Transformer Protection

  • Uploaded by: supermannon
  • 0
  • 0
  • January 2021
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Transformer Protection as PDF for free.

More details

  • Words: 4,494
  • Pages: 105
Loading documents preview...
Protection Engineering And Research Laboratories Session VII : Transformer Protection 9th

Training on Power System Element Protection, & 17th March, 2007 at L&T Manappakam, Chennai.

Dr. G. Pradeep Kumar

Contents 

Introduction



Over current protection



Parallel transformer protection



Earth faults protection



Biased differential protection



Auto transformer protection



Inter-turn fault protection



Over flux protection



Over load protection

© 2007 Protection Engineering And Research Laboratories

17th March 2007 2

Introduction © 2007 Protection Engineering And Research Laboratories

17th March 2007 3

Introduction Transformer Fault Categories

 Winding and terminal faults  Sustained or un-cleared external faults

 Abnormal operating conditions such as overload, over voltage and over fluxing  Core faults

© 2007 Protection Engineering And Research Laboratories

17th March 2007 4

Transformer Operation

I

V

A2

Ø

EP

A1

© 2007 Protection Engineering And Research Laboratories

17th March 2007 5

Transformer Operation

I

V

A2

EP

A1

© 2007 Protection Engineering And Research Laboratories

a2

ES

a1

17th March 2007 6

Transformer Operation

IP

V

A2

EP

A1

© 2007 Protection Engineering And Research Laboratories

a2

IS

ES

a1

17th March 2007 7

Transformer Connections a

A

C1

a2

A2

a1 c1

C

b1

A1

C2 B1

B2

b

B

© 2007 Protection Engineering And Research Laboratories

b2

c2 c

17th March 2007 8

Transformer Connections 

“Clock Face” numbers refer to position of low voltage phase-

neutral vector with respect to high voltage phase neutral vector 

Line connections made to highest numbered winding terminal available



Line phase designation is same as winding



Example 1 : Dy11 Transformer



High Voltage Windings

How to connect the windings ?

A Phase Windings B Phase Windings C Phase Windings

A2 B2

C2 © 2007 Protection Engineering And Research Laboratories

Low Voltage Windings

A1

a1

a2

B1

b1

b2

C1

c1

c2

17th March 2007 9

Vector Group Example Dy11 12 11

30°

© 2007 Protection Engineering And Research Laboratories

17th March 2007 10

Vector Group Example Dy11 1. Draw Phase-Neutral Voltage Vectors

A 

Line Designation a 30 ° b

C

B c

© 2007 Protection Engineering And Research Laboratories

17th March 2007 11

Vector Group Example Dy11 2. Draw Delta Connection A a

b

C

B

© 2007 Protection Engineering And Research Laboratories

c 17th March 2007 12

Vector Group Example Dy11 3. Draw A Phase Windings A a a2 A2

a1

b

A 1 C

B

© 2007 Protection Engineering And Research Laboratories

c 17th March 2007 13

Vector Group Example Dy11 4. Complete Connections A a C1

A2

a 2 a1

C 2 C

c 1

A 1 B 1

B 2

B

© 2007 Protection Engineering And Research Laboratories

b1

b2

b

c 2 c 17th March 2007 14

Vector Group Example Dy11 5. Winding representation on core

A

B

C

A 2 B 2 C2

A 1

a1

a2

B 1

b1

b2

C1

© 2007 Protection Engineering And Research Laboratories

c 1

c 2

a

b

c

17th March 2007 15

Over Current Protection of Transformer © 2007 Protection Engineering And Research Laboratories

17th March 2007 16

11kV Distribution Transformers Typical Fuse Ratings Transformer rating

Fuse

kVA

Full load current (A)

Rated current (A)

Operating time at 3 x rating(s)

100

5.25

16

3.0

200

10.5

25

3.0

300

15.8

36

10.0

500

26.2

50

20.0

1000

52.5

90

30.0

© 2007 Protection Engineering And Research Laboratories

17th March 2007 17

Distribution Transformers Protection 3.3kV 200/5

1500/5

51

50

51 N

50 N

1MVA 3.3/0.44kV

51 N

64

© 2007 Protection Engineering And Research Laboratories

1500/5

17th March 2007 18

Distribution Transformers Protection 11kV

51

50

64

1000/5

5MVA 11/3.3kV

51 N

64

1000/5

3.3kV © 2007 Protection Engineering And Research Laboratories

17th March 2007 19

Transformer Over Current Protection Requirements  Fast operation for primary short circuits  Discrimination with downstream protections  Operation within transformer withstand  Non-operation for short or long term overloads  Non-operation for magnetising inrush

