OSII PHASE – 2 DEVELOPMENT PROJECT DATA SHEETS FOR LV SWITCHGEAR NPCC Document No. :
4225-36723A-P004-001 Rev. B
Vendor Document No. :
212078DC025
OSII PHASE – 2 DEVELOPMENT PROJECT
NPCC Purchase Order Number : 4225-2014/36723-AC Equipment / Material : LV Switchgear / Interposing Relay Panel / CMAC Panel Equipment Tag Number : OS2-MCC-G-001 / OS2-IRP-PLC-001 / CMAC VENDOR DOCUMENT STATUS
A
DATA SHEETS FOR LV SWITCHGEAR
A-
ACCEPTED
B-
COMMENTS AS MARKED
C-
NOT ACCEPTED
D-
RETAINED FOR INFORMATION
ACCEPTANCE DOES NOT AFFECT VENDOR LIABILITIES AND RESPONSIBILITIES AS STIPULATED WITHIN THE PURCHASE ORDER SPECIFICATIONS AND CONDITIONS.
B
VENDOR MUST CONFIRM THAT ALL COMMENTS WILL BE INCORPORATED BEFORE PROCEEDING.
C
ALL DOCUMENTS MUST BE RESUBMITTED AFTER INCORPORATION OF COMMENTS WORK SHALL NOT PROCEED.
Sachin S. Patil 2015.07.08 08:25:05 +04'00'
B A
07-Jul-15 29-Jun-15
Rev
Date
ISSUED FOR REVIEW ISSUED FOR REVIEW
Description
Page 1 of 1
J Davies J Davies
I J Priestley I J Priestley
H Singh H Singh
Prepared By
Checked By
Approved By
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
OSII PHASE 2 DEVELOPMENT PROJECT DATA SHEET FOR 415V SWITCHBOARD
0 B A
10-03-2015 27-11-2014 30-10-2014
Rev
Date
ISSUED FOR DESIGN ISSUED FOR APPROVAL ISSUED FOR REVIEW Description Page 1 of 9
SPL SPL SPL Prepared By
NKU NKU NKU Checked By
BPR BPR BPR Approved By
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl. A 1
Description
Design Data
2 3 4 5 6 7 8 9 10 11
GENERAL Asset Plant Job / Project Ref. No. Plant TAG No. Switchboard Tag No. Type / Model No. Design Life Project Specification Standards Manufacturer’s Name and Country of Origin Local Agent
12
Painting
13
Painting Shade
14 B 15 16 17 18 19e 20 C
Paint Thickness SITE CONDITIONS Installation Altitude Ambient Temperature (Outdoor) Design Temperature Maximum Humidity Area Classification REFERENCE DRAWINGS AND DOCUMENTS
21
Single Line Diagrams
22 23 24 D 25 26
Project Specification Electrical I/O List Electrical & Instrumentation Room Equipment Layout DESIGN / SYSTEM CHARACTERISTICS System System Earthing
27
Rated Voltage
28
Rated Frequency
29
Transient Condition
30
Phase Sequence
31
Rated Short Circuit Withstand Current (Main & Earth Circuit)
32 33 34 E
Power Frequency Withstand Voltage ( 1 minute) Rated Insulation Voltage Maximum Supply Harmonic Distortion CONSTRUCTION / GENERAL FEATURES
35
Type
36 37
Execution (Fixed / Withdrawable) Mounting
38
Method of Fixing
39
Partitions, shutters and inspection windows forming part of enclosure
Supplier Data
BUNDUQ OSII 4225 OS2 OS2-MCC-G-001 # 30 Years OS2-785-JS-007 IEC # # As per BUNDUQ Painting Specification Document No. 809-SP-404-07 Light Admiralty Grey, “697” as per BS 381C #
Confirmed Confirmed Confirmed Confirmed Confirmed
Air Conditioned Switchboard Room < 1000m 8.9 C (min), 50 C (max) 40 C (Note-9) 100% Safe Area
Confirmed Confirmed Confirmed Confirmed
OS2-780-20-001 OS2-780-20-002 OS2-780-2S-102 OS2-785-JS-007 OS2-780-2S-JS-021 OS2-780-2S-107
Confirmed
