BLACK SEA GROUP POWER TRANSFORMERS
1
BLACK SEA GROUP POWER TRANSFORMERS
Power Transformers Prospect
CONTENT: Black Sea Group Presentation Delivery, Commisioning, Service Partners Main Features of the Power Transformers offered ElectroPutere Transformer Factory Products ETRA33 Transformer Factory Products BEZ Group - ETD Transformer Factory Products Service
2
BLACK SEA GROUP POWER TRANSFORMERS
ABOUT BLACK SEA GROUP BLACK SEA GROUP is formed of: 1. BLACK SEA TECHNOCHIM CO. S.R.L., having its head office in
Bucharest, Romania, registered at the Register of Commerce under no. J40/18522/1994 with C.U.I. no. 6286263 and the fiscal attribute R; Black Sea Technochim Co. is liable for Romania and European markets. 2. BLACK SEA ENERGY GENERATING EQUIPMENT TRADING (L.L.C.) having
its head office in Dubai, U.A.E., registered at the Department of Economic Development with license no. 515004 and Commercial Register no. 53617/1999; Black Sea Energy Generating Equipment Trading L.L.C. is liable for the United Arab Emirates markets. 3. SUN ORBIT FOR GENERAL TRADING CO., having its head office in
Baghdad-IRAQ, registered at Commercial Register no. 13116/2004; Sun Orbit for General Trading Co. is liable for Iraqi markets. 4. BLACK SEA POWER GENERATING FZCO, having its head office in Jebel
Ali Free Zone - Dubai, U.A.E., License no.40146 Government of Dubai. Black Sea Power Generating FZCO is liable for International, Middle East and Africa markets. The main markets for our activities are in the Middle East and Africa countries. Since its formation, as an international trade company, Black Sea Group has been dealing in the field of power generation, representing and collaborating with famous Romanian companies, for supplying of equipments and spare parts and performing of overhaul for all types of steam power stations with power up to 330MW and boilers with capacity up to 1035t/h. Due to an extensive experience, we offer to our clients high-quality products, short time delivery, competitive prices and a transparent collaboration. Highly-qualified personnel work hard so that all the products, works and services to be completed according to our clients requirements and in time. Quality Management Black Sea Technochim Co. is certified by TÜV Thüringen e.V. for the implementation and the application of the quality system according to DIN EN ISO 9001:2000.
3
BLACK SEA GROUP POWER TRANSFORMERS
From the beginning, Black Sea Group was focused intensively on quality, technical development and marketing. Black Sea Group’s main competencies include: • • • • • •
Thigh contacts with old and possible future clients; Thorough market studies and discover new possible tenders to take part to; Looks for the best designers and manufacturers for each possible future job; Black Sea Group buys the tender documents; The best offer issued on the name of one BSG member is sent to the client; Black Sea Group participates to the negotiations and signs the contracts as Main Contractor; • Black Sea Group is responsible for the necessary finances required for each offer/contract as follows: bid bonds and performance bonds, opens L/C or makes advance payments for the manufacturers; • During the development of each contract, in order to assure the best conditions in accomplishing the job, Black Sea Group is responsible for the delivery of goods from manufacturers to the client in short time, for the transportation and accommodation of the employed personnel during the rehabilitations and/or service period, insurances for the goods during the shipment and during the erection works; • Black Sea Group as Main Contractor is responsible in front of the client during the warranty period of each job performed.
4
BLACK SEA GROUP POWER TRANSFORMERS
BLACK SEA GROUP - CONTACT ROMANIA Black Sea Technochim Co. Contact person: Mrs. Aurelia Neacsu - Commercial Manager Phone: +40-21-3373951 FAX: +40-21-3366112 E-mail:
[email protected]
UNITED ARAB EMIRATES Black Sea Energy Generating Power Equipment Trading L.L.C. Contact person: Mr. Saud Thuny – Commercial Manager Mr. Tawfeeq Majeed Phone: +971-4-2727806 Mobile: +050-6587708 FAX: +971-4-2728553 E-mail:
[email protected]
Black Sea Power Generating FZCO
Contact person: Mr. Mohanad Ahmed – Commercial Manager Phone: +971-4-2727806 Mobile: +050-2589854 FAX: +971-4-2728553 E-mail:
[email protected]
IRAQ Sun Orbit for General Trading Co. Contact person:
Mr. Ossama M. Hussein Ms. Sherin Bassam Mr. Raed Yakub E-mail:
[email protected]
Mobile: +964 7901379203 Mobile: +964 7901399163 Mobile: +964 7901157503
5
BLACK SEA GROUP POWER TRANSFORMERS
DELIVERY, COMMISSIONING & START-UP, SERVICE. BLACK SEA GROUP offers: Compete range of Transformers from 1MVA upto 400MVA; 3kV upto 420kV: - Electrical Network Interconnecting Transformers and Autotransformers; -Three Phase Power Transformers for internal Services of Power Plant; -Three Phase Power Transformers with Off-Load Tap Changer; -Three Phase Power Transformers with On-Load Tap Changer or Off-Load Tap Changer; -Three Phase Power Transformers with On- Load Voltage Control; -Double Wounded, Three Phase Power Transformers with On-Load Tap Changer; ►Procurement and Delivery on site; ►Erection, Commissioning and Start-up; ►Acceptance and Performance Testing; ►Training on site or in manufacture place; ►Engineering services (inspection, analyzing and evaluation); ►Maintenance services; BLACK SEA GROUP is certified by TUV Thuringen e.V. for application of the quality system according with EN ISO 9001:2000.
6
BLACK SEA GROUP POWER TRANSFORMERS
BLACK SEA GROUP PARTNERS FOR POWER TRANSFORMERS AND FOR RELATED SERVICE ARE: 1. –ELECTROPUTERE CRAIOVAPower Transformers, Instrument Transformers, Electrical Motors, Switching Apparatus Factory-Romania. Internet:www.electroputere.ro
Transformers, Motors, Apparatus Manufacturer. 2. –ETRA 33Power Transformers Factory-Slovenija. Internet:www.etra33.si
Transformers Manufacturer. 3. -BEZ TransformatoryPower Transformers Factory-Slovakia. Internet:www.bez.sk
Transformers Manufacturer. 4. –BEZ-ETD Transformatory Power Transformers Factory-Czech. Internet:www.etd-bez.cz
Transformers Manufacturer. 5. -ICMET Research, development and Testing Institute -Romania. Internet:www.icmet.ro
Insulation testing.
7
BLACK SEA GROUP POWER TRANSFORMERS
6. –EMON ELECTRICElectric Erection -Romania. Internet:www.emon.ro
Constructions and Installations in Energetic and Telecommunication Field. Manufacturing. 7. –ELECTROMONTAJElectroenergetic Erection -Romania. Internet:www.electromontaj.ro
Constructions and Installations in Energetic Field. 8. -ICEMENERG ServiceRehabilitation and Research Institute for National Energy System –Romania. Internet:www.icemenerg.ro
Consulting, Implementation and Testing works on site.
