Web-enabled Power & Control
Motorpact™ MV motor starters 7.2kV
Abbreviations LPCT Low Power Current Transducer LV Low Voltage MV Medium Voltage O/L Over Load PLC Programmable Logic Starter RMS Root Mean Square RVAT Reduced Voltage Auto Transformer RVSS Reduced Voltage Soft Start SCR Silicon Controlled Rectifiers SSM Soft Starter Module ATM Auto Transformer Module S3 Sequential Smart Starter FVR Full Voltage Reversing SSM Soft Start Module
Motorpact 2007-TL
TVSS Transient Voltage Surge Suppressor VSD Variable Speed Drive VPIS Voltage Presence Indicator System VT Voltage Transformer (Potential Transformer) CPT Control Potential Transformer CTD Capacitor Trip Device
2
MV motor starter Rated voltage
7.2 kV
Short Circuit withstand
40kA/3s or 50kA/2s
Motor range
Up to 3800 kW
Motor type
Asynchronous (Squirrel cage)
Starter :
FVNR
RVAT
RVSS
Enclosure types
Motorpact 2007-TL
Up to IP 3X or 4X
Arc resistant
Optional: roof for IP X2
3
Motorpact = low cost of ownership Low installation cost Space saving footprint High reliability Reduced maintenance Easy to use Safety focus Global product (meets IEC and NEMA standards)
Motorpact 2007-TL
4
Low cost of ownership
Low installation cost
2 unit pre-assembled shipment
available shipment in units pre-assembled of 5 FVNR
reduces installation time and labor
minimizes risks field installation errors
Integrated low voltage wireway
simplifies field wiring and installation of protection, control and communication
Front and rear access to cable compartment
Motorpact 2007-TL
simplifies field wiring and installation of protection, control and communication
5
Low cost of ownership
Space saving footprint 400A FVNR 375 mm wide Perfect for retrofit or extension Floor space maximum economy Two FVNR single tier more compact than one double tier
375 Depth : 946 mm Height : 2300 mm Motorpact 2007-TL
6
Low cost of ownership
High reliability
Disconnector housing and contactor cradle moulds
Fewer bolted connections and parts
Simple component-to-component support assemblies
Fewer busbar connections
Requires only two-bolts per phase for a main bus connection
Pre-engineered solutions with LPCT and Sepam digital relay
Provides proven designs for the full range of motor applications
KEMA Certified
Motorpact 2007-TL
7
FVNR & ATM & SSM descriptions 3 types of Motorpact starters Reduced Voltage Auto Transformer Non-Reversing (RVAT)
Full Voltage Non-Reversing (FVNR)
Auto Transformer Module (ATM) Motorpact 2007-TL
Mechanically Latched Magnetically Held
FVNR Module
Reduced Voltage Soft Start™ Non-Reversing (RVSS)
Soft Start™ Module (SSM) 8
FVNR base module description Direct stator starting on full voltage Locked rotor current on starting is around 4 to 7 In depending on motor characteristics Starting time of 1 to 10 seconds depending on the moment of total inertia (motor + machine), motor torque and load torque The network must be able to withstand the starting current without disturbing other loads The machine being driven must be able to withstand the mechanical impact due to the motor torque
Network
This mode is very popular (simple, robust, not expensive)
Protection
Motor
Load
Main contactor
Motorpact 2007-TL
9
Auto Transformer module description Reduced voltage by auto-transformer This system is recommended for high power motors. It has the advantage of not dissipating energy. It can be used to obtain, for the same decrease in current, less reduction in torque than with the reactor starter.
Auto-transformer
Network
Ct1 Motor Ct2 Protection
Ct3 CT1 : Start Contactor CT2 : Main Contactor CT3 : Run Contactor N1
Motorpact 2007-TL
Load
1 0
Soft starter setting: torque control Network
Pro. Soft starter
Motor
Load
Reduced Voltage SoftStart motor starter (RVSS) SoftStart motor starter provides smooth, stepless acceleration and deceleration regardless of the load. This starting method lowers the starting current of the motor, reduces electrical stresses on the network and the motor. It reduces peak starting torque stresses on both the motor and mechanical load components, thereby providing longer service life and less downtime.