3 Phase + Neutral Solidly Earthed 415V +10%(Line to Line), 240V +10% (Line to Earth) 50 Hz +5% Voltage Variation +/-20% and Frequency Variation +/-10% R-Y-B Anticlockwise 40kA RMS for 1 Sec, 84kA peak 2.5kV 600V 5% THD
Confirmed Confirmed Confirmed
Compartmented Metal Enclosed (Single Front) Withdrawable Floor Standing Bolted to Plinth. Plinth to be bolted to floor mounted rails
Confirmed
Page 2 of 9
IP 32
Euro IEC439 Confirmed Confirmed Confirmed Powell UK Emdad Confirmed Confirmed 50 micron
95% Confirmed
Confirmed Confirmed Confirmed
Confirmed Confirmed Confirmed Confirmed Confirmed Confirmed Confirmed
Confirmed Confirmed Confirmed Confirmed
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl.
Description
Design Data
40 41
Overall Ingress Protection Enclosure Material and Thickness
42
Internal Separation
Form 4 , Type 5
43 44
Cable Connection Cable Entry
Front Top
45
Future Extension Provision
46
Mounting of the Relays and Meter
47 48 49 F 50 51 52 53
Overall Dimension ( L x D x H) Total Weight (kg) Heat Losses of complete Switchboard BUSBAR Main Bus Bars (Single / Double) Main Bus Bar Rating (Throughout the length of Switchboard) Neutral Bus Bar Rating Distribution Bus Bar Rating Short Circuit Rating for both Main, Neutral and Distribution Bus Bars
54 55
Bus Bar Conductor
56 57
Busbar Phase Cross-section Busbar Neutral Cross-section
IP 42 Sheet Steel , 2 mm (min)
Both Left and Right
Bare / Insulated
59
Bus Section
60 61 G 62 63 64 65 66
Earth Bus Section Earth Bus Material COMPONENTS Incomer and ACB Feeders: Breaking Device as per Standard IEC 60947 Make and Model Number Manufacturer Type Designation Number of Poles
67
Rated Current (Amp)
68 69 70 71 72 73 74
76
Rated Voltage Rated Frequency Rated Short Circuit Level Rated Peak Current Circuit Breaker Opening Time Circuit Breaker Closing Time Utilisation Category as per IEC60947 Standard IEC 60947 Auxiliary Voltage for Closing and Tripping Volts Materials of
77
75
Confirmed Confirmed Confirmed
Flush Mounted on door. Operating switches will be located within 1600mm to 200mm from floor for ease of operation # # #
Confirmed
Single 1000 A (As installed at site) # As Required 40kA RMS for 1 Sec, 84kA peak Electrolytically refined hard-drawn high conductivity copper
Confirmed Confirmed 1000A Confirmed Confirmed
# #
2 x 75 x 6 2 x 75 x 6 Confirmed
Bus Bars to be fully insulated with flame retardant materials to IEC 60332. Joints to be covered by removable flexible covers.
58
Supplier Data Confirmed Confirmed Confirmed
5532 x 1190 x 2907 4950 3550W
Confirmed
One (1)
Confirmed
Fully Rated for Short Circuit Current Hard-drawn High Conductivity Copper
Confirmed Confirmed
Withdrawal Air Circuit Breaker # # Four (4) As per 415V Switchboard SLD 415V 50 Hz 40kA for 1 Sec 84kA peak # # Category B
Confirmed Terasaki AR216H Terasaki AR216H Confirmed Confirmed Confirmed Confirmed Confirmed Confirmed 30ms 80ms Confirmed
#
240VAC
- Moving Contacts
#
Copper with silver plating with Arc tip Silver alloy
78
- Fixed Contacts
#
Copper with silver plating
79
Design of Page 3 of 9
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl.
