Loading documents preview...
Bapuji S Palki, INCRC/PowerTechnologies, 15-11-2009
Protection Application – An Overview Part 2A © ABB Group October 10, 2011 | Slide 1
© ABB Group October 10, 2011 | Slide 2
Layouts
Typical Parts of a Power Plant Substation
Busbar in Substation HV - Breaker Power plant Main Transformer
Auxiliary Transformer
Generator Breaker Excitation Transformer Excitation System
Turbine valve Turbine - Generator
Earthing System
G
Field Circuit Breaker
Generator Protection
Possible Faults
Stator Earth Faults
Rotor Earth Faults
Stator Short Circuits
Stator/Rotor Interturn faults
External faults
Generator Protection
Abnormal Operating Condition
overcurrent/overload
unbalanced load
overtemperature
over- and undervoltage
over- and underexcitation
over- and underfrequency
over-fluxing
asynchronous running
out of step
generator motoring
failures in the machine control system (i.e. AVR or governor failure)
failures in the machine cooling system
failures in the primary equipment (i.e. breaker head flashover)
open phase
• Following are the various protections recommended for the generator and generator transformer protection:
Type of fault GENERATOR STATOR Short Circuits
Asymmetry Stator overload Earth fault stator
© ABB Group October 10, 2011 | Slide 6
ANSI Device Protection Functions No.
87G 87GT 21G 51 / 27 G 46G 51G 64G1 64G2
Generator differential Overall differential Minimum impedance (or alternatively Over current / under voltage) Negative sequence Overload 95% stator earth fault 100% stator earth fault
Loss of excitation Out of step Monitoring
40G 98G 32G / 37G
Blade fatigue Inter turn fault Mag. Circuits Higher voltage Accidental energisation Monitoring
81G 95G 99G 59G 27 / 50 G
© ABB Group October 10, 2011 | Slide 7
60 G
Loss of excitation Pole slip Low forward power / reverse power (double protection for large generators) Minimum frequency Over voltage or over current Overfluxing volt / Hz Over voltage Dead machine PT fuse failure
GENERATOR ROTOR Rotor ground GENERATOR TRANSFORMER Short Circuits
Ground fault Overhang UNIT AUXILIARY TRANSFORMER Short circuit Ground fault
© ABB Group October 10, 2011 | Slide 8
64F
Rotor earth fault
87GT 51GT 87T 51NGT 87NT 87HV
Overall differential Overcurrent Transformer differential Earth fault over-current Restricted earth fault HV winding cum overhang differential
87 UAT 51 UAT 51 UAT 64 UAT
Transformer differential Over-current Restricted over-current Restricted earth fault
50/51 Unit aux. transformer
64F Field winding ground-fault RAGRA (RXNB4) 1) Instruments
© ABB Group October 10, 2011 | Slide 9
Protection and Monitoring
REG 670 – Different applications REG 670 provides extensive protection and monitoring functionality
1ph U
3ph U
3ph I
The REG 670 provides protection functions and concepts for:
Turbine (frequency, reverse power)
Generator (Main1/Main2, Main/Back-up)
Generator transformer/Step-up transformer
Auxiliary/Station service transformer
Excitation transformer
1ph U
G
1ph I
3ph I
1ph U
REG 670 focus on the optimized integration and function to protect your generator
IEC 61850
A Breakthrough for Substation Automation
One world
One technology
One standard
IEC 61850
“Combining the best properties in a new way...”
© ABB Group October 10, 2011 | Slide 12
Power transformers in a power system 400 kV AC Transmission
130 kV Subtransmission
Generation MV
Distribution
LV M
© ABB Group October 10, 2011 | Slide 13
315MVA Transformer
© ABB Group October 10, 2011 | Slide 14
Cooling Outer Ci rcui t H eat D i ssi pati on
Pump opti onal
I nner Ci rcui t H eat Producti on (Core and Wi ndi ngs)
F an opti onal
© ABB Group October 10, 2011 | Slide 15
Oi l i mmersed Tank
In principle the larger the losses in the Inner Circuit the larger the size of the Outer Circuit (coolers or radiators) There is nevertheless a limit either due to the size of the coolers or to the impossibility of cooling a certain spot (hot-spot) in the Inner Circuit A pump to move the oil is often unnecessary. The generated heat will act as a siphon
Types of Internal Faults
© ABB Group October 10, 2011 | Slide 16
Earth faults
Short-circuits
Inter turn Faults
Core Faults
Tank Faults
Reduced cooling
Abnormal Conditions
© ABB Group October 10, 2011 | Slide 17
Overload
Over voltage
Reduced system voltage
Over excitation
Overload Capability
It is possible to overload power transformers
Older transformers may withstand 140% continuously
Overloading and loss of cooling causes overheating
© ABB Group October 10, 2011 | Slide 18
Protective Relays Used ( Transformers > 5 MVA)
Gas detector relay ( Buchholz)
Over load protection
Thermal relays
Temperature monitoring relays
Over current protection
Ground fault protection
Differential protection
Interturn faults
Pressure relay for tap changer
Oil level monitor
© ABB Group October 10, 2011 | Slide 19
Protective Relays Used ( Transformers < 5 MVA)
Gas detector relay
Overload protection
Overcurrent protection
Ground fault protection
© ABB Group October 10, 2011 | Slide 20
Monitors Monitors are very important devices which detect faults and abnormal service conditions which may develop into fault.