T1 = k.I1 Motorpact 2007-TL
Φ1
1 1
Soft starter setting: usual setting
Motorpact 2007-TL
1 2
FVNR & ATM descriptions Starting mode selection table Motor & Load requirements yes
- deceleration control ?
no
- the drive between motor and load is able to withstand the mechanical stress of a direct on line start yes
no
- constant torque with high starting torque as crushers, grinders, mixers ......
yes no
Network requirement - accepts full starting current? - accepts starting voltage drop? -accepts the starting reactive consumption power?
no
Investment Increase
yes no yes
no yes
- accepts the current oscillation during an open transition?
yes
VSD specific
no yes
- accepts the harmonics during the starting period
no yes
FVNR Motorpact 2007-TL
no
RVAT
RVSS 1 3
OTHER TYPE OF MOTORPACT PANEL 2S2W: 2 Speed 2 Winding full voltage non reversing asynchronous motor starter
2300
750
Motorpact 2007-TL
1 4
OTHER TYPE OF MOTORPACT PANEL 2S1W: 2 Speed 1 Winding full voltage non reversing asynchronous motor starter (Star delta starter) 2300
375
750
750
Motorpact 2007-TL
1 5
S3: Sequential Smart Start reduced voltage non reversing asynchronous motor starter
375
Motorpact 2007-TL
750
750
750
1 6
Dimension and weight
FVNR
Motorpact 2007-TL
RVSS
RVAT
1 7
Maximum motor ratings* 200 A Service Voltage 3.3 kV 5.5 kV 6.6 kV
kW (single fuse) 900 1500 1800
400 A Service Voltage 3.3 kV 5.5 kV 6.6 kV
kW (single fuse) 950 1600 1900
kW (double fuse) 1900 3000 3800
*Maximum Rating depend on full load current, locked rotor current and run up time of motor.
Motorpact 2007-TL
1 8
MotorpactTM MV motor starter Case :
DOL (FVNR) Starter connected to the load as follow:
Motor power : 750 kW
Service voltage : 3.3 kV
Freq : 50 Hz
Cos Q : 0.85
Motor efficiency : 0.96
Service factor : 100% (Load Factor: 1)
Starting current : 5 In
Starting time : 10 s
Number start per hours : 3
Fuse calculator
Questions? How many ampere motor current ? How many ampere rating of the contactor ? How many ampere rating of the fuse ?
Motorpact 2007-TL
1 9
MotorpactTM MV motor starter Low voltage compartment (A) Disconnector (B)
A
HRC fuses (C)
E
Vacuum contactor (D) Complete motor protection with Sepam digital relay or others (E)
B C
D
Motorpact 2007-TL
2 0
Low cost of ownership
Easy to use All controls located at the same convenient operator height
Disconnector operator & pilot devices
Disconnector position viewing window
Visible isolation and “earthed” indication at eye-level
Optional back-light to view contact position
Simple direct drive disconnector mechanism
Ensures reliability and operator ease Viewing window
Mechanical interlocks
Motorpact 2007-TL
Prevent access to MV compartment when the unit is energised
2 1
Operating panel
Disconnector Closed
Motorpact 2007-TL
Disconnector Open
2 2
Disconnector 2 positions
Closed and Earthed
Positive operation
Earthed position by spring operation
Interlocked to close – MV door closed and contactor open
Visible contacts
Back-light for easy viewing (optional)
Supports top fuse holders
Motorpact 2007-TL
2 3
Voltage Presence Indication System (VPIS) (option) Line side available for
Incoming cubicle(direct incoming) Load side available at load terminal pads of motor starter
Motorpact 2007-TL
2 4
Low cost of ownership
Safety focus Loss of service continuity
category LSC2A
Partition Class PI (Cable earthing switch required)
Closed door operation (only if MV door close)
Electrical and mechanical interlocks Arc resistant type AFLR (optional) Cable earthing switch (optional) Voltage Presence Indication System (optional)
Motorpact 2007-TL
2 5
Low cost of ownership
Key Interlock • DiSCONNECTOR KEY LOCK : Lock open only, key captive Max 2 key lock • EARTH SWITCH KEY LOCK : Max 1 key lock Open or close lock
Disconnector key lock LDA Key lock
Motorpact 2007-TL
2 6
Busbar compartment Busbars up to 3150 A
Bar cooper bar (standard)
Tinned coated busbar (option)
Silver coated busbar (option)
Encapsulated/heatshrink busbars are available as an option Mounted and supported by the disconnector Short time withstand
Motorpact 2007-TL
50 kA 2s
40 kA 3s
31.5 kA 3s
25 kA 3s
2 7
Busbar Spacer (intermediate panel)
1250A
2000-2500A
Intermediate Insulator support
3000-3150A
Main Busbar
Motorpact 2007-TL
2 8
Busboot
Intermediate bus boot • For rating : 630A,1250A,2500A, 3150A • Disconnector or Insulator
End bus boot • For rating : 630A,1250A,2500A, 3150A • Disconnector or Insulator
Motorpact 2007-TL
2 9
Main busbar jointing
Motorpact 2007-TL
3 0
Load compartment Accessible only if contactor open and disconnector and cable are earthed Comprises : 1.