Description
Design Data
Supplier Data
80
- Moving Contacts
#
Double break symmetric & replaceable
81
- Fixed Contacts
#
Self coupling, body mounted & replaceable
82
Spring Charging Mechanism Motorised Spring Charging - Motor rated power (W)
83
Confirmed #
768W 1s, 134W steady state
84 85 86
- Motor operating voltage (V) Weight of draw out unit (kg) Switching Device Pad lockable in the OFF position
87
CB Auxiliary Contacts
88 89 90
Shunt Release Under voltage trip function Rated Power for Closing / Tripping Coils
91
Outgoings (MCCB) Feeders:
92 93 94
Breaking Device as per Standard IEC 60947 Make and Model Number Manufacturer Type Designation
95
Number of Poles
As per 415V Switchboard SLD
Confirmed Schneider NSX Schneider NSX Confirmed
96
Rated Current (Amp)
As per 415V Switchboard SLD
Confirmed
97
Rated Voltage
415V
Confirmed
98 99 100 101 102 103 104 105 106 107
Breaking Capacity at 415V, 50Hz Materials of - Moving Contacts - Fixed Contacts Design of - Moving Contacts - Fixed Contacts Spring Charging Mechanism Motorised Spring Charging - Motor rated power (W) - Motor operating voltage (V)
108
Weight of draw out unit (kg)
109 110
Switching Device Pad lockable in the OFF position Utilisation Category as per IEC60947
111
Contactor
112
Shunt Release
# # # 4NO + 4NC Spare Contacts to be provided for future use. The same shall be wired to the terminal block. Required Required #
240VAC 94 Confirmed
As per 415V Switchboard SLD
Confirmed
MCCB # #
Earth Fault Protection
114 115 116
Outgoing (Motor Starter) Feeders: Breaking Device MCCB Pad Lockable in “off” Position
117
Contactor Auxiliary Contacts
118 119 120 121 122 123
Contactor Duty Contactor Type Contactor Utilisation Category as per IEC 60947-1 Emergency Stop push button turn to release with accidental protection cover Auto-Manual Selector Switch CBCT for earth fault protection
50kA
# #
Not available Not available
# #
Not available Not available
# # #
N/A N/A 300 chassis 23.5, 450 chassis 27.5. Confirmed A
As per 415V Switchboard SLD
Confirmed
Required
Confirmed
Required for feeders - MCCB rating exceeds 100A
Confirmed
As per 415V Switchboard SLD MCCB Protected Contactors Required Minimum 4NO + 4NC potential free spare contacts to be provided for future use. The same shall be wired to the terminal block. # Single Air Break # Required Required Required for motors rated above 15 kW
Page 4 of 9
Confirmed Included in SR750 204-264VAC
#
# #
113
6 change-over contacts
Confirmed Confirmed Confirmed 3N/O & 2N/C AC3 Confirmed AC3 Confirmed Confirmed Confirmed
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl.
Description
Design Data
Supplier Data
124 125 126 127
Earth fault protection CT’s for Ammeter in LCS (Local Control Station) Common Control Power Supply Transformer Restarting Facility
Required for motors rated above 15 kW for motors FLC exceeding 30A Required for motors rated above 22 kW Required Not Required.
Confirmed Confirmed Confirmed Confirmed
128
Motor Starter Type
DOL (Direct On Line), unless otherwise specified.
Confirmed
129
Motor Starters Type-2 Co-ordination
Required
Confirmed
H 130
AUXILIARY VOLTAGES (Note-5) Air Circuit Breaker Panel:
131
Internal / External Voltage Supply
Two (2) numbers 240V AC UPS external supply to be provided by the CONTRACTOR.
