O&m Fire Fighting

  • Uploaded by: Rajkumar Prasad
  • 0
  • 0
  • February 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View O&m Fire Fighting as PDF for free.

More details

  • Words: 5,387
  • Pages: 38
Loading documents preview...
FEC

OPERATION AND MAINTENANCE MANUAL

CONTENTS

1. INTRODUCTION 2. PREFACE 3. REFERENCE DRAWINGS 4. SYSTEM DESCRIPTION 5. SYSTEM OPERATION 6. CONTROL PHILOSOPHY 7. COMMISSIONING PROCEDURE 8. ROUTINE TESTING 9. MAINTENANCE CHART 10.

CATALOGUES

FEC

OPERATION AND MAINTENANCE MANUAL

INTRODUCTION

FEC

OPERATION AND MAINTENANCE MANUAL

1. INTRODUCTION “Fire is an external sign of chemical action, usually the combination of Carbon and Hydrogen with Oxygen, resulting in the release of heat energy”. Fire is a necessary evil. When fire is under human’s control, it is a great asset. If human is under fire’s control, fire is a devastating foe. If fire occurs, how best can it be dealt with to extinguish? Firstly, by adopting the right mental attitude. With knowledge and ability, a fire fighter can attack a fire in the right manner and, by knowing its weakness, extinguish it in a short time. Without knowledge and ability, the fire will find out their weakness. For fire is a foe, against which no liberties can be taken. Fire should not be thought of as an intimate object. Fire, which starts unseen as a small flicker of flame, may grow at such a pace that it can quickly get out of hand. Once found, it must be extinguished with all the speed and means available or it will destroy those who seek to restrain it. Fire, when apparently extinguished, some untrained person may assume that because the flames have gone, the danger is passed, but it may not be so. Secondly, by considering each fire as an individual occurrence, the correct action in each case will depend on the position of the fire, the combustibles involved and the combustibles, which are in danger of becoming involved. There is no hard and fast rule; one who has the knowledge and training can only assert the correct action. Thirdly, by ensuring that properly maintained appliances are available for personnel to use and that all fire fighting, fire detection and alarm systems are in fully operational order. With the rapid growth of the industries and expansion of cities, fire hazards have also increased. Through considerable attention is being paid by the authorities concerned towards fire prevention and fire protection, a possible outbreak of fire cannot be detected and forestalled without an Automatic Fire Alarm System. In the absence of such a system, it is also not possible to ensure (a) an immediate transmission of call on the fire brigade in the event of an out break of fire in any premises during the closed hours, and (b) an effective control of a fire in the incipient stage, with the help of first aid and fire appliances. An Automatic Fire Alarm and Extinguishing System function through different type of detectors distributed in the premises to be protected, which causes the alarm to be actuated automatically, whenever there is possibility of a fire breaking out or immediately upon the outbreak of fire. The system helps evacuation of the premises, and extinguishes the fire as quickly as possible.

FEC

OPERATION AND MAINTENANCE MANUAL

PREFACE

FEC

OPERATION AND MAINTENANCE MANUAL

2. PREFACE

The purpose of this Manual is to appraise the user on the operation and maintenance of Fire Protection System, designed, supervised and commissioned by FEC ENGINEERING PROJECTS PVT. LTD., New Delhi for Sugar & 30 MW Cogen Plant at M/s Chadha Sugars Pvt. Ltd., Vill. Malasia, The. Dhanaura, Distt. J. P. Nagar, U.P. The Fire Protection System consists of Fire Hydrant System and Fire Alarm System. All the systems are designed and installed as per the specification and also as per rules and regulations of Tariff Advisory Committee. Needless to say, that the efficiency and effectiveness of the system largely depends upon proper maintenance of the system and regular training of the personnel operating the system. Therefore, the system shall be operated and maintained by trained personnel as per guidelines given in this manual.

FEC

OPERATION AND MAINTENANCE MANUAL

REFERENCE DRAWINGS

FEC

OPERATION AND MAINTENANCE MANUAL

3. REFERENCE DRAWINGS

3.1 Fire Protection System.

Sl No

DRAWING NO.

