Loading documents preview...
ABB AS - 1 2007
Power Management System for Industrial Plants
ABB
IndustrialIT for PMS Introduction Electrical Process System configuration Functionality PMS References Benefits
Tasc of Power Management Systems
ABB AS - 3
Avoiding blackouts in industrial plants!
Power Sharing
Load Shedding
ABB
ABB AS - 4
Operational Drivers for IndustrialIT for PMS Several Generators Power Sharing with other plants/grids
}
Power Control
Critical Loads Limited In-plant Generation Insufficient reliability of grid supply
}
Load Shedding
Generator Modes and Operation Transformer Control and Monitoring Circuit Breaker Operation
}
Object Control
Connection to other plants/grids Bus-Tie operation
}
Synchronization
ABB
Why ABB IndustrialIT for PMS?
ABB AS - 5
In-depth knowledge of the electrical process 20 years experience in PMS implementations across the world (green-field and brown-field plants) Standard software, well documented, tested, proven technology Fast Response Time for Load Shedding and Power Control High Resolution and Accuracy of Sequence of Event recording Comply to class 3 EMC immunity Single responsibility: One supplier for PMS integrated with switchgear, protection, governor, excitation, transformer, tapchanger, Motor Control Centre, Variable Speed Drive, etc. Experience with EPC’s like: ABB Lummus, Bechtel, Chiyoda, Fluor Daniel, Foster Wheeler, JGC, Kellogg, Larson & Tubro, Mitsubisi, Snamprogetti, Technip, Toyo, Toshiba, etc.
ABB
Functionality Power Management Systems
Load Shedding
Active and Reactive Power Control
Supervision, Control and Data Acquisition (SCADA):
ABB AS - 6
Generator and Turbine
Transformer and Tapchanger
Circuitbreaker, Disconnector and Earthing switches
Motor
Synchronization
ABB
ABB AS - 7
Different names for the same system
PMS :
ENMC : Electrical Network Monitoring and Control system
ELICS : ELectrical Integrated Control System
PDCS : Power Distribution and Control System
LMS :
Load Management System
ECS :
Electrical Control System
etc.
Power Management System
ABB
Information Enabled Product . . .
Drivers
=
Fonts
ABB AS - 8
Utilities
ABB
Object approach Technical Spec.
Mech. Drawing
Elec. Diagram
Simulation Model
Control Program
ABB AS - 9
Test Report
ABB
ABB AS - 10
The global standard common for IEC and ANSI ...
ABB
800xA architecture for Power Management System Plant & Enterprise Management Systems Remote Users TCP/IP Network
Operator Station
Server
Engineering Station
Control Network
Router
DCS
AC800M Controller
ProfiNet IO
IEC 61850
MV
LV M
M
M
M
ABB AS - 11
G
Substation 1
Substation 2
Substation Z
Substation N
ABB
ControlIT
ControlIT AC 800M Hardware
ABB AS - 12
AC 800M
Built in redundant Ethernet
Very low power consumption
Communication & fieldbus interfaces
Hot swap of communication- and I/O modules
Local and remote I/O options
Industry quality hardware with excellent EMC and MTBF properties
ABB
Functionality IndustrialIT for PMS
Load Shedding
?
ABB AS - 13
With Without Load Load Shedding Shedding
ABB
ABB AS - 14
Load Shedding: The types
Fast Load Shedding on Loss of Power Resources
Load Shedding on Frequency Drop
Slow Load Shedding on Overload
Slow Load Shedding for Peak Shaving
Manual Load Shedding
ABB
Load Shedding: Keywords
ABB AS - 15
Fast Exact Flexible Co-ordinated Deterministic Security and Reliability Accurate Event Logging Operator Guidance Independent Back-up System (Click here for details)
ABB
ABB’s starting-point for Load Shedding
M1
15MW
20MW
G1
G2
M2
ABB AS - 16
9MW 6MW (5) (3)
M3
M4
1MW 20MW (1) (3)
30MW
M5
M6
Secure electrical power to critical loads
Minimal disturbance to plant operation
No spurious operation
M7
10MW 7MW 12MW (2) (4) (5)
ABB
Contingency Load Shedding 33 kV level (back-up)
G
G
G
G
G
M
6 kV levelG (back-up) M
G
M
G
G
M
M
M
M
G
M
M
M
400 V level G
ABB AS - 17
M
M
M
G
M
M
M
M
M
M
M
M
M
M
G
M
M
M
M
M
M
M
M
M
M
ABB
M
Fast Load Shedding – Required data Substation 1 G
G
G
G
G
G
33 kV M
G
G
M
Substation 2
G
G
6 kV M
M
M
BLUE bays (Critical Signals): CB position 5-10 ms.
