Loading documents preview...
BUNDUQ -- Commented
ABB S.p.A - Power Products Division
ABB S.p.A - Power Products Division
ABB S.p.A - Power Products Division
ABB S.p.A - Power Products Division
ABB S.p.A - Power Products Division
ABB S.p.A - Power Products Division
Why OR gate with negation required? Check weather Negation is required since AND gate is used for operation
LED-INSERTED (Green) ISOLATED (RED)
LED - CLOSE (RED)
Indication of C.B in test position to be added in LED
OPEN (GREEN)
ABB S.p.A - Power Products Division
ABB to check whether, This signal to be taken before or after the AND gate. Since the LED (TCS Healthy)remains ON even when the CCC fails during CB isolated position.
Hour meter
DCS
ABB S.p.A - Power Products Division