© ABB Group October 10, 2011 | Slide 21
Transformer Monitors
Mechanical fault detectors
Sudden gas pressure protection
Buchholz protection
Oil level monitoring
Temperature Monitoring
© ABB Group October 10, 2011 | Slide 22
The oil thermometer
The winding thermometer
Transformer protection with 670/650 series
Introduction Transformer Protection 670/650 series Openness and flexibility Reliable Operation Complementary functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary
© ABB Group November 2009 | Slide 23
670 series – optimized for generation and transmission applications provide versatile functionality, maximum flexibility and performance to meet the highest requirements of any application in generation and transmission protection systems.
650 series – your best choice for subtransmission applications provide “off-the-shelf”, ready to use solutions for transformer protection applications primarily in subtransmission networks.
Fully compliant to the IEC 61850 standard Introduction Line Distance Protection 670/650 series Reliable Operation Complementary functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary
© ABB Group November 2009 | Slide 24
Unrivalled compatibility for new and retrofit installations
Designed for IEC 61850, implementing the core values of this standard
Ensures open, future-proof and flexible system architectures, with state-of-the-art performance
Interoperates with other IEC 61850 compliant IEDs
© ABB Group October 10, 2011 | Slide 25
The reactor absorbs the capacitive power generated in long lines
© ABB Group October 10, 2011 | Slide 26
Shunt Reactor
© ABB Group October 10, 2011 | Slide 27
AB C
A B C
L
R Lp Lp Lp
Ln
© ABB Group October 10, 2011 | Slide 28
General
Shunt reactors are used in EHV systems to limit the over voltages due to capacitive VAR generation in Long Transmission Lines The shunt reactors are normally connected
Through isolators to a line
Through circuit breakers to a busbar
© ABB Group October 10, 2011 | Slide 29
Through circuit breakers to the tertiary of a Interconnecting transformer
Different locations of reactor
© ABB Group October 10, 2011 | Slide 30
Internal Faults Faults occur in shunt reactors due to insulation breakdown, ageing of insulation, overheating due to over excitation, oil contamination and leakage
Dry air-core reactors
Phase-to-phase faults , resulting in high magnitude phase current
Phase-to-earth faults ,, resulting in a low-magnitude earth-fault current, dependent upon the size of the system earthing.
Turn-to-turn faults within the reactor bank, resulting in a very small change in phase current
Oil-immersed reactors
High current phase-to-phase and phase-to-earth faults.
Turn-to-turn faults within the reactor winding.
Miscellaneous failures such as loss of cooling or low oil
© ABB Group October 10, 2011 | Slide 31
Abnormal Conditions
Inrush currents
Inrush currents flow in connection with energisation Inrush currents usually lower than 200% of rated current
Transient overvoltages
Temporary overvoltages
© ABB Group October 10, 2011 | Slide 32
Shunt Reactor Protections
Differential protection
Distance protection
Phase over current protection
Restricted earth fault protection
Mechanical fault detectors
© ABB Group October 10, 2011 | Slide 33
Oil temperature and winding temperature protection
Monitors Monitors are very important devices which detect faults and abnormal service conditions which may develop into fault.
© ABB Group October 10, 2011 | Slide 34
Reactor Monitors
Mechanical fault detectors
Sudden gas pressure protection
Buchholz protection
Oil level monitoring
Temperature Monitoring
© ABB Group October 10, 2011 | Slide 35
The oil thermometer
The winding thermometer
Shunt reactor protection and control
Introduction Transformer Protection 670/650 series Openness and flexibility Reliable Operation Complementary functionality Control Capabilities Communication Offering and application examples Technology Summary Relion® Summary
© ABB Group November 2009 | Slide 36
Protection Phase segregated biased differential protection Low impedance restricted earth-fault High impedance differential protection
Switching control for lines and buses
© ABB Group October 10, 2011 | Slide 37
Capacitor Construction
© ABB Group October 10, 2011 | Slide 38
Power PowerFactor FactorCorrection Correction Working Power (kW) Reactive Power (kVAR)
KW is the Working Power component
kVAR is the Non- Working Power or Reactive Power component to serve inductive loads, which require magnetizing current: Motors, Transformers, Lighting ballast
KVA is the Total Power required to serve a load
Capacitors supply the reactive power component
Power Factor is a measurement of how efficiently power is being used.