HRC fuses
2.
vacuum contactor
3.
LPCT
4.
cable termination
optional : −
A. cable earthing switch with position viewing window
−
B. Control Power Transformer
−
C. Voltage Presence Indication System
−
D. Fuse blown indicator
C D A
4v 3
2
Motorpact 2007-TL
1
Bv
3 1
Load compartment - instrument transformers LPCT or CT mounted on contactor (fixed contact mould assembly)
Optional VT for protection and metering CPT Optional fused CPT (floor mounted)
Motorpact 2007-TL
3 2
Load compartment - MV fuses HRC DIN fuses independently mounted
Easy to inspect and maintain
Stricker blown fuse indicator
Supplier: Fusarc(Schneider), SIBA, Bussman,
Fuses for motor or non-motor loads
2 x 250 A Maximum
Fuselogic Blown-fuse Indication (optional)
Motorpact 2007-TL
With viewing window in door
Blown-fuse fuse protection
2 Fuse blown aux contacts (SPDT)
3 3
Load compartment - contactor
In : 200 A and 400 A
Withdrawable contactor truck
Patented finger design
Compact and lightweight
20 kg - easy to handle
Independently mounted from power fuses
Contactor removed only for maintenance
Magnetically held or mechanically latched
Mechanically Close – Open indicator
Mechanical operating counter
Aux power supply AC or DC,with range: DC range: 100/125 – 240/250V and AC range:115/120 – 230/240 (+10% ~ -15%). Voltage selection by using dip switch inside the contactor
Mismatch location
AC or DC aux power supply: internal supplied by CPT(AC) or external (AC or DC)
Open release (for mech.latch) with DC supply only (48V, 125V and 250V). Additional tripping capasitor for AC aux supply (120VAC and 240VAC)
Capasitor Trip (optional) install when using mech. Latched contactor and internal supply from CPT.
Motorpact 2007-TL
3 4
Contactor aux Contact Additional Aux contact
Motorpact 2007-TL
3 5
Contactor finger assembly Patented finger design Tests
Temperature rise 400
A continuous
Mismatch/Blocking Contactor rating and type mismatch
Motorpact 2007-TL
200 A unlatch
200A latch
400A unlatch
400A latch
3 6
Contactor to outgoing terminal Cable : 200A 400A Differentiation by means blocking truck/mismatch
Mismatch/Blocking Contactor rating and type mismatch
200 A unlatch
200A latch
400A unlatch
400A latch
Motorpact 2007-TL
3 7
Load compartment - contactor
Standard Operation for Magnetically held contactor
Motorpact 2007-TL
3 8
Load compartment - contactor
Standard Operation for Mechanically latch contactor w/o CTD
Motorpact 2007-TL
3 9
Load compartment - contactor
Standard Operation for Mechanically latch contactor with CTD
Motorpact 2007-TL
4 0
TEST POSITION in MOTORPACT
External supply From CPT
Aux contact
1. Open Disconnetor switch 2. Supply aux power from external 3. Contactor still connected 4. Test the operation by control push button
Motorpact 2007-TL
K1 sepam
K1
4 1
Low voltage compartment Ample space for :
Sepam series 20/series 40 and series 80 digital relay or Multilin PowerLogic Power Meter or Circuit Monitor Control devices
Isolated from other compartments (busbar and load compartments) Integrated low voltage wireway (*) simplifies
field wiring and installation of protection, control and communication
Motorpact 2007-TL
Customer connection
4 2
Motorpact aux contacts Disconnector switch aux contacts(Q1) : 4 SPDT , additional : 4 SPDT Fuse blown /Fuse logic aux contacts(FU1) : 2SPDT Earthing switch aux contacts (Q21): 4 SPDT Main contactor aux contacts (K1): 3NO+3NC, additonal : 3NO+3NC
Note: SPDT stand for single pole double trip
