Project Name:

04 

17.09.19 

ISSUED FOR REVIEW 

TJB 

NVK 

NVK 

03 

24.05.19 

ISSUED FOR REVIEW 

TJB 

NVK 

NVK 

02 

12.02.19 

ISSUED FOR REVIEW 

TJB 

NVK 

NVK 

01 

23.05.16 

ISSUED FOR REVIEW 

TJB 

NVK 

NVK 



18.03.16 

ISSUED FOR INFORMATION 

TJB 

NVK 

NVK 

Rev. 

Date 

Purpose 

Prepared By 

Checked By 

Approved By 

14-OCT-2019 TANEJA JUHI (MS) (C283) 1 of 35

Page 2 of 35

Revision History:    1. 115‐XS‐1801 is included.    2. IO count corrected.    3. Typo Error corrected.    4. All changes has been highlighted with Magenta Rose colour.     

14-OCT-2019 TANEJA JUHI (MS) (C283) 2 of 35

POINT DATA BASE FOR SB‐PLC NOTES:‐ 1) Unless otherwise specified, Scope shall be as per Tender document. 2) For legends / abbreviation detail refer the legends detsial as mentioned below. 3) Range / Trip / Alarm Set Point Values will be mentioned later in this document.  Trip / Alarm Set Point Values may get changed at site during commissioning. 4) Proximity Barriers / Amplifiers shall be in vendors scope & will be installed in respective PLC Panels. 5) IO's mentioned here are as per P&ID's. Spare I/O count is being mentioned as below. Spare IO qty shall be considered as per the tender requirement. 6) The communication from Soot blower PLC panel to DCS is modbus and customer to consider 2000 soft tags for indication. Modbus list will be separately given alongwith sootblower PLC vendor doc. 7) Square rooting for DP type flow trasnmitters shall be done at DCS end. 8) Refer latest Rev. of doc nos are as follows:‐‐1) P&ID for Flue gas cooler‐ HP steam circuit‐ A545‐42‐115‐1118, 2) P&ID for Flue gas cooler‐ MP steam circuit‐ A545‐42‐115‐1127, 3) P&ID for Soot blower system‐ A545‐42‐115‐1011, 3) P&ID for HP dosing system‐ A545‐42‐115‐1112, 4) P&ID for Turbine‐ A545‐42‐115‐1113. LEGEND DETAILS:‐ LEGEND FGSG FG FW ATTEMP. DIS. STM FLW I/L O/L IND. RCP HP MP LP SB ECO PRESS IS F/W F/W'DING R/T'ING SA

DESCRIPTION FLUE GAS STEAM GENERATOR FLUE GAS FEED WATER ATTEMPERATOR DISCHARGE STEAM FLOW INLET OUTLET INDICATION RECIRCULATION PUMP HIGH PRESSURE MEDIUM PRESSURE LOW PRESSURE SOOT BLOWER ECONOMISER PRESSURE INTRINSICALLY SAFE FORWARD FORWARDING RETRACTING SEAL AIR

LEGEND SH EVAP SAB F/B SEL LS RUN CMD OP CL NC NO TRQ STR STP POS TEMP MOV SW OPRTD SEQ

DESCRIPTION SUPERHEATER EVAPROATOR SEAL AIR BLOWER FEEDBACK SELECTED LIMIT SWICTH RUNNING COMMAND OPEN CLOSE NORMALLY CLOSED NORMALLY OPEN TORQUE START STOP POSITION TEMPERATURE MOTORISED OPERATED VALVE SWITCH OPERATED SEQUENCE

DESCRIPTION CONTROL LEVEL LOW LOW LOW HIGH HIGH HIGH SQUARE FOUNDATION FIELDBUS ANALOG INPUT ANALOG OUTPUT DIGITAL INPUT DIGITAL OUTPUT CONTROL VALVE SATELLITE RACK ROOM DIFFERENTIAL INTERROGATION VOLTAGE LEFT HAND SIDE RIGHT HAND SIDE PUSH BUTTON SOOT BLOWING

LEGEND CTRL LVL LO LO LO HI HI HI SQ. FF AI AO DI DO CV SRR DIFF INTER VLTG LHS RHS PB SB'ING

IO SUMMARY  QTY  SYSTEM

I/O  DESCRIPTION

SB‐PLC

ANALOG  I/P 2 WIRE

ANALOG  O/P 

ACTUAL

SPARE   (Note‐1)

TOTAL

4

1

5

AI‐IS 

4‐20mA (2 WIRE)

AI‐NON IS

4‐20mA (4 WIRE)

AI‐IS

FF [FOUNDATION FIELDBUS I/O (HPT‐IS SPURS)]

AO‐IS

4‐20mA (2 WIRE)

AO‐NON IS

4‐20mA (4 WIRE)

AO‐IS

FF

DI‐IS

PROXIMITY TYPE‐‐24VDC

DI‐NON IS 

FIELD/MCC/MOV'S/ OTHERS‐‐INTER VLTG‐240VAC/24 VDC

742

149

891

DO‐NON IS (WET)

LAMPS ‐ 24VDC WET DO

10

2

12

DO‐NON IS (PFC) 

FIELD/PDB/MOV'S/ OTHERS ‐ POT. FREE DRY CONTACT THROUGH RELAY

71

15

86

REMARKS

PLC vendor needs to consider tested dual  Redundant all I/Os.

DIGITAL INPUT

DIGITAL OUTPUT

REV.03 CHANGES ARE MARKED IN GREEN COLOUR. REV.02 CHANGES ARE MARKED IN ORANGE COLOUR. REV.01 CHANGES ARE MARKED IN BLUE COLOUR.

Page 3 of 35

PLANT : LEKKI FREE TRADE ZONE, NIGERIA

ENGINEERS INDIA LIMITED NEW DELHI

CLIENT : M/S DANGOTE OIL REFINING COMPANY LTD.

4

17/09/2019

TJB

NVK

NVK

3

24/05/2019

TJB

NVK

NVK

2

12/2/2019

TJB

NVK

NVK

DRAWING NO

REV.

0

18/3/2016

TJB

NVK

NVK

D65‐WH‐CS‐00661

3

DIVISION: ENGINEERING

DEPT: INSTRUMENTATION

REVISION

14-OCT-2019 TANEJA JUHI (MS) (C283) 3 of 35

DATE

PREPARED CHECKED BY BY

APP. BY

Sheet : 1 Of 31

Annexure‐I Dangote FGSG Package (QL1221‐2): SB PLC Panels arrangement (front  view) details  in +4200, +7000, +10650 Elevation.

Special care to be taken  in consideration for the  arrangemnet of the CB1  & CB3 Boxes  in  +7000 &  +10650 Elevation to avoid  fouling w.r.t. the bracing 

FGSG‐1 (Looking from Flue Gas Exit Path)

FGSG‐2 (Looking from Flue Gas Exit Path)

+10650 Elevation

115‐SBPLC‐1810

1200mm Width Panels Bayed together CB3

115‐SBPLC‐1811

115‐SBPLC‐2510

1200mm Width Panels Bayed together CB1

CB3

I/O + Marshalling Panels

I/O + Marshalling Panels

CB1

FOR 15 SB ( ALL "A" SERIES)

Boiler Structural Bracing

115‐SBPLC‐1809

Boiler Structural Bracing

115‐SBPLC‐1808

+10650 Elevation

115‐SBPLC‐2509

1200mm Width Panels Bayed together CB1

CB3

CB1

I/O + Marshalling Panels

I/O + Marshalling Panels

FOR 15 SB ( ALL "B" SERIES)

FOR 15 SB ( ALL "A" SERIES)

CB3

FOR 15 SB ( ALL "B" SERIES)

+7000 Elevation

115‐SBPLC‐2506

1200mm Width Panels Bayed together CB1

CB3

I/O + Marshalling Panels

CB1

FOR 15 SB ( ALL "D" SERIES)

FOR 15 SB ( ALL "C" SERIES)

Boiler Structural Bracing

I/O + Marshalling Panels

115‐SBPLC‐1807 Boiler Structural Bracing

115‐SBPLC‐1806

115‐SBPLC‐1805

1200mm Width Panels Bayed together CB3

115‐SBPLC‐2508

1200mm Width Panels Bayed together

+7000 Elevation

115‐SBPLC‐1804

115‐SBPLC‐2511

115‐SBPLC‐2507

115‐SBPLC‐2504

1200mm Width Panels Bayed together

115‐SBPLC‐2505

1200mm Width Panels Bayed together CB1

CB3

CB1

I/O + Marshalling Panels

I/O + Marshalling Panels

FOR 15 SB ( ALL "D" SERIES)

FOR 15 SB ( ALL "C" SERIES)

CB3

+4200 Elevation

115‐SBPLC‐1802

115‐SBPLC‐1803

115‐SBPLC‐1801

800mm width panel + 1200mm width panel CB3

I/O + Marshalling Panels

600mm width panel CB1

CB3

CPU Panels

CB1

FOR 15 SB (ALL "E" SERIES) + COMMON PART (AI + SB DRAIN MOV + SB ISO MOV)

1. This drawings is pictorial representation of SB PLC Panels (Front View) Physical arrangement. 2. Panel canopies have not been shown in this drawing. Please refer respective vendor document (DORL‐FGSG‐7940‐060 ‐ PR for Soot Blower PLC) for details.

Page 4 of 35

14-OCT-2019 TANEJA JUHI (MS) (C283) 4 of 35

Additional Structure included (by Thermax)  for accessibility

Additional Structure included (by  Thermax) for accessibility

CB3

115‐SBPLC‐2501

115‐SBPLC‐2502

600mm width panel

800mm width panel + 1200mm width panel

CPU Panels

CB1

CB3

I/O + Marshalling Panels

115‐SBPLC‐2503

CB1

FOR 15 SB (ALL "E" SERIES) + COMMON PART (AI + SB DRAIN MOV + SB ISO MOV)

Page 5 of 35

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

   PID No INSTRUMENT 

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SYSTEM

SET POINT FOR ALARM  ENGG UNIT 

MIN

MAX

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS  HIGH

LOW

HIGH HIGH 

   TEMP SENSOR LOW LOW 

BURNOUT TYPE STATUS 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

ANALOG INPUT

1

115‐PT‐1834

PI1834

D43‐0WH‐007815P

MP STM FOR SB'ING 

PRESS

SB PLC +4200 Elevation

4‐20mA AI

Open



0

30

Kg/cm2(g)

NA

NA

















D84‐4WH‐000237

IS

2



PAL1834

D43‐0WH‐007815P

MP STM FOR SB'ING 

PRESS LO



SOFT









Kg/cm2(g)









13.0











D84‐4WH‐000237



3



PALL1834

D43‐0WH‐007815P

MP STM FOR SB'ING 

PRESS LO LO



SOFT









Kg/cm2(g)













10.0







D84‐4WH‐000237



4

115‐PT‐1835

PI1835

D43‐0WH‐007815P

SAB DIS.

PRESS

SB PLC +4200 Elevation

4‐20mA AI

Open



0

3500

mmWC

NA

NA

















D84‐4WH‐000237

IS

5



PAL1835

D43‐0WH‐007815P

SAB DIS.

PRESS LO



SOFT









mmWC









1500.0











D84‐4WH‐000237



6



PALL1835

D43‐0WH‐007815P

SAB DIS.