8
BLACK SEA GROUP POWER TRANSFORMERS
MAIN FEATURES OF THE POWER TRANSFORMERS IN OUR PROJECTS BLACK SEA GROUP is constantly in the development and improvement of the offered products and services. Our aim is to satisfy customer’s high demand for a safe Electrical Power Generation. THE EQUIPMENTS are carried out with the best quality materials and components based on tested beyond standard margins. OUR PARTNERS are the world known companies which care perform the routine and performance tests on factory and the results are proven with the best Mean Time Between Failure. MISCELLANEOUS
The transformers belonging to these classes comply to the requirements of IEC 76 standard or standards required by the customers. MAIN REFERENCE DOCUMENTS:
IEC 60076-1 POWER TRANSFORMERS-General IEC 60076-2 POWER TRANSFORMERS-Temperature rise IEC 60076-3 POWER TRANSFORMERS-Insulation levels, dielectric tests and external clearances in air. IEC 60076-3 GUIDE to lightning impulse and switching impulse testing. IEC 60076-5 POWER TRANSFORMERS-Ability to withstand short circuit. IEC 60076-10 POWER TRANSFORMERS-Determination of sound levels. IEC 60137 Insulated bushings for alternating voltages above 1000V. IEC 60214 On-Load Tap Changers. IEC 60354 Loading guide for oil-immersed power transformers. CONDITIONS OF OPERATION
The transformers operate at ambient standard temperatures of max. +40ºC and min. -35ºC. Max. installation standard altitude above the sea level: 1000 m.
9
BLACK SEA GROUP POWER TRANSFORMERS
The transformers operate at ambient temperatures of .max.+ 50ºC and at altitude higher than 1000m are available at request. GENERAL TECHNICAL SPECIFIC FEATURES
Operating frequency: 50 Hz Operating voltage on the HV side: 110 (132);220 (230);400 (420) kV Operating voltage on the LV side: 6.3(6.9); 10.5(11); 13.8(15) kV Operating voltage on the MV side: 20 (33) kV Taping range on the HV: ± 2 x 2.5%; ± 12 x 1%; ± 17 x 1.25% Cooling type: ONAN; ONAN / ONAF; OFAF. Rated continuous power: 1 MVA ÷ 400 MVA TYPE The transformer shall be a 50-Hz outdoor type three-phase unit with ON –Load Tap Changer. The external cooling medium: air. The insulation is graded for operation with effectively earthed neutral. GENERAL The transformer is suitable for continuous operation on a three-phase 50Hz high voltage transmission system as specified. All windings of the transformers are capable of withstanding short circuit for the periods of time specified in IEC 60076 when operating on any tapping position. The transformer is suitable for cyclic overloading and long-time emergency loading duties in accordance IEC 60354. Ratings are based on the average winding temperature rise, as measured by resistance, of 55ºC and the top oil temperature rise, as measured by thermometer, of 50ºC. With the cooling air maximum temperature of 50ºC.
10
BLACK SEA GROUP POWER TRANSFORMERS
The design and manufacture of the transformers is such that the noise level is minimum and that the level of vibration does not adversely affect any clamping or produce excessive stress in any material. Noises levels shall are in accordance with IEC 60551. The maximum acceptable level is 88 dB in conformity with NEMA std.TR-1. MAGNETIC CIRCUITS The core is “core” type, with 3 parallel legs, made of high grade, non-aging electrical cold rolled grain oriented silicous steel laminations loss and high permeability. The yokes and legs are securely held by means of synthetic resin impregnated glassfiber strips. The core is clamped both at the top and bottom by means of clamping structures of steel. The structure placed on the same side are stiffened between each other by means of tie rods made of nonmagnetic alloy. The structures on the HV and LV sides are clamped between each other by means of clamping frameworks. The live part(core winding) is centered on the tank bottom by means of four guinding cones. Within the construction described above, the live part movement during shipping and installation or while in service is fully avoided. Particular care is taken to secure even mechanical pressure over the whole of the core laminations. Under steady overvoltage condition the maximum flux density not exceed 1,9 Tesla and the magnetizing current not exceed 5 % of the rated load current at normal rated voltage. WINDINGS. The winding are circular coil concentrically type. The windings shall be formed using high quality electrolytic copper conductor, insulated with pure cellulose paper. The main insulation between windings is of the multi-duct type with cylinders made of high dielectric strength transformer pressboard. The windings and connections are braced to withstand shocks, which may occur during transport or due to switching or other transient conditions during service.
11
BLACK SEA GROUP POWER TRANSFORMERS
INTERNAL EARTHING ARRANGEMENT. The magnetic circuit is earthed to the clamping structure at one point only through a removable link with a captive bolt and nut accessible placed beneath an inspection opening in the tank cover. TANK AND COVER. Transformer tank is made of electrically welded steel sheets and designed to allow the complete transformer, when arranged for transport to be lifted by crane and transported without transformer parts stressed. The plate thickness for the tank sides is of 10 mm. The cover is clamped to the tank, by screw fastening. The tank is provided with lugs, boses and hooks to enable the transformer, complete with all tank mounted accessories and filled with oil, to be lifted by powerhouse crane and pulling the transformer in 2 orthogonal directions. The wheels are suitable for a standard track (1.435 metre between inside of rail heads) for moving the transformer in 2 orthogonal directions. Four jacking pads are provided on the tank to enable the transformer, complete with oil, bushings and fittings,to be raised or lowered by jacks. Means are provided for locking the swivel movement in positions parallel to and at right angles to the longitudinal axis of the tank. The wheel loading does not exceed 13,000 kg . Tank covers shall not permanently distort when lifted. Inspection openings of ample size shall be provided to give easy access to bushings for changing ratio, or winding connections, and for testing the earth connections. The tank cover is fitted with a thermometer pocket, with captive screw cap, located in the position of maximum oil temperature at continuous maximum rating. Facility the bushing remove without removing the tank cover. A pressure relief device is provided for the rapid release of any pressure that may be generated within the the tank. The device operates at a static pressure of less than the hydraulic test pressure for transformer tanks and prevents further oil flow from the transformer following its operation. In the event that the device is a spring operated valve type it shall be provided with one set of normally open contacts, which will be used for tripping purposes.
12
BLACK SEA GROUP POWER TRANSFORMERS
OIL / AIR BUSHINGS. Oil/air bushings are designed in accordance with the requirements of IEC 60137. The HV bushings are of 145 kV condenser type; the HV neutral bushing is suitable for 72.5 kV level of condenser type; the LV bushings are suitable for min.12.5 kV level. The visible oil levels in the gauge corresponds to average oil temperatures from the minimum ambient stated in the SYSTEM PERFORMANCES to plus 90ºC. The oil levels at 15ºC and 35ºC are marked. Neutral bushings shall be mounted in position from which a connection can be made to a neutral current transformer mounted on a bracket secured to the tank. The neutral current transformer is not be in transformer manufacture standard supply.