© 2007 Protection Engineering And Research Laboratories

17th March 2007 20

Instantaneous Over Current Protection Source

LV

HV

50 51 50 set to 1.2 to 1.3 x through fault level © 2007 Protection Engineering And Research Laboratories

17th March 2007 21

Transient Overreach Concerns relay response to offset waveforms (DC transient)

Definition I1 - I2 I2

x 100

I2 I1

D.C

I1 = Steady state rms pick up current I2 = Fully offset rms pickup current

© 2007 Protection Engineering And Research Laboratories

17th March 2007 22

Instantaneous Over Current Protection HV

LV

Source

50

50

50 Inst O/C

51

51

51 Time O/C

© 2007 Protection Engineering And Research Laboratories

17th March 2007 23

Instantaneous Over Current Protection 50 set to 1.2 - 1.3 x through fault level

Relay “Behind” Transformer

Grading Margin

50 Setting © 2007 Protection Engineering And Research Laboratories

Max HV Fault Level (at Transformer) 17th March 2007 24

Instantaneous Over Current Protection

51

51/ 50

HV2

HV1

51

HV1

HV2

LV

Time LV

Current

IF(LV)

IF(HV)

1.2IF(LV) © 2007 Protection Engineering And Research Laboratories

17th March 2007 25

2-1-1 Distribution I 3Ø

I 3Ø

0.866I 3Ø I 3Ø

© 2007 Protection Engineering And Research Laboratories

17th March 2007 26

2-1-1 Distribution

HV relay

0.4 sec LV relay

0.866 I 3Ø © 2007 Protection Engineering And Research Laboratories

I 3Ø 17th March 2007 27

Parallel Transformers Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 28

Parallel Transformer Protection Directional Over Current

51 67

Grid supply

Feeders 51

67

51

51 © 2007 Protection Engineering And Research Laboratories

17th March 2007 29

Parallel Transformer Protection Non-directional Over Current

51 51

Grid supply

Bus Section

Feeders

51

51 © 2007 Protection Engineering And Research Laboratories

51 17th March 2007 30

Parallel Transformer Protection Partial Differential Grid supply

P1

P2

S1 S2

67

67 51

S2 S1 P2

P1

51 51

© 2007 Protection Engineering And Research Laboratories

51

17th March 2007 31

Earth Fault Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 32

Earth Fault in a “DY” Transformer Resistance Grounded 3 p.u. turns

x

IP

PR

1 p.u. turns

R IF



Resistor “R” limits earth fault current to load values



For a fault at “x”;

Fault current IF = x.IFL 

Effective turns ratio is 3 : x



Line current on delta side for this fault IP= (x2/ 3).IFL

© 2007 Protection Engineering And Research Laboratories

17th March 2007 33

Over Current Protection on Delta Side of “DY” Transformer If as multiple of IF.L. 1.0 0.9 

IF

Fault Current Star Side

0.8 0.7 0.6

51

0.5

Over Current Relay

0.4 0.3

Fault Current Delta Side

0.2 0.1

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

© 2007 Protection Engineering And Research Laboratories

1.0

x p.u..

17th March 2007 34

Earth Fault in a “DY” Transformer Solidly Grounded If as multiple of IF.L. 10

Fault Current Star Side

9 

IF

8 7 6 5 4 3

Fault Current Delta Side

2 1

x 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 © 2007 Protection Engineering And Research Laboratories

p.u..

17th March 2007 35

Earth Fault in a “YD” Transformer Solidly Grounded If as multiple of IF.L. IF

10

IF

9 8



7 6

IP

IN

IP

5 4 3

2 1

IN

 0.1 0.2 0.3 © 2007 Protection Engineering And Research Laboratories

0.4 0.5

0.6 0.7 0.8 0.9 1.0

p.u..