Motorpact 2007-TL
4 3
Motorpact contact resistance Descriptions Disconnection Swicth
Nominal values 450 micro Ohm
Busbar to the outgoing terminal (including DS, VCU and outgoing terminal)
50.000 micro Ohm (50 mili Ohm)
Vacuum Contactor upper pole to lower pole (without load cable)
< 200 micro Ohm
Motorpact 2007-TL
4 4
Load compartment - contactor
Connected position
Motorpact 2007-TL
Rail extended
Withdrawn position
4 5
Load compartment - cable termination Front access or front and rear accessibility
simple cable termination with rear access
Full height cable pulling area Load cable box allows for up to 1-240 mm2 or 2- 120mm² per phase Formex® cover over cable terminations
Motorpact 2007-TL
provides coverage at cable terminations
4 6
Typical cable termination
• Top and Bottom cable connection • Line connection and load connection Motorpact 2007-TL
4 7
Typical cable termination for single section and single controller
• Top and Bottom cable connection
Motorpact 2007-TL
4 8
Load compartment - cable earthing switch (option) Cable earthing switch
Formex® cover
Load cable termination
Motorpact 2007-TL
4 9
Top cable clamp assy
Top cable assy 1 or 2 cores cable Top cable assy 3 or 6 single core cable Motorpact 2007-TL
5 0
Lower cable clamp assy
Top cable assy 3 or 6 single core cable Motorpact 2007-TL
Lower cable assy 2 cores cable
5 1
Low cost of ownership
Predictive maintenance Thermal diagnosis system (optional)
Improved power availability −
Increased safety of electrical installation −
−
reduces maintenance costs no local human intervention.
Sensors installed in the sensitive areas − −
help to prevent damage to the installation (deterioration can lead to an internal arc)
Continuous monitoring of temperature rise −
detects abnormal temperature rise at the heart of power circuit
cable connexions top MV fuses holders
Activates 2 trip levels − −
pre-alarm threshold alarm threshold
Hold at the moment this offer
Motorpact 2007-TL
5 2
Temperature monitor module (DT1)
Provides continuous monitoring of joints in the equipment for predictive maintenance
Motorpact 2007-TL
5 3
POWER FACTOR CORRECTION CAPASITOR 3 phase capacitors without internal fuse Possible for FVNR with 750mm width Be careful for RVSS and S3
Motorpact 2007-TL
5 4
Enclosure - internal arc withstand (option) Tested at KEMA
following IEC 62271-200 standard
in all MV compartments
Protection on all 4 sides by pressure venting to the top
25 kA 1s
40 kA 0.5s
50 kA 0.25s
Tunnel for ceiling below < 4m
With IP X1 Motorpact 2007-TL
5 5
Enclosure – IPX1 (option)
IPX1 : • Tunnel + roof • No top entry cable (standard) non std for top entry Motorpact 2007-TL
5 6
Enclosure – main earth bar
Motorpact 2007-TL
5 7
Enclosure - internal arc withstand (option) 8-point latching door Heavy-duty vault style door handle
Frame
Door
Interlocking of hinge side
Motorpact 2007-TL
5 8
Enclosure - internal arc withstand Pressure relief flaps
(option)
Bolted rear panels
Top View
Interlocked rear panel to frame construction Top and Bottom Access Panels Easy Removal
Motorpact 2007-TL
5 9
Joining the shipping splits
Motorpact 2007-TL
6 0
Sepam series 20, 40 and series 80 Protection functions
50/51, 50N/51N, 46 49 R 38/49T 37, phase undercurrent 48/51LR, excessive starting time and locked rotor 66 starts per hour …
Options
Motorpact 2007-TL
User Machine Interfaces Logic I/Os Communication interfaces Temperature monitoring Analog output