CONSERVATOR VESSELS, OIL LEVEL GAUGES AND BREATHERS. The conservator has a level gauge, a filling cap, an adequate sump. The conservator is provided with a removable end cover at the one end. The visible oil levels in the gauge shall correspond to average oil temperatures from the minimum ambient stated in the SYSTEM PERFORMANCES in Annex no.1 to plus 90ºC. The oil levels at 15ºC and 35ºC are marked on the gauge. The oil level gauge incorporates alarm contacts, which close when the oil level falls below a definite level. The conservator is connected to a dehumidifying breather, which is mounted at approximately 1,4 m above ground level.
VALVES Valves are of the fully-way type. Padlocks are provided for locking all valves(exception for the individual radiator valves) in the open and closed positions. The valves are with an indicator readily visible from ground level which shows clearly the position of the valve. All valves hand-wheels are provided with nameplates.
13
BLACK SEA GROUP POWER TRANSFORMERS
COOLING PLANT Transformer has ONAN/ONAF cooling options. The facilities are provided at the marshaling kiosk or cubicle for the selection Automatic or Manual control of the cooling plant motors. Transformers shall be fitted with sectionalized cooling banks necessary to meet the continuous maximum rating (CMR). Transformers shall be capable of remaining in operation at full load for 20 minutes in event of failure of the cooling fans without the calculated winding hot spot temperature exceeding 150ºC. Failure of one fan in each group of fans does not reduce the continuous maximum rating of the transformer. The fan complete with its motor and supporting structure can be removed without disturbing or dismantling the cooler framework or pipe - work. COOLER CONTROL. The forced air cooling is controlled for automatic starting or stopping from contacts on the winding temperature indicating devices. ON-LOAD TAP CHANGING-OLTC- EQUIPMENT. The transformer is provided with OLTC suitable for the rated current(+20% overload) of modern design and construction of MR Type from Germany with 17 tapping positions x 1.25% in range of +10% -10% ; with fully capacitance at all taps. Tap changing is prevented when the transformer is caring a load above a predetermined maximum or when on short circuit. Tap changing however is suitably rated for operation when transformer are subjected to overload duties in accordance with IEC 60354. The equipment has an indication at the transformer and electrically at the remote control points of the tapping in use. AUTOMATE VOLTAGE REGULATOR AND TAPPING INDICATOR. The Automate Voltage Regulator is included in the offer; the regulator actuates to the motor of the OLTC. The Actual Voltage measurement is taken from existing Instrument Transformers of the Substation. The instrument transformer will be provided in the delivery by request. An Indicator device of the tapping positions for the Control Room is included in the Offer.
14
BLACK SEA GROUP POWER TRANSFORMERS
TEMPERATURE INDICATING DEVICES, ALARMS AND GAS AND OIL ACTUATED RELAYS. 1. TEMPERATURE INDICATING DEVICES, ALARMS Oil temperature indicating devices are fitted with alarm and trip contacts. Winding temperature indicating devices indicate the temperature of the hottest spot of the winding and have a load –temperature characteristic approximating to that of the main winding. Alarm and trip contacts are provided. Alarm contacts of oil and winding temperature indicating devices are adjustable over a range of 60ºC to 110ºC and trip contacts adjustable over a range 80ºC to 150ºC. Temperature indicating devices incorporate a dial and a pointer indicator and a separate pointer to register the maximum temperature reached. All temperature indicators are housed in the marshalling kiosk or cabinet and are not affected by vibration. 2. GAS AND OIL ACTUATED RELAYS. Gas and oil actuated relays are fitted to each tap selector compartment. They have alarm contacts that close on collection of gas or at low oil level and tripping contacts, which close following an oil surge.
The relays are fitted in the expansion pipe connecting the transformer tank to the conservator. OIL FLOW INDICATORS. Forced oil cooled transformers shall be provided with a visual oil indicator including contacts, in each outlet pipe connection from coolers. OIL QUALITY.
Uninhibited new insulating mineral oil for transformers type NITRO by NYNAS-Austrian manufacture which assures a safe transformer energizing at a temperature -30ºC. The U-30ºC transformer insulating mineral oil is used as an insulating and cooling environment in high-power transformers.
It can be used in warm(tropical) and mild climate countries, for altitudes up to 1500 m. The technical and quality conditions according to EN 60 296/2004.
15
BLACK SEA GROUP POWER TRANSFORMERS
One oil container with 5% from oil quantity in the main body(tank)of the transformer is recommended and it is delivered by client request on extra cost. TRANSFORMER MARSHALLING KIOSK. A weatheproof and dustproof control housing located on the transformer near the base. It is equipped with the following: (a)Earth bus for circuits requiring earth points. The bus includes one bolted type connectors of 10 mm2 stranded copper cable size for each earthed circuit. (b)Terminal blocks for termination of secondary leads, alarm, control, relay and thermocouple leads. (c)A suitable pocket or holder inside for one copy of the instruction manual. (d)A plain, removable plate located in the bottom for terminating all conduits leaving the transformer (the plate will be drilled in the field). (e)Contactors for fan motors. (f)Necessary glands for power and control cables (g)Thermostatically controlled, anti-condensation heater for 220V,single – phase system.
16
BLACK SEA GROUP POWER TRANSFORMERS
THE ACCESSORIES AND MATERIALS USED BY THE ELECTROPUTERE CRAIOVA-ROMANIA one of our Partner. 1.The HVand MV Bushings are GOB type from ABB-Germany manufacturer. 2.ON –LOAD TAP CHANGER is from MR manufacturer Germany. 3. Oil transformer-NITRO 3000x from NYNAS manufacturer Austrian.
It can be used in warm (tropical) and mild climate countries, for altitudes up to 1500m and assures a safe energizing at a temp of -30ºC. 4. Radiator panel type from EuroCooller manufacturer-France / AGUN manufacture-Turkey. 5. Cooling Battery from Solivent Ventek-France. 6. Fan 0.37kW/230/400V axial type, from ELECTROPUTERE -Romania. 7. Buchholz relay type from EMB manufacturer –Germany. 8. Magnetic oil level indicator- CAOM Pascani-Romania 9. Oil temperature indicator, type OTI Serie 34, AB Qualitrol AKM manufacturer,Sweden. 10. Winding temperature indicator,type OTI Serie 35,AB Qualitrol AKM manufacturer,Sweden. 11. Oil filtering valve and Oil draining valve, Fratelli Fortis- Italy or Armatura Cluj-Romania. 12. Copper wire with Specific Electrical Resistance 0.0214 Wmm2/mat 75ºC; 99.98% Cu BORR manufacture-Serbia.
13. Silicous steel sheet, MOH type, specific loss 1.03w/kg at 1.7 T from British Steel- England.
17
BLACK SEA GROUP POWER TRANSFORMERS
ELECTROPUTERE CRAIOVA-Romania. TRANSFORMERS FACTORY.
