Loading documents preview...
TRANSFORMER PROTECTION CAUSES OF FAILURE ENVIRONMENTAL SYSTEM
OPERATION DESIGN MANUFACTURE MATERIALS MAINTENANCE
TRANSFORMER PROTECTION
SYSTEM CAUSES OF FAILURE OVERVOLTAGES FAST TRANSIENTS LOAD REJECTION BACKFEEDING SHORTCIRCUITS
TRANSFORMER PROTECTION
OPERATIONAL CAUSES OF FAILURE LOAD DUTY OVERLOADING SWITCHING OPERATIONS OUT-OF-PHASE SYNCHRONISATION
TRANSFORMER PROTECTION
BASIC PROTECTION DIFFERENTIAL RESTRICTED EARTHFAULT
OVERFLUXING OVERCURRENT & EARTHFAULT
TRANSFORMER PROTECTION
DIFFERENTIAL PROTECTION WORKS ON MERZ-PRICE CURRENT COMPARISON PRINCIPLE RELAYS WITH BIAS CHARACTERISTIC SHOULD ONLY BE USED RELAY SHOULD BE STABLE DURING MAG-INRUSH & OVERFLUXING CONDITIONS
TRANSFORMER PROTECTION
WHY BIAS CHARACTERISTIC ? 100 / 1
100/50 KV
200 / 1 1A
1A
O
0A
OLTC SETTING IS AT MIDTAP
LOAD = 200 A
TRANSFORMER PROTECTION 100 / 1
100/50 KV
200 / 1 1A
0.9 A
O
0.1 A
OLTC SETTING IS AT 10% RELAY PICKUP SETTING IS O.2 A SO THE RELAY RESTRAINS
LOAD = 200 A
TRANSFORMER PROTECTION 100 / 1
100/50 KV
200 / 1 10 A
9A
O
1A
OLTC SETTING IS AT 10% RELAY PICKUP SETTING IS O.2 A SO THE RELAY OPERATES
2000 A
TRANSFORMER PROTECTION 100 / 1
100/50 KV
200 / 1 10 A
9A B
2000 A
B O
1A
MODIFIED PICKUP DUE TO A BIAS SETTING OF 30% IS 30% OF ((10+9)/2), THAT IS, 2.85 A BUT DIFF. CURRENT IS 1 A, SO THE RELAY RESTRAINS
TRANSFORMER PROTECTION 100 / 1
100/50 KV
200 / 1 0A
9A
2000 A B
B O
9A
MODIFIED PICKUP DUE TO A BIAS SETTING OF 30% IS 30% OF ((0+9)/2), THAT IS, 1.35 A BUT DIFF. CURRENT IS 9 A, SO THE RELAY OPERATES
TRANSFORMER PROTECTION
MAGNETISING INRUSH TRANSIENT CONDITION - OCCURS WHEN A TRANSFORMER IS ENERGISED
NORMAL OPERATING FLUX OF A TRANSFORMER IS CLOSE TO SATURATION LEVEL RESIDUAL FLUX CAN INCREASE THE MAG-CURRENT IN THE CASE OF THREE PHASE TRANSFORMER, THE POINT-ON-WAVE AT SWITCH-ON DIFFERS FOR EACH PHASE AND HENCE, ALSO THE INRUSH CURRENTS
TRANSFORMER PROTECTION INRUSH CURRENT
+ m
V
Im
STEADY STATE - m
TRANSFORMER PROTECTION INRUSH CURRENT
+ m
V
Im
STEADY STATE - m Im
2 m
V
SWITCH ON AT VOLTAGE ZERO - NO RESIDUAL FLUX
TRANSFORMER PROTECTION
MAGNETISING INRUSH IF SYMMETRICAL WAVE -- ONLY ODD HARMONICS
- 3RD AT LOW SATURATION LEVELS - HIGHER HARMONICS AT HEAVY SATURATION IF OFFSET WAVE -- MAX. INRUSH; 2ND & 3RD HARMONICS INITIAL INRUSH LIMITED BY AIR CORE INDUCTANCE INITIAL DECAY RATE HIGH -- REDUCES AS IRON COMES OUT OF SATURATION
TRANSFORMER PROTECTION
TYPICAL DECAY TIMES FOR MAG INRUSH MVA RATING
NO. OF CYCLES TO REACH 50% OF FIRST PEAK
0.5 -- 1.0
8 TO 10
1.0 -- 10
10 TO 60
> 10
60 TO 600
TRANSFORMER PROTECTION OVERFLUXING CONDITION
DIFFERENTIAL ELEMENT SHOULD BE BLOCKED FOR TRANSIENT OVERFLUXING-+ 25% OVERVOLTAGE CONDITION