17th March 2007 36

Earth Fault in a “DY” Transformer Resistance Grounded 

x2   3 For relay operation,    S

I

Differential Relay Setting = IS

x2 e.g. If  S  20%, then  20% for operation 3 i.e. x  59% Thus 59% of Y winding is not protected

Differential Relay Setting 10% 20% 30% 40% 50% © 2007 Protection Engineering And Research Laboratories

% of Star Winding Protected 58% 41% 28% 17% 7% 17th March 2007 37

Un-restricted Earth Fault Protection

51N

51

51

51

 Provides back-up protection for system  Time delay required for co-ordination © 2007 Protection Engineering And Research Laboratories

17th March 2007 38

Un-restricted Earth Fault Protection

51N

51

51 51

51N



Can provide better sensitivity (C.T. ratio not related to full load current  Improved “effective” setting)



Provides back up protection for transformer and system

© 2007 Protection Engineering And Research Laboratories

17th March 2007 39

Restricted Earth Fault Protection Star Winding

Protected Zone

REF



Relay only operates for earth faults within protected zone.



Uses high impedance principle.



Stability level : usually maximum through fault level of transformer

© 2007 Protection Engineering And Research Laboratories

17th March 2007 40

Restricted Earth Fault Protection Star Windings

A B C N LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated © 2007 Protection Engineering And Research Laboratories

17th March 2007 41

Restricted Earth Fault Protection Star Windings A B C N

LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated © 2007 Protection Engineering And Research Laboratories

17th March 2007 42

Restricted Earth Fault Protection Delta Winding

Source

REF

Protected zone

 Delta winding cannot supply zero sequence current to system

 Stability : Consider max LV fault level  Recommended setting : less than 30% minimum earth fault level © 2007 Protection Engineering And Research Laboratories

17th March 2007 43

High Impedance Differential Protected Circuit ZM

RCT

RCT RL

IF

RL

IS

VS

RL

ZM

RST R

RL



Voltage across relay circuit  VS = IF (RCT + 2 RL)



Stabilizing resistor (RST) used to limit spill current in the relay

path to less than the relay setting (IS) 

RST = (VS/IS) – RR



VK > 2VS = 2 IF (RCT + 2 RL)

© 2007 Protection Engineering And Research Laboratories

17th March 2007 44

High Impedance Differential Non-linear Resistors 

During internal faults the high impedance relay circuit offers an excessive burden to the CT‟s.



A very high voltage develops across the relay circuit and the CT‟s.



Can cause damage to insulation of CT, secondary winding and relay.



Magnitude of peak voltage VP is given by an approximate formula (based on experimental results) VP = 22 [VK (VF - VK)]



Where VF = Max. prospective voltage in the absence of saturation. (= IFmax . Relay circuit total impedance)



Metrosil required if VP > 3kV

© 2007 Protection Engineering And Research Laboratories

17th March 2007 45

Restricted Earth Fault Protection Example 1 1MVA (5%) 11000V 415V

1600/1 RCT = 4.9

80MVA

Calculate : 1)

Setting voltage (VS)

2)

Value of stabilising resistor required

1600/1 RCT = 4.8

RS

3)

Effective setting

4)

Peak voltage developed by CT‟s for internal fault

IS = 0.1 Amp

2 Core 7/0.67mm (7.41/km) 100m Long © 2007 Protection Engineering And Research Laboratories

17th March 2007 46

Restricted Earth Fault Protection Example 1 Earth fault calculation :Using 80MVA base Source impedance = 1 p.u. 1 P.U.

Transformer impedance = 0.05 x 80 = 4 p.u. 1 1 4 I1

Total impedance = 14 p.u.  I1 =

4 I2

1 = 0.0714 p.u. 14

Base current = 80 x 106 3 x 415

= 111296 Amps 4 Sequence Diagram

 IF I0

© 2007 Protection Engineering And Research Laboratories

= 3 x 0.0714 x 111296 = 23840 Amps (primary) = 14.9 Amps (secondary) 17th March 2007 47

Restricted Earth Fault Protection Example 1 (1) Setting voltage

VS = IF (RCT + 2RL) Assuming “earth” CT saturates, RCT = 4.8 ohms 2RL = 2 x 100 x 7.41 x 10-3 = 1.482 ohms  Setting voltage = 1.49 (4.8 + 1.482) = 93.6 Volts (2) Stabilising Resistor (RST) RS = (VS/ IS) – (1/IS2)

