Loading documents preview...
Reference : ETAP Training by OTI ETAP Help User
Short-Circuit Analysis Types of SC Faults
•Three-Phase Ungrounded Fault •Three-Phase Grounded Fault •Phase to Phase Ungrounded Fault •Phase to Phase Grounded Fault •Phase to Ground Fault
Fault Current •IL-G can range in utility systems from a few percent to possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all fault s). •In industrial systems the situation IL-G > I3-phase is rare. Typically IL-G .87 * I3-phase •In an industrial system, the three-phase fault conditio n is frequently the only one considered, since this typ e of fault generally results in Maximum current.
Purpose of Short-Circuit Studies • A Short-Circuit Study can be used to determine any or all of the following: • Calculate protective device close and latch capability • Determine protective device Interrupting capability • Protect equipment from large mechanical forces (maximum fault kA) • I2t protection for equipment (thermal stress) • Selecting ratings or settings for relay coordination
System Components Involved in SC Calculations • Power Company Supply • In-Plant Generators
• Transformers (using negative tolerance) • Reactors (using negative tolerance)
• Feeder Cables and Duct Systems (at lower temperature limits)
System Components Involved in SC Calculations • Overhead Lines (at lower temperature limit) • Synchronous Motors • Induction Motors • Protective Devices
Elements That Contribute Current to a Short-Circuit • Generator • Power Grid • Synchronous Motors • Induction Machines • Lumped Loads (with some % motor load) • Inverters
Elements Do Not Contribute Current in PowerStation • Static Loads • Motor Operated Valves
• All Shunt Y Connected Branches
Short-Circuit Phenomenon
i(t)
v(t)
v(t) Vm Sin( t
)
v(t)
i(t)
di Vm Sin( t ) (1) dt Solving equation 1 yields the following expression v(t)
Ri L
i(t)
Vm sin( t Z SteadyState
- )
Vm sin( - ) Z Transient (DC O ffset)
t
AC Current (Symmetrical) with No AC Decay
DC Current
AC Fault Current Including the D C Offset (No AC Decay)
Machine Reactance ( λ = L I )
AC Decay Current
Fault Current Including AC & DC Decay
ANSI Calculation Methods 1) The ANSI standards handle the AC Decay by varying machine impedance during a fault. ANSI
2) The ANSI standards handle the the dc offset by applying multiplying factors. The ANSI Terms for this current are: •Momentary Current •Close and Latch Current •First Cycle Asymmetrical Current
Sources and Models of Fault Currents in ANSI Standards Sources •Synchronous Generators •Synchronous Motors & Condensers •Induction Machines •Electric Utility Systems (Power Grids)
Models All sources are modeled by an internal voltage behind its impedance. E = Prefault Voltage R = Machine Armature Resistance X = Machine Reactance (X”d, X’d, Xd)
Synchronous Generators Synchronous Generators are modeled in three stages.
Synchronous Motors & Condenser s Act as a generator to supply fault curre nt. This current diminishes as the mag netic field in the machine decays.
Induction Machines
Transient Reactance
Treated the same as synchronous mot ors except they do not contribute to the fault after 2 sec.
Subtransient Reactance
Electric Utility Systems
Synchronous Reactance
The fault current contribution tends to r emain constant.
½
Cycle Network
This is the network used to calculate momentary short-circuit current an d protective device duties at the ½ cycle after the fault.
1 ½ to 4 Cycle Network This network is used to calculate the interrupting short-circuit current an d protective device duties 1.5-4 cycles after the fault.
30-Cycle Network This is the network used to calculate the steady-state short-circuit curre nt and settings for over current relays after 30 cycles.