3.1.1 3.1.2

FEC/CSL/01 Rev. 2 FEC/CSL/05 Rev. 1

DRAWING TITLE Layout of Fire Hydrant System (As Built) Schematic Drawing of Fire Pump House

3.2 Fire Detection and Alarm System

SI No

DRAWING NO

DRAWING TITLE

3.2.1

FEC/CSL/02 Rev. 2

Fire Alarm/Detection System for MCC Room (As Built)

3.2.2

FEC/CSL/03 Rev. 2

Fire Alarm/Detection System for Control Room (As Built)

3.2.3

FEC/CSL/04 Rev. 0

Fire Detection and Alarm System for PMCC Room (As Built)

FEC

OPERATION AND MAINTENANCE MANUAL

SYSTEM DESCRIPTION

FEC

OPERATION AND MAINTENANCE MANUAL

4 SCOPE: The following systems are provided for the plant: (a) Fire Hydrant System as per the attached Annexure. (b) Fire Detection and Alarm System for the areas under as per attached Annexure. (c) Portable Fire Extinguishers for the protected areas. 4.1 CODES AND STANDARDS: Proposed Fire Fighting System will be inline with TAC Norms. In general the following codes are followed to design the systems. 1. TAC – Hydrant System. 2. IS: 2189 – Fire Detection and Alarm system. 3. IS: 2190/TAC-Portable and mobile fire extinguishers. 4.2 DESIGN BASIS: 4.2.1 GENERAL: As per T.A.C Hydrant Manual table clause 7.2.2, ‘Power Plants’ are classified as ‘ORDINARY HAZARD OCCUPANCIES’. 4.2.2 FIRE HYDRANT SYSTEM: Following systems will be provided for the plant: (a) (b)

Yard Hydrant System for the plant consisting of single headed hydrant valves & water monitors (32 NB bore). Fire Escape Hydrant System consisting of fire escape hydrant valves for upper floors of storied blocks (Refer Annexure-A for the areas of protection)

4.2.5 PORTABLE FIRE EXTINGUISHERS: Portable/Mobile type fire extinguishers shall be provided for the areas under. In general the extinguishers shall be provided based on the rules specified in TAC hydrant manual / IS- 2190. 4.2.4 FIRE DETECTION AND ALARM SYSTEM: Fire detection and alarm system is provided for the areas mentioned in the Annexure. Proposed Fire Detection and Alarm System shall be Conventional type with detection devices such as photoelectric type smoke detectors, and manual call points. Detectors shall be of conventional type and spacing of detectors shall be as per IS 2189. Photoelectric Smoke Detectors are mounted inside the protected premises to initiate the Fire Alarm System. Incase of any Detectors being actuated a signal is transmitted to the Fire Alarm Panel which in turn actuate an Audio / Visual alarm in the Control Panel and simultaneously the External hooters located at the various places will be sounded.

FEC

OPERATION AND MAINTENANCE MANUAL

Entire FDA system is designed as per TAC regulations and IS 2189.

4.3.2 FIRE PUMP Starting & stopping of jockey & electric driven pumps are controlled through the pressure switches fitted in the hydrant and spray system headers. 4.3.3 HYDRANT SYSTEM The Fire Hydrant System shall consist of a network of pipe underground & overground which feeds pressurized water to no. of hydrant valves (indoor as well as outdoor) & water monitors. The Fire Hydrant System shall cover plant area with network of piping comprising of 150 NB, 100 NB & 80 NB pipe sizes shown in the enclosed layout drawing for fire hydrant system. The location of hydrant points in the plant is shown on the enclosed laying drawing. The fire water main network shall be maintained pressurized at all times to receive pressurized water at every fire hydrant system outlet within the plant. Pressurized water is being discharged in the pipeline with the help of two nos. 171 m3/hr. at 70 MWC head pump sets (one no. main electric driven pump + one no. stand by electric driven pump). One no. electric driven jockey pump of capacity 10.8 m3/hr. at 70 MWC head is provided in the system for keeping the system pressurized all the times. When the water requirement exceeds the quantity supplied by the jockey pump, fire main electric pump shall come into operation discharging water into the piping system, automatically due to higher pressure drop in the header. The pipe network is designed in such a way that any of hydrant outlet in the entire system delivery pressure shall not be less than 3.5 kg/cm2. The hydrant system in the yard shall be furnished with external hydrants, positioned app. one meter above the finished ground level, in accordance with statutory regulation for effective fire fighting. Near each external hydrant a M. S. hose box with two nos. 15 m fire hoses along with one no. branch pipe shall be provided. The network ring main is provided with isolation butterfly valves at strategic locations so that it is possible to carry out pipe maintenance in every run without interrupting the supply for few hours. When any of the hydrant valves in the field is opened, the water pressure in the corresponding water pipe lines shall fall rapidly, consequently the main fire water pump shall come into operation by pressure actuated switch linked to the starter of the respective pump through pump control panel. Pumps can be started manually in case of emergency. However pumps can be stopped only manually from the control panel as well.