© ABB Group October 10, 2011 | Slide 39
Increased IncreasedSystem SystemCapacity Capacity Extra capacity for more KVA released system capacity
Total Power (KVA) = Working Power (KW) ÷ Power Factor Power Factor Real Power kW Reactive Power kVAR Total Power kVA
60% 600 800
70% 600 612
80% 600 450
90% 600 291
100% 600 Zero
1000
857
750
667
600
By supplying reactive current (kVAR) close to the load, capacitors release system capacity on the entire system and reduce costs.
© ABB Group October 10, 2011 | Slide 40
Voltage VoltageStability Stability
A feeder circuit will have a voltage drop related to the impedance of the line and the power factor Adding capacitance will actually cause a voltage rise by supplying reactive current to the bus
(less current = less voltage drop)
© ABB Group October 10, 2011 | Slide 41
Products Capacitors – HV Products / Filter Capacitor Banks
Improving the performance, quality and efficiency of electrical systems
© ABB Group October 10, 2011 | Slide 42
Capacitor banks- General
Normally used in MV networks to generate reactive power
Series reactors are used to limit inrush current
Harmonic filters for thyristor controlled reactors are also variation of capacitor banks having reactance tuned to capacitance
Shunt
Capacitors-General
Shunt Capacitor Faults
Terminal shunt faults
Capacitor unit failures
Capacitor unit over voltages
Capacitor rack arc-over
Abnormal Conditions
Inrush currents
Transient over voltages
Temporary over voltages
Out rush currents
Capacitor Bank Protections
Short -circuit protection
(3I >>)
Ground-fault protection
(I )
Overload protection(3I/U >)
Under current protection
(I/U <)
Unbalance protection
(IN-N)
Fusing Capacitor Fusing Internally Fused
Fuse
© ABB Group October 10, 2011 | Slide 48
Externally Fused
Discharge Resistor
Internal Strings
Fuseless
Conventional
SPAJ
160 C : Unbalance , Overload and Under current functions
Bapuji S Palki, INCRC/PowerTechnologies, 15-11-2009
Protection Application – An Overview Part 2B © ABB Group October 10, 2011 | Slide 50
© ABB Group October 10, 2011 | Slide 51
The Electric Utility
Power Evacuation Substation Transmission Substation Switching Substation Distribution Substation
© ABB Group October 10, 2011 | Slide 52
Transmission Line
© ABB Group October 10, 2011 | Slide 53
Electrical faults in the power system
Transmission lines
85%
Busbar
12%
Transformer/ Generator
3%
100%
© ABB Group October 10, 2011 | Slide 54
Fault types
Transient faults
are common on transmission lines, approximately 80-85%
lightnings are the most common reason
© ABB Group October 10, 2011 | Slide 55
can also be caused by birds, falling trees, swinging lines etc. will disappear after a short dead interval
Persistent faults
can be caused by a broken conductor fallen down
can be a tree falling on a line
must be located and repaired before normal service
Measuring principles
© ABB Group October 10, 2011 | Slide 56
Overcurrent protection
Differential protection
Phase comparison
Distance protection
Directional- wave protection
Overcurrent protection
Are normally used in radial networks with system voltage below 70 kV where relatively long operating time is acceptable. On transmission lines directional or nondirectional over current relays are used as back-up protections.
I>
block
© ABB Group October 10, 2011 | Slide 57
I>
I>
I>
Pilot wire differential protection
© ABB Group October 10, 2011 | Slide 58
Pilot wires can be in soil or on towers. The resistance in the wires will limit the use on longer lines. The use is mostly restricted to distances up to 10 km.
Digital differential communication L1 L2 L3
DL1 DL2 DL3
© ABB Group October 10, 2011 | Slide 59
Digital communication with optical fibres or by multiplexed channels
DL1 DL2 DL3
Phase comparison load I1 φ >
Phase comparison relays compare the angle difference between the two currents at both ends of the line.
The measured time for zero crossing is transmitted to the other end.
Normally a start criteria is added to the phase angle requirement.