Reactance Representation for Utility and Synchronous Machine ½ Cycle
1 ½ to 4 Cycle
30 Cycle
X”d
X”d
X”d
X”d
X”d
X’d
Hydro-Gen with Am ortisseur winding
X”d
X”d
X’d
Hydro-Gen without Amortisseur windin g
0.75*X”d
0.75*X”d
X’d
X”d
X”d
X”d
1.5*X”d
Utility
Turbo Generator
Condenser
Synchronous Motor
Reactance Representation for Induction Machine ½ Cycle
1 ½ to 4 Cyc le
>1000 hp , <= 1800 r pm
X”d
1.5*X”d
>250, at 3600 rpm
X”d
1.5*X”d
All others, >= 50 hp
1.2*X”d
3.0*X”d
< 50 hp
1.67*X”d
Note: X”d = 1 / LRCpu
Device Duty and Usage of Fault Currents from Different Networks ½ Cycle Currents (Subtransient Network)
1 ½ to 4 Cycle Currents (Transient Network)
HV Circuit Breaker
Closing and Latching Capability
Interrupting Capability
LV Circuit Breaker
Interrupting Capability
---
--Fuse
Interrupting Capability
SWGR / MCC
Bus Bracing
---
Relay
Instantaneous Settings
---
30 Cycle currents are used for determining overcurrent settings.
Momentary Multiplying Factor
MFm is calculated based on:
• Fault X/R (Separate R & X Networks) • Location of fault (Remote / Local generation) Comparisons of Momentary capability (1/2 Cycle) SC Current Duty
Device Rating
HV CB
Asymmetrical RMS Asymmetrical Crest
C&L RMS C&L RMS
HV Bus
Asymmetrical RMS Asymmetrical Crest
Asymmetrical RMS
Symmetrical RMS Asymmetrical RMS
Symmetrical RMS Asymmetrical RMS
LV Bus
Crest
Interrupting Multiplying Factor
MFi is calculated based on:
• Fault X/R (Separate R & X Networks) • Location of Fault (Remote / Local generatio n) • Type and Rating of CB
Comparisons of Interrupting Capability (1 ½ to 4 Cycle) SC Current Duty
Device Rating
Adj. Symmetrical RMS*
Adj. Symmetrical RMS*
Adj. Symmetrical RMS***
Symmetrical RMS
HV CB
LV CB & Fuse
HV CB Closing and Latching Capability Calculate ½ Cycle Current (Imom, rms, sym) using ½ Cycle Network. • Calculate X/R ratio and Multiplying factor MFm
• Imom, rms, Asym = MFm * Imom, rms, sym
MV CB Interrupting Capability Calculate 1½ to 4 Cycle Current (Imom, rms, sym) using ½ Cycle Network. • Determine Local and Remote contributions (A “local” contribution is f ed predominantly from generators through no more than one transfo rmation or with external reactances in series that is less than 1.5 tim es generator subtransient reactance. Otherwise the contribution is d efined as “remote”). • Calculate no AC Decay ratio (NACD) and multiplying factor MFi NACD = IRemote / ITotal ITotal = ILocal + IRemote (NACD = 0 if all local & NACD = 1 if all remote) • Calculate Iint, rms, adj = MFi * Iint, rms, Symm
LV CB Interrupting Capability • LV CB take instantaneous action. • Calculate ½ Cycle current Irms, Symm (I’f) from the ½ cycle network. • Calculate X/R ratio (IEEE method or ETAP method) and MFi (based on CB type). • Calculate adjusted interrupting current Iadj, rms, symm = MFi * Irms, Symm
Fuse Interrupting Capability Calculate ½ Cycle current Iint, rms, symm from ½ Cycle Network.
• Same procedure to calculate Iint, rms, asymm as for CB.
L-G Faults
L-G Faults Symmetrical Components
Sequence Networks
L-G Fault Sequence Network Connections If
3 Ia 0
If
3 VPrefault Z1 Z 2 Z0
if Zg
0
L-L Fault Sequence Network Connections Ia 2
I a1
If
3 VPrefault Z1 Z2
L-L-G Fault Sequence Network Connections Ia 2 If
I a1 I a 0
0 Ia
VPrefault Z0 Z 2 Z1 Z0 Z 2
if Zg
0
Transformer Zero Sequence Connections
Solid Grounded Devices and L-G Faults Generally a 3 - phase fault is the most severe case. L - G faults can be greater if : Z1 Z 2 & Z 0 Z1 If this conditions are true then : I f3 I f 1 This may be the case if Generators or Y/ Connected transformer are solidly grounded.
Thank You