FEC

OPERATION AND MAINTENANCE MANUAL

4.3.3 FIRE DETECTION AND ALARM SYSTEM All type of Detectors, Manual Call Points & Hooters are connected to the panel through Control cables. Panel scans all detectors and devices and gets digital information from the devices about their status. If any one detector or MCP senses fire, then it will be known to the panel while scanning. After getting this information panel will give audible output through internal sounder and also through field hooters in the corresponding area. It also gives visual indication through “Fire LED” Display”. The LED display will give the detailed information about the Area/Zone, in which the detector is placed. Also it will actuate the corresponding tripping contacts of ventilation fans, HVAC contacts. Similar kind of arrangement is made for Manual Call point.. Panel operator should silence the inbuilt sounder by pressing “Acknowledge” push button and note the details in the display. Based on the details one has to identify the fire and extinguish the same. After extinguishing the fire, the field hooters should be silenced through “Alarm Silence” Push Button and reset the panel through “Reset” push button. In case any manual call point has been actuated, replace the break glass before resetting the panel. Otherwise the alarm condition will come again within few seconds.

==========

FEC

OPERATION AND MAINTENANCE MANUAL

4.4 ANNEXURE Scope of Supply of Equipments 4.4.1 Fire Hydrant System Sl.No 1 2 3 4 5 6 7 8

Description Bagasse Yard area Compressor Room Control Building Transformer area Switchyard Area TG Building Boiler Area ESP Area

Yard Hydrants        

Fire Escape Hydrants   

4.4.4 Fire Detection and Alarm System Sl.No

Fire Detection and Alarm System Control Room Fire Detection and Alarm System For MCC Room Fire Detection and Alarm System For PMCC Room

1 2 3

3.4.5 1.

Description

Portable Extinguishers

Please refer drawing no. FEC/CSL/01 Rev.002 .

Type of Detectors Smoke Detectors (Optical Type) Smoke Detectors ( Optical Type) Smoke Detectors (Optical Type)

Total No. of Detectors 14 Nos. 10 Nos 12 Nos.

FEC

OPERATION AND MAINTENANCE MANUAL

SYSTEM OPERATION

FEC

OPERATION AND MAINTENANCE MANUAL

5 SYSTEM OPERATION This section will explain how to operate the erected fire protection and detection system incase of a fire situation. As explained earlier in this manual, fire extinguishing will greatly depend on which the system is brought into action. Hence it is essential that the persons going to use the system are well aware about the following procedure. 5.1 HYDRANT SYSTEM 5.1.1 Operation of Hydrant valve Open the nearest hose box with the key provided. If the key is missing then break the glass door. Take the hose with coupling and branch pipes with nozzle from the hose box. Connect two hoses using hose coupling. Connect the branch pipe with nozzle to one end of hose having female coupling. Connect the other end of hose with male coupling to the hydrant valve. Hold the hosepipe with branch pipe and nozzle properly. Open the hydrant valve gradually. Play the water jet towards the seat of fire. 5.1.2 Operation of Water Monitor Release the lock nut for vertical movement of the monitor nozzle. Adjust the jet towards the fire vertically and lock it. Release the horizontal movement lock nut if required. Adjust the jet towards the fire horizontally and lock it. Open the Isolation valve provided in the monitor gradually.