6 1
current sensor (standard CT)
F
One block sensor consits of 3 CTs Low burden < 2.5VA (ratio <50A) and < 5VA (ratio>50A) Protection class : 5P5 and 10P5 Metering class : 0.5, 1 and 3 Single depth and Double depth (<50A) Max. 3 Block single CT or 1 Block Double CT + 1 Block Single CT
F
H2
Secondary ratio : 1A or 5A Primary ratio : 50A, 100A, 150A, 200A, 250A, 300A, 400A
Freq: 50…400Hz Motorpact CT specification Motorpact 2007-TL
6 2
Low power current transducer (standard LPCT) One sensor for all applications (50A ~ 400A)
100A / 22.5 mV 2500/1
0.5625 Ω
High accuracy for protection and metering
Sepam Measuring and Protection
Linear across a wide current range Saturation value above 16 kA Accuracy 10.0% 5.0%
1.5% 0.75% 0.5% 5A Motorpact 2007-TL
20A
100A
800A
1000A 16000 A 6 3
Control Power Transformer (CPT) Auxiliary Control Power supply : External DC or AC supply Internal AC supply by using CPT CPT or VRCR(small burden:200VA) Power CPT : 300VA, 500VA, 750VA and 2000VA MV Primary fuse for CPT (Ph-Ph) : 0.63A, 1A, 2A and 3.15A. Ferraz fuse. Fuse holders are loacated below the contactor. Secondary of CPT is protected by MCB Primary Voltage : 2400V, 3300, 4160, 4800, 5000, 5500, 6000V, 6600V,6900V Secondary voltage: 110/220V (dual voltage) Freq: 50/60Hz CPT & VT Fuse holder
Motorpact 2007-TL
6 4
Voltage Transformer (VT) Voltage for metering device or protection relay Power Output: 50VA/Phase (100VA) at 30 deg. C. Accuracy : 2.4% at 15VA Primary VT is protected by MV fuses Secondary side is protected by MCB Primary Voltage : 2400V, 3300, 4200, 4800, 5000, 5500, 6000V, 6600V,6900V(6300V under development) Freq; 50/60Hz Insulation level : 6.9kV (60kV BIL) Secondary voltage: 110V
CPT & VT Fuse holder
Motorpact 2007-TL
6 5
Fuse tube Fuse holder for primary fuse of CPT or/and VT Long tube : (20mm x 190mm) for voltage > 5.5kV Short tube : (20mm x 127mm) for voltage < 5.5kV Thermal rating max : 5A . Insulation level : 6.9kV (60kV BIL) No special tools to remove or insert the MV fuse Located below the contactor chassis
Motorpact 2007-TL
6 6
Ground Fault sensor With Sepam relay If solidly Grounded (low resistance) ZCT 50/5A(AAF00309) + CSH 30 or CSH 120 or 200 If High Resistance Grounded (un grounded system)
AAF00309 AAF00311 AAF00310 AAF00308
CSH 280 (470/1 - AAF 00311) + Resistor for zero sensor
Others relay (Without Sepam relay ) If solidly Grounded (low resistance)
CSH 120/200
ZCT 50/5A If High Resistance Grounded (un grounded system) Zero seq. Sensor 2000/1 (AAF00310) or Zero seq. Sensor 50/0.025 (AAF00308) Note: the above sensor is installed on the same place of the block CT Motorpact 2007-TL
6 7
Surge Arrestor Distribution Class and Intermediate Class distribution class : near the load (low kA) Intermediate class : outgoing feeders with several downstream feeders (high kA) Line side or Load side Line side : install on the busbar side Load side : install on the cable load side
Rated Voltage : 3kV, 6kV and 9KV 6kV for service voltage : < 5kV 9 kV for service voltage : > 5kV
Motorpact 2007-TL
6 8
MV motor starter FVNR basic single line diagram Disconnector closed/ earthed
HRC fuses
Withdrawable vacuum contactor
Sepam series 20,40 or 80
LPCT
Cable earthing switch (optional) Motorpact 2007-TL
6 9
MV motor starter FVNR with options
CPT fuses
Control Power Transformer Second set of CT’s
Motorpact 2007-TL
7 0
Reduced Voltage Solid State (RVSS)
Motorpact Soft Start™ Ranges
