Web-enabled Power & Control

Motorpact™ MV motor starters 7.2kV

Abbreviations LPCT Low Power Current Transducer LV Low Voltage MV Medium Voltage O/L Over Load PLC Programmable Logic Starter RMS Root Mean Square RVAT Reduced Voltage Auto Transformer RVSS Reduced Voltage Soft Start SCR Silicon Controlled Rectifiers SSM Soft Starter Module ATM Auto Transformer Module S3 Sequential Smart Starter FVR Full Voltage Reversing SSM Soft Start Module

Motorpact 2007-TL

TVSS Transient Voltage Surge Suppressor VSD Variable Speed Drive VPIS Voltage Presence Indicator System VT Voltage Transformer (Potential Transformer) CPT Control Potential Transformer CTD Capacitor Trip Device

2

MV motor starter  Rated voltage 

7.2 kV

 Short Circuit withstand 

40kA/3s or 50kA/2s

 Motor range 

Up to 3800 kW

 Motor type 

Asynchronous (Squirrel cage)

 Starter : 

FVNR



RVAT



RVSS

 Enclosure types

Motorpact 2007-TL



Up to IP 3X or 4X



Arc resistant



Optional: roof for IP X2

3

Motorpact = low cost of ownership  Low installation cost  Space saving footprint  High reliability  Reduced maintenance  Easy to use  Safety focus  Global product (meets IEC and NEMA standards)

Motorpact 2007-TL

4

Low cost of ownership

Low installation cost

 2 unit pre-assembled shipment 

available shipment in units pre-assembled of 5 FVNR



reduces installation time and labor



minimizes risks field installation errors

 Integrated low voltage wireway 

simplifies field wiring and installation of protection, control and communication

 Front and rear access to cable compartment 

Motorpact 2007-TL

simplifies field wiring and installation of protection, control and communication

5

Low cost of ownership

Space saving footprint  400A FVNR 375 mm wide  Perfect for retrofit or extension  Floor space maximum economy  Two FVNR single tier more compact than one double tier

375 Depth : 946 mm Height : 2300 mm Motorpact 2007-TL

6

Low cost of ownership

High reliability

 Disconnector housing and contactor cradle moulds 

Fewer bolted connections and parts



Simple component-to-component support assemblies

 Fewer busbar connections 

Requires only two-bolts per phase for a main bus connection

 Pre-engineered solutions with LPCT and Sepam digital relay 

Provides proven designs for the full range of motor applications

 KEMA Certified

Motorpact 2007-TL

7

FVNR & ATM & SSM descriptions 3 types of Motorpact starters  Reduced Voltage Auto Transformer Non-Reversing (RVAT)

 Full Voltage Non-Reversing (FVNR)  

 Auto Transformer Module (ATM) Motorpact 2007-TL

Mechanically Latched Magnetically Held

 FVNR Module

 Reduced Voltage Soft Start™ Non-Reversing (RVSS)

 Soft Start™ Module (SSM) 8

FVNR base module description Direct stator starting on full voltage  Locked rotor current on starting is around 4 to 7 In depending on motor characteristics  Starting time of 1 to 10 seconds depending on the moment of total inertia (motor + machine), motor torque and load torque  The network must be able to withstand the starting current without disturbing other loads  The machine being driven must be able to withstand the mechanical impact due to the motor torque

Network

 This mode is very popular (simple, robust, not expensive)

Protection

Motor

Load

Main contactor

Motorpact 2007-TL

9

Auto Transformer module description Reduced voltage by auto-transformer  This system is recommended for high power motors. It has the advantage of not dissipating energy.  It can be used to obtain, for the same decrease in current, less reduction in torque than with the reactor starter.

Auto-transformer

Network

Ct1 Motor Ct2 Protection

Ct3 CT1 : Start Contactor CT2 : Main Contactor CT3 : Run Contactor N1

Motorpact 2007-TL

Load

1 0

Soft starter setting: torque control Network

Pro. Soft starter

Motor

Load

Reduced Voltage SoftStart motor starter (RVSS) SoftStart motor starter provides smooth, stepless acceleration and deceleration regardless of the load. This starting method lowers the starting current of the motor, reduces electrical stresses on the network and the motor. It reduces peak starting torque stresses on both the motor and mechanical load components, thereby providing longer service life and less downtime.