PRESS LO LO



SOFT









mmWC













1350.0







D84‐4WH‐000237



7

115‐TT‐1825

TI1825

D43‐0WH‐007815P

LHS SB DRAIN LINE

TEMP

SB PLC +4200 Elevation

4‐20mA AI

Open



0

400

DegC

NA

NA

















D84‐4WH‐000237

IS

8



TALL1825

D43‐0WH‐007815P

LHS SB DRAIN LINE

TEMP LO LO



SOFT









DegC













210.0







D84‐4WH‐000237



9

115‐TT‐1826

TI1826

D43‐0WH‐007815P

RHS SB DRAIN LINE

TEMP

SB PLC +4200 Elevation

4‐20mA AI

Open



0

400

DegC

NA

NA

















D84‐4WH‐000237

IS

10



TALL1826

D43‐0WH‐007815P

RHS SB DRAIN LINE

TEMP LO LO



SOFT









DegC













210.0







D84‐4WH‐000237



1

115‐ZSH‐1819

ZSH1819

D43‐0WH‐007815P

OP LS

MOV‐1819

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

2

115‐ZSL‐1819

ZSL1819

D43‐0WH‐007815P

CL LS

MOV‐1819

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

3

115‐TSH‐1819

TSH1819

D43‐0WH‐007815P

OP TRQ LS

MOV‐1819

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

4

115‐TSL‐1819

TSL1819

D43‐0WH‐007815P

CL TRQ LS

MOV‐1819

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

5

115‐XTM‐1819

XTM1819

D43‐0WH‐007815P

TRIP F/B

MOV‐1819

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

6

115‐XR‐1819

XR1819

D43‐0WH‐007815P

REMOTE SEL

MOV‐1819

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

7

115‐ZSH‐1820

ZSH1820

D43‐0WH‐007815P

OP LS

MOV‐1820

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

8

115‐ZSL‐1820

ZSL1820

D43‐0WH‐007815P

CL LS

MOV‐1820

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

9

115‐TSH‐1820

TSH1820

D43‐0WH‐007815P

OP TRQ LS

MOV‐1820

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

10

115‐TSL‐1820

TSL1820

D43‐0WH‐007815P

CL TRQ LS

MOV‐1820

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

11

115‐XTM‐1820

XTM1820

D43‐0WH‐007815P

TRIP F/B

MOV‐1820

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

12

115‐XR‐1820

XR1820

D43‐0WH‐007815P

REMOTE SEL

MOV‐1820

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

13

115‐ZSH‐1821

ZSH1821

D43‐0WH‐007815P

OP LS

MOV‐1821

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

14

115‐ZSL‐1821

ZSL1821

D43‐0WH‐007815P

CL LS

MOV‐1821

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

15

115‐TSH‐1821

TSH1821

D43‐0WH‐007815P

OP TRQ LS

MOV‐1821

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.

2‐Wired.

PROXIMITY BARRIER

2‐Wired.

PROXIMITY BARRIER

2‐Wired.

PROXIMITY BARRIER

2‐Wired.

PROXIMITY BARRIER

DIGITAL INPUT

14-OCT-2019 TANEJA JUHI (MS) (C283) 5 of 35

1

Page 6 of 35

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.





YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Pot. Free at MOV, interposing relay at SB‐PLC  end.





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MOV‐1806A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TRQ SW OPRTD

MOV‐1806A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

TRIP F/B

MOV‐1806A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

XR1806A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1806A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐ZSR‐1806BB

ZSR1806BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1806BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

31

115‐ZSF‐1806BB

ZSF1806BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1806BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

32

115‐WSF‐1806BB

WSF1806BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1806BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

33

115‐WSR‐1806BB

WSR1806BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1806BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

34

115‐XT‐1806BB

XT1806BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1806BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

35

115‐XA‐1806BB

XA1806BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1806BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

36

115‐ZLH‐1806B

ZLH1806B

D43‐0WH‐007815P

OP LS

MOV‐1806B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

37

115‐ZLL‐1806B

ZLL1806B

D43‐0WH‐007815P

CL LS

MOV‐1806B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

38

115‐TLX‐1806B

TLX1806B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1806B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

39

115‐XTM‐1806B

XTM1806B

D43‐0WH‐007815P

TRIP F/B

MOV‐1806B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

40

115‐XR‐1806B

XR1806B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1806B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

41

115‐ZSR‐1806CC

ZSR1806CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1806CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1806CC

SB PLC +7000 Elevation

DI‐POT. FREE

INSTRUMENT 

SYSTEM

MIN

MAX

16

115‐TSL‐1821

TSL1821

D43‐0WH‐007815P

CL TRQ LS

MOV‐1821

SB PLC +4200 Elevation

DI‐POT. FREE

Open













17

115‐XTM‐1821

XTM1821

D43‐0WH‐007815P

TRIP F/B

MOV‐1821

SB PLC +4200 Elevation

DI‐POT. FREE

Open











18

115‐XR‐1821

XR1821

D43‐0WH‐007815P

REMOTE SEL

MOV‐1821

SB PLC +4200 Elevation

DI‐POT. FREE

Open









19

115‐ZSR‐1806AA

ZSR1806AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1806AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open







20

115‐ZSF‐1806AA

ZSF1806AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1806AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open





21

115‐WSF‐1806AA

WSF1806AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1806AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



22

115‐WSR‐1806AA

WSR1806AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1806AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open

23

115‐XT‐1806AA

XT1806AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1806AA

SB PLC +10650 Elevation

DI‐POT. FREE

24

115‐XA‐1806AA

XA1806AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1806AA

SB PLC +10650 Elevation

25

115‐ZLH‐1806A

ZLH1806A

D43‐0WH‐007815P

OP LS

MOV‐1806A

26

115‐ZLL‐1806A

ZLL1806A

D43‐0WH‐007815P

CL LS

27

115‐TLX‐1806A

TLX1806A

D43‐0WH‐007815P

28

115‐XTM‐1806A

XTM1806A

29

115‐XR‐1806A

30

42

115‐ZSF‐1806CC

ZSF1806CC

D43‐0WH‐007815P

F/W POS. LS

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI. Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

14-OCT-2019 TANEJA JUHI (MS) (C283) 6 of 35

2

Page 7 of 35

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

43

   PID No INSTRUMENT 

SYSTEM

115‐WSF‐1806CC

WSF1806CC

D43‐0WH‐007815P

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

F/W'DING F/B

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

MIN

MAX





FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS  HIGH

LOW

HIGH HIGH 







   TEMP SENSOR LOW LOW  ‐

BURNOUT TYPE STATUS 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

NO

D84‐4WH‐000237

 IS/  Non‐IS

LRSB‐1806CC

SB PLC +7000 Elevation

DI‐POT. FREE

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















Non IS  Interrogation Voltage 24V DC, 2A 24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

44

115‐WSR‐1806CC

WSR1806CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1806CC

SB PLC +7000 Elevation

45

115‐XT‐1806CC

XT1806CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1806CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

46

115‐XA‐1806CC

XA1806CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1806CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

47

115‐ZLH‐1806C

ZLH1806C

D43‐0WH‐007815P

OP LS

MOV‐1806C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

48

115‐ZLL‐1806C

ZLL1806C

D43‐0WH‐007815P

CL LS

MOV‐1806C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

49

115‐TLX‐1806C

TLX1806C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1806C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

50

115‐XTM‐1806C

XTM1806C

D43‐0WH‐007815P

TRIP F/B

MOV‐1806C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

51

115‐XR‐1806C

XR1806C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1806C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

52

115‐ZSR‐1806DD

ZSR1806DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1806DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

53

115‐ZSF‐1806DD

ZSF1806DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1806DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

54

115‐WSF‐1806DD

WSF1806DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1806DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

55

115‐WSR‐1806DD

WSR1806DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1806DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

56

115‐XT‐1806DD

XT1806DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1806DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

57

115‐XA‐1806DD

XA1806DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1806DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

58

115‐ZLH‐1806D

ZLH1806D

D43‐0WH‐007815P

OP LS

MOV‐1806D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

59

115‐ZLL‐1806D

ZLL1806D

D43‐0WH‐007815P

CL LS

MOV‐1806D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

60

115‐TLX‐1806D

TLX1806D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1806D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

61

115‐XTM‐1806D

XTM1806D

D43‐0WH‐007815P

TRIP F/B

MOV‐1806D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

62

115‐XR‐1806D

XR1806D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1806D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

63

115‐ZSR‐1806EE

ZSR1806EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1806EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

64

115‐ZSF‐1806EE

ZSF1806EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1806EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

65

115‐WSF‐1806EE

WSF1806EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1806EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

66

115‐WSR‐1806EE

WSR1806EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1806EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

67

115‐XT‐1806EE

XT1806EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1806EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

68

115‐XA‐1806EE

XA1806EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1806EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

69

115‐ZLH‐1806E

ZLH1806E

D43‐0WH‐007815P

OP LS

MOV‐1806E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 7 of 35

3

Page 8 of 35

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A







YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MOV‐1807A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

CL LS

MOV‐1807A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1807A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

XTM1807A

D43‐0WH‐007815P

TRIP F/B

MOV‐1807A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐XR‐1807A

XR1807A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1807A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

85

115‐ZSR‐1807BB

ZSR1807BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1807BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

86

115‐ZSF‐1807BB

ZSF1807BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1807BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

87

115‐WSF‐1807BB

WSF1807BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1807BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

88

115‐WSR‐1807BB

WSR1807BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1807BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

89

115‐XT‐1807BB

XT1807BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1807BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

90

115‐XA‐1807BB

XA1807BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1807BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

91

115‐ZLH‐1807B

ZLH1807B

D43‐0WH‐007815P

OP LS

MOV‐1807B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

92

115‐ZLL‐1807B

ZLL1807B

D43‐0WH‐007815P

CL LS

MOV‐1807B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

93

115‐TLX‐1807B

TLX1807B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1807B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

94

115‐XTM‐1807B

XTM1807B

D43‐0WH‐007815P

TRIP F/B

MOV‐1807B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

95

115‐XR‐1807B

XR1807B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1807B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

96

115‐ZSR‐1807CC

ZSR1807CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1807CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

70

115‐ZLL‐1806E

ZLL1806E

D43‐0WH‐007815P

CL LS

MOV‐1806E

SB PLC +4200 Elevation

DI‐POT. FREE

Open













71

115‐TLX‐1806E

TLX1806E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1806E

SB PLC +4200 Elevation

DI‐POT. FREE

Open











72

115‐XTM‐1806E

XTM1806E

D43‐0WH‐007815P

TRIP F/B

MOV‐1806E

SB PLC +4200 Elevation

DI‐POT. FREE

Open









73

115‐XR‐1806E

XR1806E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1806E

SB PLC +4200 Elevation

DI‐POT. FREE

Open







74

115‐ZSR‐1807AA

ZSR1807AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1807AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open





75

115‐ZSF‐1807AA

ZSF1807AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1807AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



76

115‐WSF‐1807AA

WSF1807AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1807AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open

77

115‐WSR‐1807AA

WSR1807AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1807AA

SB PLC +10650 Elevation

DI‐POT. FREE

78

115‐XT‐1807AA

XT1807AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1807AA

SB PLC +10650 Elevation

79

115‐XA‐1807AA

XA1807AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1807AA

80

115‐ZLH‐1807A

ZLH1807A

D43‐0WH‐007815P

OP LS

81

115‐ZLL‐1807A

ZLL1807A

D43‐0WH‐007815P

82

115‐TLX‐1807A

TLX1807A

83

115‐XTM‐1807A

84

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 8 of 35

4

Page 9 of 35

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

MIN

MAX

























   TEMP SENSOR LOW LOW 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW

HIGH HIGH 















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

BURNOUT TYPE STATUS 

INSTRUMENT 

SYSTEM

97

115‐ZSF‐1807CC

ZSF1807CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1807CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open

98

115‐WSF‐1807CC

WSF1807CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1807CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

99

115‐WSR‐1807CC

WSR1807CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1807CC

SB PLC +7000 Elevation

100

115‐XT‐1807CC

XT1807CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1807CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

101

115‐XA‐1807CC

XA1807CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1807CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

102

115‐ZLH‐1807C

ZLH1807C

D43‐0WH‐007815P

OP LS

MOV‐1807C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

103

115‐ZLL‐1807C

ZLL1807C

D43‐0WH‐007815P

CL LS

MOV‐1807C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

104

115‐TLX‐1807C

TLX1807C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1807C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

105

115‐XTM‐1807C

XTM1807C

D43‐0WH‐007815P

TRIP F/B

MOV‐1807C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

106

115‐XR‐1807C

XR1807C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1807C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

107

115‐ZSR‐1807DD

ZSR1807DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1807DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

108

115‐ZSF‐1807DD

ZSF1807DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1807DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

109

115‐WSF‐1807DD

WSF1807DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1807DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

110

115‐WSR‐1807DD

WSR1807DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1807DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

111

115‐XT‐1807DD

XT1807DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1807DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

112

115‐XA‐1807DD

XA1807DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1807DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

113

115‐ZLH‐1807D

ZLH1807D

D43‐0WH‐007815P

OP LS

MOV‐1807D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

114

115‐ZLL‐1807D

ZLL1807D

D43‐0WH‐007815P

CL LS

MOV‐1807D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115

115‐TLX‐1807D

TLX1807D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1807D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

116

115‐XTM‐1807D

XTM1807D

D43‐0WH‐007815P

TRIP F/B

MOV‐1807D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

117

115‐XR‐1807D

XR1807D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1807D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

118

115‐ZSR‐1807EE

ZSR1807EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1807EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

119

115‐ZSF‐1807EE

ZSF1807EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1807EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

120

115‐WSF‐1807EE

WSF1807EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1807EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

121

115‐WSR‐1807EE

WSR1807EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1807EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

122

115‐XT‐1807EE

XT1807EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1807EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

123

115‐XA‐1807EE

XA1807EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1807EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 9 of 35

5

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 10 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A







YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A









YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1808AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