2300V up to 2300kw 3300V up to 3400kw 4160V up to 4300kw 6900V up to 7100kw
50 / 60 Hz Full Digital Control
Motorpact 2007-TL
7 1
Reduced Voltage Solid State (RVSS)
Motorpact Soft Start™ Advanced Motor Protection
Options: – Ground Fault – RTD modules
Heavy Duty Silicon Control Rectifier (SCR) stack Arc Resistant
Motorpact 2007-TL
7 2
Motorpact RVSS - HMI Full digital control
LCD operator interface Non-Volatile memory
Digital sequencer
Ensures proper contactor sequence
Fiber-Optic isolation
between digital controller and power module/SCR
Metering functions
Motorpact 2007-TL
Voltage Current Power Factor KVAR kW
7 3
Motorpact Soft Start ™ Controller Applications
Motorpact 2007-TL
Pumps
Ball Mills
Blowers
Rod Mills
Compressors
Conveyors
Chillers
Natural Gas Compressors
Fans
Centrifugal Blowers
Chippers
Other Applications
7 4
Motorpact SoftStart™ 6 Goals Beyond On-Off
Motorpact 2007-TL
Protect the Motor and Load Reduce Mechanical Stress Limit Starting Current Reduce Stress on the Electrical Grid Reduce Electrical System Disturbance Provide Soft Stopping
Meter and Record
Communicate
7 5
Motorpact SoftStart™ Benefits Eliminate Torque Shock Damage Prevent belt slipping, coupling damage Increases motor AND drive train reliability Keep Starting kVA to a Minimum Maintain future flexibility Soft Start and Soft Stop Pumps Reduce hydraulic / mechanical problems Low Cost Ratio vs. MV VFDs
Motorpact 2007-TL
Can be considered as an alternate in some cases
7 6
Motorpact SoftStart™ Heavy Duty Ratings 500% for 60 Seconds
Nearest competitor is 500% for 30 sec.
600% for 30+ Seconds
Capable of Class 30 “Mill Duty” motors
200% for up to 2 Minutes
Allows for long accel times
Tested at 50˚C
Motorpact 2007-TL
Most others tested at 40˚ C
7 7
Motorpact SoftStart™ Compartment 2
1
Compartment 1 Compartment 2
Line disconnector Isolates motor starter from power supply
1 2 2
4
Vacuum contactor Provides start sequence to SCR stack (in main contactor cubicle)
5 3
SCR stack
5
Provides voltage ramp and advanced protection features
3
4
4
By-pass contactor By-passes the SCR when motor is at full speed
5
3
LV control Control and HMI of motor starter with power system
Motorpact 2007-TL
7 8
Motorpact SoftStart™
Designed for Safety High MV to LV Electrical Isolation
Magnetic isolation of Gate Pulses
Fiber optic isolation for firing control and signal interfaces
Door Interlocking Isolated LV Compartment
Motorpact 2007-TL
7 9
Motorpact SoftStart™ Electrical Isolation Diagram Magnetic Isolation
Gate Drive
MTR
Motorpact 2007-TL
= MV = 120V = 28V = Fiber Optic
Sensing Systems
Optical Isolation
LV Controls
8 0
Reduced voltage auto-transformer motor starter (RVAT) B
A
Line current lower than motor current Provides high torque per A of line current Medium or heavy duty 3 Contactors Main(1), Run(2), Start(3) Includes surge protection Provides switching transient protection for autotransformer 50, 65, and 80 % Taps (4) Closed transition from start to run 1125 mm or 1500 mm width. Internal arc withstand Auto Transformer capacity (50Hz)
Motorpact 2007-TL
<3.6kV : 1100kW 7.2kV : 1550kW 3 starting at cold (2 consecutive after running) Starting time 15 sec Insulation Class F
C
D E
H I
3
J K
F
L
G
M
8 1
Reduced voltage auto-transformer motor starter
1 MAIN CONTACTOR
2 RUN CONTACTOR
4 AUTO TRANSFORMER
3 START CONTACTOR
Motorpact 2007-TL
8 2
(A)
(A)
(C)
(C)
(B)
(C)
(B)
M
First stage : C is open A and B are closed B must be closed before A.