OVERFLUXING WAVEFORM CONTAINS VERY HIGH 5TH HARMONIC CONTENT
43% 5TH HARMONIC CONTENT
TRANSFORMER PROTECTION
BIASED DIFF. PROTECTION FAST OPERATION ADJUSTABLE CHARACTERISTIC HIGH THROUGH FAULT STABILITY CT RATIO COMPENSATION MAGNETISING INRUSH RESTRAINT OVERFLUXING 5TH HARMONIC RESTRAINT
TRANSFORMER PROTECTION
DDT 12/32 FOR TRANSFORMERS UPTO 5 MVA INDUCTION DISC TYPE BIAS 20,30,40% PICKUP CURRENT 40-100% TIME DELAYED
TRANSFORMER PROTECTION DTH 31/32
FOR TRANSFORMERS ABOVE 5 MVA STATIC HIGH SPEED WITH 2ND & 5TH HARMONIC RESTRAINT
BIAS 15%, 30%, 45% PICKUP CURRENT 15%
UNBIASED HIGHSET
TRANSFORMER PROTECTION
OPERATING TIME (CYCLES)
NEED FOR HIGHSET UNIT 6 LOWSET WITH HAR. RESTRAINT
4
2
0 10 20 30 40 FAULT CURRENT (XIn)
TRANSFORMER PROTECTION
OPERATING TIME (CYCLES)
NEED FOR HIGHSET UNIT 6 LOWSET WITH HAR. RESTRAINT
4
2
INST. HIGHSET ELEMENT 0 10 20 30 40 FAULT CURRENT (XIn)
TRANSFORMER PROTECTION
MBCH BIASED DIFF. RELAY MANY NOVEL FEATURES MBCH 12 FOR 2 WNDG TFRS MBCH 13 FOR 3 WNDG TFRS MBCH 16 FOR OTHER APPLICATIONS
TRANSFORMER PROTECTION
TYPICAL MAG INRUSH WAVEFORMS
A B C
1/3 Cycle minimum
TRANSFORMER PROTECTION
COMPARITIVE CHARACTERISTICS (WITHOUT HIGHSET) OPERATING TIME (CYCLES)
6
RELAY WITH HAR. RESTRAINT 4
2 MBCH 0
10
20
30
FAULT CURRENT (XIn)
40
TRANSFORMER PROTECTION
ROLE OF BIAS
3
2
Operate
Differential current (x In) = I1+ I2 + I3 + I 4 1
Restrain
Setting range (0.1 - 0.5) 0
1
2
3
4
Effective bias (x In) = I1 + I 2 + I 3 + I 4 2
TRANSFORMER PROTECTION SATURATION DETECTOR NO SATURATION
I1 I2 I 1 + I2 I1 - I2 I1
I2
TRANSFORMER PROTECTION SATURATION DETECTOR NO SATURATION
SATURATION DUE TO THRO’ FAULT
I1 I2 I 1 + I2 I1 - I2 I1
I2
TRANSFORMER PROTECTION SATURATION DETECTOR NO SATURATION
SATURATION DUE TO THRO’ FAULT
I1 I2 I 1 + I2 I1 - I2 I1
I2
INTERNAL FAULT
TRANSFORMER PROTECTION USE OF ICT Dy1(-30 )
Interposing CT provides Vector correction Yd11(+30 )
Ratio correction Zero sequence compensation
R
R
R
TRANSFORMER PROTECTION
VECTOR GROUP CORRECTION Dy1 (-30 )
Yy0 0
87
Yd11 +30
Yy0, Yd1, Yd5 , Yy6, Yd7, Yd11, Ydy0 0 , -30 , -150 , 180,+150, +30 , 0
TRANSFORMER PROTECTION
SELECTION OF SUITABLE VECTOR CORRECTION FACTOR
Dy11 (+30 )
Yy0 0
87
Yd1 -30
TRANSFORMER PROTECTION
CT RATIO MISMATCH CORRECTION
200/1
33kV : 11kV 10 MVA IL = 175A
I L = 525A
0.875A
400/1
1.31 Amps 1A
1A
1.14
0.76
87
TRANSFORMER PROTECTION
ZERO SEQUENCE COMPENSATION +VE SEQUENCE CURRENTS BALANCE REQUIRE ZERO SEQUENCE CURRENT TRAPS FOR STABILITY
A
B
C
TRANSFORMER PROTECTION HIGH IMPEDANCE REF
Increased sensitivity for earth faults REF elements for each transformer winding CTs may be shared with differential element