OP LS

MOV‐1808A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

CL LS

MOV‐1808A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TLX1808A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1808A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐XTM‐1808A

XTM1808A

D43‐0WH‐007815P

TRIP F/B

MOV‐1808A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

139

115‐XR‐1808A

XR1808A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1808A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

140

115‐ZSR‐1808BB

ZSR1808BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1808BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

141

115‐ZSF‐1808BB

ZSF1808BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1808BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

142

115‐WSF‐1808BB

WSF1808BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1808BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

143

115‐WSR‐1808BB

WSR1808BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1808BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

144

115‐XT‐1808BB

XT1808BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1808BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

145

115‐XA‐1808BB

XA1808BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1808BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

146

115‐ZLH‐1808B

ZLH1808B

D43‐0WH‐007815P

OP LS

MOV‐1808B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

147

115‐ZLL‐1808B

ZLL1808B

D43‐0WH‐007815P

CL LS

MOV‐1808B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

148

115‐TLX‐1808B

TLX1808B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1808B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

149

115‐XTM‐1808B

XTM1808B

D43‐0WH‐007815P

TRIP F/B

MOV‐1808B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

150

115‐XR‐1808B

XR1808B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1808B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

124

115‐ZLH‐1807E

ZLH1807E

D43‐0WH‐007815P

OP LS

MOV‐1807E

SB PLC +4200 Elevation

DI‐POT. FREE

Open













125

115‐ZLL‐1807E

ZLL1807E

D43‐0WH‐007815P

CL LS

MOV‐1807E

SB PLC +4200 Elevation

DI‐POT. FREE

Open











126

115‐TLX‐1807E

TLX1807E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1807E

SB PLC +4200 Elevation

DI‐POT. FREE

Open









127

115‐XTM‐1807E

XTM1807E

D43‐0WH‐007815P

TRIP F/B

MOV‐1807E

SB PLC +4200 Elevation

DI‐POT. FREE

Open







128

115‐XR‐1807E

XR1807E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1807E

SB PLC +4200 Elevation

DI‐POT. FREE

Open





129

115‐ZSR‐1808AA

ZSR1808AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1808AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



130

115‐ZSF‐1808AA

ZSF1808AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1808AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open

131

115‐WSF‐1808AA

WSF1808AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1808AA

SB PLC +10650 Elevation

DI‐POT. FREE

132

115‐WSR‐1808AA

WSR1808AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1808AA

SB PLC +10650 Elevation

133

115‐XT‐1808AA

XT1808AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1808AA

134

115‐XA‐1808AA

XA1808AA

D43‐0WH‐007815P

AUTO SEL.  

135

115‐ZLH‐1808A

ZLH1808A

D43‐0WH‐007815P

136

115‐ZLL‐1808A

ZLL1808A

137

115‐TLX‐1808A

138

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 10 of 35

6

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 11 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MIN

MAX













Open











Open











LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

INSTRUMENT 

SYSTEM

151

115‐ZSR‐1808CC

ZSR1808CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1808CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open

152

115‐ZSF‐1808CC

ZSF1808CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1808CC

SB PLC +7000 Elevation

DI‐POT. FREE

153

115‐WSF‐1808CC

WSF1808CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1808CC

SB PLC +7000 Elevation

DI‐POT. FREE

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

154

115‐WSR‐1808CC

WSR1808CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1808CC

SB PLC +7000 Elevation

155

115‐XT‐1808CC

XT1808CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1808CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

156

115‐XA‐1808CC

XA1808CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1808CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

157

115‐ZLH‐1808C

ZLH1808C

D43‐0WH‐007815P

OP LS

MOV‐1808C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

158

115‐ZLL‐1808C

ZLL1808C

D43‐0WH‐007815P

CL LS

MOV‐1808C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

159

115‐TLX‐1808C

TLX1808C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1808C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

160

115‐XTM‐1808C

XTM1808C

D43‐0WH‐007815P

TRIP F/B

MOV‐1808C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

161

115‐XR‐1808C

XR1808C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1808C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

162

115‐ZSR‐1808DD

ZSR1808DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1808DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

163

115‐ZSF‐1808DD

ZSF1808DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1808DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

164

115‐WSF‐1808DD

WSF1808DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1808DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

165

115‐WSR‐1808DD

WSR1808DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1808DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

166

115‐XT‐1808DD

XT1808DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1808DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

167

115‐XA‐1808DD

XA1808DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1808DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

168

115‐ZLH‐1808D

ZLH1808D

D43‐0WH‐007815P

OP LS

MOV‐1808D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

169

115‐ZLL‐1808D

ZLL1808D

D43‐0WH‐007815P

CL LS

MOV‐1808D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

170

115‐TLX‐1808D

TLX1808D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1808D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

171

115‐XTM‐1808D

XTM1808D

D43‐0WH‐007815P

TRIP F/B

MOV‐1808D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

172

115‐XR‐1808D

XR1808D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1808D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

173

115‐ZSR‐1808EE

ZSR1808EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1808EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

174

115‐ZSF‐1808EE

ZSF1808EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1808EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

175

115‐WSF‐1808EE

WSF1808EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1808EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

176

115‐WSR‐1808EE

WSR1808EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1808EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

177

115‐XT‐1808EE

XT1808EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1808EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 11 of 35

7

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 12 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MIN

MAX













Open











Open











LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

INSTRUMENT 

SYSTEM

178

115‐XA‐1808EE

XA1808EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1808EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open

179

115‐ZLH‐1808E

ZLH1808E

D43‐0WH‐007815P

OP LS

MOV‐1808E

SB PLC +4200 Elevation

DI‐POT. FREE

180

115‐ZLL‐1808E

ZLL1808E

D43‐0WH‐007815P

CL LS

MOV‐1808E

SB PLC +4200 Elevation

DI‐POT. FREE

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

181

115‐TLX‐1808E

TLX1808E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1808E

SB PLC +4200 Elevation

182

115‐XTM‐1808E

XTM1808E

D43‐0WH‐007815P

TRIP F/B

MOV‐1808E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

183

115‐XR‐1808E

XR1808E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1808E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

184

115‐ZSR‐1809AA

ZSR1809AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1809AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

185

115‐ZSF‐1809AA

ZSF1809AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1809AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

186

115‐WSF‐1809AA

WSF1809AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1809AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

187

115‐WSR‐1809AA

WSR1809AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1809AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

188

115‐XT‐1809AA

XT1809AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1809AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

189

115‐XA‐1809AA

XA1809AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1809AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

190

115‐ZLH‐1809A

ZLH1809A

D43‐0WH‐007815P

OP LS

MOV‐1809A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

191

115‐ZLL‐1809A

ZLL1809A

D43‐0WH‐007815P

CL LS

MOV‐1809A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

192

115‐TLX‐1809A

TLX1809A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1809A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

193

115‐XTM‐1809A

XTM1809A

D43‐0WH‐007815P

TRIP F/B

MOV‐1809A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

194

115‐XR‐1809A

XR1809A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1809A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

195

115‐ZSR‐1809BB

ZSR1809BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1809BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

196

115‐ZSF‐1809BB

ZSF1809BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1809BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

197

115‐WSF‐1809BB

WSF1809BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1809BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

198

115‐WSR‐1809BB

WSR1809BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1809BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

199

115‐XT‐1809BB

XT1809BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1809BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

200

115‐XA‐1809BB

XA1809BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1809BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

201

115‐ZLH‐1809B

ZLH1809B

D43‐0WH‐007815P

OP LS

MOV‐1809B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

202

115‐ZLL‐1809B

ZLL1809B

D43‐0WH‐007815P

CL LS

MOV‐1809B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

203

115‐TLX‐1809B

TLX1809B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1809B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

204

115‐XTM‐1809B

XTM1809B

D43‐0WH‐007815P

TRIP F/B

MOV‐1809B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 12 of 35

8

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 13 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

INSTRUMENT 

SYSTEM

205

115‐XR‐1809B

XR1809B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1809B

SB PLC +10650 Elevation

DI‐POT. FREE

Open

206

115‐ZSR‐1809CC

ZSR1809CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1809CC

SB PLC +7000 Elevation

DI‐POT. FREE

207

115‐ZSF‐1809CC

ZSF1809CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1809CC

SB PLC +7000 Elevation

208

115‐WSF‐1809CC

WSF1809CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1809CC

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR LOW LOW 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW

HIGH HIGH 















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

BURNOUT TYPE STATUS 

MIN

MAX













Open











DI‐POT. FREE

Open









SB PLC +7000 Elevation

DI‐POT. FREE

Open









DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

209

115‐WSR‐1809CC

WSR1809CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1809CC

SB PLC +7000 Elevation

210

115‐XT‐1809CC

XT1809CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1809CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

211

115‐XA‐1809CC

XA1809CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1809CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

212

115‐ZLH‐1809C

ZLH1809C

D43‐0WH‐007815P

OP LS

MOV‐1809C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

213

115‐ZLL‐1809C

ZLL1809C

D43‐0WH‐007815P

CL LS

MOV‐1809C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

214

115‐TLX‐1809C

TLX1809C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1809C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

215

115‐XTM‐1809C

XTM1809C

D43‐0WH‐007815P

TRIP F/B

MOV‐1809C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

216

115‐XR‐1809C

XR1809C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1809C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

217

115‐ZSR‐1809DD

ZSR1809DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1809DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

218

115‐ZSF‐1809DD

ZSF1809DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1809DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

219

115‐WSF‐1809DD

WSF1809DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1809DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

220

115‐WSR‐1809DD

WSR1809DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1809DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

221

115‐XT‐1809DD

XT1809DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1809DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

222

115‐XA‐1809DD

XA1809DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1809DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

223

115‐ZLH‐1809D

ZLH1809D

D43‐0WH‐007815P

OP LS

MOV‐1809D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

224

115‐ZLL‐1809D

ZLL1809D

D43‐0WH‐007815P

CL LS

MOV‐1809D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

225

115‐TLX‐1809D

TLX1809D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1809D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

226

115‐XTM‐1809D

XTM1809D

D43‐0WH‐007815P

TRIP F/B

MOV‐1809D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

227

115‐XR‐1809D

XR1809D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1809D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

228

115‐ZSR‐1809EE

ZSR1809EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1809EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

229

115‐ZSF‐1809EE

ZSF1809EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1809EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

230

115‐WSF‐1809EE

WSF1809EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1809EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

231

115‐WSR‐1809EE

WSR1809EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1809EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 13 of 35

9

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 14 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A











YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A













YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1810AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TRIP F/B

LRSB‐1810AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1810AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

ZLH1810A

D43‐0WH‐007815P

OP LS

MOV‐1810A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐ZLL‐1810A

ZLL1810A

D43‐0WH‐007815P

CL LS

MOV‐1810A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

247

115‐TLX‐1810A

TLX1810A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1810A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

248

115‐XTM‐1810A

XTM1810A

D43‐0WH‐007815P

TRIP F/B

MOV‐1810A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

249

115‐XR‐1810A

XR1810A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1810A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

250

115‐ZSR‐1810BB

ZSR1810BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1810BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

251

115‐ZSF‐1810BB

ZSF1810BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1810BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

252

115‐WSF‐1810BB

WSF1810BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1810BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

253

115‐WSR‐1810BB

WSR1810BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1810BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

254

115‐XT‐1810BB

XT1810BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1810BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

255

115‐XA‐1810BB

XA1810BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1810BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

256

115‐ZLH‐1810B

ZLH1810B

D43‐0WH‐007815P

OP LS

MOV‐1810B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

257

115‐ZLL‐1810B

ZLL1810B

D43‐0WH‐007815P

CL LS

MOV‐1810B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

258

115‐TLX‐1810B

TLX1810B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1810B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

232

115‐XT‐1809EE

XT1809EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1809EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open













233

115‐XA‐1809EE

XA1809EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1809EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open