◘ Network Interconnecting Transformers; ◘ Step –up Transformers; ◘ Auxiliary Transformers; ◘ Three phase Regulating Power Transformers; ◘ Service;
THE MOSTLY RECENT REFERENCE LIST AS BELOW:
18
BLACK SEA GROUP POWER TRANSFORMERS TYPE TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF TTOS – ONAN/ONAF
RATED OUTPUT (KVA)
VOLTAGE (KV)
40000/50000
150/21
40000/50000
150/21
31500/25000/12500
132/33/11,5
44000/63000
132/34,5
17500/2500
132/33
6300
132/6,3
7000/10000
33/11,5
7000/10000
33/11,05
11200/16000
33/11,5
250000/250000/80000
400/121/20
TTOS - ONAN
30000
66/20
TTO - ONAN
250
20/0,4
TTOS – ONAN/ONAF
40000/50000
150/21
TTUS – OFAF
16000
66/6,6
TTO-OFAF
ATOS
VOLTAGE CONTROL (%)
VECTOR GROUP
NOS (pcs)
YEAR of DELIVERY
APPLICABLE CODE/STD
YNyn-0
8
2003
IEC
YNyn-0
10
2003
IEC
2
2003
IEC
YNd1
1
2003
IEC
10
YNd1
2
2003
IEC
12
YNd1
1
2003
IEC
Dyn11
1
2003
IEC
Dyn11
2
2003
IEC
Dyn11
3
2003
IEC
Ynyn-0
1
2003
IEC
Ynd11
4
2003
IEC
Znyn1
4
2003
IEC
YNyn-0
5
2003
IEC
YNd11
1
2003
IEC
YNyn0-d1
5
2003
IEC
+12,5 - 17,5 +12,5 - 17,5 +10x1,25 10x1,25 16 1,25
+7,5 -10,5 +7,5 -10,5 +7,5 -10,5 16 10 30 15 11 15 9x1,78 +12,5 - 17,5 9x1,78 +10x1,25 10x1,25
YNyn0-d1
280000/280000/60000
400/157,5/30
TTOS ONAN/ONAF
42000
11,5/150
5
YNd1
2
2003
IEC
TTOS – ONAF
24000/12000/12000
15/6,3/6,3
10
Dy
2
2003
ANSI
COUNTRY-CUSTOMER
REMARKS
GREECE – PPC GREECE – PPC GERMANIA – ABB// IRAQ KALLAR GERMANIA – ABB// IRAQ TASLUJA GERMANIA – ABB// IRAQ OLD DOKAN GERMANIA – ABB// IRAQ NEW DOKAN GERMANIA – ABB // IRAQ ARBAT GERMANIA – ABB// IRAQ QALADIZA GERMANIA – ABB// IRAQ MALKANDY ROMANIA ST-ORADEA SYRIA PEEGT SYRIA PEEGT GREECE – PPC SIRYA ACBMC CEMENT PLANT GREECE – PPC GREECE - PPC EGIPT - CEPC CAIRO NORTH POWER St.
S/S S/S S/S S/S S/S S/S S/S T S/S S/S S/S S T S/S T
19
BLACK SEA GROUP POWER TRANSFORMERS
TYPE
RATED OUTPUT (KVA)
VOLTAGE (KV)
VOLTAGE CONTROL ( %)
VECTOR GROUP
NOS (pcs)
YEAR of DELIVERY
APPLICABLE CODE/STD
ATOS
280000/280000/60000
400/157,5/30
+10x1,25 10x1,25
YNyn0-d1
3
2004
IEC
GREECE – PPC
T
TTOS – ONAN
3000
15/0,4
+ 8 x1,25
YMd11
1
2004
IEC
GREECE – PPC
S/S
TTOS – ONAN/ONAF
16000
132/33
Ynd-1
1
2004
IEC
JORDAN -NEPCO
S/S
TTOS – ONAN
200
33/0.4
Znyn11
1
2004
IEC
JORDAN - NEPCO
S/S
TTOS - ONAN
30000
66/20
?9x1,78
Ynd11
4
2004
IEC
SYRIA – PEEGT
S/S
TTO - ONAN
100
20/0,4
-
Znyn1
4
2004
IEC
SYRIA - PEEGT
S/S
TTOS - OFAF
180000
161,25/15,75
+5; -15x0,93
YNd1
1
2004
IEC
GREECE - PPC
S/S
+3x1.67 9x1.67 +2x2.5 2x2.5
TTOS – ONAN/ONAF TTOS – ONAN/ONAF/OFAF TTOS – ONAN/ONAF/OFAF
48000/67300
150/11,5
8x1,25
Ynd1
4
2004
IEC
36000/60000/67300
150/11,5
3x2,5
Ynd1
1
2004
IEC
50000/83500/93500
150/11,5
3x2,5
Ynd1
1
2004
IEC
ATOS-OFAF
400000
400/231/22
-
Yn a-d5
1
2004
IEC
TTOS-ONAN/ONAF
12000
157,5/6.3
Ymd1
1
2004
IEC
TTOS-ONAN/ONAF
40000/50000
150/21
Ynyn-0
1
2004
IEC
TTOS-ONAN/ONAF
30000/35000
150/15/6,6
Ynynod11
1
2004
IEC
TTOS-ONAN/ONAF
40000/50000
150/15,75-21
+6x1,25 10x1.25
Dyn1
1
2004
IEC
TTOS – ONAF
100000
150/20-20
+12x1,25
Dy
1
2004
IEC
TTO - OFWF
216000
15,75/242
-
Ynd5
2
2004
IEC
+10 -5 +12,5 -17,5 8x1,2
COUNTRY-CUSTOMER
GRECIA – PPC HERON THERMOELECTRICAL GREECE – PPC TERNA SA – GEK GROUP GREECE – PPC TERNA SA – GEK GROUP BOSNIA & HERTEGOVINAELECTROISTOK GREECE-PPC GREECE-PPC AREVA GREECE GREECE-PPC HERACLES HGC GREECE-PPC ABB GREECE GREECE-PPC ROMANIA- PFI VATECH
REMARKS
S/S S/S S/S T S/S S/S S/S S/S S/S P/P
P = ELECTRIC POWER PRODUCTION; S/S = ELECTRIC SUBSTATION; T = ELECTRIC POWER TRANSPORT P/P = POWER PLANTS; D = ELECTRIC POWER DISTRIBUTION; MI = MINING INDUSTRY; S = SPECIAL
20
BLACK SEA GROUP POWER TRANSFORMERS
RATED OUTPUT (KVA)
VOLTAGE (KV)
TTOS – ONAN/ONAF
80000
132/33
TTOS-ONAN
200
33/0.4
TTOS – ONAN/ONAF
45000
132/33
TTO - OFWF
216000
15,75/242
TTOS – ONAN/ONAF
20000/26000
33/11,5
ATOS-OFAF
200000/200000/60000
231/121/10,5
67500/78000
11-11,5/150
21250
19/6,3
40000/50000
150/21
53000/66000
161,25/6,3/6,3
40000/50000
150/15,75-21
280000/280000/60000
400/157,5/30
TYPE
TTOSONAN/ONAF TTOSONAN/ONAF TTOSONAN/ONAF TTOSONAN/ONAF TTOSONAN/ONAF ATOS
VOLTAGE CONTROL ( %)
VECTOR GROUP
NOS (pcs)
YEAR of DELIVERY