FEC

OPERATION AND MAINTENANCE MANUAL

After the valve is opened, if the water is not playing on the seat of fire, adjust the horizontal and vertical locks to direct the water towards the seat of fire. 5.1.3 Operation of Fire Escape Hydrant Repeat the procedure as explained for hydrant valve.

5.3 FIRE DETECTION AND ALARM SYSTEM As the system is totally automatic in operation, manual intervention to operate the system is not required and only the system has to be reset for normal operation after a fire condition. Fire detection and alarm system operation can be classified in to two types.  

Automatic operation. Manual operation.

5.3.1 Automatic operation In Automatic Fire Alarm System, different types of Fire Detectors located at the various locations are connected to the Main Fire Alarm Panel through cables. During fire condition, the detectors will sense the fire and report it to the panel and does the necessary alarm (in panel and the field). Fore more details refer 4.3.7 5.3.2 Manual Operation In Manual Operation, during ‘fire’, the Manual Call Point’s "BREAK GLASS" has to be broken to initiate the alarm on the panel and the panel will do all the alarm, annunciation and controls. To reset the system for normal operation, "BREAK GLASS” of the Manual Call Point has to be replaced and the panel has to be reset through “Reset” Push Button. Purpose of this manual call points is to inform the panel about the fire condition when the fire is detected manually. Just by pressing the manual call point, the signal can be transferred to the panel. All the other operations of the panel shall be same as of automatic operation. When the manual call point is pressed the panel display unit will display the exact location of manual call point, so that the operator can identify the location and can take appropriate action to extinguish the fire. 5.4 PUMPS AND ACCESSORIES 5.4.1 Operation of Pumps for Hydrant System In the event of fire, when any hydrant valve is opened in any part of the network, the resultant fall in header pressure will bring the electric motor driven hydrant pump in to operation automatically to supply water to the hydrant system. Failure to start pump on demand will result in further fall in header pressure or if the header pressure still falls, even when pump is running, then the signal from pressure switch will open the motor actuated valve & simultaneously start the stand-by

FEC

OPERATION AND MAINTENANCE MANUAL

diesel engine driven pump automatically. Thus, an automatic sequential starting of pumps is maintained. 5.4.3 Manual operation Pumps can be started manually in case of emergency by pressing the push button in the control cum annunciation panel. However, pumps can be stopped only manually.

CONTROL PHILOSOPHY

FEC

OPERATION AND MAINTENANCE MANUAL

Control Philosophy There are three pumps in the system. 1.

Jockey Pump

1 No.

2.

Main Electric Driven Pump

1 No.

3.

Stand by Electric Driven Pump

1 No.

Jockey Pump (P1) 2

2

Jockey Pump auto starts when pressure drops at 5.4 kg/cm & stops when pressure reaches at 7.5 kg/cm . Electric Driven Pump (P2 - P3) 2

One Electric Driven Pump auto starts when pressure drops at 3.8 kg/cm & stops when pressure reaches at 7.0 2

kg/cm . One pump shall remain as stand by. In all conditions only two pumps will be operating ( One Jockey Pump & One Electric Pump) Start

Stop

P1 (Jockey Pump)

5.4 kg/cm

2

7.5 kg/cm

2

P2 (Electric Driven Main Pump)

3.8 kg/cm

2

7.5 kg/cm

2

P3 (Electric Driven Stand by Pump)

3.8 kg/cm

2

7.5 kg/cm

2

-

The jockey pump will restart for 10-15 seconds after 50 minutes.

FEC

OPERATION AND MAINTENANCE MANUAL

COMMISSIONING PROCEDURE

FEC

OPERATION AND MAINTENANCE MANUAL

PRE COMMISSIONING CHECK

Pump House Equipments MECHANICAL

Check for Tightness of the Pipe connections & Flushed the piping Properly Check for the Correct direction of Non Return valves in the Discharge side of the Pumps Check for the Supports & Clamps for the pipes Check for the Locations and Range of the Instruments Check for the setting of pressure switches Check for the Coupling Guards of rotating equipment are in position Check for the minimum level of the Fuel in the Day Tanks Check for the Tightness of all Fuel piping between tank and Diesel Engine Fuel inlet and outlet Check for the Proper alignment of the Pump & prime mover Check for the Oil /Greasing as per recommendation of the manufacturer Check the Direction of Driver corresponding to the Direction of the Pump ELECTRICAL

