Generator Protection

  • Uploaded by: Rajesh Pillai
  • 0
  • 0
  • January 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Generator Protection as PDF for free.

More details

  • Words: 1,089
  • Pages: 22
Loading documents preview...
GENERATOR PROTECTION

Rajesh pillai

CONTENTS 1. 2. 3. 4. 5. 6. 7. 8.

OVER CURRENT (51) NGR/ NGT SELECTION STATOR E/F 90-95% (64S) STATOR E/F 95-100% (64S) DIFFERENTIAL PROTECTION (87) VOLTAGE CONTROLLED O/C (51V) VOLTAGE RESTRAINED O/C (51V) UNBALANCE ARMATURE CURRENT (46)

CONTENTS 8. 9. 10. 11. 12. 13. 14. 15.

ROTOR E/F (Ist & 2nd STAGE) (64F1 & F2) FIELD FAILURE (LOSS OF EXCITATION) (40) OVER FLUXING (59 V/Hz) OVER VOLTAGE (59) IN - ADVERTANT ENERGISATION (27/50) U/F & O/F (81 U & O) MOTORING (RPR) (32) POLE SLIP (78)

Stability Curve • Unit Can generate max 125 MW if prime mover P (MW) is capable. C Rotor Current Limit

B 0.8

100, 0.8 0.87

Stator Stability Limit Flame Stability

25,0.2 100 Q (Lag) A 0.8

MVAr

D

Q (Lead)

Over Current Protection 51 • Over Current in generator can occur due to system disturbance accompanied by generator or line tripping. • O/L withstand capacity as ANSI C50.13 – 1977 • Stator Current % 116 130 154 226 • Time (sec) 120 60 30 10 • Generally wired for alarm to allow operator to take corrective action at 105%

O/C Relay Ch’r TD

K

t = Operation time

T = ---------- x ------------------ + L K, α = Constant 7 (I/Is)α-1 I = Current measured L = Constant, TD – Time Dial

Curve

Standard

K

α

L

Std Inv

IEC

0.14

0.02

0

Very Inv

IEC

13.5

1

0

Ext. Inv

IEC

80

2

0

Long Inv

UK

120

1

0

Very Inv

IEEE

3.922

2

0.0228

NGR SELECTION

Current Amps

• Limit the E/F Current • Current Limitation based on Generator Capability Curve. 80 70

Generator core damage

Repairable Damage 25 No damage 0,0

1

2

3 4 Time In Sec

12

NGR CALCULATION • To limit the E/F current at 100 amps : (V/√3) Required NGR resistance : --------Current • If other generators are ungrounded then unbalance current becomes a line current & insulation will be stressed • Don't mix-up different types of grounding. • Don’t Earth NGR body

Neutral Grounding Transformer • • • •

If NGT Resistance is 0.9 Ohm Resistance Rp =0.9*(11/√3/240)2 0.9*700 = 630 Ohm Max. E/F Current = (11000/√3) ---------------

R

630 = 10 Amps

Trafo 11/√3/240

U3<

STATOR E/F 90 – 95% • Phase to ground faults are very severe leading to melting of steel laminations & possibility of core damage. • E/F current setting : 5 Amp • % winding unprotected = 5/100 = .05*100=5% % winding protected = 100-5 = 95% • In NGT scheme Neutral to ground voltage is sensed by the relay but it is insensitive to 3rd Harmonic voltage

Stator E/F 95 – 100% • Very close to the neutral. • If first E/F is not sensed by the relay & meanwhile 2nd E/F developed then E/F current is not limited by the NGR/NGT. E/F current is very high • All the generators are produce the 3rd harmonic voltages under normal condition and if fault is near neutral then 3rd harmonic voltages are markedly comes down & this is used for detection.

Neutral Grounding Transformer Tuned for 50Hz & Block 150 Hz

Trafo 11/√3/240

Filter

R

64 ND

U3<

Uf

Tunned For Tunned For 50 Hz 150 Hz

Tunned to permit 3rd Harmonic

No Trip Trip

• At Unity Power factor : – PF Var 3rd H & Internal EMF relay is malfunctioned

so 95 %

• When 5 volt setting is done then chance of malfunction is increased due to relay has to operate at 50 Hz & block 3rd Harmonics

Differential Protection (87) • • • • •

Unit Type Protection For Stator phase to phase fault Turn to turn fault can’t detected Damage of the winding & stator core Two Scheme – High Impedance – Low impedance

Differential Protection • Slope =Io/Ir, If Io>Ir Relay Operates

RC

OC

RC

Iop (IS-IL) Operate

IR=(IS+IL)/2

Case Study for PS class CT • For 5P10 or 15 class CT is saturate in external heavy faults. And at that time a fault is occurred in the zone then the CT is not sense the fault & does not operate. • So PS class CT is should be recommended for 5P10 differential protection even in numerical relays • In this transformer one no. coil is burnt

Fault

Voltage Controlled O/C Relay • Backup of Differential Protection • Two time/ current Ch’r • During Sustained O/L or External Faults in system – Relay assumes long inverse Ch’r – Voltage is near normal

• During Close in faults – Voltages collapses – Relay assumes normal IDMT Ch’r – Under Voltage element is used to step change in relay setting

Voltage Controlled O/C Relay

Operating Time

• Switch over from one curve to other curve when voltage is less than 30% • If Generator directly connected to bus bar W/O GT then, occurrence of faults in the System then always voltage External Fault shrinks and relay O/L Ch’r malfunctioned Fault Ch’r

PSM

Voltage Restrained O/C Relay • Only one IDMT Type Ch’r. • Ch’r is modified continuously as per terminal voltage. • Distance type impedance relay (21) is the back up protection. • Used for terminal feed static excitation system • When terminal voltage falls pickup current values are also falls linearly.

Voltage Restrained O/C Relay

Ipickup = 1.5 Rat • Vt>0.2, Ipickup = 0.3 Rat

Current

• Iy is set 1.5 to 2 rated • When, 1.0 Iy • Vt>0.8, 0.2 Iy

• DMT time delay = 1 Sec

Ux1 0.2

Ux2 Voltage 0.8

Negative Sequence Protection Unbalance Armature Current (46) • • • • • •

Open phase of a line One open pole of a CB Non linear system loading A close unbalance fault not cleared properly Stator winding fault. This is Back up protection for uncleared system faults • I2 rated current can melt the rotor Ia + α2Ib + αIc

• I2 3

= ----------------------------

Where α = 1.0 ∟120’

Negative Sequence Protection

– K = 40 to 60

• For H2/ Water Cooled – K = 10 to 20

I22t = 20

I2 PU

• 5th & 11th Harmonics make a problem • I22t = K • For Air Cooled M/C

• High K > High Cost • So K is kept 10 -15 • Continuous Current withstands

Time In sec

– Air Cooled M/C = 30 to 40% – H2 / Water Cooled M/C 10 to 15%

• Set the relay below the above withstand values for alarm (5 to 10 Sec Delay)

Related Documents


More Documents from "kishansai"