Confirmed
132 133 134 135 136
Control Circuits and ACB Coils Protection and Auxiliary Relays Signals / Indications Spring Changing Motor Outgoing Feeders:
240V AC+/-10%, 50Hz 240V AC+/-10%, 50Hz 240V AC+/-10%, 50Hz 240V AC+/-10%, 50Hz
Confirmed Confirmed Confirmed Confirmed
137
Internal / External Voltage Supply
External – 240V AC supply
Confirmed
138 139
Control, Indication, Protection Circuits Protection Relays / Control Units
Confirmed Confirmed
140
Panel Anti-condensation Heaters and Lighting
240V AC+/-10%, 50Hz 240V AC+/-10% One External supply (240V AC +/- 10%, 1Ph+N, 50Hz +/-5%) at one point to be provided by the CONTRACTOR
141
Outgoing Motor Feeders:
142
Internal / External Voltage Supply
Internal / External- AC supply
Confirmed
143
Control, Protection Circuits and contactor coil
240V AC internally derived
Confirmed
144
Intelligent motor controller units (MFCU) & Indication
240V AC+/-10%, 50Hz
Confirmed
145
Motor Anti-condensation Heaters (Note-7)
One External supply (240V AC +/- 10%, 1Ph+N, 50Hz +/-5%) at one point to be provided by the CONTRACTOR
Confirmed
146
Test Supply (See Note-10)
147 148
Internally derived by the Supplier through control transformer (Ratio: 415V/240V).
240V AC UPS power consumption of total switchboard (in watts) 240V AC power consumption of total switchboard (in VA and watts)
I 149 150
CURRENT TRANSFORMER (Note-4) CT for Incomer: Metering CT:
151
- Ratio
152 153 154
- Burden - Accuracy Class Protection CT:
155 156 157
CT for Outgoing Feeders:
158 J 159 160
CT Shorting Link VOLATGE TRANSFORMER (Note-4) Incomer VT: - Type Designation
# #
Confirmed
Confirmed (Transformer ratio 415/228V) 4225-36723A-P001001 4225-36723A-P001001
As per 415V Switchboard SLD
Confirmed
# Class 1.0
15VA Confirmed
- Ratio
As per 415V Switchboard SLD
Confirmed
- Class
5P20
Confirmed
As per 415V Switchboard SLD
Confirmed
Required
# Page 5 of 9
Incomer only
500/20751
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl.
Description
161
- Type
162
- Standard IEC 60044-1
163 164 165 166 167 168 169 170 171
- Nominal transformer ratio (as per SLD’s) A - Rated Short circuit thermal current (1 s) kA - Rated peak withstand current kA - Material of insulation
172
- Accuracy Class
173
Other VTs
174
Design Data # #
# # # #
Rated output: - For protection/Metering VA Class of Accuracy - Ratio - Burden
Supplier Data Earthed type voltage transformer IEC60044-2 (Pre 2015), IEC61869-2 (2015 onwards). 415/110 N/A N/A Polyester/Presspahn
# # 415V / 110V #
30VA 1 Confirmed 30VA
Metering Class 1.0
Confirmed
As per 415V Switchboard SLD
N/A
- Type Designation
#
N/A
175
- Withdrawal type
#
N/A
176
- Standard IEC 60044-2
#
N/A
177
- Nominal transformer ratio (as per SLD’s) A
#
N/A
178
- Rated Output VA
#
N/A
179
VT for Outgoing Feeders:
K
As per 415V Switchboard SLD
Confirmed
As per Project Specification and 415V Switchboard SLD
Confirmed
CONTROL, PROTECTION AND MONITORING (Note-5 & 6)
180
Incomer Protection Relay
181
Outgoing Motor Feeders Protection Relay (Microprocessor Based Intelligent Unit)
#
182
Outgoing Feeder Protection Relay (Microprocessor Based Intelligent Unit)
For feeder rated above 100A
183
Protection, Control, Indication and Monitoring
As per OS2-780-2S-102 (4225-P-1009)
Confirmed
Interface with RTU (Both Hardware and Serial Link)
As per OS2-780-2S-102 (4225-P-1009) and I/O List : OS2-780-2S-JS-021 (4225-P-LI-002)
Confirmed
184 185
Remote Interrogation / Setting Modifications
Required
Confirmed
Serial Data Link Interface
Dual Redundant MODBUS over TCP/IP (RJ 45). Relays to be Daisy Chained for Serial Data Communication with RTU.
