Tc809a I56-3807-001

  • Uploaded by: Leonardo Benitez
  • 0
  • 0
  • March 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Tc809a I56-3807-001 as PDF for free.

More details

  • Words: 583
  • Pages: 2
Loading documents preview...
By Todd Alford at 3:49 pm, Jan 14, 2008

I56-3807-001

Installation AND MAINTENANCE Instructions

Model TC809A1059 Monitor Module SPECIFICATIONS Normal Operating Voltage: Maximum Current Draw: Average Operating Current: EOL Resistance: Maximum IDC wiring resistance: Maximum IDC Voltage: Maximum IDC Current: Temperature Range: Humidity: Dimensions: Accessories:

1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com

15 to 32 VDC 5.0mA (LED on) 375μA (group poll); 350μA (direct poll); 600μA (communicating, IDC shorted) 47K Ohms 1,500 Ohms 11 Volts 450µA 32°F to 120°F (0°C to 49°C) 10% to 93% Non-condensing 41⁄2˝ H × 4˝ W × 11⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep box.) SMB500 Electrical Box MOUNTING The TC809A1059 mounts directly to 4-inch square electrical boxes (see Figure 2). The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available.

BEFORE INSTALLING This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.

Figure 2. Module mounting:

NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION The TC809A1059 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary decade switches. It provides either a 2-wire or 4-wire fault tolerant initiating circuit for normally open contact fire alarm, supervisory, or security devices. The module has a panel controlled LED indicator. TC809A1059 is also UL listed as a commercial proprietary burglar alarm accessory. COMPATIBILITY REQUIREMENTS To ensure proper operation, these modules shall be connected to listed compatible system control panels only.

ISOLATED QUADRANT

Figure 1. Controls and indicators:

C1066-00

WIRING NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only. 1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. 2. Set the address on the module per job drawings. 3. Secure module to electrical box (supplied by installer), as shown in Figure 2.

C1067-00

HW-460-006

1

I56-3807-001

Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B: TO NEXT DEVICE

)–(

)–(

)+(

)+(

FROM PANEL OR PREVIOUS DEVICE

MONITOR MODULE

ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INTIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.

CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY

)–( )+( 47K EOL RESISTOR ELR-47K

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMENDED

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B POWER LIMITED: 450µA MAX. @ 11 VDC MAX ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.

C0918-00

Figure 4. Typical 4-wire fault tolerant initiating circuit configuration, NFPA Style D: TO NEXT DEVICE

)–(

)-(

)+(

)+(

ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INTIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.

FROM PANEL OR PREVIOUS DEVICE

MONITOR MODULE CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY )–( )+(

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMENDED

EOL RESISTOR IS INTERNAL AT TERMINALS 8 & 9

INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

C0919-02

HW-460-006

2

I56-3807-001 ©2007 Honeywell

Related Documents

Tc809a I56-3807-001
March 2021 0

More Documents from "Leonardo Benitez"

Tc809a I56-3807-001
March 2021 0
January 2021 2
February 2021 4
February 2021 1
March 2021 0