ABB AS - 18
Power Flow
1 s.
Substation N 6 kV
M
M
M
M
M
RED bays (Load Shed Groups): Open Command 5-10 ms. CB position 1 s. Power Flow 1 s.
ABB
Fast Load Shedding – Busbar Load Tables 16 MW
16 MW
G1
G2
M1
M5
M2
M4
M6
2MW 2MW 5MW 5MW (2) (6) (5) (1)
ABB AS - 19
M3
M7 5MW 5MW (3) (7)
M8
2MW 2MW (4) (8)
Busbar Left 1. 0 MW 2. 2 MW 3. 2 MW 4. 2 MW 5. 7 MW 6. 9 MW 7. 9 MW 8. 9 MW
Busbar Right 1. 0 MW 2. 0 MW 3. 5 MW 4. 5 MW 5. 5 MW 6. 5 MW 7. 10 MW 8. 12 MW
ABB
Fast Load Shedding – Contingency Load Table 16 MW
16 MW
G1
G2
M1
M5
M2
M3
M4
M6
2MW 2MW 5MW 5MW (2) (6) (5) (1)
M7 5MW 5MW (3) (7)
M8
2MW 2MW (4) (8)
Busbar L + Busbar R = 1. 0 MW 0 MW 2. 2 MW 0 MW 3. 2 MW 5 MW 4. 2 MW 5 MW 5. 7 MW 5 MW 6. 9 MW 5 MW 7. 9 MW 10 MW 8. 9 MW 12 MW
Cont. 1 0 MW 2 MW 7 MW 7 MW 12 MW 14 MW 19 MW 21 MW
ABB AS - 20
PInhibit = PGeneration – PLoads = 32 – 21 = 11 MW
ABB
Fast Load Shedding – Trip of Generator 2 16 MW
16 MW
G1
G2
M1
M5
M2
M4
M6
2MW 2MW 5MW 5MW (2) (6) (5) (1)
ABB AS - 21
M3
Power Balance:
M7 5MW 5MW (3) (7)
M8
Σ PGen + PSR ≥ Σ PLoad + PInhibit
PSR = 5 MW
16 + 5 ≥ 21 + 11
21 ≥ 32 Shed 11 MW
Check Table Shed ≤ Prio 5
Shed M1, M3 and M5
2MW 2MW (4) (8)
ABB
Display Load Shedding SLD (before) 5.7 MW
Generator trip
7.2 MW 1.5 MW 50.12. Hz
ABB AS - 22
3.3 kV
MW
2.2
MW
1.8
1.8 MW
2.1 MW
ABB
ABB AS - 23
ABB
Display Load Shedding SLD (after) 3.9
MW
4.8 MW 1.5 MW 50.12. Hz
3.3 kV
MW
0.0
MW
1.8 MW
1.8
2.1 MW
ABB AS - 24
Ethernet TCP/IP
ABB
Display Load Shedding SLD (after) 3.9
MW
4.8 MW 1.5 MW 50.12. Hz
ABB AS - 25
3.3 kV
MW
0.0
MW
1.8
1.8 MW
2.1 MW
ABB
ABB AS - 26
Display Accumulated LoadShed table
ABB
IT for Functionality Industrial PMS Display Generator Capability Diagram
Load Shedding
Active and Reactive Power Control
P Rotor Instability Line
Maximum Excitation (Rotor Heating) Turbine Maximum
MVA-circle (Stator Heating)
Minimum Minimum PF-Leading Excitation Minimum PF-lagging Operating Minimum
ABB AS - 27
Q-Lead
Q-Lag
ABB
ABB AS - 28
ABB
Turbine Control
Primary Turbine Controller
ABB AS - 29
Droop or isochronous
PMS provides:
Manual control (Droop)
Manual MW setpoint
Automatic frequency control
Automatic setpoint control (MW sharing)
Automatic mode change:
CB trip
Turbine trip etc.