T1 = k.I1 Motorpact 2007-TL

Φ1

1 1

Soft starter setting: usual setting

Motorpact 2007-TL

1 2

FVNR & ATM descriptions Starting mode selection table Motor & Load requirements yes

- deceleration control ?

no

- the drive between motor and load is able to withstand the mechanical stress of a direct on line start yes

no

- constant torque with high starting torque as crushers, grinders, mixers ......

yes no

Network requirement - accepts full starting current? - accepts starting voltage drop? -accepts the starting reactive consumption power?

no

Investment Increase

yes no yes

no yes

- accepts the current oscillation during an open transition?

yes

VSD specific

no yes

- accepts the harmonics during the starting period

no yes

FVNR Motorpact 2007-TL

no

RVAT

RVSS 1 3

OTHER TYPE OF MOTORPACT PANEL 2S2W: 2 Speed 2 Winding full voltage non reversing asynchronous motor starter

2300

750

Motorpact 2007-TL

1 4

OTHER TYPE OF MOTORPACT PANEL 2S1W: 2 Speed 1 Winding full voltage non reversing asynchronous motor starter (Star delta starter) 2300

375

750

750

Motorpact 2007-TL

1 5

S3: Sequential Smart Start reduced voltage non reversing asynchronous motor starter

375

Motorpact 2007-TL

750

750

750

1 6

Dimension and weight

FVNR

Motorpact 2007-TL

RVSS

RVAT

1 7

Maximum motor ratings* 200 A Service Voltage 3.3 kV 5.5 kV 6.6 kV

kW (single fuse) 900 1500 1800

400 A Service Voltage 3.3 kV 5.5 kV 6.6 kV

kW (single fuse) 950 1600 1900

kW (double fuse) 1900 3000 3800

*Maximum Rating depend on full load current, locked rotor current and run up time of motor.

Motorpact 2007-TL

1 8

MotorpactTM MV motor starter  Case : 

DOL (FVNR) Starter connected to the load as follow:



Motor power : 750 kW



Service voltage : 3.3 kV



Freq : 50 Hz



Cos Q : 0.85



Motor efficiency : 0.96



Service factor : 100% (Load Factor: 1)



Starting current : 5 In



Starting time : 10 s



Number start per hours : 3

Fuse calculator

Questions? How many ampere motor current ? How many ampere rating of the contactor ? How many ampere rating of the fuse ?

Motorpact 2007-TL

1 9

MotorpactTM MV motor starter  Low voltage compartment (A)  Disconnector (B)

A

 HRC fuses (C)

E

 Vacuum contactor (D)  Complete motor protection with Sepam digital relay or others (E)

B C

D

Motorpact 2007-TL

2 0

Low cost of ownership

Easy to use  All controls located at the same convenient operator height 

Disconnector operator & pilot devices

 Disconnector position viewing window 

Visible isolation and “earthed” indication at eye-level



Optional back-light to view contact position

 Simple direct drive disconnector mechanism 

Ensures reliability and operator ease Viewing window

 Mechanical interlocks 

Motorpact 2007-TL

Prevent access to MV compartment when the unit is energised

2 1

Operating panel

Disconnector Closed

Motorpact 2007-TL

Disconnector Open

2 2

Disconnector  2 positions 

Closed and Earthed

 Positive operation 

Earthed position by spring operation



Interlocked to close – MV door closed and contactor open

 Visible contacts 

Back-light for easy viewing (optional)

 Supports top fuse holders

Motorpact 2007-TL

2 3

Voltage Presence Indication System (VPIS) (option)  Line side available for

Incoming cubicle(direct incoming)  Load side available at load terminal pads of motor starter

Motorpact 2007-TL

2 4

Low cost of ownership

Safety focus  Loss of service continuity 

category LSC2A

 Partition Class PI (Cable earthing switch required)

 Closed door operation (only if MV door close)

 Electrical and mechanical interlocks  Arc resistant type AFLR (optional)  Cable earthing switch (optional)  Voltage Presence Indication System (optional)

Motorpact 2007-TL

2 5

Low cost of ownership

Key Interlock • DiSCONNECTOR KEY LOCK : Lock open only, key captive Max 2 key lock • EARTH SWITCH KEY LOCK : Max 1 key lock Open or close lock

Disconnector key lock LDA Key lock

Motorpact 2007-TL

2 6

Busbar compartment  Busbars up to 3150 A 

Bar cooper bar (standard)