234

115‐ZLH‐1809E

ZLH1809E

D43‐0WH‐007815P

OP LS

MOV‐1809E

SB PLC +4200 Elevation

DI‐POT. FREE

Open









235

115‐ZLL‐1809E

ZLL1809E

D43‐0WH‐007815P

CL LS

MOV‐1809E

SB PLC +4200 Elevation

DI‐POT. FREE

Open







236

115‐TLX‐1809E

TLX1809E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1809E

SB PLC +4200 Elevation

DI‐POT. FREE

Open





237

115‐XTM‐1809E

XTM1809E

D43‐0WH‐007815P

TRIP F/B

MOV‐1809E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



238

115‐XR‐1809E

XR1809E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1809E

SB PLC +4200 Elevation

DI‐POT. FREE

Open

239

115‐ZSR‐1810AA

ZSR1810AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1810AA

SB PLC +10650 Elevation

DI‐POT. FREE

240

115‐ZSF‐1810AA

ZSF1810AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1810AA

SB PLC +10650 Elevation

241

115‐WSF‐1810AA

WSF1810AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1810AA

242

115‐WSR‐1810AA

WSR1810AA

D43‐0WH‐007815P

R/T'ING F/B

243

115‐XT‐1810AA

XT1810AA

D43‐0WH‐007815P

244

115‐XA‐1810AA

XA1810AA

245

115‐ZLH‐1810A

246

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 14 of 35

10

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 15 of 35

259

   PID No INSTRUMENT 

SYSTEM

115‐XTM‐1810B

XTM1810B

D43‐0WH‐007815P

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

TRIP F/B

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

MIN

MAX





FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS  HIGH

LOW

HIGH HIGH 

YES





   TEMP SENSOR LOW LOW  ‐

BURNOUT TYPE STATUS 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

NC

D84‐4WH‐000237

 IS/  Non‐IS

MOV‐1810B

SB PLC +10650 Elevation

DI‐POT. FREE

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















Non IS  Interrogation Voltage 24V DC, 2A 24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

260

115‐XR‐1810B

XR1810B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1810B

SB PLC +10650 Elevation

261

115‐ZSR‐1810CC

ZSR1810CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1810CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

262

115‐ZSF‐1810CC

ZSF1810CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1810CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

263

115‐WSF‐1810CC

WSF1810CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1810CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

264

115‐WSR‐1810CC

WSR1810CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1810CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

265

115‐XT‐1810CC

XT1810CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1810CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

266

115‐XA‐1810CC

XA1810CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1810CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

267

115‐ZLH‐1810C

ZLH1810C

D43‐0WH‐007815P

OP LS

MOV‐1810C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

268

115‐ZLL‐1810C

ZLL1810C

D43‐0WH‐007815P

CL LS

MOV‐1810C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

269

115‐TLX‐1810C

TLX1810C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1810C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

270

115‐XTM‐1810C

XTM1810C

D43‐0WH‐007815P

TRIP F/B

MOV‐1810C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

271

115‐XR‐1810C

XR1810C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1810C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

272

115‐ZSR‐1810DD

ZSR1810DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1810DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

273

115‐ZSF‐1810DD

ZSF1810DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1810DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

274

115‐WSF‐1810DD

WSF1810DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1810DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

275

115‐WSR‐1810DD

WSR1810DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1810DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

276

115‐XT‐1810DD

XT1810DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1810DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

277

115‐XA‐1810DD

XA1810DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1810DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

278

115‐ZLH‐1810D

ZLH1810D

D43‐0WH‐007815P

OP LS

MOV‐1810D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

279

115‐ZLL‐1810D

ZLL1810D

D43‐0WH‐007815P

CL LS

MOV‐1810D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

280

115‐TLX‐1810D

TLX1810D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1810D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

281

115‐XTM‐1810D

XTM1810D

D43‐0WH‐007815P

TRIP F/B

MOV‐1810D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

282

115‐XR‐1810D

XR1810D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1810D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

283

115‐ZSR‐1810EE

ZSR1810EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1810EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

284

115‐ZSF‐1810EE

ZSF1810EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1810EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

285

115‐WSF‐1810EE

WSF1810EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1810EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 15 of 35

11

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 16 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

INSTRUMENT 

SYSTEM

286

115‐WSR‐1810EE

WSR1810EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1810EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open

287

115‐XT‐1810EE

XT1810EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1810EE

SB PLC +4200 Elevation

DI‐POT. FREE

288

115‐XA‐1810EE

XA1810EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1810EE

SB PLC +4200 Elevation

289

115‐ZLH‐1810E

ZLH1810E

D43‐0WH‐007815P

OP LS

MOV‐1810E

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR LOW LOW 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW

HIGH HIGH 















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

BURNOUT TYPE STATUS 

MIN

MAX













Open











DI‐POT. FREE

Open









SB PLC +4200 Elevation

DI‐POT. FREE

Open









DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

290

115‐ZLL‐1810E

ZLL1810E

D43‐0WH‐007815P

CL LS

MOV‐1810E

SB PLC +4200 Elevation

291

115‐TLX‐1810E

TLX1810E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1810E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

292

115‐XTM‐1810E

XTM1810E

D43‐0WH‐007815P

TRIP F/B

MOV‐1810E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

293

115‐XR‐1810E

XR1810E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1810E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

294

115‐ZSR‐1811AA

ZSR1811AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1811AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

295

115‐ZSF‐1811AA

ZSF1811AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1811AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

296

115‐WSF‐1811AA

WSF1811AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1811AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

297

115‐WSR‐1811AA

WSR1811AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1811AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

298

115‐XT‐1811AA

XT1811AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1811AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

299

115‐XA‐1811AA

XA1811AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1811AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

300

115‐ZLH‐1811A

ZLH1811A

D43‐0WH‐007815P

OP LS

MOV‐1811A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

301

115‐ZLL‐1811A

ZLL1811A

D43‐0WH‐007815P

CL LS

MOV‐1811A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

302

115‐TLX‐1811A

TLX1811A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1811A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

303

115‐XTM‐1811A

XTM1811A

D43‐0WH‐007815P

TRIP F/B

MOV‐1811A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

304

115‐XR‐1811A

XR1811A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1811A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

305

115‐ZSR‐1811BB

ZSR1811BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1811BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

306

115‐ZSF‐1811BB

ZSF1811BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1811BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

307

115‐WSF‐1811BB

WSF1811BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1811BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

308

115‐WSR‐1811BB

WSR1811BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1811BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

309

115‐XT‐1811BB

XT1811BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1811BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

310

115‐XA‐1811BB

XA1811BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1811BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

311

115‐ZLH‐1811B

ZLH1811B

D43‐0WH‐007815P

OP LS

MOV‐1811B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

312

115‐ZLL‐1811B

ZLL1811B

D43‐0WH‐007815P

CL LS

MOV‐1811B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 16 of 35

12

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 17 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MOV‐1811C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TRQ SW OPRTD

MOV‐1811C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

TRIP F/B

MOV‐1811C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

XR1811C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1811C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐ZSR‐1811DD

ZSR1811DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1811DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

328

115‐ZSF‐1811DD

ZSF1811DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1811DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

329

115‐WSF‐1811DD

WSF1811DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1811DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

330

115‐WSR‐1811DD

WSR1811DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1811DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

331

115‐XT‐1811DD

XT1811DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1811DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

332

115‐XA‐1811DD

XA1811DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1811DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

333

115‐ZLH‐1811D

ZLH1811D

D43‐0WH‐007815P

OP LS

MOV‐1811D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

334

115‐ZLL‐1811D

ZLL1811D

D43‐0WH‐007815P

CL LS

MOV‐1811D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

335

115‐TLX‐1811D

TLX1811D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1811D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

336

115‐XTM‐1811D

XTM1811D

D43‐0WH‐007815P

TRIP F/B

MOV‐1811D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

337

115‐XR‐1811D

XR1811D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1811D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

338

115‐ZSR‐1811EE

ZSR1811EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1811EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1811EE

SB PLC +4200 Elevation

DI‐POT. FREE

INSTRUMENT 

SYSTEM

MIN

MAX

313

115‐TLX‐1811B

TLX1811B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1811B

SB PLC +10650 Elevation

DI‐POT. FREE

Open













314

115‐XTM‐1811B

XTM1811B

D43‐0WH‐007815P

TRIP F/B

MOV‐1811B

SB PLC +10650 Elevation

DI‐POT. FREE

Open











315

115‐XR‐1811B

XR1811B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1811B

SB PLC +10650 Elevation

DI‐POT. FREE

Open









316

115‐ZSR‐1811CC

ZSR1811CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1811CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open







317

115‐ZSF‐1811CC

ZSF1811CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1811CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open





318

115‐WSF‐1811CC

WSF1811CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1811CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



319

115‐WSR‐1811CC

WSR1811CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1811CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open

320

115‐XT‐1811CC

XT1811CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1811CC

SB PLC +7000 Elevation

DI‐POT. FREE

321

115‐XA‐1811CC

XA1811CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1811CC

SB PLC +7000 Elevation

322

115‐ZLH‐1811C

ZLH1811C

D43‐0WH‐007815P

OP LS

MOV‐1811C

323

115‐ZLL‐1811C

ZLL1811C

D43‐0WH‐007815P

CL LS

324

115‐TLX‐1811C

TLX1811C

D43‐0WH‐007815P

325

115‐XTM‐1811C

XTM1811C

326

115‐XR‐1811C

327

339

115‐ZSF‐1811EE

ZSF1811EE

D43‐0WH‐007815P

F/W POS. LS

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI. Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

14-OCT-2019 TANEJA JUHI (MS) (C283) 17 of 35

13

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 18 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A







YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1812AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

F/W'DING F/B

LRSB‐1812AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1812AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

XT1812AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1812AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐XA‐1812AA

XA1812AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1812AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

355

115‐ZLH‐1812A

ZLH1812A

D43‐0WH‐007815P

OP LS

MOV‐1812A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

356

115‐ZLL‐1812A

ZLL1812A

D43‐0WH‐007815P

CL LS

MOV‐1812A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

357

115‐TLX‐1812A

TLX1812A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1812A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

358

115‐XTM‐1812A

XTM1812A

D43‐0WH‐007815P

TRIP F/B

MOV‐1812A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

359

115‐XR‐1812A

XR1812A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1812A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

360

115‐ZSR‐1812BB

ZSR1812BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1812BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

361

115‐ZSF‐1812BB

ZSF1812BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1812BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

362

115‐WSF‐1812BB

WSF1812BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1812BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

363

115‐WSR‐1812BB

WSR1812BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1812BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

364

115‐XT‐1812BB

XT1812BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1812BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

365

115‐XA‐1812BB

XA1812BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1812BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

366

115‐ZLH‐1812B

ZLH1812B

D43‐0WH‐007815P

OP LS

MOV‐1812B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

340

115‐WSF‐1811EE

WSF1811EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1811EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open













341

115‐WSR‐1811EE

WSR1811EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1811EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open











342

115‐XT‐1811EE

XT1811EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1811EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open









343

115‐XA‐1811EE

XA1811EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1811EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open







344

115‐ZLH‐1811E

ZLH1811E

D43‐0WH‐007815P

OP LS

MOV‐1811E

SB PLC +4200 Elevation

DI‐POT. FREE

Open





345

115‐ZLL‐1811E

ZLL1811E

D43‐0WH‐007815P

CL LS

MOV‐1811E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



346

115‐TLX‐1811E

TLX1811E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1811E

SB PLC +4200 Elevation

DI‐POT. FREE

Open

347

115‐XTM‐1811E

XTM1811E

D43‐0WH‐007815P

TRIP F/B

MOV‐1811E

SB PLC +4200 Elevation

DI‐POT. FREE

348

115‐XR‐1811E

XR1811E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1811E

SB PLC +4200 Elevation

349

115‐ZSR‐1812AA

ZSR1812AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1812AA

350

115‐ZSF‐1812AA

ZSF1812AA

D43‐0WH‐007815P

F/W POS. LS

351

115‐WSF‐1812AA

WSF1812AA

D43‐0WH‐007815P

352

115‐WSR‐1812AA

WSR1812AA

353

115‐XT‐1812AA

354

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 18 of 35

14

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 19 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

MIN

MAX

























   TEMP SENSOR LOW LOW 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW

HIGH HIGH 















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

BURNOUT TYPE STATUS 

INSTRUMENT 

SYSTEM

367

115‐ZLL‐1812B

ZLL1812B

D43‐0WH‐007815P

CL LS

MOV‐1812B

SB PLC +10650 Elevation

DI‐POT. FREE

Open

368

115‐TLX‐1812B

TLX1812B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1812B

SB PLC +10650 Elevation

DI‐POT. FREE

Open

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

369

115‐XTM‐1812B

XTM1812B

D43‐0WH‐007815P

TRIP F/B

MOV‐1812B

SB PLC +10650 Elevation

370

115‐XR‐1812B

XR1812B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1812B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

371

115‐ZSR‐1812CC

ZSR1812CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1812CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

372

115‐ZSF‐1812CC

ZSF1812CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1812CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

373

115‐WSF‐1812CC

WSF1812CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1812CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

374

115‐WSR‐1812CC

WSR1812CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1812CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

375

115‐XT‐1812CC

XT1812CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1812CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

376

115‐XA‐1812CC

XA1812CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1812CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

377

115‐ZLH‐1812C

ZLH1812C

D43‐0WH‐007815P

OP LS

MOV‐1812C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

378

115‐ZLL‐1812C

ZLL1812C

D43‐0WH‐007815P

CL LS

MOV‐1812C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

379

115‐TLX‐1812C

TLX1812C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1812C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