RVAT
(A)
(B)
M
Second stage : A remains closed C remains open and B is opened
M
Third stage : A remains closed B remains open and C is closed
The current path is shown in red. It is obvious that the motor is always supplied even during the second stage, when B is open.
First stage : the motor is starting with reduced voltage. Second stage: the motor is running in series with part of the autotransformer winding. Third stage: the motor runs at full voltage. Motorpact 2007-TL
8 3
Incoming LV cables from below, cubicle by cubicle
1
2
3
Motorpact 2007-TL
4
8 4
Incoming LV cables from top, cubicle by cubicle
Motorpact 2007-TL
8 5
Civil engineering Lined up with MCset switchgear Incomer - Bus sectioning - IncomerMC set
Motorpact 2007-TL
interface Motorpact
8 6
Civil engineering stand-alone motor control with RVSS SoftStartTM motor starter
Incoming cable and metering
3150 A Busbar
Motorpact 2007-TL
Front
8 7
Motorpact™ MV motor starters Smart choice for MV- MCC application Incoming cable and metering
Front
Motorpact 2007-TL
8 8
Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity
Loss of Service Continuity Class (LSC) • Architecture based on “safe compartment access”
Several levels of service continuity during maintenance
LSC 2B Maintainability of defined parts with no need of cable disconnection (separate cable compartment)
• Safe access to compartment • With power flow in busbar and the other units • MV Cable in separate compartment • Cable of unit under maintenance can remain energized
LSC 2A • Safe access to compartment • With power flow in busbar and the other units • MV Cables must be earthed
Maintainability of one functional unit allowing normal service of the remaining units of the switchboard (busbar in a separate compartment)
MOTORPACT MOTORPACT
LSC 1 • Metal enclosed not of LSC2 class
Motorpact 2007-TL
8 9
Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity
Partition Class I or M • Classification based on electrical field presence in safe access compartment
Partition Class PM Personnel comfort during maintenance
3.110 Shutter Part of metal-enclosed switchgear and controlgear that can be moved from a position where it permits contacts of a removable part, or moving contact of a disconnector to engage fixed contacts, to a position where it becomes a part of the enclosure or partition shielding the fixed contacts.
• All partitions and shutters of safe access compartment shall be metallic with some current carrying capacity
Partition Class PI • Partitions or shutters may be partially or totally of Definition insulating material
“Metal enclosed” compliant during maintenance Applicable mainly to withdrawable system
Electrical and mechanical safety according to IEC 60466 or 60137
Motorpact Motorpact Motorpact 2007-TL
9 0
Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having current carrying capacity
Internal Arc Class IAC • Classification based on consequences of internal arc on personnel safety
Accessibility Types • A : restricted to authorized personnel only. • B : unrestricted, including general public.
IAC classified Personnel safety in case • No projection of parts of internal arc towards accessible sides • No ignition of indicators
Motorpact complies with AFLR type
Safety in case of internal fault during service condition Demonstrated by type tests (completely defined by the standard)
IAC not classified • No tests performed to assess behavior of enclosure under arc conditions
• Enclosure Identification code: F - for Front side • L L - for Lateral side R - for Rear side
Motorpact 2007-TL
9 1
Motorpact 2007-TL
9 2
Motorpact 2007-TL
9 3
Motorpact 2007-TL
9 4
Motorpact 2007-TL
9 5
Motorpact 2007-TL
9 6
Motorpact 2007-TL
9 7
Motorpact 2007-TL
9 8
Motorpact 2007-TL
9 9
Motorpact 2007-TL
1 0 0
Motorpact 2007-TL
1 0 1
Motorpact 2007-TL
1 0 2
Motorpact 2007-TL
1 0 3
Motorpact 2007-TL
1 0 4
Motorpact 2007-TL
1 0 5
Motorpact 2007-TL
1 0 6
Motorpact 2007-TL
1 0 7
Motorpact 2007-TL
1 0 8
Motorpact 2007-TL
1 0 9
Motorpact 2007-TL
1 1 0
Motorpact 2007-TL
1 1 1
Motorpact 2007-TL
1 1 2
Motorpact 2007-TL
1 1 3
Redundant S3 Alternate Configuration
One SoftStart used to start all motors Second SoftStart used as back up in case first fails. SoftStart has incoming and outgoing contactors for isolation
Motorpact 2007-TL
1 1 4