APPLICABLE CODE/STD
COUNTRY-CUSTOMER
REMARKS
Ynd1
3
2005
IEC
JORDAN - NEPCO
S/S
Znyn11
1
2005
IEC
JORDAN - NEPCO
Special
+3x1,67 9x1,67
Ynd1
2
2005
IEC
JORDAN - NEPCO
S/S
-
Ynd5
1
2005
IEC
ROMANIA - PFI VATECH
P/P
Dyn1
2
2005
IEC
GHANA
S/S
Yna0d5
7
2005
IEC
ROMANIA / TRANSELECTRICA
S/S
Ynd1
1
2005
IEC
GREECE - PPC
S/S
Yny0
1
2005
IEC
GREECE – PPC/RODAX
S/S
Ynyn-0
1
2005
IEC
GREECE – PPC/AREVA
S/S
Ynd1
1
2005
IEC
GREECE – PPC/RODAX
S/S
Dyn1
2
2005
IEC
GREECE - PPC/VA TECH
S/S
YNyn0-d1
1
2005
IEC
GREECE - PPC
S/S
+3x1,67 9x1,67 +2x2.5 -2x2.5
+7x1,33 8x1,33 231+8x1,25 231-8x1,25 +8x1,25 8x1,25 +8x1,25 8x1,25 +12,5 -17,5 +8x1,25 8x1,25 +6x1,25 10x1,25 +10x1,25 10x1,25
P = ELECTRIC POWER PRODUCTION; S/S = ELECTRIC SUBSTATION; T = ELECTRIC POWER TRANSPORT P/P = POWER PLANTS; D = ELECTRIC POWER DISTRIBUTION; MI = MINING INDUSTRY; S = SPECIA
21
BLACK SEA GROUP POWER TRANSFORMERS
ELECTROPUTERE PRODUCT-POWER TRANSFORMER 280 MVA; 400 / 15 kV; OFAF
22
BLACK SEA GROUP POWER TRANSFORMERS
ELECTROPUTERE product . 90 MVA; 161/ 15.75kV/kV; OFAF 23
BLACK SEA GROUP POWER TRANSFORMERS
ELECTROPUTERE product. 72 MVA; 21/6.3/6.3 kV/kV/kV; ONAN/ ONAF 24
BLACK SEA GROUP POWER TRANSFORMERS
ELECTROPUTERE product. 40/ 50 MVA; 150/ 21 kV/kV; ONAN/ ONAF.
25
BLACK SEA GROUP POWER TRANSFORMERS
ELECTROPUTERE product. 18 MVA; 21/ 6.3 kV/ kV; ONAN 26
BLACK SEA GROUP POWER TRANSFORMERS
ELECTRICAL NETWORK INTERCONNECTING TRANSFORMERS
Rating (MVA)
Voltage (kV)
Uk Po Pk (%) (kW) (kW)
63/44
132 / 34.5 12.5
39
265
Connection group YNd1
Wdg. Material Cu
Overall Overall Weight Dimensions (kg) (LxWxH)(mm) 90.000 8200x5100x6000
27
BLACK SEA GROUP POWER TRANSFORMERS
THREE PHASE POWER TRANSFORMERS WITH NO LOAD TAP CHANGING Rating (MVA)
Voltage (kV)
Uk (%)
10.5/ 138 135 13.83 ±2x2.5% 10.5/ 420 160 ±2x2.5% 15/ 420 160 ±2x2.5%
Overall Dimensions (LxWxH)(mm)
68
315
Y0d-11
Cu 125.000
8000x5600x6500
17
89
445
YNd-1
Cu 230.000
12900x6500x10500
13
89
445
YNd-1
Cu 230.000
12900x6500x10500
130
570
YNd-1
Cu 290.000
12900x6500x10900
34
224
YNd-1
Cu 112.000
8000x5600x6900
18/ 400 250 13.83 ±2x2.5% (45)/60/75 11.5/132
Overall Po Pk Connection Wdg. Weight (kW) (kW) group Material (kg)
14
28
BLACK SEA GROUP POWER TRANSFORMERS
29
BLACK SEA GROUP POWER TRANSFORMERS
30
BLACK SEA GROUP POWER TRANSFORMERS
31
BLACK SEA GROUP POWER TRANSFORMERS
32
BLACK SEA GROUP POWER TRANSFORMERS
33
BLACK SEA GROUP POWER TRANSFORMERS
DOUBLE WOUNDED, THREE PHASE POWER TRANSFORMERS WITH ON LOAD VOLTAGE CONTROL
Rating (MVA) 63/50/25
Voltage (kV) 132/33/11.5
Uk Po Pk (%) (kW) (kW) 19
31
233
Connection group YNd1yn0
Wdg. Material Cu
Overall Overall Weight Dimensions (kg) (LxWxH)(mm) 102500 8500x5400x6500
34
BLACK SEA GROUP POWER TRANSFORMERS
35
BLACK SEA GROUP POWER TRANSFORMERS
THREE PHASE POWER TRANSFORMERS FOR THE INTERNAL SERVICES OF THE POWER PLANT Rating (MVA) 56
Voltage (kV) 132±2x2.5%/6.6
Overall Uk Po Pk Connection Wdg. Overall Dimensions Weight (%) (kW) (kW) group Material (LxWxH)(mm) (kg) 28
189
YNd-11
16 33±9x1.78%/6.3 10 10.5 12.5 132±8x1.25%/6.9 10.65 10 8 15±2x2.5%/6.9 10 7.5 8 132±2x2.5%/6.6 10 7 3/3.36 11.5±2x2.5%/0.4 5.75 2.9
75 65 50 50
4/4.48 11.5±2x2.5%/3.3 5 10.5±2x2.5%/6.6 1.6 11±2x2.5%/0.4
19
5.75 7.5 5.75
Cu 86.000
6900x4300x6000
YNd-1 YNd-1 Dyn-1 YNyn0
Cu Cu Cu Cu
37.000 40.000 18.000 32.000
4700x3150x3500 5000x4000x4800 3800x2350x3600 4500x3500x4200
24
Dyn-1
Cu
5.100
3150x2100x2550
5.5 33 6.2 38 2.2 14.96
Dyn-1 Dyn-1 Dyn-11
Cu Cu Cu
5.100 5.100 5.100
3150x2600x3000 2900x2800x3050 2150x1950x2400
36
BLACK SEA GROUP POWER TRANSFORMERS
37
BLACK SEA GROUP POWER TRANSFORMERS
38
BLACK SEA GROUP POWER TRANSFORMERS
39
BLACK SEA GROUP POWER TRANSFORMERS
40
BLACK SEA GROUP POWER TRANSFORMERS
41
BLACK SEA GROUP POWER TRANSFORMERS