380

115‐XTM‐1812C

XTM1812C

D43‐0WH‐007815P

TRIP F/B

MOV‐1812C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

381

115‐XR‐1812C

XR1812C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1812C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

382

115‐ZSR‐1812DD

ZSR1812DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1812DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

383

115‐ZSF‐1812DD

ZSF1812DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1812DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

384

115‐WSF‐1812DD

WSF1812DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1812DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

385

115‐WSR‐1812DD

WSR1812DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1812DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

386

115‐XT‐1812DD

XT1812DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1812DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

387

115‐XA‐1812DD

XA1812DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1812DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

388

115‐ZLH‐1812D

ZLH1812D

D43‐0WH‐007815P

OP LS

MOV‐1812D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

389

115‐ZLL‐1812D

ZLL1812D

D43‐0WH‐007815P

CL LS

MOV‐1812D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

390

115‐TLX‐1812D

TLX1812D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1812D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

391

115‐XTM‐1812D

XTM1812D

D43‐0WH‐007815P

TRIP F/B

MOV‐1812D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

392

115‐XR‐1812D

XR1812D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1812D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

393

115‐ZSR‐1812EE

ZSR1812EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1812EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 19 of 35

15

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 20 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A









YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1813AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

F/W POS. LS

LRSB‐1813AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1813AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

WSR1813AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1813AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐XT‐1813AA

XT1813AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1813AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

409

115‐XA‐1813AA

XA1813AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1813AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

410

115‐ZLH‐1813A

ZLH1813A

D43‐0WH‐007815P

OP LS

MOV‐1813A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

411

115‐ZLL‐1813A

ZLL1813A

D43‐0WH‐007815P

CL LS

MOV‐1813A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

412

115‐TLX‐1813A

TLX1813A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1813A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

413

115‐XTM‐1813A

XTM1813A

D43‐0WH‐007815P

TRIP F/B

MOV‐1813A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

414

115‐XR‐1813A

XR1813A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1813A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

415

115‐ZSR‐1813BB

ZSR1813BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1813BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

416

115‐ZSF‐1813BB

ZSF1813BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1813BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

417

115‐WSF‐1813BB

WSF1813BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1813BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

418

115‐WSR‐1813BB

WSR1813BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1813BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

419

115‐XT‐1813BB

XT1813BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1813BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

420

115‐XA‐1813BB

XA1813BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1813BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

394

115‐ZSF‐1812EE

ZSF1812EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1812EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open













395

115‐WSF‐1812EE

WSF1812EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1812EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open











396

115‐WSR‐1812EE

WSR1812EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1812EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open









397

115‐XT‐1812EE

XT1812EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1812EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open







398

115‐XA‐1812EE

XA1812EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1812EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open





399

115‐ZLH‐1812E

ZLH1812E

D43‐0WH‐007815P

OP LS

MOV‐1812E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



400

115‐ZLL‐1812E

ZLL1812E

D43‐0WH‐007815P

CL LS

MOV‐1812E

SB PLC +4200 Elevation

DI‐POT. FREE

Open

401

115‐TLX‐1812E

TLX1812E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1812E

SB PLC +4200 Elevation

DI‐POT. FREE

402

115‐XTM‐1812E

XTM1812E

D43‐0WH‐007815P

TRIP F/B

MOV‐1812E

SB PLC +4200 Elevation

403

115‐XR‐1812E

XR1812E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1812E

404

115‐ZSR‐1813AA

ZSR1813AA

D43‐0WH‐007815P

REST POS. LS

405

115‐ZSF‐1813AA

ZSF1813AA

D43‐0WH‐007815P

406

115‐WSF‐1813AA

WSF1813AA

407

115‐WSR‐1813AA

408

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 20 of 35

16

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 21 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A







YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A









YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1813CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

OP LS

MOV‐1813C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

CL LS

MOV‐1813C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TLX1813C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1813C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐XTM‐1813C

XTM1813C

D43‐0WH‐007815P

TRIP F/B

MOV‐1813C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

436

115‐XR‐1813C

XR1813C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1813C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

437

115‐ZSR‐1813DD

ZSR1813DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1813DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

438

115‐ZSF‐1813DD

ZSF1813DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1813DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

439

115‐WSF‐1813DD

WSF1813DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1813DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

440

115‐WSR‐1813DD

WSR1813DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1813DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

441

115‐XT‐1813DD

XT1813DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1813DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

442

115‐XA‐1813DD

XA1813DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1813DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

443

115‐ZLH‐1813D

ZLH1813D

D43‐0WH‐007815P

OP LS

MOV‐1813D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

444

115‐ZLL‐1813D

ZLL1813D

D43‐0WH‐007815P

CL LS

MOV‐1813D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

445

115‐TLX‐1813D

TLX1813D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1813D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

446

115‐XTM‐1813D

XTM1813D

D43‐0WH‐007815P

TRIP F/B

MOV‐1813D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

447

115‐XR‐1813D

XR1813D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1813D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

421

115‐ZLH‐1813B

ZLH1813B

D43‐0WH‐007815P

OP LS

MOV‐1813B

SB PLC +10650 Elevation

DI‐POT. FREE

Open













422

115‐ZLL‐1813B

ZLL1813B

D43‐0WH‐007815P

CL LS

MOV‐1813B

SB PLC +10650 Elevation

DI‐POT. FREE

Open











423

115‐TLX‐1813B

TLX1813B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1813B

SB PLC +10650 Elevation

DI‐POT. FREE

Open









424

115‐XTM‐1813B

XTM1813B

D43‐0WH‐007815P

TRIP F/B

MOV‐1813B

SB PLC +10650 Elevation

DI‐POT. FREE

Open







425

115‐XR‐1813B

XR1813B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1813B

SB PLC +10650 Elevation

DI‐POT. FREE

Open





426

115‐ZSR‐1813CC

ZSR1813CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1813CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



427

115‐ZSF‐1813CC

ZSF1813CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1813CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open

428

115‐WSF‐1813CC

WSF1813CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1813CC

SB PLC +7000 Elevation

DI‐POT. FREE

429

115‐WSR‐1813CC

WSR1813CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1813CC

SB PLC +7000 Elevation

430

115‐XT‐1813CC

XT1813CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1813CC

431

115‐XA‐1813CC

XA1813CC

D43‐0WH‐007815P

AUTO SEL.  

432

115‐ZLH‐1813C

ZLH1813C

D43‐0WH‐007815P

433

115‐ZLL‐1813C

ZLL1813C

434

115‐TLX‐1813C

435

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 21 of 35

17

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 22 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A











YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MOV‐1813E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

REST POS. LS

LRSB‐1814AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1814AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

WSF1814AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1814AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐WSR‐1814AA

WSR1814AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1814AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

463

115‐XT‐1814AA

XT1814AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1814AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

464

115‐XA‐1814AA

XA1814AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1814AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

465

115‐ZLH‐1814A

ZLH1814A

D43‐0WH‐007815P

OP LS

MOV‐1814A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

466

115‐ZLL‐1814A

ZLL1814A

D43‐0WH‐007815P

CL LS

MOV‐1814A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

467

115‐TLX‐1814A

TLX1814A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1814A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

468

115‐XTM‐1814A

XTM1814A

D43‐0WH‐007815P

TRIP F/B

MOV‐1814A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

469

115‐XR‐1814A

XR1814A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1814A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

470

115‐ZSR‐1814BB

ZSR1814BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1814BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

471

115‐ZSF‐1814BB

ZSF1814BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1814BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

472

115‐WSF‐1814BB

WSF1814BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1814BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

473

115‐WSR‐1814BB

WSR1814BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1814BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

474

115‐XT‐1814BB

XT1814BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1814BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

448

115‐ZSR‐1813EE

ZSR1813EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1813EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open













449

115‐ZSF‐1813EE

ZSF1813EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1813EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open











450

115‐WSF‐1813EE

WSF1813EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1813EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open









451

115‐WSR‐1813EE

WSR1813EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1813EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open







452

115‐XT‐1813EE

XT1813EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1813EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open





453

115‐XA‐1813EE

XA1813EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1813EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



454

115‐ZLH‐1813E

ZLH1813E

D43‐0WH‐007815P

OP LS

MOV‐1813E

SB PLC +4200 Elevation

DI‐POT. FREE

Open

455

115‐ZLL‐1813E

ZLL1813E

D43‐0WH‐007815P

CL LS

MOV‐1813E

SB PLC +4200 Elevation

DI‐POT. FREE

456

115‐TLX‐1813E

TLX1813E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1813E

SB PLC +4200 Elevation

457

115‐XTM‐1813E

XTM1813E

D43‐0WH‐007815P

TRIP F/B

MOV‐1813E

458

115‐XR‐1813E

XR1813E

D43‐0WH‐007815P

REMOTE SEL

459

115‐ZSR‐1814AA

ZSR1814AA

D43‐0WH‐007815P

460

115‐ZSF‐1814AA

ZSF1814AA

461

115‐WSF‐1814AA

462

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 22 of 35

18

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 23 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MIN

MAX













Open











Open











LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

INSTRUMENT 

SYSTEM

475

115‐XA‐1814BB

XA1814BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1814BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open

476

115‐ZLH‐1814B

ZLH1814B

D43‐0WH‐007815P

OP LS

MOV‐1814B

SB PLC +10650 Elevation

DI‐POT. FREE

477

115‐ZLL‐1814B

ZLL1814B

D43‐0WH‐007815P

CL LS

MOV‐1814B

SB PLC +10650 Elevation

DI‐POT. FREE

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

478

115‐TLX‐1814B

TLX1814B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1814B

SB PLC +10650 Elevation

479

115‐XTM‐1814B

XTM1814B

D43‐0WH‐007815P

TRIP F/B

MOV‐1814B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

480

115‐XR‐1814B

XR1814B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1814B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

481

115‐ZSR‐1814CC

ZSR1814CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1814CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

482

115‐ZSF‐1814CC

ZSF1814CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1814CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

483

115‐WSF‐1814CC

WSF1814CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1814CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

484

115‐WSR‐1814CC

WSR1814CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1814CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

485

115‐XT‐1814CC

XT1814CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1814CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

486

115‐XA‐1814CC

XA1814CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1814CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

487

115‐ZLH‐1814C

ZLH1814C

D43‐0WH‐007815P

OP LS

MOV‐1814C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

488

115‐ZLL‐1814C

ZLL1814C

D43‐0WH‐007815P

CL LS

MOV‐1814C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

489

115‐TLX‐1814C

TLX1814C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1814C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

490

115‐XTM‐1814C

XTM1814C

D43‐0WH‐007815P

TRIP F/B

MOV‐1814C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

491

115‐XR‐1814C

XR1814C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1814C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

492

115‐ZSR‐1814DD

ZSR1814DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1814DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

493

115‐ZSF‐1814DD

ZSF1814DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1814DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

494

115‐WSF‐1814DD

WSF1814DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1814DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

495

115‐WSR‐1814DD

WSR1814DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1814DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

496

115‐XT‐1814DD

XT1814DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1814DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

497

115‐XA‐1814DD

XA1814DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1814DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

498

115‐ZLH‐1814D

ZLH1814D

D43‐0WH‐007815P

OP LS

MOV‐1814D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

499

115‐ZLL‐1814D

ZLL1814D

D43‐0WH‐007815P

CL LS

MOV‐1814D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

500

115‐TLX‐1814D

TLX1814D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1814D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

501

115‐XTM‐1814D

XTM1814D

D43‐0WH‐007815P

TRIP F/B

MOV‐1814D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 23 of 35

19

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 24 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A













YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MOV‐1814E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

REMOTE SEL

MOV‐1814E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

REST POS. LS

LRSB‐1815AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

ZSF1815AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1815AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐WSF‐1815AA

WSF1815AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1815AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

517

115‐WSR‐1815AA

WSR1815AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1815AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

518

115‐XT‐1815AA

XT1815AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1815AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

519

115‐XA‐1815AA

XA1815AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1815AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

520

115‐ZLH‐1815A

ZLH1815A

D43‐0WH‐007815P

OP LS

MOV‐1815A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

521

115‐ZLL‐1815A

ZLL1815A

D43‐0WH‐007815P

CL LS

MOV‐1815A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

522

115‐TLX‐1815A

TLX1815A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1815A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

523

115‐XTM‐1815A

XTM1815A

D43‐0WH‐007815P

TRIP F/B

MOV‐1815A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

524

115‐XR‐1815A

XR1815A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1815A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

525

115‐ZSR‐1815BB

ZSR1815BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1815BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