Where IS = relay current setting

RS = (93.6/0.1) – (1/ 0.12) = 836 ohms © 2007 Protection Engineering And Research Laboratories

17th March 2007 48

“B” Weber/m2 (Tesla) (multiply by Kv to obtain rms secondary volts)

Restricted Earth Fault Protection Example 1

1.6

Kv

1.2

Ki

Line & Neutral CT

158

0.341

Earth CT

236

0.275

0.8

0.4

0

0.04

0.08

0.12

“H” AT/mm (multiply by Ki to obtain total exciting current in Amps) © 2007 Protection Engineering And Research Laboratories

17th March 2007 49

Restricted Earth Fault Protection Example 1 (3) Effective setting IP = CT ratio x (IS + IMAG) Line & Neutral CTs Flux density at 93.6V = 93.6/158 = 0.592 Tesla From graph, mag. Force at 0.592 Tesla = 0.015 AT/mm Mag. Current = 0.015 x 0.341 = 0.0051 Amps

‘Earth’ CT Flux density at 93.6V = 93.6/236 = 0.396 Tesla From graph, mag. Force at 0.396 Tesla = 0.012 AT/mm Mag. Current = 0.012 x 0.275 = 0.0033 Amps Thus, effective setting = 1600 x (0.1 + [(4 x 0.0051) + 0.0033]) = 197. 92A © 2007 Protection Engineering And Research Laboratories

17th March 2007 50

Restricted Earth Fault Protection Example 1 Transformer full load current = 1391 Amps  Effective setting = (198/1391) x 100% = 14.2% x rated 4)

Peak voltage = 22[VK (VF - VK)] VF = 14.9 x VS/IS = 14.9 x 936 = 13946 Volts For „Earth‟ CT, VK = 1.4 x 236 = 330 Volts (from graph)  VP = 22 [330 (13946 - 330)] = 6kV Thus, non-linear resistor is to be used.

© 2007 Protection Engineering And Research Laboratories

17th March 2007 51

Restricted Earth Fault Protection Parallel Transformer T1

N A B C

Bus Section

T2

415 Volt Switchboard © 2007 Protection Engineering And Research Laboratories

17th March 2007 52

Parallel Transformer CT in Earth Circuit N A B C

T1

51N

Bus Section Open

T2

51N

© 2007 Protection Engineering And Research Laboratories

415 Volt Switchboard

17th March 2007 53

Parallel Transformer CT in Earth & Neutral Circuits T1

NA B C

51N

Bus section open

T2

51N 415 volt switchboard © 2007 Protection Engineering And Research Laboratories

17th March 2007 54

Parallel Transformer Residual CT Connection N A B C

T1

F2

Bus section Will mal-operate if bus section is open for fault at F1 T2

F1 415 volt switchboard No mal-operation for fault at F2 (but setting must be greater than load neutral current) © 2007 Protection Engineering And Research Laboratories

17th March 2007 55

Biased Differential Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 56

Differential Protection 

Phase differential protection may be justified for larger transformers (generally > 5MVA).



Provides fast operation on any winding



Measuring principle : 

Based on the same circulating current principle as the restricted earth fault protection



However, it employs the biasing technique, to maintain stability for heavy through fault current



Biasing allows mismatch between CT outputs.



Biasing is essential for transformers with tap changing facility.



Another important requirement of transformer differential protection is immunity to magnetising in rush current.

© 2007 Protection Engineering And Research Laboratories

17th March 2007 57

Biased Differential Protection Differential Current

I1

BIAS

BIAS

I1 - I2

OPERATE

I2 RESTRAIN

OPERATE

I1 - I2 (I1+I2)/ 2

Mean Thro‟ Current

Bias = Differential current / Mean through current © 2007 Protection Engineering And Research Laboratories

17th March 2007 58

Biased Differential Protection PROTECTED ZONE HV

LV

R



Correct application of differential protection requires CT ratio and winding connections to match those of transformer.



CT secondary circuit should be a “replica” of primary system.