SUPPLY MOBILE TRANSFORMER, for emergency cases where have to solve the problem of power transformer failure : 10MVA;33/11 kV power transformer 20MVA;33/11 kV power transformer The supply consists of: -the power transformer loaded on the truck and well fitted -the low-bed semitrailler is dedicated to be hooked to a horseshoeshaped coupling device at a rear of the engine drive; 4 axles with air hydraulic suspension. Accessories: ABS breaking system; 24 V electrical part. -the transformer and the truck are well earthed -the spare parts of the power transformer -the spare parts of the truck General dimensions are: (a)total length:13 700…12 200 mm (b)width: 2500 mm (c)total height:4 800…4 500 mm (d) max. weight:58 000…45 50
Mobile substation. 20MVA(10MVA); 33/11kV. Type SJ44 (SJ35)
42
BLACK SEA GROUP POWER TRANSFORMERS
BLACK SEA GROUP PARTNER IN SLOVENIA:
ETRA 33 factory - Slovenia:
◘ Power transformers;
◘ Step –up Transformers; ◘ Distribution transformers; ◘ Special transformers;
43
BLACK SEA GROUP POWER TRANSFORMERS
ETRA 33 TRANSFORMERS FACTORY (SLOVENIA)
REFERENCE LIST OF TRANSFORMERS LEGEND of symbols: ANT 3-phase autotransformer with OFF-LOAD tap changer ART 3-phase autotransformer with ON-LOAD tap changer BT 3-phase generator (block) transformer NT,VT 3-phase transformer with OFF-LOAD tap changer RT 3-phase transformer with ON-LOAD tap changer RNT 3-phase transformer with ON-LOAD tap changer and OFF-LOAD tap Changer ERT single phase transformer with ON-LOAD tap changer M transformer is filled with organic ester MIDEL 7131
Type
Rated Power [MVA]
BT
150
RT
150
RT
80
BT
75
RT
65
UT
63,12
NT
63
RT
63
RT
60
Voltage Ratio in [kV], Tappings and Vector Group 121/13.8; YNd5 220±12x1.25%/ 115/10.5; YNyn0 d5 138±9x1,67%/5 2/20; YNyn0(d5) 121/10.65; YNd5 130±10x1.42%/ 66/22; YNd11d11 112/0.7001+ 0,7071/20; YNy0d11 d11 145±2x2,5%/ 10,7; YNd11 110±10x1.5%/3 6.75/10.5, YNyn0(d5) 66±6x1,5%/22 YNyn0
Qty.
Year of Deli very
Country
Customer
1
2003
Slovenia
Termoelektrarna Trbovlje
1
2000
Slovenia
Elektro Slovenija, Ljublajana ***
1
2004
Sweden
Fortum Distribution AB, Holmagärde
1
2001
Slovenia
1
2001
Norway
Dravske elektrarne Maribor, HE Formin *** Stratnett SF SS Mosjøen
1
2004
Slovenia
Talum Kidričevo
1
2006
Sweden
Billerud AB, Gruvöns Bruk
2
2005
Yugoslavia
Elektroprivreda Crne Gore
1
2006
Norway
Nord Trøndelag Elektrisitetsverk FKF
44
BLACK SEA GROUP POWER TRANSFORMERS
Type
Rated Power [MVA]
NT
55
NT
55
RT
50
NT
50
RT
50
RT
50
RT
48
RT
40
NT
40
RT
40
RT
40
RT
40
RT
40
RT
40
RT
40
RT
40
RT
40
NT
35
NT
35
Voltage Ratio in [kV], Tappings and Vector Group 44±2x2,5%/ 10,5; YNd11 116±2x2,5%/ 10.5; YNd5 76±9x1,33%/22, 5, YNyn0 115±1x5%/ 10.5; YNd5 145±9x1,67%/1 1,5/1,5; YNyn0(d11) 77±9x1.67%/ 10.5; YNyn0 132±9x1.67%/1 1, YNd5 126±13x1,154% /11, YNd11 110±1x2,5%/6,3 , YNd1 145±9x1,67%/1 1, YNyn0 145±9x1,67%/1 1, YNyn0 110±12x1.33%/ 21(10.5)/10.5, YNyn6(d5) 110±10x1.5%/3 6.75/6.3, YNyn0d5 110±10x1.5%/1 0.5/10.5, YNyn0(d5) 132±8x1,67%/2 2/22, YNyn0(d11) 132±10x1,2%/1 8,6(22) , YNyn0 65±8x1,5%/23, YNyn0 33±2.5%/11, YNd11 33±2.5%/11, YNd11
Qty.
Year of Deli very
Country
Customer
1
2006
Sweden
Billerud AB, Karlborg
1
2001
Slovenia
1
2006
Sweden
Soške elektrarne Nova Gorica, HE Doblar Fortum Distribution AB
1
2004
Slovenia
1
2003
Sweden
3
2001
Sweden
Hallsta pappersbruk
1
2003
Sweden
1
2006
Hungary
Stora enso Newsprint, Hylte Bruk ETV-Eröterv Rt
2
2006
Slovakia
U.S.Steel Košice
1
2006
Sweden
Billerud AB, Gruvöns Bruk
3
2005
Sweden
Billerud AB, Gruvöns Bruk
2
2005
Slovenia
Elektro Maribor, RTP Ptuj
1
2005
R/F of BiH
Elektroprivreda BiH TPP Tuzla
2
2005
Yugoslavia
Elektroprivreda Crne Gore
2
2002
Norway
Tafjord Kraftnett AS
1
2002
Norway
Ǿstnett AS
1
2001
Norway
4
2005
5
2004
Saudi Arabia Saudi Arabia
Trønder Energi Nett, Trondheim Siemens DDIT for Yamama Project Siemens DDIT for Yamama Project
Termoelektrarna – Toplarna Lubljana Fortum Distribution AB, Hagfors
45
BLACK SEA GROUP POWER TRANSFORMERS
Type
Rated Power [MVA]
RT
31,5
RT
31,5
RT
30
RT
30
RT
30
RT
30
RT
30
RT
25
RT
25
RT
25
RT
25
Voltage Ratio in [kV], Tappings and Vector Group 132±9x1,67%/6 6(33)/11, YNyn0d11 110±12x1.33%/ 21/10.5, YNyn6(d5) 45±8x1,67%11, 5/11,5,YNyn0 65±8x1,5%/23/1 1,5; YNyn0(d5) 67(48)±10x1%/2 3(10,6); YNyn0 65±8x1,5/23,YN yn0 67(48)±10x1%/2 3(10,6); YNyn0 110±8x1.25%/2 1,YNyd11 110±8x2%/6.3,Y Nyd11 67(48)±10x1%/2 3(10,6); YNyn0 33±8x1.67%/ 6.3;Dyn11
Qty.