526

115‐ZSF‐1815BB

ZSF1815BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1815BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

527

115‐WSF‐1815BB

WSF1815BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1815BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

528

115‐WSR‐1815BB

WSR1815BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1815BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

502

115‐XR‐1814D

XR1814D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1814D

SB PLC +7000 Elevation

DI‐POT. FREE

Open













503

115‐ZSR‐1814EE

ZSR1814EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1814EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open











504

115‐ZSF‐1814EE

ZSF1814EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1814EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open









505

115‐WSF‐1814EE

WSF1814EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1814EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open







506

115‐WSR‐1814EE

WSR1814EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1814EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open





507

115‐XT‐1814EE

XT1814EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1814EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



508

115‐XA‐1814EE

XA1814EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1814EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open

509

115‐ZLH‐1814E

ZLH1814E

D43‐0WH‐007815P

OP LS

MOV‐1814E

SB PLC +4200 Elevation

DI‐POT. FREE

510

115‐ZLL‐1814E

ZLL1814E

D43‐0WH‐007815P

CL LS

MOV‐1814E

SB PLC +4200 Elevation

511

115‐TLX‐1814E

TLX1814E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1814E

512

115‐XTM‐1814E

XTM1814E

D43‐0WH‐007815P

TRIP F/B

513

115‐XR‐1814E

XR1814E

D43‐0WH‐007815P

514

115‐ZSR‐1815AA

ZSR1815AA

515

115‐ZSF‐1815AA

516

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 24 of 35

20

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 25 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A











YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A













YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1815CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TRIP F/B

LRSB‐1815CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1815CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

ZLH1815C

D43‐0WH‐007815P

OP LS

MOV‐1815C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐ZLL‐1815C

ZLL1815C

D43‐0WH‐007815P

CL LS

MOV‐1815C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

544

115‐TLX‐1815C

TLX1815C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1815C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

545

115‐XTM‐1815C

XTM1815C

D43‐0WH‐007815P

TRIP F/B

MOV‐1815C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

546

115‐XR‐1815C

XR1815C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1815C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

547

115‐ZSR‐1815DD

ZSR1815DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1815DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

548

115‐ZSF‐1815DD

ZSF1815DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1815DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

549

115‐WSF‐1815DD

WSF1815DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1815DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

550

115‐WSR‐1815DD

WSR1815DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1815DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

551

115‐XT‐1815DD

XT1815DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1815DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

552

115‐XA‐1815DD

XA1815DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1815DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

553

115‐ZLH‐1815D

ZLH1815D

D43‐0WH‐007815P

OP LS

MOV‐1815D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

554

115‐ZLL‐1815D

ZLL1815D

D43‐0WH‐007815P

CL LS

MOV‐1815D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

555

115‐TLX‐1815D

TLX1815D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1815D

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

529

115‐XT‐1815BB

XT1815BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1815BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open













530

115‐XA‐1815BB

XA1815BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1815BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open











531

115‐ZLH‐1815B

ZLH1815B

D43‐0WH‐007815P

OP LS

MOV‐1815B

SB PLC +10650 Elevation

DI‐POT. FREE

Open









532

115‐ZLL‐1815B

ZLL1815B

D43‐0WH‐007815P

CL LS

MOV‐1815B

SB PLC +10650 Elevation

DI‐POT. FREE

Open







533

115‐TLX‐1815B

TLX1815B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1815B

SB PLC +10650 Elevation

DI‐POT. FREE

Open





534

115‐XTM‐1815B

XTM1815B

D43‐0WH‐007815P

TRIP F/B

MOV‐1815B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



535

115‐XR‐1815B

XR1815B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1815B

SB PLC +10650 Elevation

DI‐POT. FREE

Open

536

115‐ZSR‐1815CC

ZSR1815CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1815CC

SB PLC +7000 Elevation

DI‐POT. FREE

537

115‐ZSF‐1815CC

ZSF1815CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1815CC

SB PLC +7000 Elevation

538

115‐WSF‐1815CC

WSF1815CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1815CC

539

115‐WSR‐1815CC

WSR1815CC

D43‐0WH‐007815P

RETRCCTING F/B

540

115‐XT‐1815CC

XT1815CC

D43‐0WH‐007815P

541

115‐XA‐1815CC

XA1815CC

542

115‐ZLH‐1815C

543

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 25 of 35

21

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 26 of 35

556

   PID No INSTRUMENT 

SYSTEM

115‐XTM‐1815D

XTM1815D

D43‐0WH‐007815P

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

TRIP F/B

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

MIN

MAX





FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS  HIGH

LOW

HIGH HIGH 

YES





   TEMP SENSOR LOW LOW  ‐

BURNOUT TYPE STATUS 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

NC

D84‐4WH‐000237

 IS/  Non‐IS

MOV‐1815D

SB PLC +7000 Elevation

DI‐POT. FREE

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















Non IS  Interrogation Voltage 24V DC, 2A 24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

557

115‐XR‐1815D

XR1815D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1815D

SB PLC +7000 Elevation

558

115‐ZSR‐1815EE

ZSR1815EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1815EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

559

115‐ZSF‐1815EE

ZSF1815EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1815EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

560

115‐WSF‐1815EE

WSF1815EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1815EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

561

115‐WSR‐1815EE

WSR1815EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1815EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

562

115‐XT‐1815EE

XT1815EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1815EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

563

115‐XA‐1815EE

XA1815EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1815EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

564

115‐ZLH‐1815E

ZLH1815E

D43‐0WH‐007815P

OP LS

MOV‐1815E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

565

115‐ZLL‐1815E

ZLL1815E

D43‐0WH‐007815P

CL LS

MOV‐1815E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

566

115‐TLX‐1815E

TLX1815E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1815E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

567

115‐XTM‐1815E

XTM1815E

D43‐0WH‐007815P

TRIP F/B

MOV‐1815E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

568

115‐XR‐1815E

XR1815E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1815E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

569

115‐ZSR‐1816AA

ZSR1816AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1816AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

570

115‐ZSF‐1816AA

ZSF1816AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1816AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

571

115‐WSF‐1816AA

WSF1816AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1816AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

572

115‐WSR‐1816AA

WSR1816AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1816AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

573

115‐XT‐1816AA

XT1816AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1816AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

574

115‐XA‐1816AA

XA1816AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1816AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

575

115‐ZLH‐1816A

ZLH1816A

D43‐0WH‐007815P

OP LS

MOV‐1816A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

576

115‐ZLL‐1816A

ZLL1816A

D43‐0WH‐007815P

CL LS

MOV‐1816A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

577

115‐TLX‐1816A

TLX1816A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1816A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

578

115‐XTM‐1816A

XTM1816A

D43‐0WH‐007815P

TRIP F/B

MOV‐1816A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

579

115‐XR‐1816A

XR1816A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1816A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

580

115‐ZSR‐1816BB

ZSR1816BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1816BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

581

115‐ZSF‐1816BB

ZSF1816BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1816BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

582

115‐WSF‐1816BB

WSF1816BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1816BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 26 of 35

22

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 27 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

INSTRUMENT 

SYSTEM

583

115‐WSR‐1816BB

WSR1816BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1816BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open

584

115‐XT‐1816BB

XT1816BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1816BB

SB PLC +10650 Elevation

DI‐POT. FREE

585

115‐XA‐1816BB

XA1816BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1816BB

SB PLC +10650 Elevation

586

115‐ZLH‐1816B

ZLH1816B

D43‐0WH‐007815P

OP LS

MOV‐1816B

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR LOW LOW 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW

HIGH HIGH 















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

BURNOUT TYPE STATUS 

MIN

MAX













Open











DI‐POT. FREE

Open









SB PLC +10650 Elevation

DI‐POT. FREE

Open









DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

587

115‐ZLL‐1816B

ZLL1816B

D43‐0WH‐007815P

CL LS

MOV‐1816B

SB PLC +10650 Elevation

588

115‐TLX‐1816B

TLX1816B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1816B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

589

115‐XTM‐1816B

XTM1816B

D43‐0WH‐007815P

TRIP F/B

MOV‐1816B

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

590

115‐XR‐1816B

XR1816B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1816B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

591

115‐ZSR‐1816CC

ZSR1816CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1816CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

592

115‐ZSF‐1816CC

ZSF1816CC

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1816CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

593

115‐WSF‐1816CC

WSF1816CC

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1816CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

594

115‐WSR‐1816CC

WSR1816CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1816CC

SB PLC +7000 Elevation

595

115‐XT‐1816CC

XT1816CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1816CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

596

115‐XA‐1816CC

XA1816CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1816CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

597

115‐ZLH‐1816C

ZLH1816C

D43‐0WH‐007815P

OP LS

MOV‐1816C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

598

115‐ZLL‐1816C

ZLL1816C

D43‐0WH‐007815P

CL LS

MOV‐1816C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

599

115‐TLX‐1816C

TLX1816C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1816C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

600

115‐XTM‐1816C

XTM1816C

D43‐0WH‐007815P

TRIP F/B

MOV‐1816C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

601

115‐XR‐1816C

XR1816C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1816C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

602

115‐ZSR‐1816DD

ZSR1816DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1816DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

603

115‐ZSF‐1816DD

ZSF1816DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1816DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

604

115‐WSF‐1816DD

WSF1816DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1816DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

605

115‐WSR‐1816DD

WSR1816DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1816DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

606

115‐XT‐1816DD

XT1816DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1816DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

607

115‐XA‐1816DD

XA1816DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1816DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

608

115‐ZLH‐1816D

ZLH1816D

D43‐0WH‐007815P

OP LS

MOV‐1816D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

609

115‐ZLL‐1816D

ZLL1816D

D43‐0WH‐007815P

CL LS

MOV‐1816D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 27 of 35

23

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 28 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

MOV‐1816E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TRQ SW OPRTD

MOV‐1816E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

TRIP F/B

MOV‐1816E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

XR1816E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1816E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐ZSR‐1817AA

ZSR1817AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1817AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

625

115‐ZSF‐1817AA

ZSF1817AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1817AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

626

115‐WSF‐1817AA

WSF1817AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1817AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

627

115‐WSR‐1817AA

WSR1817AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1817AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

628

115‐XT‐1817AA

XT1817AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1817AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

629

115‐XA‐1817AA

XA1817AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1817AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

630

115‐ZLH‐1817A

ZLH1817A

D43‐0WH‐007815P

OP LS

MOV‐1817A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

631

115‐ZLL‐1817A

ZLL1817A

D43‐0WH‐007815P

CL LS

MOV‐1817A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

632

115‐TLX‐1817A

TLX1817A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1817A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

633

115‐XTM‐1817A

XTM1817A

D43‐0WH‐007815P

TRIP F/B

MOV‐1817A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

634

115‐XR‐1817A

XR1817A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1817A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

635

115‐ZSR‐1817BB

ZSR1817BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1817BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1817BB

SB PLC +10650 Elevation

DI‐POT. FREE

INSTRUMENT 

SYSTEM

MIN

MAX

610

115‐TLX‐1816D

TLX1816D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1816D

SB PLC +7000 Elevation

DI‐POT. FREE

Open













611

115‐XTM‐1816D

XTM1816D

D43‐0WH‐007815P

TRIP F/B

MOV‐1816D

SB PLC +7000 Elevation

DI‐POT. FREE

Open











612

115‐XR‐1816D

XR1816D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1816D

SB PLC +7000 Elevation

DI‐POT. FREE

Open









613

115‐ZSR‐1816EE

ZSR1816EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1816EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open







614

115‐ZSF‐1816EE

ZSF1816EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1816EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open





615

115‐WSF‐1816EE

WSF1816EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1816EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



616

115‐WSR‐1816EE

WSR1816EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1816EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open

617

115‐XT‐1816EE

XT1816EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1816EE

SB PLC +4200 Elevation

DI‐POT. FREE

618

115‐XA‐1816EE

XA1816EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1816EE

SB PLC +4200 Elevation

619

115‐ZLH‐1816E

ZLH1816E

D43‐0WH‐007815P

OP LS

MOV‐1816E

620

115‐ZLL‐1816E

ZLL1816E

D43‐0WH‐007815P

CL LS

621

115‐TLX‐1816E

TLX1816E

D43‐0WH‐007815P

622

115‐XTM‐1816E

XTM1816E

623

115‐XR‐1816E

624

636

115‐ZSF‐1817BB

ZSF1817BB

D43‐0WH‐007815P

F/W POS. LS

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI. Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

14-OCT-2019 TANEJA JUHI (MS) (C283) 28 of 35

24

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 29 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A







YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A





















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1817CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1817CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

637

115‐WSF‐1817BB

WSF1817BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1817BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open