Tinned coated busbar (option)



Silver coated busbar (option)

 Encapsulated/heatshrink busbars are available as an option  Mounted and supported by the disconnector  Short time withstand

Motorpact 2007-TL



50 kA 2s



40 kA 3s



31.5 kA 3s



25 kA 3s

2 7

Busbar  Spacer (intermediate panel)

1250A

2000-2500A

Intermediate Insulator support

3000-3150A

 Main Busbar

Motorpact 2007-TL

2 8

Busboot

Intermediate bus boot • For rating : 630A,1250A,2500A, 3150A • Disconnector or Insulator

End bus boot • For rating : 630A,1250A,2500A, 3150A • Disconnector or Insulator

Motorpact 2007-TL

2 9

Main busbar jointing

Motorpact 2007-TL

3 0

Load compartment  Accessible only if contactor open and disconnector and cable are earthed  Comprises : 1.

HRC fuses

2.

vacuum contactor

3.

LPCT

4.

cable termination



optional : −

A. cable earthing switch with position viewing window



B. Control Power Transformer



C. Voltage Presence Indication System



D. Fuse blown indicator

C D A

4v 3

2

Motorpact 2007-TL

1

Bv

3 1

Load compartment - instrument transformers LPCT or CT mounted on contactor (fixed contact mould assembly)

Optional VT for protection and metering CPT Optional fused CPT (floor mounted)

Motorpact 2007-TL

3 2

Load compartment - MV fuses  HRC DIN fuses independently mounted 

Easy to inspect and maintain



Stricker blown fuse indicator



Supplier: Fusarc(Schneider), SIBA, Bussman,

 Fuses for motor or non-motor loads 

2 x 250 A Maximum

 Fuselogic Blown-fuse Indication (optional)

Motorpact 2007-TL



With viewing window in door



Blown-fuse fuse protection



2 Fuse blown aux contacts (SPDT)

3 3

Load compartment - contactor 

In : 200 A and 400 A



Withdrawable contactor truck



Patented finger design



Compact and lightweight 

20 kg - easy to handle



Independently mounted from power fuses



Contactor removed only for maintenance



Magnetically held or mechanically latched



Mechanically Close – Open indicator



Mechanical operating counter



Aux power supply AC or DC,with range: DC range: 100/125 – 240/250V and AC range:115/120 – 230/240 (+10% ~ -15%). Voltage selection by using dip switch inside the contactor

Mismatch location



AC or DC aux power supply: internal supplied by CPT(AC) or external (AC or DC)



Open release (for mech.latch) with DC supply only (48V, 125V and 250V). Additional tripping capasitor for AC aux supply (120VAC and 240VAC)



Capasitor Trip (optional) install when using mech. Latched contactor and internal supply from CPT.

Motorpact 2007-TL

3 4

Contactor aux Contact  Additional Aux contact

Motorpact 2007-TL

3 5

Contactor finger assembly  Patented finger design  Tests 

Temperature rise  400

A continuous

Mismatch/Blocking Contactor rating and type mismatch

Motorpact 2007-TL



200 A unlatch



200A latch



400A unlatch



400A latch

3 6

Contactor to outgoing terminal Cable :  200A  400A  Differentiation by means blocking truck/mismatch

Mismatch/Blocking Contactor rating and type mismatch 

200 A unlatch



200A latch



400A unlatch



400A latch

Motorpact 2007-TL

3 7

Load compartment - contactor

Standard Operation for Magnetically held contactor

Motorpact 2007-TL

3 8

Load compartment - contactor

Standard Operation for Mechanically latch contactor w/o CTD

Motorpact 2007-TL

3 9

Load compartment - contactor

Standard Operation for Mechanically latch contactor with CTD

Motorpact 2007-TL

4 0

TEST POSITION in MOTORPACT

External supply From CPT

Aux contact

1. Open Disconnetor switch 2. Supply aux power from external 3. Contactor still connected 4. Test the operation by control push button

Motorpact 2007-TL

K1 sepam

K1

4 1

Low voltage compartment  Ample space for : 





Sepam series 20/series 40 and series 80 digital relay or Multilin PowerLogic Power Meter or Circuit Monitor Control devices