Account for; 

Difference in current magnitude



Phase shift



Zero sequence currents

© 2007 Protection Engineering And Research Laboratories

17th March 2007 59

Differential Protection CT Connections P1

P2

A2

A1

A

a1

B

© 2007 Protection Engineering And Research Laboratories

a2

P2

P1

C 17th March 2007 60

Differential Protection Interposing CT Connections P1 S1

P2

A2

A1

a1

a2

P2

S2

S1

S2

S1 P1

P2

R R R

© 2007 Protection Engineering And Research Laboratories

P1 S2

Interposing CT provides 

Vector correction



Ratio correction



Zero sequence compensation

17th March 2007 61

Differential Protection Example 2 15MVA 66kV / 11kV

150/5 P1

P2

S1

S2

A2

A1 a1

a2

800/5 P2 S2

P1

S1

Dy1

 For the application shown above, consider (1)

Winding full load current

(2)

Effect of tap changer (if any)

(3)

C.T. polarities

© 2007 Protection Engineering And Research Laboratories

17th March 2007 62

Differential Protection Example 2 15MVA 66kV / 11kV

150/5 P1

P2

S1

S2

A2

A1 a1

a2

800/5 P2 S2

P1 S1

Dy1

Assuming no tap changer Full load currents :-

66kV : 131 Amp = 4.37 A (sec.) 11kV : 787 Amp = 4.92 A (sec.) However, require 11kV C.T.‟s to be connected in  Thus, secondary current = 3 x 4.92 = 8.52A

 RATIO CORRECTION IS REQUIRED © 2007 Protection Engineering And Research Laboratories

17th March 2007 63

Differential Protection Example 2 150/5 P1 P2 S1

A2

A1

a1

a2

S2

800/5 P2 P1 S1

??

S2

?? S2

S1

??

R

P1

P2

??

R R

© 2007 Protection Engineering And Research Laboratories

17th March 2007 64

Differential Protection Example 2  It is a normal practice to connect 11kV C.T.‟s in “Star” and utilise a

“Star”/”Delta” interposing C.T. (this

method reduces lead VA burden on the line C.T.‟s).  Current from 66kV side = 4.37 A  Thus, current required from “Delta” winding of ICT = 4.37A  Current input to “Star” winding of ICT = 4.92 A   Required ICT ratio = 4.92 / (4.37 /3) = 4.92 / 2.52  Can also be expressed as  5 / 2.56 © 2007 Protection Engineering And Research Laboratories

17th March 2007 65

Differential Protection Example 2 150/5 P1 P2 S1

A2

A1

a1

a2

S2

800/5 P2 P1 S1

4.37A

S2

4.92A S2

S1

(2.56)

R

P1

P2

(5)

R R

© 2007 Protection Engineering And Research Laboratories

17th March 2007 66

Differential Protection Example 2 – Effect of Tap Changer  Assume 66kV +5%, -15%  Interposing C.T. ratio should be based on mid tap position  Mid Tap (-5%) = 62.7 kV  Primary current (@15 MVA) = 138 Amp  Secondary current = 4.6 Amp   Interposing C.T. ratio required = 4.92 / (4.6/ 3) = 4.92 / 2.66  May also be expressed as : 5 / 2.7  As compared with 5 / 2.56 based on nominal voltage © 2007 Protection Engineering And Research Laboratories

17th March 2007 67

Differential Protection Example 2 – Vector Group Current distribution verification P1

S1

P2

A2

A1

a1

a2

P2

P1

S1

S2

S2

S1 P1

S2

P2

R R R

© 2007 Protection Engineering And Research Laboratories

17th March 2007 68

Differential Protection Example 2 – Vector Group Current distribution verification P1

S1

P2

A2

A1

a1

a2

P2

P1

S1

S2

S2

S1 P1

S2

P2

R R R

© 2007 Protection Engineering And Research Laboratories

17th March 2007 69

Differential Protection Example 2 – Vector Group Current distribution verification P1

S1

P2

A2

A1

a1

a2

P2

P1

S1

S2

S2

S1 P1

S2

P2

R R R

© 2007 Protection Engineering And Research Laboratories

17th March 2007 70

Differential Protection Example 2 – Vector Group Current distribution verification P1