Check the Cable Terminations in the Motors and panels Check the Direction of Rotation of Motors & Engine with Corresponding pumps Check the Control cable Terminations in the panel and Instruments Check the Interlocking arrangement of pumps Check for the availability of Keys for Panels Check for the proper Earthling of the Panels & Equipment in side the Pump Room

Hydrant System Check the Tightness of all flanged joints of Isolation Valves and Hydrant Valves Check for the Smooth operation of Valves Check for the Supports of above ground pipes Check for the operation of Spring locks of hydrants and Hoses Check for the Availability of Hose & Branch pipe in the boxes near to the hydrants Check for the Availability of keys for Hose boxes

FEC

OPERATION AND MAINTENANCE MANUAL

Fire Detection and Alarm system Check the Tightness of all Devices, MCPs, and Detectors & Junction Boxes in the Field and in the Buildings. Check for the Terminations in all the Panels and Instruments Check for the availability /Provision of Power supply to the Panel Check for the connection of the panel to the battery Check for the Location identification in the panel with the corresponding Detector Check for the proper operation of control modules and Monitor modules Check for the neatness of wiring and termination in the panels Check for the proper Earthling of the Panels Ensure the cabling is free from earth /Short circuit /open faults Ensure the Devices are connected properly Ensure the mains & battery is connected to the panel Ensure the panels are earthed properly Ensure the addresses given in the panel is correct corresponding to the address given to the devices Ensure the internal and external wiring is dressed and terminated properly. Ensure all Junction Boxes are fixed and terminated properly.

COMMISSIONING PROCEDURE PUMPS

The pumps will be commissioned one by one adopting following procedures 1) Switch off the out going switches for all pumps 2) Close the delivery Isolation Valve of all the pumps

Commissioning of Jockey Pump 1) Kept open the Recirculation line to the Tank 2) Put the Auto-Manual Selector switch in “Manual Mode” 3) Put the Main switch for the Jockey Pump ON Open the Isolation valve in the Delivery header of Jockey pump-1& Recirculation Valve to the Tank Gradually once the prime mover pick up its full speed

FEC

OPERATION AND MAINTENANCE MANUAL

4) Start & run the Jockey pump for a minute by pressing the Start Push button for checking Vibration, Direction of rotation and undo Noise etc. 5) Re start the Jockey Pump and allow to run for 5- 10 minutes 6) Check the water Pressure at the Pressure Gauge for gradual increase in pressure 7) Close the Recirculation line to hold the pressure in the system. 8) Stop the Jockey Pump by pressing the Stop Push button in the local control Panel 9) Put the Auto Manual Switch to “Auto Mode” the Jockey pump shall start Automatically .If not, open the recirculation line to drain the system pressure. 10) Close the Recirculation Valve to hold the system pressure 11) The Pump shall Stop Automatically once the Pressure at the preset pressure 7.0 Bars. 12) Switch “OFF” the outgoing feeder in the panel for Jockey pump

Commissioning of Main Pumps 1) Kept open the Recirculation line to the Tank 2) Put the Auto-Manual Selector switch in “Manual Mode” 3) Put the Main switch for the Main Pump “ON “ 4) Open the Isolation valve in the Delivery header & Recirculation Valve to the Tank 5) Start & Run the Main Pump for a minute by pressing the Start Push button for checking Vibration, Direction of rotation and undo Noise etc. 6) Re start the Main Pump and allow to run for 10 -15 minutes 7) Check the Pressure at the Pressure Gauge for gradual increase 8) Close the Recirculation line to hold the pressure in the system. 9) Stop the Main Pump by pressing the Stop Push button in the local control Panel 10) Put the Auto Manual Switch to “Auto Mode” the Jockey pump shall start Automatically .If not, open the recirculation line to drain the system pressure. 11) Close the Recirculation Valve to hold the system pressure 12) Stop The Pump Manually once the Pressure attained the preset . 13) Switch “OFF” the outgoing feeder in the panel for Main pump Repeat the procedure for commissioning of Stand by pump

FEC

OPERATION AND MAINTENANCE MANUAL

COMMISSIONING OF HYDRANT SYSTEM

1)

Kept open all the Isolation Valves in the Hydrant system and External Hydrants Valves Except the Interconnecting Valve in the Delivery header

2)

Start any one of the Main Hydrant pump manually and allow water to flow through the hydrants till clear water start to flow.