638

115‐WSR‐1817BB

WSR1817BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1817BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open











639

115‐XT‐1817BB

XT1817BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1817BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open









640

115‐XA‐1817BB

XA1817BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1817BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open







641

115‐ZLH‐1817B

ZLH1817B

D43‐0WH‐007815P

OP LS

MOV‐1817B

SB PLC +10650 Elevation

DI‐POT. FREE

Open





642

115‐ZLL‐1817B

ZLL1817B

D43‐0WH‐007815P

CL LS

MOV‐1817B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



643

115‐TLX‐1817B

TLX1817B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1817B

SB PLC +10650 Elevation

DI‐POT. FREE

Open

644

115‐XTM‐1817B

XTM1817B

D43‐0WH‐007815P

TRIP F/B

MOV‐1817B

SB PLC +10650 Elevation

DI‐POT. FREE

645

115‐XR‐1817B

XR1817B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1817B

SB PLC +10650 Elevation

646

115‐ZSR‐1817CC

ZSR1817CC

D43‐0WH‐007815P

REST POS. LS

LRSB‐1817CC

647

115‐ZSF‐1817CC

ZSF1817CC

D43‐0WH‐007815P

F/W POS. LS

648

115‐WSF‐1817CC

WSF1817CC

D43‐0WH‐007815P

F/W'DING F/B

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

649

115‐WSR‐1817CC

WSR1817CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1817CC

SB PLC +7000 Elevation

650

115‐XT‐1817CC

XT1817CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1817CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

651

115‐XA‐1817CC

XA1817CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1817CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

652

115‐ZLH‐1817C

ZLH1817C

D43‐0WH‐007815P

OP LS

MOV‐1817C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

653

115‐ZLL‐1817C

ZLL1817C

D43‐0WH‐007815P

CL LS

MOV‐1817C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

654

115‐TLX‐1817C

TLX1817C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1817C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

655

115‐XTM‐1817C

XTM1817C

D43‐0WH‐007815P

TRIP F/B

MOV‐1817C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

656

115‐XR‐1817C

XR1817C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1817C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

657

115‐ZSR‐1817DD

ZSR1817DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1817DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

658

115‐ZSF‐1817DD

ZSF1817DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1817DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

659

115‐WSF‐1817DD

WSF1817DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1817DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

660

115‐WSR‐1817DD

WSR1817DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1817DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

661

115‐XT‐1817DD

XT1817DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1817DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

662

115‐XA‐1817DD

XA1817DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1817DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

663

115‐ZLH‐1817D

ZLH1817D

D43‐0WH‐007815P

OP LS

MOV‐1817D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 29 of 35

25

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 30 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

MIN

MAX

























   TEMP SENSOR LOW LOW 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW

HIGH HIGH 















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

BURNOUT TYPE STATUS 

INSTRUMENT 

SYSTEM

664

115‐ZLL‐1817D

ZLL1817D

D43‐0WH‐007815P

CL LS

MOV‐1817D

SB PLC +7000 Elevation

DI‐POT. FREE

Open

665

115‐TLX‐1817D

TLX1817D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1817D

SB PLC +7000 Elevation

DI‐POT. FREE

Open

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

666

115‐XTM‐1817D

XTM1817D

D43‐0WH‐007815P

TRIP F/B

MOV‐1817D

SB PLC +7000 Elevation

667

115‐XR‐1817D

XR1817D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1817D

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

668

115‐ZSR‐1817EE

ZSR1817EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1817EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

669

115‐ZSF‐1817EE

ZSF1817EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1817EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

670

115‐WSF‐1817EE

WSF1817EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1817EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

671

115‐WSR‐1817EE

WSR1817EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1817EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

672

115‐XT‐1817EE

XT1817EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1817EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

673

115‐XA‐1817EE

XA1817EE

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1817EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

674

115‐ZLH‐1817E

ZLH1817E

D43‐0WH‐007815P

OP LS

MOV‐1817E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

675

115‐ZLL‐1817E

ZLL1817E

D43‐0WH‐007815P

CL LS

MOV‐1817E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

676

115‐TLX‐1817E

TLX1817E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1817E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

677

115‐XTM‐1817E

XTM1817E

D43‐0WH‐007815P

TRIP F/B

MOV‐1817E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

678

115‐XR‐1817E

XR1817E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1817E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

679

115‐ZSR‐1818AA

ZSR1818AA

D43‐0WH‐007815P

REST POS. LS

LRSB‐1818AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

680

115‐ZSF‐1818AA

ZSF1818AA

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1818AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

681

115‐WSF‐1818AA

WSF1818AA

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1818AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

682

115‐WSR‐1818AA

WSR1818AA

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1818AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

683

115‐XT‐1818AA

XT1818AA

D43‐0WH‐007815P

TRIP F/B

LRSB‐1818AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

684

115‐XA‐1818AA

XA1818AA

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1818AA

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

685

115‐ZLH‐1818A

ZLH1818A

D43‐0WH‐007815P

OP LS

MOV‐1818A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

686

115‐ZLL‐1818A

ZLL1818A

D43‐0WH‐007815P

CL LS

MOV‐1818A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

687

115‐TLX‐1818A

TLX1818A

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1818A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

688

115‐XTM‐1818A

XTM1818A

D43‐0WH‐007815P

TRIP F/B

MOV‐1818A

SB PLC +10650 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

689

115‐XR‐1818A

XR1818A

D43‐0WH‐007815P

REMOTE SEL

MOV‐1818A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

690

115‐ZSR‐1818BB

ZSR1818BB

D43‐0WH‐007815P

REST POS. LS

LRSB‐1818BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 30 of 35

26

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 31 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A









YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +10650 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1818CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

F/W POS. LS

LRSB‐1818CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

F/W'DING F/B

LRSB‐1818CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

INSTRUMENT 

SYSTEM

MIN

MAX

691

115‐ZSF‐1818BB

ZSF1818BB

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1818BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open













692

115‐WSF‐1818BB

WSF1818BB

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1818BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open











693

115‐WSR‐1818BB

WSR1818BB

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1818BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open









694

115‐XT‐1818BB

XT1818BB

D43‐0WH‐007815P

TRIP F/B

LRSB‐1818BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open







695

115‐XA‐1818BB

XA1818BB

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1818BB

SB PLC +10650 Elevation

DI‐POT. FREE

Open





696

115‐ZLH‐1818B

ZLH1818B

D43‐0WH‐007815P

OP LS

MOV‐1818B

SB PLC +10650 Elevation

DI‐POT. FREE

Open



697

115‐ZLL‐1818B

ZLL1818B

D43‐0WH‐007815P

CL LS

MOV‐1818B

SB PLC +10650 Elevation

DI‐POT. FREE

Open

698

115‐TLX‐1818B

TLX1818B

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1818B

SB PLC +10650 Elevation

DI‐POT. FREE

699

115‐XTM‐1818B

XTM1818B

D43‐0WH‐007815P

TRIP F/B

MOV‐1818B

SB PLC +10650 Elevation

700

115‐XR‐1818B

XR1818B

D43‐0WH‐007815P

REMOTE SEL

MOV‐1818B

701

115‐ZSR‐1818CC

ZSR1818CC

D43‐0WH‐007815P

REST POS. LS

702

115‐ZSF‐1818CC

ZSF1818CC

D43‐0WH‐007815P

703

115‐WSF‐1818CC

WSF1818CC

D43‐0WH‐007815P

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

704

115‐WSR‐1818CC

WSR1818CC

D43‐0WH‐007815P

RETRCCTING F/B

LRSB‐1818CC

SB PLC +7000 Elevation

705

115‐XT‐1818CC

XT1818CC

D43‐0WH‐007815P

TRIP F/B

LRSB‐1818CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

706

115‐XA‐1818CC

XA1818CC

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1818CC

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

707

115‐ZLH‐1818C

ZLH1818C

D43‐0WH‐007815P

OP LS

MOV‐1818C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

708

115‐ZLL‐1818C

ZLL1818C

D43‐0WH‐007815P

CL LS

MOV‐1818C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

709

115‐TLX‐1818C

TLX1818C

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1818C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

710

115‐XTM‐1818C

XTM1818C

D43‐0WH‐007815P

TRIP F/B

MOV‐1818C

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

711

115‐XR‐1818C

XR1818C

D43‐0WH‐007815P

REMOTE SEL

MOV‐1818C

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

712

115‐ZSR‐1818DD

ZSR1818DD

D43‐0WH‐007815P

REST POS. LS

LRSB‐1818DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

713

115‐ZSF‐1818DD

ZSF1818DD

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1818DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

714

115‐WSF‐1818DD

WSF1818DD

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1818DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

715

115‐WSR‐1818DD

WSR1818DD

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1818DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

716

115‐XT‐1818DD

XT1818DD

D43‐0WH‐007815P

TRIP F/B

LRSB‐1818DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

717

115‐XA‐1818DD

XA1818DD

D43‐0WH‐007815P

AUTO SEL.  

LRSB‐1818DD

SB PLC +7000 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

14-OCT-2019 TANEJA JUHI (MS) (C283) 31 of 35

27

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 32 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

   TEMP SENSOR

SET POINT FOR ALARM  ENGG UNIT 

FAILURE  CONTROL  CONT.  ACTION  ALGORITHM  POS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

















NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A







YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A









YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A



























NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

LRSB‐1818EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

OP LS

MOV‐1818E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

D43‐0WH‐007815P

CL LS

MOV‐1818E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

TLX1818E

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1818E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

115‐XTM‐1818E

XTM1818E

D43‐0WH‐007815P

TRIP F/B

MOV‐1818E

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

733

115‐XR‐1818E

XR1818E

D43‐0WH‐007815P

REMOTE SEL

MOV‐1818E

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS  Interrogation Voltage 24V DC, 2A

734

115‐HSO‐1801

HSO1801

D43‐0WH‐007815P

SB'ING SEQ STR PB 

Push Button

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

735

115‐HS‐1801

HS1801

D43‐0WH‐007815P

SB'ING SEQ RESET PB 

Push Button

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

736

115‐HSC‐1801

HSC1801

D43‐0WH‐007815P

SB'ING SEQ STP  PB

Push Button

SB PLC +4200 Elevation

DI‐POT. FREE

Open















YES











NC

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

737

115‐XS‐1801

XS1801

D43‐0WH‐007815P

SB Hooter Test PB

Push Button

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























MTS

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

738

115‐XAA‐1801

XAA1801

D43‐0WH‐007815P

HOOTER/ALARM ACCEPT PB

Push Button

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

739

115‐HSO‐1801‐1

HSO1801‐1

D43‐0WH‐007815P

SB'ING SEQ STR PB 

From DCS

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

740

115‐HSC‐1801‐1

HSC1801‐1

D43‐0WH‐007815P

 SB'ING SEQ STP  PB

From DCS

SB PLC +4200 Elevation

DI‐POT. FREE

Open



























NC

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC, 2A  from SB PLC

741

115‐HS‐1801‐1

HS1801‐1

D43‐0WH‐007815P

SB'ING SEQ RESET PB

From DCS



DI‐SERIAL

Open



























NO

D84‐4WH‐000237

NA

Communication through Modbus

742

115‐XAA‐1801‐1

XAA1801‐1

D43‐0WH‐007815P

HOOTER/ALARM ACCEPT PB

From DCS



DI‐SERIAL

Open



























NO

D84‐4WH‐000237

NA

Communication through Modbus

INSTRUMENT 

SYSTEM

MIN

MAX

718

115‐ZLH‐1818D

ZLH1818D

D43‐0WH‐007815P

OP LS

MOV‐1818D

SB PLC +7000 Elevation

DI‐POT. FREE

Open













719

115‐ZLL‐1818D

ZLL1818D

D43‐0WH‐007815P

CL LS

MOV‐1818D

SB PLC +7000 Elevation

DI‐POT. FREE

Open











720

115‐TLX‐1818D

TLX1818D

D43‐0WH‐007815P

TRQ SW OPRTD

MOV‐1818D

SB PLC +7000 Elevation

DI‐POT. FREE

Open









721

115‐XTM‐1818D

XTM1818D

D43‐0WH‐007815P

TRIP F/B

MOV‐1818D

SB PLC +7000 Elevation

DI‐POT. FREE

Open







722

115‐XR‐1818D

XR1818D

D43‐0WH‐007815P

REMOTE SEL

MOV‐1818D

SB PLC +7000 Elevation

DI‐POT. FREE

Open





723

115‐ZSR‐1818EE

ZSR1818EE

D43‐0WH‐007815P

REST POS. LS

LRSB‐1818EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open



724

115‐ZSF‐1818EE

ZSF1818EE

D43‐0WH‐007815P

F/W POS. LS

LRSB‐1818EE

SB PLC +4200 Elevation

DI‐POT. FREE

Open

725

115‐WSF‐1818EE

WSF1818EE

D43‐0WH‐007815P

F/W'DING F/B

LRSB‐1818EE

SB PLC +4200 Elevation

DI‐POT. FREE

726

115‐WSR‐1818EE

WSR1818EE

D43‐0WH‐007815P

R/T'ING F/B

LRSB‐1818EE

SB PLC +4200 Elevation

727

115‐XT‐1818EE

XT1818EE

D43‐0WH‐007815P

TRIP F/B

LRSB‐1818EE

728

115‐XA‐1818EE

XA1818EE

D43‐0WH‐007815P

AUTO SEL.  