Year of Deli very
Country
Customer
1
2004
Iceland
Landsvirkjun, Bessastadir Substation
2
2004
Slovenia
Elektro Ljubljana
2
2005
Sweden
Jönköping Energi Nät AB
1
2004
Norway
Trønder Energi Nett AS
1
2002
Norway
Østnett AS
1
2002
Norway
1
2001
Norway
Trønder Energi Nett, Trondheim Østnett AS
1
2004
Romania
ROMENERGO Romania
2
2004
Romania
OLTCHIM Romania
1
2002
Norway
Østnett AS
5
2004
Saudi Arabia
Siemens DDIT for Yamama Project
46
BLACK SEA GROUP POWER TRANSFORMERS
47
BLACK SEA GROUP POWER TRANSFORMERS
ETRA 33 TRANSFORMER FACTORY.
48
BLACK SEA GROUP POWER TRANSFORMERS
BLACK SEA GROUP PARTNER IN SLOVAKIA:
BEZ TRANSFORMATORY factory – Slovak Republic ◘ Distribution transformers: -Oil filled transformers; -Dry and cast resin transformers; ◘ Ecological cast resin transformers; ◘ Amorphous transformers BEZ-ETD TRANSFORMATORY factory – Czech Republic ◘ Power Transformers; ◘ Step –up Transformers; ◘ Service( repair works; technical activities ); 49
BLACK SEA GROUP POWER TRANSFORMERS
ETD Transformers Factory (former SKODA ENERGO) – Czech Republic
REFERENCE LIST OF TRANSFORMERS TRANSFORMERS UP TO 72, 5 kV Year of manufacture 2001 2004 2004 2005 2005 2005 2005 2006 2006 2006
Country of destination Czech Republic Czech Republic Netherlands Czech Republic Cuba Slovak Republic Slovak Republic Pakistan Czech Republic Cuba
No. of pcs
Output MVA
Voltage ratio kV
Foxconn
2
16
35/6,3
Strekov
1
16
23/10,5 kV
De Eendracht Karton
1
16
20/10,5
Vyskov u Loun
1
16
23/10,5
15
20
13,8\34,5
Zilinska teplar
2
16
22/6.3
Zilinska teplar
1
32
22/6.3
MAN SRN Sokolovska uhelna Vresova BEZ Transf
1
25
21/11
1
25
10,5/6,6
2
20
34,5/13,8
Power plant
50
BLACK SEA GROUP POWER TRANSFORMERS
Transformers up to 120 kV Year of manufacture 2005 2005 2005 2005 2005 2005 2005 2005 2005 2005 2006 2006 2006 2006 2006 2006 2006 2006 2006 2006
Country of destination Slovak Republic Czech Republic Czech Republic Czech Republic Czech Republic Czech Republic Czech Republic Slovak Republic Slovak Republic Slovak Republic Czech Republic Czech Republic Czech Republic Czech Republic Slovak Republic Czech Republic Czech Republic Czech Republic Czech Republic Czech Republic
No. of pcs
Output MVA
1
40
Voltage ratio kV/kV 110/23
1
40
115/23
Opocinek
1
40
110/36,75
Prostejov
1
40
110/23
CEZ, SCE
1
40
110/23
EZ Praha/Hostejn
2
16
110/23
PRE Praha/Zlicin
1
40
110/23,25
ZS Brno/Breclav Gemerska Horka Kechnek
1
16
110/23
2
40
110/23
Sucany
1
25
110/23
OHL ZS / Breclav
1
12,5
110/27
VaTech/Krupta
1
40
110/23
CEZ/ Razecek
1
40
110/23
OHL ZS/Grygov
2
25
110/23
SSE Zilina
1
40
110/23
ABB/Kladno
1
60
110/11,5
Sokolovska uhelna Vresova CEZ/Rokycany
1
63
110/1,5
1
40
110/23
CEZ/Vsetin
1
50
110/23
JM montze Cernovice
1
25
110/23
Power plant Sukany
Vyskov
51
BLACK SEA GROUP POWER TRANSFORMERS
Transformers up to 145 kV
Year of manufacture 2004 2005 2006
Country of destination Czech Republic Slovak Republic Slovak Republic
Power plant
Trebovice Liptovska Mara Liptovska Mara
No. of pcs 1
91
Voltage ratio kV/kV 121/11
3
63
121/10,5
1
63
121/10,5
Output MVA
Transformers up to 240 kV Year of manufacture
2003
Country of destination Czech Republic Czech Republic
2004
Egypt
2000
Power plant VE Orlik Actherm
Egyptalum
No. of pcs 4
220/3
Voltage ratio kV/kV 242/15/15
1
25
220/23/(6,3)
2
150
220/132/11
Output MVA
Transformers up to 420 kV Year of manufacture 2000
Country of destination
Power plant
Yugoslavia
Kolubara B
Bangladesh
Ashuganj
No. of pcs 1 1
410
Voltage ratio kV/kV 410/22
200/3
245/15,75
Output MVA
2001
52
BLACK SEA GROUP POWER TRANSFORMERS
53
BLACK SEA GROUP POWER TRANSFORMERS
54
BLACK SEA GROUP POWER TRANSFORMERS
55
BLACK SEA GROUP POWER TRANSFORMERS
56
BLACK SEA GROUP POWER TRANSFORMERS
57
BLACK SEA GROUP POWER TRANSFORMERS
58
BLACK SEA GROUP POWER TRANSFORMERS
59
BLACK SEA GROUP POWER TRANSFORMERS
Partners of BLACK SEA GROUPfor services concerning to Power Transformers.
ICMET craiova-Researche instituteTEST INSULATING MATERIALS
ICMET CRAIOVA -ROMANIA S ERVICES OFFERED High voltage tests for HV equipment (transformers, cables, switchgears, GIS, etc.) inside the electromagnetic screened hall of ICMET
High voltage tests on site:
-Full wave (1.2 / 50 s ) and tail chopped wave voltage impulse tests (between 2 and 8 s) at voltages up to 4200 kV and energy 336 kWs
- Applied voltage tests at frequencies between 25 and 150 Hz up to 800 kV
AC sparkover voltage test of arresters up to 60 kV
- AC or DC voltage test of high voltage - Single and three-phase induced voltage test, 5 MVA, 2 cables up to 100 kV min. - AC voltage test of SF6 enclosed - DC voltage tests uo to 1200 kV 30 mA, up to 1200 kV stations up to 250 kV (resonant equipment) - Oscillating switching impulse tests
- Induced voltage test of distribution transformers
- Aperiodic switching impulse tests up to 2600 kV
- External insulation test under artificial rain for equipment up to 400 kV rated voltage
- Partial discharge and radio interference measurements
- Switching impulse test for instrument and power transformers by electromagnetic induction
- Partial discharge measurement at instrument and power transformers by electric and ultrasonic method.