I2 φ >
α I1 I2
e 1
e 2
α
e1 e -
2
I2
func- φ tion φ
I1 I2
© ABB Group October 10, 2011 | Slide 60
The principle of distance protection
ZK=Uk/Ik
Uk
Uk=0 metallic fault
Zk
A
Z< © ABB Group October 10, 2011 | Slide 61
Ik
B
Fault resistance
multi-phase faults
consist only of arc resistance
© ABB Group October 10, 2011 | Slide 62
L1
L1
L2
L2
L3
earth faults
consist of arc and tower
footing resistance
Warrington´s formula
Rarc =
L3
28707 x L 1.4
I
L= length of arc in meters I= the actual fault current in A
Footing resistance
Distance protection on short lines jX
Quadrilateral characteristic improves sensitivity for higher RF/XF ratio It still has some limitations:
RF XF
© ABB Group October 10, 2011 | Slide 63
R
the value of set RF/XF ratio is limited to 5
jX
Distance protection on long lines
Load impedance limits the reach in resistive direction High value of RF/XF ratio is generally not necessary Circular (mho) characteristic
R
© ABB Group October 10, 2011 | Slide 64
Has no strictly defined reach in resistive direction Needs limitations in resistive direction (blinder)
The principle of distance protection
t t3 t2 t1
l
A
B f 1
Z<
C f 3
f 2
Z<
Z<
Z<
t t3 t2
l © ABB Group October 10, 2011 | Slide 65
t1
The principle of distance protection
Reach setting of zones
R/ X Relation
GFC (General Fault Criterion) GFC
ZL
ZL
Zb
© ABB Group October 10, 2011 | Slide 66
PLCC equipment
© ABB Group October 10, 2011 | Slide 67
Power Swing Blocking function X Power swing locus
R ∆t
∆t = 40 ms
© ABB Group October 10, 2011 | Slide 68
Series compensated system jX
B´
A
XC =70%
100%
Xl =100%
B
F1
gape flashed
Consideration for line distance protections
B A
70%
© ABB Group October 10, 2011 | Slide 69
R
gape not flashed
• Correct direction discrim-ination at voltage reversal (negative fault reactance) • variation in resulted line impedance
Line distance protection with Relion® 670/650 series For maximum reliability of your power system Introduction Line
Distance Protection
670/650
series
Reliable
Operation
Complementary functionality Control
Capabilities
Full scheme distance protection with independent phase selection
Power swing detection
Wide range of scheme communication logics
Five zone distance protection
Communication Offering
and
application
examples
Technology ®
Relion
Summary
© ABB Group November 2009 Slide 70
Summary
Phase to phase
Phase to earth faults
Fully compliant to the IEC 61850 standard Introduction Line
Distance Protection
670/650
series
Reliable
Operation
Complementary
Unrivalled compatibility for new and retrofit installations
Designed for IEC 61850, implementing the core values of this standard
Ensures open, future-proof and flexible system architectures, with state-of-the-art performance
Interoperates with other IEC 61850 compliant IEDs
functionality Control
Capabilities
Communication Offering
and
application
examples
Technology
Summary
®
Relion
Summary
© ABB Group November 2009 Slide 71
© ABB Group October 10, 2011 | Slide 72
Auto Auto reclosing reclosing Cycle Cycle OH-lines High fault-rate (80-90%)
Fast simultaneous Fault clearing
© ABB Group October 10, 2011 | Slide 73
AUTORECLOSING AUTORECLOSINGCYCLE CYCLE
OH-lines Intermittent faults (80-90%)
Successful AR-rate : High (80-90%)
© ABB Group October 10, 2011 | Slide 74
Auto reclosing principles
95% of faults are transient type
3 Ph autoreclosing synchrocheck is used
1 Ph autoreclosing needs identification of faulty phase
© ABB Group October 10, 2011 | Slide 75
Helps verify phase angles are not out of phase e.g: due to heavy power swing
Phase identification is difficult for high resistance faults
Single-pole Reclosing Single-Pole Reclosing A B C
© ABB Group October 10, 2011 | Slide 76
A B C
Artificial extinction of secondary arc by Fixed Four-reactor Scheme ABC
ABC
L
R Lp Lp Lp
Ln
© ABB Group October 10, 2011 | Slide 77
Synchronism and Energizing check UBus
ULine
UBus
FreqDiff < 50-300 mHz o PhaseDiff < 5-75 UDiff < 5-50% Ur UHigh > 50-120% Ur
U Bus
1-ph
U Line
3-ph (or 1-ph)
ULow < 10-100% Ur SYNC-BLOCK
© ABB Group October 10, 2011 | Slide 78
Fuse fail
ULine
© ABB Group October 10, 2011 | Slide 79
Need for Busbar protection In its absence fault clearance takes place in Zone-II of distance relay by remote end tripping
This means slow and unselective tripping and wide spread black out
Effect of delayed clearance
© ABB Group October 10, 2011 | Slide 80
Greater damage at fault point Indirect shock to connected equipments like shafts of Generator and windings of transformer.