Confirmed
186 187
DACM panel with dual redundant Ethernet switches
Required
Confirmed
188
Time Stamping
189
Test Blocks
190
Interlocks
191
ACB Contactor ON / OFF Contacts
L
Not Required Required As per Clause#6.9 of the Specification and 415V SLD To be provided with ACB Service Position contacts in series
Motor manager 6 Feeder manager 6
Confirmed Confirmed (Incomer only) Confirmed From SR750
METERING AND INDICATIONS
192
Metering and Indications
193 194
Indication Lamp Colour of Indication Lamps: Page 6 of 9
As per 415V Switchboard SLD and Specification
Confirmed
Cluster LED
Confirmed
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl.
Description
Design Data
195 196 197 198 199 200 201
Stopped / Open Running / Closed Fault Trip Circuit Healthy Power / Heater Supply On Spring Charged Trip Circuit Supervision
Red Green Amber Blue White Blue White
202
Lamp Test Facility
M 203
CONNECTIONS Cable / Busduct
204
Power Cable Size for Incomer / Feeders
205
Control Cable Size
206
Earthing Cable Size (for External Connection)
207
Low Voltage Terminals (One conductor for each terminal)
208 209 210
Spare Terminal Blocks Segregation of wiring Cable Entry
211
Cable Gland Plate (Undrilled)
N 212 213
Required common per Panel Cables for Incomer and Outgoing Incomer – 2R x 1C x 300 sq. mm./Phase Outgoing Feeders - As per 415V Switchboard SLD Control Wiring: 1.5 sq. mm. min., CT and Power Wiring: 2.5 sq. mm. min. 1C x 240 sq. mm. XLPE copper cable Screw Clamp / Stud if > 6 sq. mm. then straight shank compression type cable lugs
Supplier Data Confirmed Confirmed Confirmed White Confirmed Confirmed Confirmed Confirmed (Incomer only) Confirmed Confirmed
Confirmed Confirmed
Confirmed
20% min. Required for different voltages Top Required. Brass gland plate required for single core cables
Confirmed Confirmed Confirmed Confirmed
ACCESSORIES AND MISCELLANEOUS Handling Truck Number of Handling Truck
Required #
Confirmed 1
214
Dimension and Weight of handling Trucks
#
215
Anti-condensation Heater
216 217 218 219 220 221 222 O 223 224 225 226 227 228 229 P 230 231
Anti-condensation Heater Ingress Protection Anti-condensation Heater Power Rating Plinth Padlocking Facility Lifting Eyebolts Label (English) Main Label (Front / Back) INSPECTION AND TESTING Routine Tests: All Routine Tests as per IEC and Specification Test Certificate Witnessed / Not Witnessed Type Tests: Type Test Certificates Witnessed / Not Witnessed DOCUMENTATION Completed Data sheet General Arrangement Drawings
232
SLD/Schematic Drawings
233 234
Wiring Diagrams Test Reports and Certificates
Required for each panel with individual thermostat and Isolation CB IP 50 # Required Required Required As per Specification Both
Confirmed Confirmed 40W By NPCC Confirmed Lifting beams Confirmed Confirmed
Required Required Witnessed at Manufacturer Works
Confirmed Confirmed
Required Not Witnessed
Confirmed Confirmed
Required with Bid and after Award Required with Bid and after Award
Confirmed Confirmed
Required after Award Required after Award Required with Bid and after Award Page 7 of 9
H: 1720, W: 630, D: 300. 50kg
Confirmed
Confirmed, schematics only N/A Confirmed
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
Sl.