64
64
64
TRANSFORMER PROTECTION
LIMITATION OF E/F CURRENT 1.0 Current (x full load)
0.2
IF
Source
IF
IS
IS
R
1.0 0.2 Fault position from neutral
R
Differential relay setting
% of Star winding protected
10% 20% 30% 40% 50%
58% 41% 28% 17% 7%
TRANSFORMER PROTECTION REF CONNECTIONS
3 Phase 3 wire
TRANSFORMER PROTECTION REF CONNECTIONS
3 Phase 3 wire
R CAG14
TRANSFORMER PROTECTION REF CONNECTIONS
3 Phase 3 wire
Delta winding
R CAG14
TRANSFORMER PROTECTION REF CONNECTIONS
3 Phase 3 wire
Delta winding
R CAG14
3 Phase 4 wire
TRANSFORMER PROTECTION REF CONNECTIONS
3 Phase 3 wire
Delta winding
R CAG14
3 Phase 4 wire
Alt’ 3 phase 4 wire V
TRANSFORMER PROTECTION
REF CASE I : NORMAL CONDITION P1
P2
P2
64
P1
UNDER NORMAL CONDITIONS NO CURRENT FLOWS THRO’ RELAY
TRANSFORMER PROTECTION
REF CASE II : EXTERNAL EARTH FAULT P1
P2
P2
64
P1
FOR AN EXTERNAL EARTH FAULT, THE CURRENT CIRCULATES BETWEEN THE PHASE & NEUTRAL CTs; NO CURRENT THRO’ THE RELAY
TRANSFORMER PROTECTION
REF CASE III : INTERNAL EARTH FAULT P1
P2
P2
64
P1
FOR AN INTERNAL EARTH FAULT THE UNBALANCED CURRENT FLOWS THRO’ THE RELAY
TRANSFORMER PROTECTION
HIGH IMPEDANCE DIFF. PROT. FOR AUTO TRANSFORMER
R
R
R
TRANSFORMER PROTECTION
OVERFLUXING -- BASIC THEORY V = kf Causes Low frequency High voltage Geomagnetic disturbances
2m
m Ie
Effects Tripping of differential element (Transient overfluxing) Damage to transformers (Prolonged overfluxing)
TRANSFORMER PROTECTION
OVERFLUXING PROTECTION V
K f
Trip and alarm outputs for clearing prolonged overfluxing Alarm : Definite time characteristic to initiate corrective action
Trip : IDMT or DT characteristic to clear overfluxing condition
TRANSFORMER PROTECTION
BACKUP PROTECTION FOR TRANSFORMERS INFLUENCING FACTORS : VECTOR CONFIGURATION TYPE OF EARTHING INFEED CONDITIONS
TRANSFORMER PROTECTION
STAR -- DELTA UNGROUNDED
~
LOAD
CAG 37 50 CDG 31
51 CDG 31
51 64 67 N CDD 21
VDG 14
TRANSFORMER PROTECTION WHERE DO WE NEED 3 O/C ?
2:1:1 DISTRIBUTION FOR PH--PH FAULT IF MIN. F.C > 4 X FULL LOAD, THEN 2 O/C CAN BE USED
TRANSFORMER PROTECTION
UNRESTRICTED E/F PROTECTION 3 x 51 51N
PROVIDES BACKUP PROTECTION FOR SYSTEM TIME DELAY REQUIRED FOR COORDINATION
TRANSFORMER PROTECTION
STAR -- STAR INTERCONNECTED
CAG 17 50
50 CAG 17
CDD 21
67
67 CDD 21
67 N
67 N
CDD 21
CDD 21
H.S CAN BE APPLIED ON BOTH SIDES DIREC. O/C & E/F RELAYS ARE PREFERRED
TRANSFORMER PROTECTION
OVERLOAD PROTECTION RATING OF A TFR IS BASED ON THE ALLOWABLE TEMPERATURE RISE ABOVE AN ASSUMED MAX. AMBIENT TEMPERATURE SHORT PERIODS OF OVERLOAD ARE PERMISSIBLE TO AN EXTENT DEPENDING ON PREVIOUS LOADING
TRANSFORMER PROTECTION
OVERLOAD PROTECTION
(CONTD..)