 Isolated from other compartments (busbar and load compartments)  Integrated low voltage wireway (*)  simplifies

field wiring and installation of protection, control and communication

Motorpact 2007-TL

Customer connection

4 2

Motorpact aux contacts Disconnector switch aux contacts(Q1) : 4 SPDT , additional : 4 SPDT  Fuse blown /Fuse logic aux contacts(FU1) : 2SPDT  Earthing switch aux contacts (Q21): 4 SPDT Main contactor aux contacts (K1): 3NO+3NC, additonal : 3NO+3NC

Note: SPDT stand for single pole double trip

Motorpact 2007-TL

4 3

Motorpact contact resistance Descriptions Disconnection Swicth

Nominal values 450 micro Ohm

Busbar to the outgoing terminal (including DS, VCU and outgoing terminal)

50.000 micro Ohm (50 mili Ohm)

Vacuum Contactor upper pole to lower pole (without load cable)

< 200 micro Ohm

Motorpact 2007-TL

4 4

Load compartment - contactor

Connected position

Motorpact 2007-TL

Rail extended

Withdrawn position

4 5

Load compartment - cable termination  Front access or front and rear accessibility 

simple cable termination with rear access

 Full height cable pulling area  Load cable box allows for up to 1-240 mm2 or 2- 120mm² per phase  Formex® cover over cable terminations 

Motorpact 2007-TL

provides coverage at cable terminations

4 6

Typical cable termination

• Top and Bottom cable connection • Line connection and load connection Motorpact 2007-TL

4 7

Typical cable termination for single section and single controller

• Top and Bottom cable connection

Motorpact 2007-TL

4 8

Load compartment - cable earthing switch (option) Cable earthing switch

Formex® cover

Load cable termination

Motorpact 2007-TL

4 9

Top cable clamp assy

Top cable assy 1 or 2 cores cable Top cable assy 3 or 6 single core cable Motorpact 2007-TL

5 0

Lower cable clamp assy

Top cable assy 3 or 6 single core cable Motorpact 2007-TL

Lower cable assy 2 cores cable

5 1

Low cost of ownership

Predictive maintenance  Thermal diagnosis system (optional) 

Improved power availability −



Increased safety of electrical installation −





reduces maintenance costs no local human intervention.

Sensors installed in the sensitive areas − −



help to prevent damage to the installation (deterioration can lead to an internal arc)

Continuous monitoring of temperature rise −



detects abnormal temperature rise at the heart of power circuit

cable connexions top MV fuses holders

Activates 2 trip levels − −

pre-alarm threshold alarm threshold

Hold at the moment this offer

Motorpact 2007-TL

5 2

Temperature monitor module (DT1)

Provides continuous monitoring of joints in the equipment for predictive maintenance

Motorpact 2007-TL

5 3

POWER FACTOR CORRECTION CAPASITOR  3 phase capacitors without internal fuse  Possible for FVNR with 750mm width  Be careful for RVSS and S3

Motorpact 2007-TL

5 4

Enclosure - internal arc withstand (option)  Tested at KEMA 

following IEC 62271-200 standard



in all MV compartments

 Protection on all 4 sides by pressure venting to the top 

25 kA 1s



40 kA 0.5s



50 kA 0.25s

 Tunnel for ceiling below < 4m

With IP X1 Motorpact 2007-TL

5 5

Enclosure – IPX1 (option)

IPX1 : • Tunnel + roof • No top entry cable (standard)  non std for top entry Motorpact 2007-TL

5 6

Enclosure – main earth bar

Motorpact 2007-TL

5 7

Enclosure - internal arc withstand (option) 8-point latching door Heavy-duty vault style door handle

Frame

Door

Interlocking of hinge side

Motorpact 2007-TL

5 8

Enclosure - internal arc withstand Pressure relief flaps

(option)

Bolted rear panels

Top View

Interlocked rear panel to frame construction  Top and Bottom Access Panels  Easy Removal 

Motorpact 2007-TL

5 9

Joining the shipping splits

Motorpact 2007-TL

6 0

Sepam series 20, 40 and series 80  Protection functions       

50/51, 50N/51N, 46 49 R 38/49T 37, phase undercurrent 48/51LR, excessive starting time and locked rotor 66 starts per hour …

 Options     

Motorpact 2007-TL

User Machine Interfaces Logic I/Os Communication interfaces Temperature monitoring Analog output

6 1

current sensor (standard CT)