Types of BB Protections
High impedance
Medium impedance
Low impedance
© ABB Group October 10, 2011 | Slide 81
Blockable O/C relay ( For radial systems in distribution systems)
High impedance bus differential relay Basic features SETTING VR > IF ( RCT + 2 RL) VK > 2 VR
RL A
VR
RCT B
FOR VR TO BE ZERO FOR EXTERNAL FAULT nA = nB 1 + RA / ZA 1 + RB / ZB n = TURNS RATIO R = RCT + 2 RL Z = MAGNETIZING IMPEDANCE
© ABB Group October 10, 2011 | Slide 82
Limitations of High impedance differential relay
© ABB Group October 10, 2011 | Slide 83
Puts stringent requirements on CTs
Need for dedicated CTs
Identical CT ratios , magnetising impedances
Aux CTs not acceptable
Inability to cope with increasing fault levels
RADSS medium impedance relay
IR1
T MD n MD
Ud3 dR D2
US
© ABB Group October 10, 2011 | Slide 84
D1
REB500 - Numerical Busbar and Breaker Failure Protection
ABB Network Partner AG
REB 500
C E
Distributed installation ABB Network Partner AG
REB 500
ABB Network Partner AG
C E Bay Unit
© ABB Group October 10, 2011 | Slide 85
Central Unit
REB 500
ABB Network Partner AG
C E Bay Unit
REB 500
ABB Network Partner AG
C E Bay Unit
REB 500
C E Bay Unit
Advantages of medium/ Low impedance relays
Free from any need for Identical CT ratios or matched CTs
Other relays can be included in the same CT core
Increasing fault levels have no impact
© ABB Group October 10, 2011 | Slide 86
1000/5
200/5
3.5 A
5/1
500 A
200 A
700 A
500/5
5A
5/0.5
5/0.2 0.7 A
0.2 A
Diff. relay RADSS IN SINGLE BUS © ABB Group October 10, 2011 | Slide 87
5A
0.5 A
REQUIREMENTS ON THE ISOLATOR AUXILIARY CONTACTS Isolator Aux. Contact ‘a’ should close before the primary contact a
b
closes and Aux contact’ b’ closes after the primary contact opens.
O
C Throw-over relay
0% Main contact Aux. Contact a Aux. Contact b © ABB Group October 10, 2011 | Slide 88
100%
DOUBLE BUSBAR SYSTEM WITH TRANSFER BUS BUS - A BUS - B
AUX. BUS
© ABB Group October 10, 2011 | Slide 89
1½- BREAKER SYSTEM RADSS - A L1
L3
L5
L2
L4
L6
BUS - A
BUS - B
RADSS - B
© ABB Group October 10, 2011 | Slide 90
Busbar Protection REB670
© ABB Group April 2009 Slide 91
© ABB Group October 10, 2011 | Slide 92
History - Circuit breaker development
Example: 420 kV
Air Blast
…around 1960
© ABB Group October 10, 2011 | Slide 93
Oil Minimum
SF6 Gas
…around 1980
…today’s technology
Interrupters Interrupter design
© ABB Group October 10, 2011 | Slide 94
+
Relay back-up RELAY SYSTEM
CHANNEL
52
50
-
52a
52 52a
RELAY SYSTEM
CHANNEL +
© ABB Group October 10, 2011 | Slide 95
Breaker back-up 5
1
6
2
Z<
7
8 3
4
For uncleared fault shown CB’s to be tripped are 1, 3, 4 & 6
© ABB Group October 10, 2011 | Slide 96
Classical CBFP Breaker Failure Protection
I> I>
I>
I>
+ if trip from relay
© ABB Group October 10, 2011 | Slide 97
t trip
© ABB Group October 10, 2011 | Slide 98
Introduction
Majority faults are earth faults
Earth fault protection depends on type of earthing
Effectively earthed
Reactance earthed
High resistance earthed
Resonance earthed
© ABB Group October 10, 2011 | Slide 99
Measurement of earth fault current
© ABB Group October 10, 2011 | Slide 100
Measurement of zero sequence voltage L1 L2 L3
U 0>
Earth fault protection in solidly earthed systems IDMT earth fault relays are used to detect earth faults in effectively earthed system
© ABB Group October 10, 2011 | Slide 102
Directional Earth Fault Relay
© ABB Group October 10, 2011 | Slide 103
Directional earth fault relays are used
Can use communication link
Inrush current stabilization may be required for sensitive settings
Directional earth fault relay for High resistance earthed system
Directional earth fault relay used when in feed of capacitive current from an object is higher than 60% of required sensitivity Measures active component of fault current
© ABB Group October 10, 2011 | Slide 104
Earth fault in resonance earthed network A B C
ΣI01
C0
ΣI02 L
RL
U0 Ief
R0
Earth fault in isolated network A B C
ΣI01
C0
U0 ΣI02
Ief
R0
Directional earth fault relay
© ABB Group October 10, 2011 | Slide 107
Restricted earth fault relay
© ABB Group October 10, 2011 | Slide 108
© ABB Group October 10, 2011 | Slide 109
What is Substation Automation ? A combination of:
© ABB Group October 10, 2011 | Slide 110
Protection
Monitoring
Control
Communication
What is Substation Automation ?