S1

P2

A2

A1

a1

a2

P2

P1

S1

S2

S2

S1 P1

S2

P2

R R R

© 2007 Protection Engineering And Research Laboratories

17th March 2007 71

Combined REF and Differential Protection A2

A1 a1

a2

P1

P2

S1

P1

S1 REF

P2

S2

S2

P2 P1 S1

S2 To differential relay © 2007 Protection Engineering And Research Laboratories

17th March 2007 72

Virtual ICT in Numerical Relays Power transformer

Ratio correction

Vector correction

Virtual ICT

Differential element

© 2007 Protection Engineering And Research Laboratories

Virtual ICT

17th March 2007 73

Stability for Inrush Currents © 2007 Protection Engineering And Research Laboratories

17th March 2007 74

Transformer Magnetizing Characteristics

Twice Normal Flux

Normal Flux

Normal No Load Current

No Load Current at Twice Normal Flux

© 2007 Protection Engineering And Research Laboratories

17th March 2007 75

Transformer Magnetizing Current Steady State V + m

 Im

- m

© 2007 Protection Engineering And Research Laboratories

17th March 2007 76

Magnetizing Inrush Current Switch on at voltage zero - No residual flux

Im 2m

 V

© 2007 Protection Engineering And Research Laboratories

17th March 2007 77

Effect of Inrush Current on Differential Protection Effect of magnetising current  Appears on one side of transformer only  Seen as fault by differential relay  Normal steady state magnetising current is less than relay setting  Transient magnetising inrush could cause relay to operate © 2007 Protection Engineering And Research Laboratories

17th March 2007 78

Effect of Inrush Current on Differential Protection Solution 1 : Time delay  Allow magnetising current to die away before relay can operate  Slows operation for genuine transformer faults

© 2007 Protection Engineering And Research Laboratories

17th March 2007 79

Effect of Inrush Current on Differential Protection Solution 2 : 2nd (and 5th) harmonic restraint  Makes relay immune to magnetising inrush  Slow operation may result for genuine

transformer faults if CT saturation occurs

© 2007 Protection Engineering And Research Laboratories

17th March 2007 80

Effect of Inrush Current on Differential Protection Solution 3 : Gap measurement technique  Inhibits relay operation during magnetising inrush  Operate speed for genuine transformer faults unaffected by significant CT saturation

© 2007 Protection Engineering And Research Laboratories

17th March 2007 81

Gap Measurement Technique Typical Magnetising Inrush Waveforms

A B C

© 2007 Protection Engineering And Research Laboratories

17th March 2007 82

Gap Measurement Technique Bias Differential Threshold

Differential comparator

T1 = 5ms

T2 = 22ms Trip

© 2007 Protection Engineering And Research Laboratories

17th March 2007 83

Gap Measurement Technique Stability for Inrush Current Bias differential threshold

Differential comparator

Trip T1 = 5ms

T2 = 22ms

Differential input

Comparator output T1

Trip T2 Reset

© 2007 Protection Engineering And Research Laboratories

17th March 2007 84

Gap Measurement Technique Operation for Internal Faults Bias differential threshold

Differential comparator

Trip T1 = 5ms

T2 = 22ms

Differential input

Comparator output

T1 Trip T2 Reset © 2007 Protection Engineering And Research Laboratories

17th March 2007 85

Auto Transformer Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 86

Auto Transformer Protection High Impedance Differential (a) Earth Fault Scheme A B

C

87

© 2007 Protection Engineering And Research Laboratories

High impedance relay

17th March 2007 87

Auto Transformer Protection High Impedance Differential (b) Phase and Earth Fault Scheme A B C a b c 87 87 87

n © 2007 Protection Engineering And Research Laboratories

17th March 2007 88

Inter-turn Fault Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 89

Inter-turn Fault

E

CT Load Shorted turn

Nominal turns ratio Fault turns ratio Current ratio

- 11,000 / 240 - 11,000 / 1 - 1 / 11,000

Requires Buchholz relay © 2007 Protection Engineering And Research Laboratories

17th March 2007 90

Inter-turn Fault Inter-turn fault current Vs number of turns shorted 10

100 Fault current in short circuited turns

80

8

Fault current 60

6

(multiples of rated current)