F

 One block sensor consits of 3 CTs  Low burden < 2.5VA (ratio <50A) and < 5VA (ratio>50A)  Protection class : 5P5 and 10P5  Metering class : 0.5, 1 and 3  Single depth and Double depth (<50A)  Max. 3 Block single CT or 1 Block Double CT + 1 Block Single CT

F

H2

 Secondary ratio : 1A or 5A  Primary ratio : 50A, 100A, 150A, 200A, 250A, 300A, 400A

 Freq: 50…400Hz Motorpact CT specification Motorpact 2007-TL

6 2

Low power current transducer (standard LPCT)  One sensor for all applications (50A ~ 400A)

100A / 22.5 mV 2500/1

0.5625 Ω

 High accuracy for protection and metering

Sepam Measuring and Protection

 Linear across a wide current range  Saturation value above 16 kA Accuracy 10.0% 5.0%

1.5% 0.75% 0.5% 5A Motorpact 2007-TL

20A

100A

800A

1000A 16000 A 6 3

Control Power Transformer (CPT)  Auxiliary Control Power supply :  External DC or AC supply  Internal AC supply by using CPT  CPT or VRCR(small burden:200VA)  Power CPT : 300VA, 500VA, 750VA and 2000VA  MV Primary fuse for CPT (Ph-Ph) : 0.63A, 1A, 2A and 3.15A.  Ferraz fuse.  Fuse holders are loacated below the contactor.  Secondary of CPT is protected by MCB  Primary Voltage : 2400V, 3300, 4160, 4800, 5000, 5500, 6000V, 6600V,6900V  Secondary voltage: 110/220V (dual voltage)  Freq: 50/60Hz CPT & VT Fuse holder

Motorpact 2007-TL

6 4

Voltage Transformer (VT)  Voltage for metering device or protection relay  Power Output: 50VA/Phase (100VA) at 30 deg. C. Accuracy : 2.4% at 15VA  Primary VT is protected by MV fuses  Secondary side is protected by MCB  Primary Voltage : 2400V, 3300, 4200, 4800, 5000, 5500, 6000V, 6600V,6900V(6300V under development)  Freq; 50/60Hz  Insulation level : 6.9kV (60kV BIL)  Secondary voltage: 110V

CPT & VT Fuse holder

Motorpact 2007-TL

6 5

Fuse tube  Fuse holder for primary fuse of CPT or/and VT  Long tube : (20mm x 190mm) for voltage > 5.5kV  Short tube : (20mm x 127mm) for voltage < 5.5kV  Thermal rating max : 5A .  Insulation level : 6.9kV (60kV BIL)  No special tools to remove or insert the MV fuse  Located below the contactor chassis

Motorpact 2007-TL

6 6

Ground Fault sensor  With Sepam relay  If solidly Grounded (low resistance)   ZCT 50/5A(AAF00309) + CSH 30 or   CSH 120 or 200  If High Resistance Grounded (un grounded system)

AAF00309 AAF00311 AAF00310 AAF00308

  CSH 280 (470/1 - AAF 00311) + Resistor for zero sensor

 Others relay (Without Sepam relay )  If solidly Grounded (low resistance)

CSH 120/200

  ZCT 50/5A  If High Resistance Grounded (un grounded system)   Zero seq. Sensor 2000/1 (AAF00310) or   Zero seq. Sensor 50/0.025 (AAF00308) Note: the above sensor is installed on the same place of the block CT Motorpact 2007-TL

6 7

Surge Arrestor  Distribution Class and Intermediate Class  distribution class : near the load (low kA)  Intermediate class : outgoing feeders with several downstream feeders (high kA)  Line side or Load side  Line side : install on the busbar side  Load side : install on the cable load side

 Rated Voltage : 3kV, 6kV and 9KV  6kV for service voltage : < 5kV  9 kV for service voltage : > 5kV

Motorpact 2007-TL

6 8

MV motor starter FVNR basic single line diagram Disconnector closed/ earthed

HRC fuses

Withdrawable vacuum contactor

Sepam series 20,40 or 80

LPCT

Cable earthing switch (optional) Motorpact 2007-TL

6 9

MV motor starter FVNR with options

CPT fuses

Control Power Transformer Second set of CT’s

Motorpact 2007-TL

7 0

Reduced Voltage Solid State (RVSS)