Substitution for conventional control panels
Substitution for other sub systems
A more efficient way of controlling your substation
© ABB Group October 10, 2011 | Slide 111
The conventional way Control Board
Telecontrol RTU
Alarming
Synchronization
Busbar Protection
MARSHALING RACK
Local ControlTELE-
© ABB Group October 10, 2011 | Slide 112
Interlocking ALARMING
Measuring NISATION
Bay BUSBAR Protection PROTECTION
System Engineering Tool
The New Way
Station Monitoring System
Station HMI Gateway Station Clock
Communication only during engineering IED Tool
Station bus Bay Control
Web Client
Object Protection
Control & Protection
Multi Object Protection
IEDs
Process bus
Merging Unit
© ABB Group October 10, 2011 | Slide 113
Merging Unit
Multi Bay Control
Conventional Control & Protection Fault Recording 225kV LIGNE ABOBO 1
Station Level
ABB
125VDC Distribut uion Batt ery A
=D04+R01
125VDC Distributuion Bat tery B
Bay Protection 225kV LIGNE ABOBO 1
ABB
125VDC Distribut uion Batt ery A
Busbar Protection 125VDC Distribut uion Batt ery A
225kV LIGNE ABOBO 1
ABB
=D04+R01
125VDC Distribut uion Batt ery A
125VDC Distributuion Bat tery B
125VDC Distributuion Bat tery B
Event Recording =D04+R01
225kV LIGNE ABOBO 1
ABB
125VDC Distribut uion Batt ery A
=D04+R01
125VDC Distributuion Bat tery B
R E L3146* A B w N oeP rtakn
ABB RTU 200 I N 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT 1
1
9
2
10
3
n d a ciI6 t5 0 n d a ciI6 t5 0
1
4
12
5
13
6
14
7
15
8
16
ON/OFF
056 ci tcadn I
056c i tcadn I
0 56c tic adn I
BAY CONTROL RELAY RE C316*4
=W 1
RTU 200 I N 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT =W 2
1
9
2
10
3
1 -Q 1
4
12
5
13
6
14
7
15
8
16
ON/OFF V o e in sr4 .2 b
E F R M
c c
LOCAL CO NTROL
METERI NG n d a ciI6 t5 0 R E L3146*
n d a ciI6 t5 0
A B w N oeP rtakn
RTU 200 I N 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 OUT
ABB 3
1
9
2
10
3
1
4
12
5
8
13
6
14
7
15
8
16
ON/OFF
LI NE PROTECTION RELAY REL316*4 R E B 50 A B w N oeP rtakn
ABB
BUSBAR PROTECTION REB500
225kV LIGNE ABOBO 1
ABB
ABB
Bay Level
225kV LIGNE ABOBO 1
ABB
=D04+R01
125VDC Distributuion Bat tery B
SCADA RTU
For each function a dedicated device and separate Panel
Control Panel
ABB
=D04+R01
ABB
=W1
=W2
-Q1 SEL
-Q2 SEL
-Q0 SEL
TESTE LAMPE
Extensive station wide cabling
OUVRI RFERMER ABB
ESC
EXE
Local Control
DISTANCE LOC
Process Level
Marshalling
Extensive bay cabling
GIS or AIS Switchgear
-Q2 -Q0 -Q1
-Q9
-Q8
Substitution of Conventional Technology Bay Control/Protection Cubicles Fällanden Steuerung / Schutz
Fällanden Steuerung / Schutz
MicroSCADA
=AD17-KB2
=AD17-KB2
Feldsteuergerät REC216 mit Messung und Synchrocheck
Feldsteuergerät REC216 mit Messung und Synchrocheck
Interbay bus Ethernet Switches d gi ta l
LEITUNGSHA UPTSCHUTZ REL316* 4 PRÜFSTECKER I 0
I 0
STUFENVERL. WE-BLOCK
Reset AUS
I 0 SCHUTZ EIN/A US
di gi t al
LEITUNGSHA UPTSCHUTZ REL316* 4 PRÜFSTECKER I 0
I 0
STUFENVERL. WE-BLOCK
Reset AUS
I 0 SCHUTZ EIN/A US
-Q2
-Q1
COM 581 ABBPower Automation AG
COM581
NCC / RCC
Communication Converter
-Q0
Marshalling
-Q9
C
Control Cubicle Relays for control / logic Transducers, Meters Switches, Lamps Annunciators, Terminals
-Q8 Protection Cubicle
SER / Fault Recorder
SCADA RTU NCC / RCC
Modern SA Architecture
Station Level
Network Control Center NCC
ABB Network Partner AG
C
125VDC Distributuion Battery B REL316*4
ABBNetwor kPar nt er
ABB
1 2 3 4 5 6 7 8
Basic Functionality
125VDC Distributuion Battery A
Bay Level
=D04+R01
225kV LIGNE ABOBO 1
ABB
9 10 11 12 13 14 15 16
BAY CONTROL RELAY REC316*4 =D 04 A B OB O 1
ABB P OWE R
MON I T OR I N G U N I T