729

115‐ZLH‐1818E

ZLH1818E

D43‐0WH‐007815P

730

115‐ZLL‐1818E

ZLL1818E

731

115‐TLX‐1818E

732

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

24 VDC +ve will go to SB PDB pot. free contact  and will return to PLC as a DI.

These are Push Buttons on Soot Blower PLC.

24 VDC +ve will go to DCS pot. free contact  and will return to SB PLC as a DI. (Note‐c)

Refer Modbus Mapping List for details. (Note‐ c)

14-OCT-2019 TANEJA JUHI (MS) (C283) 32 of 35

1

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

   PID No INSTRUMENT 

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SYSTEM

SET POINT FOR ALARM  ENGG UNIT 

MIN

MAX

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS  HIGH

LOW

HIGH HIGH 

   TEMP SENSOR LOW LOW 

BURNOUT TYPE STATUS 

CONTACT  STATUS 

FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

DIGITAL OUTPUT

Page 33 of 35

1

115‐HSO‐1819

HSO1819

D43‐0WH‐007815P

SB‐PLC OP CMD

MOV‐1819

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC from  MOV

Relay ‐ Pot. Free Dry DO

2

115‐HSC‐1819

HSC1819

D43‐0WH‐007815P

SB‐PLC CL CMD

MOV‐1819

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC from  MOV

Relay ‐ Pot. Free Dry DO

3

115‐HSO‐1820

HSO1820

D43‐0WH‐007815P

SB‐PLC OP CMD

MOV‐1820

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC from  MOV

Relay ‐ Pot. Free Dry DO

4

115‐HSC‐1820

HSC1820

D43‐0WH‐007815P

SB‐PLC CL CMD

MOV‐1820

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC from  MOV

Relay ‐ Pot. Free Dry DO

5

115‐HSO‐1821

HSO1821

D43‐0WH‐007815P

SB‐PLC OP CMD

MOV‐1821

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC from  MOV

Relay ‐ Pot. Free Dry DO

6

115‐HSC‐1821

HSC1821

D43‐0WH‐007815P

SB‐PLC CL CMD

MOV‐1821

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

Interrogation Voltage 24V DC from  MOV

Relay ‐ Pot. Free Dry DO

7

115‐HSO‐1806A

HSO1806A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1806AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

8

115‐HSO‐1806B

HSO1806B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1806BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

9

115‐HSO‐1806C

HSO1806C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1806CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

10

115‐HSO‐1806D

HSO1806D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1806DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

11

115‐HSO‐1806E

HSO1806E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1806EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

12

115‐HSO‐1807A

HSO1807A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1807AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

13

115‐HSO‐1807B

HSO1807B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1807BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

14

115‐HSO‐1807C

HSO1807C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1807CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

15

115‐HSO‐1807D

HSO1807D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1807DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

16

115‐HSO‐1807E

HSO1807E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1807EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

17

115‐HSO‐1808A

HSO1808A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1808AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

18

115‐HSO‐1808B

HSO1808B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1808BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

19

115‐HSO‐1808C

HSO1808C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1808CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

20

115‐HSO‐1808D

HSO1808D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1808DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

21

115‐HSO‐1808E

HSO1808E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1808EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

22

115‐HSO‐1809A

HSO1809A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1809AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

23

115‐HSO‐1809B

HSO1809B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1809BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

24

115‐HSO‐1809C

HSO1809C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1809CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

25

115‐HSO‐1809D

HSO1809D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1809DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

26

115‐HSO‐1809E

HSO1809E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1809EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

27

115‐HSO‐1810A

HSO1810A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1810AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

28

115‐HSO‐1810B

HSO1810B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1810BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

29

TANEJA JUHI HSO1810C (MS) (C283)D43‐0WH‐007815P 115‐HSO‐1810C

SB‐PLC STR CMD

LRSB‐1810CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

14-OCT-2019

33 of 35

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor. 29

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

Page 34 of 35

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC



















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC





















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

LRSB‐1812DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

SB‐PLC STR CMD

LRSB‐1812EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1813AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

HSO1813B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1813BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

115‐HSO‐1813C

HSO1813C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1813CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

45

115‐HSO‐1813D

HSO1813D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1813DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

46

115‐HSO‐1813E

HSO1813E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1813EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

47

115‐HSO‐1814A

HSO1814A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1814AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

48

115‐HSO‐1814B

HSO1814B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1814BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

49

115‐HSO‐1814C

HSO1814C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1814CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

50

115‐HSO‐1814D

HSO1814D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1814DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

51

115‐HSO‐1814E

HSO1814E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1814EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

52

115‐HSO‐1815A

HSO1815A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1815AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

53

115‐HSO‐1815B

HSO1815B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1815BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

54

115‐HSO‐1815C

HSO1815C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1815CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

55

115‐HSO‐1815D

HSO1815D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1815DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

56

115‐HSO‐1815E

HSO1815E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1815EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

57

115‐HSO‐1816A

HSO1816A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1816AA

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

58

115‐HSO‐1816B

HSO1816B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1816BB

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

INSTRUMENT 

SYSTEM

MIN

MAX

30

115‐HSO‐1810D

HSO1810D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1810DD

SB PLC +7000 Elevation

DO‐POT FREE

Open













31

115‐HSO‐1810E

HSO1810E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1810EE

SB PLC +4200 Elevation

DO‐POT FREE

Open











32

115‐HSO‐1811A

HSO1811A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1811AA

SB PLC +10650 Elevation

DO‐POT FREE

Open









33

115‐HSO‐1811B

HSO1811B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1811BB

SB PLC +10650 Elevation

DO‐POT FREE

Open







34

115‐HSO‐1811C

HSO1811C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1811CC

SB PLC +7000 Elevation

DO‐POT FREE

Open





35

115‐HSO‐1811D

HSO1811D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1811DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



36

115‐HSO‐1811E

HSO1811E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1811EE

SB PLC +4200 Elevation

DO‐POT FREE

Open

37

115‐HSO‐1812A

HSO1812A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1812AA

SB PLC +10650 Elevation

DO‐POT FREE

38

115‐HSO‐1812B

HSO1812B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1812BB

SB PLC +10650 Elevation

39

115‐HSO‐1812C

HSO1812C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1812CC

40

115‐HSO‐1812D

HSO1812D

D43‐0WH‐007815P

SB‐PLC STR CMD

41

115‐HSO‐1812E

HSO1812E

D43‐0WH‐007815P

42

115‐HSO‐1813A

HSO1813A

43

115‐HSO‐1813B

44

14-OCT-2019

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO

TANEJA JUHI (MS) (C283) 34 of 35

30

PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA

4

17/9/2019

TJB

NVK

NVK

3

24/5/2019

TJB

NVK

NVK

CONSULTANT: EIL 

2

12/2/2019

TJB

NVK

NVK

EIL JOB No.: A545

1

23/05/2016

TJB

NVK

NVK

ElL Doc. No.: DORL‐FGSG‐7940‐059

0

18/3/2016

TJB

NVK

NVK

TL Doc. No.: D65‐WH‐CS‐00661

REVISION

DATE

PREPARED BY

CHECKED BY

APP. BY

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. DIVISION : ENGINEERING

ENGINEERS INDIA LIMITED    NEW DELHI

DRAWING NO

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002

DEPT : INSTRUMENTATION

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

DORC DOC. No.:  A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007

REV.

3

REMARK

NOTES ID

POINT DATA BASE FOR  SB‐PLC LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No.

DISPLAY RANGE

 SI No

   PID No

 CONTROL  ROOM /  SRR NO 

TAG COMMENT

 SIGNAL TYPE

LINEAR /   LOOP TYPE (OPEN / CLOSE) SQ. ROOT

SET POINT FOR ALARM  ENGG UNIT 

FAILURE CONT.   CONTROL  ACTION  ALGORITHM  POS 

   TEMP SENSOR FUNCTIONAL /  LOGIC DIAG

 IS/  Non‐IS

HIGH

LOW















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC



















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC





















NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

SB PLC +10650 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

LRSB‐1818CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

SB‐PLC STR CMD

LRSB‐1818DD

SB PLC +7000 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1818EE

SB PLC +4200 Elevation

DO‐POT FREE

Open



























NO

D84‐4WH‐000237

Non IS 

DO Relay; Pot. Free Dry contact /  suitable for 230 VAC

ASR1801

D43‐0WH‐007815P

ALL SB IN REST POS.

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

115‐SBA‐1801

SBA1801

D43‐0WH‐007815P

SB IN AUTO

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

74

115‐ASO‐1801

ASO1801

D43‐0WH‐007815P

AUTO SEQ ON

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

75

115‐ASC‐1801

ASC1801

D43‐0WH‐007815P

AUTO SEQ COMPLETED

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

76

115‐MF‐1801

MF1801

D43‐0WH‐007815P

MECHNICAL FAULT

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

77

115‐TO‐1801

TO1801

D43‐0WH‐007815P

MP STM TEMP OK

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

78

115‐PO‐1801

PO1801

D43‐0WH‐007815P

MP STM PRESS OK

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

79

115‐PO‐1802

PO1802

D43‐0WH‐007815P

SA PRESS OK

Lamp

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4WH‐000237

Non IS  DO Relay: Wet 24 V DC

These Signals are Lamp Indications on Soot  Blower PLC Panel.

80

681‐HTR‐1801

HTR1801

D43‐0WH‐007815P

MECHNICAL FAULT ALARM ‐  HOOTER

Hooter

SB PLC +4200 Elevation

DO‐WET

Open



























NO

D84‐4HR‐000172

Non IS  DO Relay: Wet 24 V DC

Hooter located on SB PLC Panel.

INSTRUMENT 

SYSTEM

MIN

MAX

59

115‐HSO‐1816C

HSO1816C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1816CC

SB PLC +7000 Elevation

DO‐POT FREE

Open













60

115‐HSO‐1816D

HSO1816D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1816DD

SB PLC +7000 Elevation

DO‐POT FREE

Open











61

115‐HSO‐1816E

HSO1816E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1816EE

SB PLC +4200 Elevation

DO‐POT FREE

Open









62

115‐HSO‐1817A

HSO1817A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1817AA

SB PLC +10650 Elevation

DO‐POT FREE

Open







63

115‐HSO‐1817B

HSO1817B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1817BB

SB PLC +10650 Elevation

DO‐POT FREE

Open





64

115‐HSO‐1817C

HSO1817C

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1817CC

SB PLC +7000 Elevation

DO‐POT FREE

Open



65

115‐HSO‐1817D

HSO1817D

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1817DD

SB PLC +7000 Elevation

DO‐POT FREE

Open

66

115‐HSO‐1817E

HSO1817E

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1817EE

SB PLC +4200 Elevation

DO‐POT FREE

67

115‐HSO‐1818A

HSO1818A

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1818AA

SB PLC +10650 Elevation

68

115‐HSO‐1818B

HSO1818B

D43‐0WH‐007815P

SB‐PLC STR CMD

LRSB‐1818BB

69

115‐HSO‐1818C

HSO1818C

D43‐0WH‐007815P

SB‐PLC STR CMD

70

115‐HSO‐1818D

HSO1818D

D43‐0WH‐007815P

71

115‐HSO‐1818E

HSO1818E

72

115‐ASR‐1801

73

LOW LOW 

CONTACT  STATUS 

HIGH HIGH 

BURNOUT TYPE STATUS 

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

240VAC Phase will come from SB MCC to DO  Relay pot free contact and will return to SB  MCC through DO for actuating the auxilary  contactor.

Note: 1. Soot Blower PLC & Soot Blower PDB shall be kept side‐by‐side in Field on FGSG Structure. All SB PLC Panels and SB PDB Panels are distributed through‐out Elevation +4200, +7000, +10650 (Refer Annexure‐I for typical represenattion of distribution of Panels). Communication from SB PLC to Customer DCS shall be through Modbus (Modbus cable from SB PLC to DCS shall be in customer's scope).

Page 35 of 35