Primary input current 40

4

20

2

0

5

10

15

20

Primary current (multiples of rated current)

25

Turns short-circuited (% of winding) © 2007 Protection Engineering And Research Laboratories

17th March 2007 91

Buchholz Relay Installation 3 x internal pipe Conservator diameter (minimum) 5 x internal pipe diameter (minimum)

Oil conservator 3 minimum Transformer

© 2007 Protection Engineering And Research Laboratories

17th March 2007 92

Buchholz Relay Petcock

Counter balance weight

Alarm bucket Mercury switch

Oil level

To oil conservator

From transformer

Trip bucket

Aperture adjuster Drain plug

Deflector plate

© 2007 Protection Engineering And Research Laboratories

17th March 2007 93

Over Flux Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 94

Over Fluxing in Transformers  Generator transformers and grid transformers  Usually only a problem during run-up or shut down, but can be caused by loss of load / load shedding etc.  Flux  V/ f  Effects of over fluxing, increase in,  Magnetizing current  Winding temperature  Noise and vibration  Overheating of laminations and metal parts (caused by stray flux) © 2007 Protection Engineering And Research Laboratories

17th March 2007 95

Over Fluxing in Transformers Theory

V=kf Causes

2m m

 Low frequency  High voltage

Im

 Geomagnetic disturbances

Effects  Tripping of differential element (Transient over fluxing)  Damage to transformers (Prolonged over fluxing) © 2007 Protection Engineering And Research Laboratories

17th March 2007 96

5th Harmonic Restraint  Blocks differential element for transient over fluxing 25% Overvoltage condition

43% 5th Harmonic content © 2007 Protection Engineering And Research Laboratories

17th March 2007 97

Over Flux Protection  Protective relay responds to V/f ratio  Measured from voltage input  Two stage protection Stage 1

-

lower A.V.R. or alarm

Stage 2

-

Trip field or transformer

 Definite time of Inverse time

© 2007 Protection Engineering And Research Laboratories

17th March 2007 98

Over Flux Protection

V/f = k  Trip and alarm outputs for clearing prolonged over fluxing Alarm : Definite time characteristic to initiate corrective action Trip : IDMT or DT characteristic to clear over-fluxing condition

Settings Pick-up 1.5 to 3.0 i.e.

110V x 1.05 = 2.31 50Hz

DT setting range 0.1 to 60 seconds © 2007 Protection Engineering And Research Laboratories

17th March 2007 99

Over Flux Protection Application Circuit breaker position repeat relay

RL1-1

AUX relay Lower AVR

DC

DC

Inhibit AVR raise Alarm RL2-1

RL2-2

Alarm

© 2007 Protection Engineering And Research Laboratories

Generator field circuit breaker trip coil

17th March 2007 100

Over Load Protection © 2007 Protection Engineering And Research Laboratories

17th March 2007 101

Transformer Overload and Life of Insulation 100

Relative rate of using life 



With ambient of 20C, hot spot rise of 78  is design normal. A further rise of 6 C doubles rate of using life.

10

1.0 98 0.1 80

90 100 110 120 130 140 Hot spot temp

© 2007 Protection Engineering And Research Laboratories

C

17th March 2007 102

Over Heating Protection Trip

Iload TD setting

Top oil of power transformer

Alarm

On

Fan control

Iload Off

On

Pump control Off

Temp. indication

Heater Local Thermal replica

Temperature sensing resistor

© 2007 Protection Engineering And Research Laboratories

Remote

17th March 2007 103

Thermal Over Load Protection  Thermal replica for 1Ø or 3Ø protection.  Adjustable time constant : 5 mins. to 160 mins.  Current settings : Thermal : 0.4 IN to 1.175 IN Instantaneous : 2 IN to 25 IN  Thermal state indication

 Separately adjustable trip and alarm settings © 2007 Protection Engineering And Research Laboratories

17th March 2007 104

Thank you © 2007 Protection Engineering And Research Laboratories

17th March 2007 105

Related Documents

Transformer Protection
January 2021 1
Transformer Protection
January 2021 2
Transformer Protection
January 2021 5
Transformer Protection
January 2021 5
Transformer Protection
January 2021 1

More Documents from "hozipek5599"

Transformer Protection
January 2021 1