Motorpact Soft Start™  Ranges    

2300V up to 2300kw 3300V up to 3400kw 4160V up to 4300kw 6900V up to 7100kw

 50 / 60 Hz  Full Digital Control

Motorpact 2007-TL

7 1

Reduced Voltage Solid State (RVSS)

Motorpact Soft Start™  Advanced Motor Protection 

Options: – Ground Fault – RTD modules

 Heavy Duty Silicon Control Rectifier (SCR) stack  Arc Resistant

Motorpact 2007-TL

7 2

Motorpact RVSS - HMI  Full digital control  

LCD operator interface Non-Volatile memory

 Digital sequencer 

Ensures proper contactor sequence

 Fiber-Optic isolation 

between digital controller and power module/SCR

 Metering functions     

Motorpact 2007-TL

Voltage Current Power Factor KVAR kW

7 3

Motorpact Soft Start ™ Controller Applications

Motorpact 2007-TL

 Pumps

 Ball Mills

 Blowers

 Rod Mills

 Compressors

 Conveyors

 Chillers

 Natural Gas Compressors

 Fans

 Centrifugal Blowers

 Chippers

 Other Applications

7 4

Motorpact SoftStart™ 6 Goals Beyond On-Off      

Motorpact 2007-TL

Protect the Motor and Load Reduce Mechanical Stress Limit Starting Current Reduce Stress on the Electrical Grid Reduce Electrical System Disturbance Provide Soft Stopping 

Meter and Record



Communicate

7 5

Motorpact SoftStart™ Benefits  Eliminate Torque Shock Damage  Prevent belt slipping, coupling damage  Increases motor AND drive train reliability  Keep Starting kVA to a Minimum  Maintain future flexibility  Soft Start and Soft Stop Pumps  Reduce hydraulic / mechanical problems  Low Cost Ratio vs. MV VFDs 

Motorpact 2007-TL

Can be considered as an alternate in some cases

7 6

Motorpact SoftStart™ Heavy Duty Ratings  500% for 60 Seconds 

Nearest competitor is 500% for 30 sec.

 600% for 30+ Seconds 

Capable of Class 30 “Mill Duty” motors

 200% for up to 2 Minutes 

Allows for long accel times

 Tested at 50˚C 

Motorpact 2007-TL

Most others tested at 40˚ C

7 7

Motorpact SoftStart™ Compartment 2

1

Compartment 1 Compartment 2

Line disconnector Isolates motor starter from power supply

1 2 2

4

Vacuum contactor Provides start sequence to SCR stack (in main contactor cubicle)

5 3

SCR stack

5

Provides voltage ramp and advanced protection features

3

4

4

By-pass contactor By-passes the SCR when motor is at full speed

5

3

LV control Control and HMI of motor starter with power system

Motorpact 2007-TL

7 8

Motorpact SoftStart™

Designed for Safety  High MV to LV Electrical Isolation 

Magnetic isolation of Gate Pulses



Fiber optic isolation for firing control and signal interfaces

 Door Interlocking  Isolated LV Compartment

Motorpact 2007-TL

7 9

Motorpact SoftStart™ Electrical Isolation Diagram Magnetic Isolation

Gate Drive

MTR

Motorpact 2007-TL

= MV = 120V = 28V = Fiber Optic

Sensing Systems

Optical Isolation

LV Controls

8 0

Reduced voltage auto-transformer motor starter (RVAT) B

A

 Line current lower than motor current  Provides high torque per A of line current  Medium or heavy duty  3 Contactors Main(1), Run(2), Start(3)  Includes surge protection  Provides switching transient protection for autotransformer  50, 65, and 80 % Taps (4)  Closed transition from start to run  1125 mm or 1500 mm width.  Internal arc withstand  Auto Transformer capacity (50Hz)     

Motorpact 2007-TL

<3.6kV : 1100kW 7.2kV : 1550kW 3 starting at cold (2 consecutive after running) Starting time 15 sec Insulation Class F

C

D E

H I

3

J K

F

L

G

M

8 1

Reduced voltage auto-transformer motor starter

1 MAIN CONTACTOR

2 RUN CONTACTOR

4 AUTO TRANSFORMER

3 START CONTACTOR

Motorpact 2007-TL

8 2

(A)

(A)

(C)

(C)

(B)

(C)

(B)

M

First stage : C is open A and B are closed B must be closed before A.