3)

Close the hydrant Valves except 4 hydrants at remotest points and allow to remove the air trapped in the U/G line

4)

Open the top most Landing Valves in each risers to release the air and dirty water from the riser.

5)

Close the landing valves once the clear water starts to flow through the landing Valve

6)

Kept open the isolation Valve in the Upstream side of the Air release valve on all wet risers.

7)

Check for Isolation valves for any Gland leakages , fix it by tightening the Gland packings adequately.

FIRE DETECTION AND ALARM SYSTEM. The entire installation shall be tested to ensure that it operates satisfactorily, and that •

All Detectors and Manual Call Points function correctly.



All ancillary equipment’s functions correctly.

Smoke Detectors / Heat Detectors: 1. Create a Smoke / Heat by using any reliable source near to the smoke / heat detector. 2. After sometime, observe the alarm in the corresponding panel 3. The fire signal will be transferred to Main Fire Alarm Panel. 4. Observe the Area name of the respected area of fire. 5. Observe the sound of the corresponding Hooter. 6. By pressing ‘Alarm Silenced Push button’ in the panel, the respected area hooter will be silenced. 7. After completion of testing, press “Reset:” Push Button to restore the panel to normal Condition.

FEC

OPERATION AND MAINTENANCE MANUAL

6.3.2 Manual Call Point:

1. Activate the Manual Call point By Removing the Manual Call Point glass.or By pulling the lever 2. Observe the alarm in the main Fire Alarm Panel 3. The fire signal will be transferred to main Fire Alarm Panel 4. Observe the Area name of the respected area of fire./Operation of MCP 5. Observe the sound of the corresponding Hooter. 6. By pressing “Alarm Silence” Push button in the panel, the respected area hooter will be 7. After completion of testing, press, “Reset Push Button” to restore the panel to normal ==========

silenced. Condition.

FEC

OPERATION AND MAINTENANCE MANUAL

ROUTINE TESTING

FEC

OPERATION AND MAINTENANCE MANUAL

7 ROUTINE TESTING Even though the system is well designed and well installed, it is very much essential that the system is tested in a routine and maintained properly for getting the system to service when it is badly needed. It is desired to operate the system in automatic mode, as its need in an event of fire cannot be neglected. However, manual starting should not be ignored. To maintain both automatic and manual operating to keep intact, routine testing is vital. 7.1 PUMPING Automatic starting sequence of the pumps can be checked by periodically in the following manner. Open the nearest hydrant valve slowly and checkup the pressure at which the jockey pump starts. After five minutes close the hydrant valve completely and see whether the jockey pump stops automatically at 7.0 bar. Keep the jockey pump in manual mode and open the nearest hydrant valve fully. Check up the pressure at which the electrical driven main pump starts. After that close the hydrant valve and stop the pump manually. Repeat above by keeping jockey pump and main pump in manual mode and check the pressure at which the diesel engine driven standby pump starts. Engine shall also be manually started with batteries on line, once in a week to confirm the healthy condition of the battery. It shall be run on load for about 10 minutes. 7.2 HYDRANT SYSTEM It is recommended to carryout “wet-drill” once in a week at different hydrant points and monitor. This will have a check on all sections and will prevent settling of mud at valve seats and in pipes. It will also confirm that sectionalizing sluice valves are all open. 7.4 FIRE DETECTION AND ALARM SYSTEM Healthiness of the detector shall be checked visually by seeing the LED glowing. Every week the battery should be checked for the charge availability. Daily, Panel display shall be checked for any event happenings. If there is any fault the same should be attended immediately to rectify the same. 7.6 EXTINGUISHERS

FEC

OPERATION AND MAINTENANCE MANUAL

Check the pressure gauge in the extinguishers visually. When the pressure is less than the stipulated value send for refilling. Check the extinguishers are not misplaced and kept in proper place for ready to use.