=W1 =W2 -Q1 SEL
-Q2 SEL
LAMPE TESTE
-Q0 SEL
OUVRIR
ESC
ABB
FERMER
LO C
LOCAL CONTROL ABB
METERING REL316*4
ABBNetwor kPar nt er
1 2 3 4 5 6 7 8
DIS T A NCE
EXE
9 10 11 12 13 14 15 16
LINE PROTECTION RELAY REL316*4 ABB
ABBNetwor kPar nt er
REB500
BUSBAR PROTECTION REB500
-Q2 -Q0 -Q1
-Q9
-Q8
Features and Benefits
E
Interbay Bus
Process Level
COM581
Implementation of Intelligent Technology Intelligent Primary Equipment
MicroSCADA =D04+R01
225kV LIGNE ABOBO 1
ABB
125VDC Distributuion Battery A
125VDC Distributuion Battery B REL316*4
ABBNetworkPartner
ABB
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
BAY CONTROL RELAY REC316*4 =D 04 A B OB O 1
ABB P OWE R
MON I T OR I N G U N I T
=W1 =W2 -Q1 SEL
M M
Interbay bus Ethernet Switches
-Q2 SEL
M OUVRIR
ESC
-Q2
-Q51
-Q0 PISA A
-Q8 -Q9 -Q8
LO C
METERING
9 10 11 12 13 14 15 16
di gi t al
i it l
LINE PROTECTION RELAY REL316*4
Drive control & monitoring circuitry
ABB
ABBNetworkPartner
REB500
BUSBAR PROTECTION REB500
COM 581 ABBPower Automation AG
COM581
NCC / RCC
Communication Converter
C
-Q0
-T1 -Q9
DIS T A NCE
EXE
REL316*4
ABBNetworkPartner
1 2 3 4 5 6 7 8
-Q2
-Q1
FERMER
LOCAL SET REMOTE OPERATION
PISA
PISA A PISA B
Feeder Marshalling
-Q1
ABB
t
d gi tal
LAMPE TESTE
-Q0 SEL
ABB
?
LOCAL CONTROL
Sampling AD-Conversion Signal Processing Signal Filtering
Process Bus
Station Level
Intelligent SA Architecture
Network Control Center NCC
ABB Network Partner AG
C
Interbay Bus 125VDC Distributuion Battery A
Bay Level
=D04+R01
225kV LIGNE ABOBO 1
ABB
125VDC Distributuion Battery B REL316*4
ABBNetworkPartner
ABB
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
BAY CONTROL RELAY REC316*4 =D 04 A B OB O 1
ABB P OWE R
MON I T OR I N G U N I T
=W1 =W2
M M
-Q1 SEL
-Q2 SEL
LAMPE TESTE
-Q0 SEL
M
ABB
OUVRIR
FERMER
ESC
EXE
LOCAL SET REMOTE OPERATION
?
LOCAL CONTROL
1 2 3 4 5 6 7 8
DIS T A NCE LO C
METERING REL316*4
ABBNetworkPartner
ABB
9 10 11 12 13 14 15 16
LINE PROTECTION RELAY REL316*4 ABB
ABBNetworkPartner
REB500
BUSBAR PROTECTION REB500
-Q2
-Q0 -Q1
-Q51
PISA B
PISA A
PISA A
PISA
Process Level
Process B u
-T1
-Q9
-Q8
s
Basic Functionality
E
FEATURES AND BENEFITS
COM581
Functional Structure of Modern SA
Station Level
Functions Allocation Network Control Center NCC
ABB Network Partner AG
COM581
C E
Scalable System Extensions SCADA Remote Communication Fault evaluation Monitoring Events and alarms Supervision & Control Data Exchange
Interbay Bus 125VDC Distributuion Battery A
1 2 3 4 5 6 7 8
Bay Level
125VDC Distributuion Battery B REL316*4
ABBNetworkPartner
ABB
Process Level
=D04+R01
225kV LIGNE ABOBO 1
ABB
9 10 11 12 13 14 15 16
BAY CONTROL RELAY REC316*4 =D 04 A B OB O 1
ABB P OWE R
Monitoring
MON I T OR I N G U N I T
=W1 =W2 -Q1 SEL
-Q2 SEL
LAMPE TESTE
-Q0 SEL
OUVRIR
ESC
ABB
FERMER
LO C
LOCAL CONTROL ABB
METERING REL316*4
ABBNetworkPartner
1 2 3 4 5 6 7 8
DIS T A NCE
EXE
9 10 11 12 13 14 15 16
LINE PROTECTION RELAY REL316*4 ABB
ABBNetworkPartner
REB500
BUSBAR PROTECTION REB500
GIS or AIS Switchgear Instrument Transformers Power Transformers Surge Arresters
-Q2 -Q0 -Q1
-Q9
-Q8
Intelligent Substation Automation Functional Structure
Functions Allocation
Station Level
Network Control Center NCC
ABB Network Partner AG
C E
Interbay Bus 125VDC Distributuion Battery A
125VDC Distributuion Battery B REL316*4
ABBNetworkPartner
ABB
1 2 3 4 5 6 7 8
Bay Level
=D04+R01
225kV LIGNE ABOBO 1
ABB
9 10 11 12 13 14 15 16
BAY CONTROL RELAY REC316*4 =D 04 A B OB O 1
ABB P OWE R
MON I T OR I N G U N I T
=W1 =W2
M M
-Q1 SEL
-Q2 SEL
Monitoring
LAMPE TESTE
-Q0 SEL
M OUVRIR
ESC
ABB
FERMER
LOCAL SET REMOTE OPERATION
?