RVAT

(A)

(B)

M

Second stage : A remains closed C remains open and B is opened

M

Third stage : A remains closed B remains open and C is closed

The current path is shown in red. It is obvious that the motor is always supplied even during the second stage, when B is open.

First stage : the motor is starting with reduced voltage. Second stage: the motor is running in series with part of the autotransformer winding. Third stage: the motor runs at full voltage. Motorpact 2007-TL

8 3

Incoming LV cables from below, cubicle by cubicle

1

2

3

Motorpact 2007-TL

4

8 4

Incoming LV cables from top, cubicle by cubicle

Motorpact 2007-TL

8 5

Civil engineering Lined up with MCset switchgear Incomer - Bus sectioning - IncomerMC set

Motorpact 2007-TL

interface Motorpact

8 6

Civil engineering stand-alone motor control with RVSS SoftStartTM motor starter

Incoming cable and metering

3150 A Busbar

Motorpact 2007-TL

Front

8 7

Motorpact™ MV motor starters Smart choice for MV- MCC application Incoming cable and metering

Front

Motorpact 2007-TL

8 8

Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity

Loss of Service Continuity Class (LSC) • Architecture based on “safe compartment access”

Several levels of service continuity during maintenance

LSC 2B Maintainability of defined parts with no need of cable disconnection (separate cable compartment)

• Safe access to compartment • With power flow in busbar and the other units • MV Cable in separate compartment • Cable of unit under maintenance can remain energized

LSC 2A • Safe access to compartment • With power flow in busbar and the other units • MV Cables must be earthed

Maintainability of one functional unit allowing normal service of the remaining units of the switchboard (busbar in a separate compartment)

MOTORPACT MOTORPACT

LSC 1 • Metal enclosed not of LSC2 class

Motorpact 2007-TL

8 9

Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity

Partition Class I or M • Classification based on electrical field presence in safe access compartment

Partition Class PM Personnel comfort during maintenance

3.110 Shutter Part of metal-enclosed switchgear and controlgear that can be moved from a position where it permits contacts of a removable part, or moving contact of a disconnector to engage fixed contacts, to a position where it becomes a part of the enclosure or partition shielding the fixed contacts.

• All partitions and shutters of safe access compartment shall be metallic with some current carrying capacity

Partition Class PI • Partitions or shutters may be partially or totally of Definition insulating material

“Metal enclosed” compliant during maintenance Applicable mainly to withdrawable system

Electrical and mechanical safety according to IEC 60466 or 60137

Motorpact Motorpact Motorpact 2007-TL

9 0

Motorpact to IEC 62271-200 Fully enclosed in metal enclosure and having current carrying capacity

Internal Arc Class IAC • Classification based on consequences of internal arc on personnel safety

Accessibility Types • A : restricted to authorized personnel only. • B : unrestricted, including general public.

IAC classified Personnel safety in case • No projection of parts of internal arc towards accessible sides • No ignition of indicators

Motorpact complies with AFLR type

Safety in case of internal fault during service condition Demonstrated by type tests (completely defined by the standard)

IAC not classified • No tests performed to assess behavior of enclosure under arc conditions

• Enclosure Identification code: F - for Front side • L L - for Lateral side R - for Rear side

Motorpact 2007-TL

9 1

Motorpact 2007-TL

9 2

Motorpact 2007-TL

9 3

Motorpact 2007-TL

9 4

Motorpact 2007-TL

9 5

Motorpact 2007-TL

9 6

Motorpact 2007-TL

9 7

Motorpact 2007-TL

9 8

Motorpact 2007-TL

9 9

Motorpact 2007-TL

1 0 0

Motorpact 2007-TL

1 0 1

Motorpact 2007-TL

1 0 2

Motorpact 2007-TL

1 0 3

Motorpact 2007-TL

1 0 4

Motorpact 2007-TL

1 0 5

Motorpact 2007-TL

1 0 6

Motorpact 2007-TL

1 0 7

Motorpact 2007-TL

1 0 8

Motorpact 2007-TL

1 0 9

Motorpact 2007-TL

1 1 0

Motorpact 2007-TL

1 1 1

Motorpact 2007-TL

1 1 2

Motorpact 2007-TL

1 1 3

Redundant S3 Alternate Configuration

 One SoftStart used to start all motors  Second SoftStart used as back up in case first fails.  SoftStart has incoming and outgoing contactors for isolation

Motorpact 2007-TL

1 1 4