MAINTENANCE CHART

FEC

OPERATION AND MAINTENANCE MANUAL

8 MAINTENANCE PROCEDURE The system requires a simple day-to-day maintenance. Before taking up maintenance work, notify the authorities that the system is undergoing maintenance. All persons who might receive an alarm signal should be notified in advance to avoid unnecessary response.

8.1 Maintenance of Fire Extinguishers

8.1.1 Routine maintenance 8.1.1.1 8.1.1.2 8.1.1.3 8.1.1.4 8.1.1.5 8.1.1.6 8.1.1.7 8.1.1.8 8.1.1.9 8.1.1.10 8.1.1.11 8.1.1.12

Check all moving parts are Working properly Check the nozzle is not obstructed Check for leakage of extinguishing medium from the glands and nozzle Polish brass parts Clean superficially Weigh gas cartridges, if there loss of more than 10% of original mass, send it for clogging Grease the cap threads and plunger Check the vent holes for clogging Check the sealing washer & replace if necessary Operation test- half the number of water type Extinguishers Operation test- half the number of dry powder Extinguishers Examine the inside surface of the cylinder for condition of plating, rusting.

Weekly Weekly Weekly Weekly Weekly Monthly Monthly Monthly Monthly Annually Annually Annually

8.1.2 Refilling schedule 8.1.2.3

CO2 Fire Extinguishers

As and when due

FEC

OPERATION AND MAINTENANCE MANUAL 8.1.2.4

Dry chemical type (Gas Cartridges)

As and when due

8.1.3 Schedule of hydraulic pressure testing of extinguishers SI.No. 8.1.3.3 8.1.3.4

Type of Extinguisher

Test interval

Test pressure

Duration

3 Years 3 Years

17.5 kg/cm2 25 kg/cm2

2.5 Minutes 2.5 Minutes

CO2 type Dry chemical type

Note: Extinguishers found leaking (or) distorted in the Hydraulic pressure test shall be rejected and discarded. Under no circumstances such extinguishers be welded / repaid and re used.

8.2 Maintenance of Reservoir 8.2.1 Routine Maintenance 8.2.1.1 8.2.1.2 8.2.1.3 8.2.1.4

Level checking Cleaning Expansion joints (if any) Interior of steel tanks (if applicable)

Weekly Once in 2 years Annually Once in 3 years

8.3 Maintenance of Pump 8.3.1 Routine Maintenance 8.3.1.1 8.3.1.2 8.3.1.3 8.3.1.4 8.3.1.5 8.3.1.6 8.3.1.7

Running test Flow test Lubrication Gland packing Pump coupling alignment overhauling Accuracy of pressure gauges

Daily 5 minutes Annually Quarterly weekly Annually Once in 2 years. Annually

8.3.2 Electrical Maintenance 8.3.2.1 8.3.2.2

Exercise isolating switch & circuit breaker Operated manual starting means (Electrical)

Monthly Annually

FEC

OPERATION AND MAINTENANCE MANUAL 8.3.2.3 8.3.2.4 8.3.2.5

Lubricate mechanical moving parts (Excluding starters & relays Calibrate pressure switch settings Grease motor bearing

Annually Annually Annually

8.5 Maintenance of Motor 8.5.1 Routine Maintenance 8.5.1.1 8.5.1.2 8.5.1.3

Lubrication Starter contact Checking Insulation resistance check

Weekly Weekly Half yearly

8.7 Maintenance of hydrant mains 8.7.1 Routine Maintenance 8.7.1.1 8.7.1.2

To be tested with the pump delivering at its max. pressure & all hydrant valves closed Run the pump(s) with 2x15m hose pipes (per hydrant) connected to 2 hydrant