LOCAL CONTROL ABB
LO C
METERING REL316*4
ABBNetworkPartner
1 2 3 4 5 6 7 8
DIS T A NCE
EXE
9 10 11 12 13 14 15 16
LINE PROTECTION RELAY REL316*4 ABB
ABBNetworkPartner
REB500
BUSBAR PROTECTION REB500
s
-Q2
-Q0 -Q1
-Q51
PISA B
PISA A
PISA A
PISA
Process B u
Process Level
COM581
Scalable System Extensions SCADA Remote Communication Fault evaluation Monitoring Events and alarms Supervision & Control Data Exchange
-T1
-Q9
-Q8
Intelligent or “smart” AIS / GIS Switchgear Data acquisition Sensors & Actuators Power Transformers Surge Arrestors
Intelligent SA: Control, Protection and Sensors ABB
=D04+R01
225kV LIGNE ABOBO 1
ABB
Actuator for isolator & earthing switch control
PISA PISA
PISA
PISA
125VDC Distributuion Battery A ABB
125VDC Distributuion Battery B REL316*4
ABB Network Partner
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
Line Protection 1 I Abgangsschutz
BAY CONTROL RELAY REC316*4 ABB
=D04 ABOBO 1
POWER MONITORING UNIT =W1
=W2
M
-Q1 SEL
M
-Q2 SEL
LAMPE TESTE
-Q0 SEL
Feldleitgerät Bay Controller
M
Switches
? ABB
LOCAL
OUVRIR
FERMER
ESC
EXE
LOC
OPERATION
LOCAL CONTROL
Actuator for circuit breaker control
ABB
1 2 3 4 5 6 7 8
DISTANCE
SET
REMOTE
METERING REL316*4
ABB Network Partner
9 10 11 12 13 14 15 16
PISA A
Line Protection 2 II Abgangsschutz LINE PROTECTION RELAY REL316*4
PISA A
ABB
ABB Network Partner
REB500
PISA B
Busbar Protection
Sensors for current & voltage measurement
Process Bus
BUSBAR PROTECTION REB500
Interbay bus 1 Interbay bus 2
Monitoring via IEDs for Protection
Advanced analysis tools
Alarm Classes
Automatic printing Summary report
GPS
User friendly visualization Universal Time synchronization
CONCISE / FAST Distance to Fault Mo 12. 11. 96
GMT 17:02.43.305
Ayer Rajah & Labrador
Feeder One
Sequence of Events ABB Network Partner AG
IED Parameter
# Of trips C E
ABB Network Partner AG
REL 316*4
ABB Network Partner AG
REL 316*4 ABB Network Partner AG
1
9
1
9
2
10
2
10
1
9
3
11
3
11
2
10
4
12
4
12
3
11
5
13
5
13
4
12
6
14
6
14
5
13
7
15
7
15
6
14
8
16
8
16
7
15
8
16
C
C
E
E
REL 316*4
C E
Station level supervision
Single Line Diagram:
Diagnostic: Fault Recording and Evaluation
Automatic fault location printout
Remote Control via Network Control Centre (NCC)
The goal of the IEC 61850 standard Interoperability
The ability for IED’s from one or several manufacturer to exchange information and use the information for the their own functions.
Free Configuration The standard shall support different philosophies and allow a free allocation of functions e.g. it will work equally well for centralized (RTU like) or decentralized (SCS like) systems. Long Term Stability The standard shall be future proof, i.e. it must be able to follow the progress in communication technology as well as evolving system requirements.
© ABB Group October 10, 2011 | Slide 127
© ABB Group October 10, 2011 | Slide 128