- Combined voltage tests: LI - AC, SI - AC, DC - LI, DC SI
60
BLACK SEA GROUP POWER TRANSFORMERS
ICMET CRAIOVA -ROMANIA Reference list: I. Three Phases Power Transformers Type and routine tests S(MVA) / U (kV)
Factory
Made for
(0.063; 0.1; 0.16; 0.2; 0.2; 0.4; 0.63; 0.8) MVA / (20; 20; 20; 20; 33; 20; 20; 6) kV
ABB Bucharest
Dubay Romania Sudan Syria
1 MVA / 6.6 kV
ELECTROPUTERE Bangladesh
(1.5; 5; 10; 15; 20) MVA / (34.5; 69; 69; 69; 69) kV
ELECTROPUTERE Brazil
(0.15; 0.25; 20; 50) MVA / (15; 22; 115; 115) kV
ELECTROPUTERE Cambodgia
176 MVA / 72 kV
ELECTROPUTERE Canada
(0.4; 1; 6.3; 16; 40; 63; 90; 405)MVA / (6; 6; 35; 38; 24; 110; 345; 363) kV
ELECTROPUTERE China
(1.6; 1.6) MVA / (6; 33) kV
ELECTROPUTERE Cuba
(10; 31.5; 38) MVA / (66; 132; 154) kVA
ELECTROPUTERE Cyprus
(16; 20; 21; 25) MVA / (132; 66; 132; 66) kV
ELECTROPUTERE Egypt
20 MVA / 33 kV
ELECTROPUTERE Ghana
(10; 18.75; 25; 50; 60; 72; 72; 90)MVA / (150; 66; 150; 150; 150; 161.25; 21; 161.25) kV
ELECTROPUTERE Greece
8 MVA / 54 kV
ELECTROPUTERE India
(10; 18; 86) MVA / (150; 11.5; 156.8) kV
ELECTROPUTERE Indonesia
(0.2; 63) MVA / (33; 132) kV
ELECTROPUTERE Jordan
(1; 7.5; 15; 30; 45; 90) MVA / (11; 33; 33; 33; 132; 132) kV
ELECTROPUTERE Malaysia
(0.3; 50; 75; 100; 100; 100) MVA / (13.8 138; 138; 138; 138) kV
ELECTROPUTERE Philippines
(400; 250; 216) MVA / (400; 400; 242) kV
ELECTROPUTERE Romania
4 MVA / 10 kV
ELECTROPUTERE Russia
(0.1; 0.25; 0.4; 0.63; 1; 2.5; 16; 20; 30; 80; 125) MVA ELECTROPUTERE Syria / (20; 66; 20; 20; 20; 66; 66; 66; 230; 230) kV (2.5; 40; 63) MVA / (35; 150; 150) kV
ELECTROPUTERE Sudan
(20; 40) MVA / (132; 132) kV
ELECTROPUTERE Uganda
(15; 20; 25; 31.5; 50; 65) MVA / (154; 30; 154; 132; 154; 154) kV
ELECTROPUTERE Turkey
200 MVA / 231 kV
ELECTROPUTERE Yugoslavia
61
BLACK SEA GROUP POWER TRANSFORMERS
Partners of BLACK SEA GROUPfor services concerning to Power Transformers.
ICEMENERG SA-Rehabilitation and Research Institute for National Energy System (Romania). ICEMENERG SA offers professional services, as: ◘ Services in Power Substations field for Apparatus andTransformers insulation and life duration assessment, ◘ Prophylactic and Routine Tests for electrical Equipment in Primary and Secondary substations, ◘ Strength assessment of the overhead and underground Lines, ◘ Tests and Measurements concerning switching overvoltages, overcurrents, Electric and Magnetic fields and their influence to the electric Networks. References:
Dielectric properties of power transformers insulation by dielectric loss (tgd) measurement in the automate mode.
62
BLACK SEA GROUP POWER TRANSFORMERS
System front panel.
Diagnose result.
Equipment for quantity evaluation of moisture content of a Paper-Oil transformer insulation, based on the bias factor.
Three Phase RC group. Switching overvoltage protection for Generators and Motors
63
BLACK SEA GROUP POWER TRANSFORMERS
Partners of BLACK SEA GROUPfor services concerning to Power Transformers.
EMON Electric as erection company -Romania. EMON Electric has a large experience in Primary / Secondary Electrical Distribution Substations with Projects development in Romania and Overseas. EMON Electric Company is certified by Germanischer Lloyd Certification GmbH,20459 Hamburg for the application of the quality system according to DIN EN ISO 9001:2000. Business Areas: -Hitgh Voltage up to 400 kV Power Substation, -Hitgh Voltage up to 400 kV Power Lines, -Medium Voltage Power Substation and power Network CLIENT ELECTRICA MUNTENIA NORD SA –A SDFEE PLOIESTI – ACM 4 SIEMENS AG – TRANSPORTATION SYSTEMS in progress TRANSELECTRICA SA – AREVA – in progress ELECTROEXPERT ELECTRICA MUNTENIA NORD SA – SDFEE PLOIESTI ELECTICA SA – SISE MUNTENIA NORD EUROELECTRIC SA BUCURESTI CD ELECTRIC SRL BRASOV ELECON SA BRASOV CN CFR SA – REGIONALA CFR BUCURESTI TRANSELECTRICA SA – in progress DUCATTI ENERGIA ROMANIA SA BUSTENI BEN ELECTRO SERV SRL BRAILA ELECTRICA MUNTENIA NORD SA – SDFEE PLOIESTI – in progress ELCO BUCURESTI SA MULTIPROD ENERGO SRL BUZAU
PROJECT Deviation works of 20 kV electrical line – PT Pompe Azuga ES Columbia HV outgoings and cable connection to Substation Ploiesti Vest 220/110/20kV Targoviste Substation Retrofit – 220110Kv switchgears – primary switching equipment CSI – V1, 20/0,4 KV, 2*630KVA concrete envelope substation, Busteni DUCATI hall electrical power supply. CHIRESCU PENSION electrical power supply 110/20kv Busteni station warning installation repair CSI- V0 concrete envelope substation CSI-V3 20/0,4 KV, 630KVA Fagaras concrete envelope substation CSI-V0, 20/0,4 KV, 160KVA concrete envelope substation Aerial concrete envelope substation current repair and low voltage connector for VALEA CALUGAREASCA RAILWAY 200 MVA Targoviste electrical station, AT3 current repair 2*630KVA DUCATTI concrete envelope substation service CSI-V2 20/0.4 KV 1000 KVA concrete envelope substation PLOIESTI VEST substation electrical power supply – 110 kv Columbia station works 1000Kva 10/0,4 Kv metallic envelope substation 6/0,4 KV 250 KVA concrete envelope substation
64