ABB
Generator Control
Primary AVR:
ABB AS - 30
Droop or voltage control
PMS provides:
Manual control (Droop)
Manual setpoint control (setpoint is PF)
Automatic Voltage Control (AVR receives raise/lower from PMS)
Automatic setpoint control (MVar sharing)
Automatic mode change:
CB trip
ABB
Active and Reactive Power Control
In island operation:
Maintain system frequency
Maintain system voltage
Connected to grid:
Control active power exchange
Control re-active power exchange
Share active and reactive power amongst the machines
ABB AS - 31
Participation factors
Efficient Power Generation optimization
Spinning Reserve optimization
Standby optimization
NOx constraints
P
Objectives Q-Lead
Coordinated control of power generation
Achieve stable operation
Q-Lag
ABB
Generator Control 5.7 MW 7.2 MW 1.5 MW 50.12. Hz 3.3 kV
ABB AS - 32
1.6
MW
2.2
MW
1.8 MW
1.8
2.1 MW
3.3 3.3 50.0 50.0 2.2 2.2 0.9 0.9 0.9 0.9 120.0 120.0 20.0 20.0
ABB
Integration with Protection & Control Units
ABB AS - 33
Protection Measuring of U,I,E, calculation of P & Q
Monitoring & Control
Interlockings
Alarm annunciation
Event Time Tagging
Disturbance Recording
Local storage of trip-events
Communication to PMS
ABB
ABB AS - 34
Synchronisation
Automatic Synchronisation
Manual Synchronisation
Adjust voltage magnitude
Adjust voltage frequency
Adjust voltage angle
Rough adjustments by PMS
Fine tuning by a Synchroniser
Close the breaker by the Synchoniser
ABB
Industrial plants / complexes / platforms Customer’s needs
Reliable Electrical Power.
Stable operation to avoid blackouts.
ABB’s response
Power Management system including Load Sheding system based on dynamic fast loadbalance Power Control.
ABB AS - 36
Customer’s benefits
No more blackouts due to trip chain of own generation units.
Reduced consumption electrical power from utility company due to better inhouse generation control. N+1 purpose.
ABB
QatarGas II LNG Customer’s needs
Experienced PMS supplier to be able to cope with new concept for LNG Compressor drives systems
ABB’s response
ABB AS - 37
Intelligent Power Management System controlling: 3* STG’s (each 44 MW) 1* GTG (33 MW) 6* VFD/GTG (each 45 MW) including: * NOx constrains considerations * Power flow limitations to QG 1 and QG 3 & 4 * Contingency Load Shedding.
Customer’s benefits
Reliable operation and avoiding black-outs.
ABB
Malaysia MLNG, Petronas/Shell Customer’s needs
Extension of Power Distribution System with 100 MW to 300 MW for two extra LNG trains
ABB’s response
Intelligent Power Management System including Load Shedding and Power Control
Is-limiters between the three 33 kV substations (triangle configuration)
ABB bv - 60
ABB AS - 38
Customer’s benefits
No need for a 132 kV substation including six 132/33 kV Power Transformers
Reliable operation and avoiding black-outs.
ABB
Named Project References HAR, refinery in Greece Shell Pernis refinery in the Netherlands Shell BLNG in Brunei Shell PDO in Oman ThaiOil, ThaiLube, RRC refineries in Thailand La Roche, CHP in UK
ABB AS - 39
Petrobras: REPAR, REDUC, RLAM refineries in Brazil Reliance: Hazira, Jamnagar & Haldia refineries in India
AFPC, Omar refinery in Syria ABF, Petronas MLNG Satu, Dua & Tiga in Malaysia StatOil Gullfaks, LNG Hammersfest & BP Amoco Valhall QatarGas II, III & IV, PS2 & PS3 in Qatar
ABB
ABB AS - 40
Named Customer References
ABB
ABB PMS allows you to:
Avoid black-outs (up to 500 kUSD / hour)
Power control including voltage control, frequency control, sharing power among generators and tie-line(s).
High Speed Contingency Load Shedding (< 100 ms.)
Reduce electricity costs FEEDER TERMINAL
ABB Network Partner
Minimize operational costs
Decreased number of operators Event driven maintenance Transformer Overload Management Single Window concept
ABB Transmit Oy Network Partner
?
Uaux = 80...2 65 Vdc/ac
Ion = 1/5 A (Io)
1MRS xxxxxx
fn = 50 Hz
Un = 100/110 V (U)
98 15 0
In = 1/5 A (I)
Uon = 100/110 V (Uo)
9 50 9
Reduce investment costs The total switched-off In case of a accumulated shortage of electrical power,
ABB AS - 41
REF541
Peak-shaving Re-active Power Control & Sharing
Minimized cabling and engineering The Optimizing Power shortcurrents Human Control, the Machine stability by Standby a Interfaces circuitbreaker of the Optimization, operation for all or the of secure the available power to critical loads Optimized network design
n+1 Limit electrical theswitching Criteria, electrical electrical the sub-systems number SCADA, generationimport of none generator etc. during canare and bepeak performed integrated distribution starts and by in Serial by interfaces off the with protection important &time control loads No need for big oversizing primary equipment the Maintaining the are system reduce Energy a spaghetti network trigger and peak adynamic good not for based ofwiring maintenance by aofPower plant the charges System Factor units according avoid toManagement load &operators cable tables ducts
ABB