SUSTAINED EXCESSIVE OVERLOAD LEADS TO DETERIORATION OF INSULATION TEMP. OF 98*C GIVES NORMAL LIFE SPAN OF 20-30 YRS
LIFE SPAN IS HALVED FOR EVERY 6*C TEMP. INCREASE PROTECTION -- DEFINITE TIME DELAYED O/C
TRANSFORMER PROTECTION TYPICAL PROTECTIONS FOR TRANSFORMER
51
51
64 51N
50N
ICT
50 87
TRANSFORMER PROTECTION
CT REQUIREMENTS RELAY
VK >
IMAG <
DDT
2 IF ( RCT+2RL+RB )
@ VK/4, 3%In
DTH
40 In ( RCT+2RL )
@ VK/4, 3%In
MBCH
24 In ( RCT+2RL )
@ VK/2, 10%In
CAG 14
2 IF ( RCT+2RL )
@ VK/2, 3%In
TRANSFORMER PROTECTION
CT REQUIREMENTS RELAY
VK >
IMAG <
DDT
2 IF ( RCT+2RL+RB )
@ VK/4, 3%In
DTH
40 In ( RCT+2RL )
@ VK/4, 3%In
MBCH
24 In ( RCT+2RL )
@ VK/2, 10%In
CAG 14
2 IF ( RCT+2RL )
@ VK/2, 3%In
TRANSFORMER PROTECTION
CT REQUIREMENTS RELAY
VK >
IMAG <
DDT
2 IF ( RCT+2RL+RB )
@ VK/4, 3%In
DTH
40 In ( RCT+2RL )
@ VK/4, 3%In
MBCH
24 In ( RCT+2RL )
@ VK/2, 10%In
CAG 14
2 IF ( RCT+2RL )
@ VK/2, 3%In
TRANSFORMER PROTECTION
CT REQUIREMENTS RELAY
VK >
IMAG <
DDT
2 IF ( RCT+2RL+RB )
@ VK/4, 3%In
DTH
40 In ( RCT+2RL )
@ VK/4, 3%In
MBCH
24 In ( RCT+2RL )
@ VK/2, 10%In
CAG 14
2 IF ( RCT+2RL )
@ VK/2, 3%In
TRANSFORMER PROTECTION
CT REQUIREMENTS FOR O/C RELAYS ELEMENT
CLASS
OUTPUT VOLTAGE
INST.
5 P10
TO DRIVE 2 X ISET
IDMT
5 P 10
TO DRIVE 10 X ISET
TRANSFORMER PROTECTION
CT REQUIREMENTS FOR O/C RELAYS ELEMENT
CLASS
OUTPUT VOLTAGE
INST.
5 P10
TO DRIVE 2 X ISET
IDMT
5 P 10
TO DRIVE 10 X ISET
TRANSFORMER PROTECTION
SETTING CRITERIA BIASED DIFF. CURRENT PICKUP IS SET JUST ABOVE THE STANDING UNBALANCE CURRENT DUE TO OLTC, CT MISMATCH AND ERRORS BIAS SLOPE SHOULD TAKE CARE OF SATURATION DUE TO HEAVY THRO’ FAULT
TRANSFORMER PROTECTION
SETTING CRITERIA (CONTD...) HIGH IMPEDANCE DIFF. & REF LOWEST POSSIBLE SETTING STAB. RESISTOR = IF (RCT + 2RL)/Is - (VA BURDEN)/ Is2 WHERE IF = RCT = RL = Is =
MAX. FAULT CURRENT CT SECONDARY RESISTANCE ONE-WAY LEAD RESISTANCE SETTING CURRENT
TRANSFORMER PROTECTION
SETTING CRITERIA (CONTD...) OVERFLUXING RELAY CHARACTERISTIC SHOULD MATCH THE TFR WITHSTAND
O/C & E/F TO BE CO-ORDINATED WITH DOWNSTREAM RELAYS
TRANSFORMER PROTECTION
INSTANTANEOUS ELEMENT SETTING
R
IF
RELAY SETTING > IF AND MAG INRUSH PICKUP = 1.3 X MVA / ( 1.732 X KV X pu IMP.)
THANK YOU
50
51
WORLD LEADER IN PROTECTION & CONTROL
abcd
24
87 64
67 67N
99