Fortnightly Weekly

8.7.1.3

All cut-off valves to be operated and oiled

Monthly

8.7.1.4

Overhaul all cut off values

Annually

8.8 Maintenance of hydrant valves 8.8.1 Routine Maintenance 8.8.1.1 8.8.1.2

Physical checking & Polishing of brass parts Painting of stand posts

Weekly Annually

8.9 Maintenance of Hose pipes & Nozzles 8.9.1 Routine Maintenance 8.9.1.1

Hose boxes/Hose stations to be inspected externally

Weekly

FEC

OPERATION AND MAINTENANCE MANUAL 8.9.1.2

Cleaning of Hose boxes/ Hose stations internally & externally

Monthly

8.9.1.3

Polishing of hose couplings / branch pipes

Fortnightly

8.9.1.4

Washing of hose pipes in clean water & drying

After each use

8.10 Maintenance of Fire Alarm system 8.10.1 Maintenance schedule SI.No:

Component

Visual Inspection

Testing

-

For every six months

8.10.1.1 Control equipment a)

Functions

b)

Fuses

Weekly

For every six months

c)

Lamps and LEDs

Weekly

For every six months

d)

Primary (main) power supply

Weekly

For every six months

e)

Secondary power supply

Weekly

For every six months

8.10.1.2 Batteries a)

Charger test

-

For every six months

b)

Load voltage test

-

For every six months

c)

Specific gravity

-

For every six months

8.10.2 Maintenance Procedures SI. No

Device

Method

8.10.2.1Control equipment

a)

Functions

b)

Fuses

c)

Lamps and LEDs

d)

Primary (main) Power supply

Verification of proper receipt of alarm, supervisory and trouble signals, circuit supervisory including detection of open circuits and short circuits, and power supply supervision for detection of loss of AC power and disconnection of secondary batteries Remove fuse and verify for accurate rating. Operate ‘Lamp test’ switch and verify whether lamps / LEDs illuminates. Secondary (standby) power supply shall be disconnected and tested under maximum load, including of all alarm appliances requiring of simultaneous

FEC

OPERATION AND MAINTENANCE MANUAL

e)

Secondary (standby) power supply

operation it shall be reconnected at the end of test. Disconnect primary (main) power supply and verify required trouble indication for loss of power occurs. Operate general alarm systems for a minimum of 5 min. Reconnect primary power supply at the end of test.

8.10.2.2 Batteries a)

Visual inspection

b)

battery replacement

c)

Charger test

e)

Secondary (standby)power supply

f)

Specific gravity

Inspect batteries for corrosion. Visually inspect the level of electrolyte. Batteries shall be replaced in accordance with the recommendation of the manufacturer or when the recharged battery voltage or currant falls below the manufacture’s recommendation. With the batteries fully charged and connected to the changer, measure the voltage across the batteries. The voltage shall be 2.30 volts per cell ± 0.2 volt. Disconnect primary (main) power supply and verify that required trouble indication for loss of power occurs. Operate general alarm systems for a min. of 5 minutes. Reconnect primary power supply at the end of test. The specific gravity of the liquid in the cells shall be measured. Generally a range of 1.205 – 1.220 is typical for regular lead-acid batteries. A hydrometer that shows only a pass or fail condition of the battery and does not indicate the specific gravity shall not be used.

FEC

OPERATION AND MAINTENANCE MANUAL

CATALOGUES

FEC

OPERATION AND MAINTENANCE MANUAL

General 1. Pump 2. Pressure Gauge 3. Pressure Switch 4. Non Return Valve Hydrant System 1. Hydrant Valve 2. Hose Box 3. Hose 4. Branch Pipe 5. Gate Valve 6. Water Monitor

Fire Detection and Alarm System 1. Main Fire Alarm Panel 2. Optical smoke detector 3. Hooter 4. Manual call Point 5. control Panel

FEC

OPERATION AND MAINTENANCE MANUAL

GENERAL

FEC

OPERATION AND MAINTENANCE MANUAL

HYDRANT SYSTEM

FEC

OPERATION AND MAINTENANCE MANUAL

FIRE DETECTION & ALARM SYSTEM

FEC

OPERATION AND MAINTENANCE MANUAL

FEC

OPERATION AND MAINTENANCE MANUAL

Related Documents


More Documents from "KCFUNG"

O&m Fire Fighting
February 2021 1
Samsung Lsmr.pptx
January 2021 2
Django Durga
January 2021 1
Legal Research Methods
February 2021 3
Cmm 25-63-05
January 2021 1
Ess Mss
January 2021 1