Description
Design Data
Supplier Data Confirmed Confirmed Confirmed
235 236 237 Q
FAT Procedure Inspection and Test Plan O&M Manuals SHIPPING
Required after Award Required after Award Required after Award
238
Shipping Dimensions (L x D x H)
#
239
Number of Packing Units
#
240
Provision of Impact Recorders
#
N/A
241
Trip Value of Impact Recorders
#
N/A
4225-36723A-Z005001 4225-36723A-Z005001
Notes: 1. #: Supplier to fill up in the ‘Supplier Data Column’. 2.
RTU: Remote Terminal Unit; ESD :Emergency Shutdown System; ISSS : Integrated Safety Shutdown System
3.
Supplier data column shall be completed as “CONFIRMED” or clearly showing deviations, if any for the specified design data.
4.
CTs & VTs sizing calculations shall be submitted by the SUPPLIER for the CONTRACTOR approval.
5.
Closing, Tripping, Protection, Indication and anti-condensation heater circuits shall be protected by individual dual pole MCBs.
6.
All protection modules shall be microprocessor based, programmable, withdrawable type with integral protection, control, monitoring and facility for serial communications. Electrical System interface with RTU will be DAISY- chained serially and shall have one redundant serial interface with RTU (MODBUS over TCP/IP).
7.
Anti-Condensation Heater (ACH) for LV Motors (>3.7kW) shall be provided with indication lamp at switchboard.
8.
All Measuring Instruments Degree of protection shall be IP 52.
9.
The equipment shall be designed operating continuously for the maximum ambient temperature of 40°C and for at least eight (8) hours at a maximum design ambient temperature of 50°C for HVAC failure.
10. During test condition the auxiliary supply for motor contactor shall be provided from the common control transformer. The common control transformer shall be adequately rated to cater the largest contactor in the switchboard. Also supplier shall provide necessary flexible/jumpers for test arrangement as required. 11. Standard manufacturer's data sheets for the type of relays offered shall be submitted with the Tender. 12. ESD trip Signal for all feeders shall be hardwired and interface with ISSS-ESD system. All feeders of 415V switchgear shall be provided with SIL2 rated ESD relays to receive ESD trip signals. The switchgear shall be provided with link in terminal block to bypass the ESD trip command. 13. Vendor to advise the space required at front, back and sides of 415V switchgear. 14. Vendor shall furnish the below mentioned additional information for power and motor feeders: a)
Motor Feeders- (see 2120780100CM1) Feeder Rating / Feeder
MCCB Type
MCCB Rating
Type of Motor
Contactor
Starter
Type / Rating
Equipment 0.75 kW
NSX100N
MA2.5
NSX100N NSX100N
Protection
Range
Relay / CBCT
DOL
LC1-D80
MM6
DOL
LC1-D80
MM6
DOL
LC1-D80
MA6.3
Page 8 of 9
Earth Fault
Relay Type /
MA6.3
1.1 kW 1.5 kW
Thermal
CT Ratio
N/A
N/A
N/A
N/A
N/A
N/A
MM6
DATA SHEET FOR 415V SWITCHBOARD BUNDUQ Document No. : OS2-785-2S-MCC-006 Rev. 0 NPCC Document No. : 4225-P-DS-006
NSX100N
DOL
NSX100N
MM6
DOL
LC1-D80
NSX100N
DOL
LC1-D80
NSX100N
DOL
LC1-D80
NSX100N
DOL
LC1-D80
MA25
Page 9 of 9
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
MM6
MA12.5
5.5kW
N/A
MM6
MA12.5
3.7 kW
N/A MM6
MA12.5
3.0 kW
7.5kW
LC1-D80
MA6.3
2.2 kW
MM6